Firman P03611 Le manuel du propriétaire

Catégorie
Groupes électrogènes
Taper
Le manuel du propriétaire
P/N:336745454 Rev:00
OWNERS MANUAL
Read all safety precautions and instructions carefully
before operating equipment.
Ensure engine is stopped and level before performing
any maintenance or service.
IMPORTANT:
Record product information to reference when ordering parts or
obtaining warranty coverage.
Serial Number:
PORTABLE GENERATOR
MODEL NUMBER
P03605
Rev Level:00
DO NOT RETURN TO
STORE!
CALL US FIRST!
CUSTOMER HOTLINE
1-844-347-6261
FOR QUESTIONS OR SERVICE
INFORMATION
Purchase Date:
Table of Contents
English Customer Service: 1-844-FIRMAN1
. . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Safety Precautions . . . . . . . . . . . . . . . . . . . . .2
Unpacking the Generator. . . . . . . . . . . . . . . .6
Parts Included. . . . . . . . . . . . . . . . . . . . . . . .6
Removal of Shipping Supports . . . . . . . . . 7
Controls and Features. . . . . . . . . . . . . . . . . .8
Generator. . . . . . . . . . . . .. . . . . . . . . . . . . .8
Control Panel. . . . . . . . . . . . . . . . . . . . . . . 9
Specifications. . . . . . . . . . . . . . . . . . . . . . . . 10
Add Engine Oil . . . . . . . . . . . . . . . . . . . . . . 11
Low Oil Shutdown . . . . . . . . . . . . . . . . . . .11
Add Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operation at High Altitude . . . . . . . . . . .12
Grounding. . . . .. . . . . . . . . . . . . . . .. . . . . .13
System.. . . . . . . . . . . . . . . . . . . . . . .. . . . . .13
Operation . . . . . . . . . . . . . . . . . . . . . . . . .. . . . 14
Generator Location . . . . . . . . . . . . . . . . . . 14
Surge Protection . . . . . . . . . . . . .. . . . . . . .14
Starting the Generator . . . . . . . . . . . .. . . 15
Connecting Electrical Loads . . . . . . . .. . . 16
Stopping the Engine . . . . . . . . . . . . . . . . . 16
Low Oil Shutdown . . . . . . . . . . . . . . . . . . 17
Do Not Overload Generator . . . . . . . . . . . 17
Introduction
Connecting to a Buildings Electrical
Maintenance And Storage. . . . . . . . . . . . . . 18
Maintenance Schedule . . . . . . . . . . . . . 18
Engine Maintenance .. . . . . . . . . . . .. . . . 19
Change Engine Oil . . .. . . . . . . . . . . . . . 19
Air Filter Maintenance. . . . . . . . . . . . . .19
Spark Plug Maintenance. . . . . . . . . . . . 20
Cleaning Fuel Strainer . . . . . . . . . . . . 20
. . . 20
Generator Maintenance . . . . . . . . . . . . . . 21
Service and Storage . . . . . . . . . . . . . . . .. 22
Trouble Shooting . . . . . . . . . . . . . . . . . . . . .23
Parts Diagram and Parts List . . . . . . . . . . 24
Generator Parts Diagram . . . . . . . . . . . . 24
Engine Parts Diagram . . . . . . . . . .. . . . . 25
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . 26
Service Information . . . . . . . . . . . . . .. . . . . 28
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Inspect Muffler and Spark Arrester
Thank you for purchasing a FIRMAN generator.
Page 01
Important Safety Information
The manufacturer cannot possibly anticipate every possible circumstance that might involve a
hazard. The warnings in this manual and the tags and decals affixed to the unit are therefore not
all-inclusive. If you use a procedure, work method or operating technique that the manufacturer
does not specifically recommend you must satisfy yourself that it is safe for you and others. You
must also make sure that the procedure work method or operating technique that you choose
does not render the generator unsafe.
DANGER WARNING CAUTION
DANGER indicates a
potentially hazardous
situation which, if not
avoided. WILL result in
death or serious injury.
WARNING indicates a
potentially hazardous
situation which, if not
avoided, could result in
death or serious injury.
CAUTION indicates a
potentially hazardous
situation which, if not
avoided, may result in minor
or moderate personal injury,
or property damage.
