Lumination LPL Series Recessed Troffer Guide d'installation

Catégorie
Accessoires de moto
Taper
Guide d'installation
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 4
(Rev 4/19/23)
IND676-LPL-Gen-D-Recessed-Trofer-Installation-Guide_R01
Proline® LED Luminaire
LPL Gen D Series
Installation Guide
IND676 | DOC 2002763
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Prepare Electrical Wiring
Electrical Requirements
• The LED luminaire must be connected to the mains
supply according to its ratings on the product label.
• Class 1 wiring should be in accordance with NEC.
Grounding Instructions
• The grounding and bonding of the overall system
shall be done in accordance to local electric code
of the country where the luminaire is installed.
Save These Instructions
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
CAN ICES-005(A)/NMB-005(A)
Note: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communi-
cations. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
WARNING/AVERTISSEMENT
RISK ELECTRIC SHOCK
Turn power o before inspection, installation or removal.
Properly ground electrical enclosure.
RISK OF FIRE
Follow all NEC and local codes.
Use only UL approved wire for input/output connections.
Minimum size 18 AWG (0.75mm2).
Do not install insulation within 3 inches (76 mm)
of luminaire top.
RISQUES DE DÉCHARGES ÉLECTRIQUES
Coupez l’alimentation avant d’inspecter, installer ou déplacer
le luminaire.
Assurez-vous de correctement mettre à la terre le boîtier
d’alimentation électrique.
RISQUES D’INCENDIE
Respectez tous les codes NEC et codes locaux.
N’utilisez que des ls approuvés par UL pour les entrées/sorties
de connexion. Taille minimum 18 AWG (0.75mm2).
Maintenir une distance de 76 mm (3 pouces) entre le luminaire
et l’isolant.
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 4
(Rev 4/19/23)
IND676-LPL-Gen-D-Recessed-Trofer-Installation-Guide_R01
Proline® LED Luminaire (LPL Gen D Series) Installation Guide
TURN OFF POWER at the source to
the luminaire.
Insert luminaire into T-bar ceiling grid. Unit
should not move freely within the ceiling grid.
To ensure a consistent appearance, align
xtures in the same orientation throughout
the ceiling pattern.
1
3 4
Default lumen level is M(medium), and default
CCT is 4000K. For other lumen level or CCT,
loosen screw and remove switch cover, then
set switch to the desired lumen level or CCT by
screwdriver. Re-attach cover and tighten screw.
Bend the brackets on the housing to make sure
they hook to T-Bar.
Secure safety cable to connection hole as needed
to meet local seismic requirements. Safety cable
and method of attachment to the building
are provided by contractor according to local
building codes.
2
Luminaire Installation
CCT switch Switch cover
Lumen switch
Screw
Connection hole for safety cable
T-Bar
Bracket on the housing
T-Bar
Sensor enclosure
(optional)
K.O. for EMBB only
LPL22x
LPL22x
Series
LPL22x Series
T-Bar
Sensor enclosure
(optional)
K.O. for
EMBB only
LPL24x Series
Model Lumen Level CCT
22x H/M (default)L 3500K/4000k(default)/5000k
24x H/M (default)L 3500K/4000k(default)/5000k
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 4
(Rev 4/19/23)
IND676-LPL-Gen-D-Recessed-Trofer-Installation-Guide_R01
Proline® LED Luminaire (LPL Gen D Series) Installation Guide
Remove electrical enclosure cover with three Knock-Outs on the top. Carefully remove knockout for
AC mains input wires. Install UL listed electrical ttings in the knockout holes for wire protection.
Connect the AC mains to the black (line) and white (neutral) input wires of the xture by using UL listed
connectors or wire-nutsfor 14-18 AWG.
Connect the ground wire to the green-yellow ground wire of luminaire. When connecting dimming
controller, wires must run through a separate knockout hole equipped with an appropriate wire restraint
or cable gland. Then, re-attach and x electrical enclosure cover with screw by screwdriver.
1
Option: Follow diagram for 0-10V. Run wires from controller through a dierent knockout than the AC
input wire. At the output side of xture, make appropriate connections by using UL listed connectors or
wire-nuts. To combine with LFAMBA0VQFAEL, LCAMBA0NRFAEL, LCAMBA0TSFAEL, LCAMBA0TQFAEL,
LFAMBADVQFA, LCAMBA0NRFAB2,LCAMBA0TSFAB2, LCAMBA0TQFAB2, LCAMBA0NRFA, LCAMBA0TSFA
or LCAMBA0TQFA, please follow the install instructions provided with those products.
NOTE: Please cover dimming leads with wire nuts if leads not be connected.
2
Electrical Connections - Basic version
AC mains Dimming
Electrical enclosure cover
Green/Yellow
White
Line
Neutral
Fixture
Ground
Violet
Pink
AC Mains
Black
To 010V
Dimmer
010V(+)
010V(-)
Optional Installation: 0 –10V Volt Dimming
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 4 of 4
(Rev 4/19/23)
IND676-LPL-Gen-D-Recessed-Trofer-Installation-Guide_R01
Proline® LED Luminaire (LPL Gen D Series) Installation Guide
Remove sensor enclosure cover. Carefully remove knockout for AC mains input wires. Install UL listed
electrical ttings in the knockout holes for wire protection.
LPL22x
Connect the AC mains to the black (line) and white (neutral) input wires of the LED driver by using
UL listed connectors or wire-nuts for 18-14 AWG.
LPL24x
Connect the AC mains to the brown (line) and blue (neutral) input wires of the LED driver by using
UL listed connectors or wire-nuts for 18-14 AWG.
Connect the ground wire to the green-yellow ground wire of luminaire. When connecting dimming
controller, wires must run through a separate knockout hole equipped with an appropriate wire restraint
or cable gland. Then, re-attach and x enclosure cover with screw by screw driver.
1
Electrical Connections - Sensor version
Sensor enclosure cover
AC mains
Line
Neutral
Ground Green/Yellow
White (or Blue)
AC Mains
Black (or Brown)
Fixture
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Lumination LPL Series Recessed Troffer Guide d'installation

Catégorie
Accessoires de moto
Taper
Guide d'installation