Toxic Fumes
Fire Hazard
Hot Surface.
Do Not Touch the Surface.
Kickback
Risk of Electric Shock
Explosion Hazard
Rotating Parts Entanglement
Hazard
Operators Manual
INTRODUCTION
English Customer Service: 1-844-FIRMAN1
SAFETY PRECAUTIONS
Page 02
WARNING
WARNING
POISONOUS GAS HAZARD.
WARNING
English Customer Service: 1-844-FIRMAN1
Page 03
CORRECT USAGE
Example location to reduce risk of carbon monoxide poisoning
ONLY use outside and downwind, far away from windows, doors and vents.
Direct exhaust away from occupied spaces.
INCORRECT USAGE
Do not operate in any of the following locations:
Near any door, window or vent
Garage
Basement
Crawl Space
Living Area
Attic
Entry Way
Porch
Mudroom
English Customer Service: 1-844-FIRMAN1
Page 04
WHEN OPERATING EQUIPMENT
DO NOT tip engine or equipment at angle
which causes fuel to spill.
DO NOT stop engine by moving choke
control to “Start” position.
WHEN TRANSPORTING, MOVING
OR REPAIRING EQUIPMENT
Transport/move/repair with fuel tank
EMPTY or with fuel shutoff valve OFF.
DO NOT tip engine or equipment at angle
which causes fuel to spill.
Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT
WITH FUEL IN TANK
WARNING
WARNING
Generator voltage could cause
electrical shock or burn resulting
in death or serious injury.
WARNING
NEVER start or stop engine with electrical
devices plugged in and turned on.
WARNING
Fuel and its vapors are extremely flammable
and explosive which could cause burns, fire,
or explosion resulting in death or serious
injury and/or property damage.
WHEN ADDING OR DRAINING FUEL
Turn generator engine OFF and let it cool at
least 2 minutes before removing fuel cap.
Loosen cap slowly to relieve pressure in tank.
Fill or drain fuel tank outdoors.
DO NOT overfill tank. Allow space for fuel
expansion.
If fuel spills, wait until it evaporates before
starting engine.
Keep fuel away from sparks, open flames,
pilot lights, heat, and other ignition sources.
Check fuel lines, tank, cap, and fittings
frequently for cracks or leaks. Replace if
necessary.
DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
Ensure spark plug, muffler, fuel cap, and air
cleaner are in place.
DO NOT crank engine with spark plug
removed.
Use approved transfer equipment, suitable
for the intended use, to prevent backfeed by
isolating generator from electric utility
workers.
English Customer Service: 1-844-FIRMAN1
Page 05
WARNING
Unintentional sparking
could cause fire or
electric shock resulting
in death or serious
injury.
WHEN ADJUSTING OR MAKING REPAIRS TO
YOUR GENERATOR
Disconnect the spark plug wire from the
spark plug and place the wire where it cannot
contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug
removed.
WARNING
NEVER operate generator without protective
housing or covers.
DO NOT wear loose clothing, jewelry or
anything that could be caught in the starter
or other rotating parts.
Tie up long hair and remove jewelry.
DO NOT exceed the generators wattage
amperage capacity.
Start generator and let engine stabilize
before connecting electrical loads.
NOTE:
CAUTION
Exceeding generators wattage/amperage capacity
could damage generator and/or electrical devices
connected to it.
Connect electrical loads in OFF position,
then turn ON for operation.
Turn electrical loads OFF and disconnect
from generator before stopping generator.
DO NOT use generator with electrical cords
which are worn, frayed, bare or otherwise
damaged.
DO NOT operate generator in the rain or
wet weather.
DO NOT handle generator or electrical
cords while standing in water, while
barefoot, or while hands or feet are wet.
DO NOT allow unqualified persons or
children to operate or service generator.
WARNING
Exhaust heat/gases could ignite combustibles,
structures or damage fuel tank causing a fire,
resulting in death or serious injury and/or
property damage.
Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot
exhaust gases.
Allow equipment to cool before touching.
It is a violation of California Public Resource
Code, Section 4442, to use or operate the
engine on any forest-covered, brush-covered,
or grass-covered land unless the exhaust
system is equipped with a spark arrester, as
defined in Section 4442, maintained in
effective working order. Other states or
federal jurisdictions may have similar laws.
Contact the original equipment manufacturer,
retailer, or dealer to obtain a spark arrester
designed for the exhaust system installed on
this engine.
Replacement parts must be the same and
installed in the same position as the original
parts.
When using generator for backup power,
notify utility company.
Use a ground fault circuit interrupter (GFCI)
in any damp or highly conductive area,
such as metal decking or steel work.
DO NOT touch bare wires or receptacles.
English Customer Service: 1-844-FIRMAN1
Page 06
Use generator only for intended uses.
If you have questions about intended use,
ask dealer or contact local service center.
Operate generator only on level surfaces.
DO NOT expose generator to excessive
moisture, dust, dirt, or corrosive vapors.
DO NOT insert any objects through cooling
slots.
If connected devices overheat, turn them off
and disconnect them from generator.
Shut off generator if:
-Electrical output is lost.
-Equipment sparks, smokes, or emits flames.
-Unit vibrates excessively.
WARNING
Medical and Life Support Uses.
In case of emergency, call 911 immediately.
NEVER use this product to power life support
devices or life support appliances.
NEVER use this product to power medical
devices or medical appliances.
Inform your electricity provider immediately
if you or anyone in your household depends
on electrical equipment to live.
Inform your electrical provider immediately
if a loss of power would cause you or anyone
in your household to experience a medical
emergency.
NOTE:
Improper treatment of generator could damage
it and shorten its life.
UNPACKING THE GENERATOR
Parts Included
Your gasoline powered generator ships with
the following parts:
English Customer Service: 1-844-FIRMAN1
1. Engine Oil(Bottle) . . . . . . . . . . . . . . . . . . . . . . . 1
2. Oil Funnel . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. Wrench for Spark plug . . . . . . . . . . . . . . . . . . . .1
5. Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
6. Quick Reference Guide . . . . . . . . . . . . . . . . . . . 1
4. Double Open wrench (10mm & 12mm). . . . 2
2
1
Quick
Reference
Guide
3
Manual
6
5
4
Page 07
REMOVAL OF SHIPPING SUPPORTS
Before you can run your new generator, follow
these simple instructions:
CAUTION
Failure to remove these items can result
in damage to your generator, possible
Personal injury and void your warranty.
Refer to the following instructions and pictures
to remove the attached engine support brackets
(red) under the engine.
3. You may discard these brackets, as they are no longer
required for normal operation of your generator.
Your generator is now ready for use. Refer to
your owner's manual for proper oil fill and
startup instructions.
Engine Support Brackets
(red color)
Remove these 4 nuts &
bolts as indicated.
Supplied wrenches
English Customer Service: 1-844-FIRMAN1
Page 08
CONTROLS AND FEATURES
Generator
1- Fuel Gauge
2- 5.0 Gallon Capacity Fuel Tank
3- Fuel Cap
4- Choke Lever
5- Fuel Valve
6- Air Filter
7- 208cc FIRMAN OHV Engine
8- Recoil Starter
9-
10- Outlet Cover
11- Control Panel
Oil Filler Cap
*We are always working to improve our products. Therefore, the enclosed product may differ
slightly from the image on this page.
English Customer Service: 1-844-FIRMAN1
1
2
®
Page 09
Control Panel
1
2
4-1 Data-Minder(Multi-Meter)Push the
SELECT button to show the Voltage, Hertz and
running hours. If the low oil indicator is lit,
check the oil level.
9
8
6
7
Ground Terminal – Consult an electrician
for local grounding regulations.
120V, 20A Duplex (NEMA 5-20R)
5
120V, 30A RV (NEMA TT-30R)
Total power drawn from all receptacles must not exceed the name plate rating.
NOTE:
Outlet Cover - Protect the receptacles from
dust and debris.
3
120/240V, 30A Twist-Lock – (NEMA L14-
30R) May be used to supply power for the
operation of 120/240 Volt, 30Amp.
4
Voltage Selector Switch – To select
between 120 Volt or 240 Volt.
1
2
3
4
5
6
7
8
9
240V
120V
A - Digital display
B - AC voltage indicator
C - Frequency indicator
D - Hour indicator
E - Low oil indicator
F - Select button
English Customer Service: 1-844-FIRMAN1
Maximum full load 30 Amp current may be
drawn from this 120 Volt receptacle.
20 Amp of current may be drawn from this
120 Volt receptacle.
Engine Switch – Flip the switch to the “ON(l)
position and pull the recoil starter to start the
generator. Turn to the OFF(O)” position to
turn off the generator.
9
Page 10
SPECIFICATIONS
Model
Rated AC Voltage
Phase
Power Factor
Voltage Regulator
Alternator Type
Running Watts
Starting Watts
Engine
Engine Type
Displacement
Low Oil Shutdown
Ignition System
Starting System
Fuel
Capacity Fuel Tank
Lubricating Oil Capacity
Carburetor Type
Air Cleaner
P.T.O. Shaft Rotation
120/240V
P03605
3650
AVR
Single
1
Single Cylinder, 4-Stroke OHV Air Cooled
208cc
Breakless Ignition Type, Flywheel Magneto
Unleaded Automotive Gasoline
Recoil
5.0 Gallon
20.3 oz(0.6L)
Counter Clockwise (Facing P.T.O.)
Float
Brushed
Polyurethane Type
Yes
4550
FIRMAN
Rated Fequency
60Hz
Oil Type
See “Add Engine Oil” Section
Spark Plug
AN IMPORTANT MESSAGE ABOUT TEMPERATURE:
When operated above 7F(2C) there may be a decrease in power.
Maximum wattage and current are subject to and limited by such factors as fuel BTU content
ambient temperature, altitude, engine condition and etc. Maximum power decreases about
3.5% for each 1,000 feet above sea level; and will also decrease about 1% for each 1F(-12.2°C)
above 6F(16°C) ambient temperature.
TORCH F6RTC/NGK BPR6ES/CHAMPION RN9YC
English Customer Service: 1-844-FIRMAN1
ADD ENGINE OIL
Page 11
1.Place generator on a flat, level surface.
2.Clean area around oil fill and remove yellow
oil fill cap/dipstick.
3.Wipe dipstick clean.
NOTE:
The engine is equipped with a low oil shut-off and
will stop when the oil level in the crankcase falls
below the threshold level.
NOTE:
We consider the first 5 hours of run time to be
the break-in period for the unit. During the break
in period stay at or below 50% of the running
watt rating and vary the load occasionally to allow
stator windings to heat and cool. Adjusting the
load will also cause engine speed to vary and help
seat piston rings.
CAUTION
The unit is equipped with a low oil shutdown.If
the oil level becomes lower than required,the
sensor will activate a warning device or stop the
engine.
If generator shuts off and the oil level is within
specifications, check to see if generator is sitting
at an angle that forces oil to shift. Place on an
even surface to correct this. If engine fails to
start, the oil level may not be sufficient to
deactivate low oil level switch. Make sure the
sump is completely full of oil.
(H)
DRAIN PLUG
(L)
5.Replace oil fill cap/dipstick and fully tighten.
6.Oil level should be checked prior to each use
or at least every 8 hours of operation. Keep oil
level maintained.
4.Using oil funnel, slowly pour contents of
provided oil bottle into oil fill opening to the
"H" mark on dipstick. Be careful do not
overfill. Overfilling with oil could cause the
engine to not start or hard starting.
H
L
Low oil shutdown
Degrees Celsiusº(Outside)
Full Synthetic 5W-30
Degrees Fahrenheitº(Outside)
5W-30 10W-40
10W-30
CAUTION
English Customer Service: 1-844-FIRMAN1
ADD FUEL
Page 12
Fuel must meet these requirements:
Clean, fresh, unleaded gasoline.
Use regular UNLEADED gasoline with the
generator engine with a minimum 87 octane
/ 87 AKI (91 RON).
For high altitude use, see "Operation at High
Altitude".
Do not use gasoline with more than 10%
alcohol such as E85 or ethanol.
Failure to follow Operator's Manual for fuel
recommendations voids warranty.
Avoid generator damage.
DO NOT use unapproved gasoline such as E85.
DO NOT mix oil in gasoline.
DO NOT modify engine to run on alternate fuels.
WARNING
Fuel and its vapors are extremely flammable
and explosive which could cause burns, fire or
explosion resulting in death, serious injury
and/or property damage.
WHEN ADDING FUEL
Fill fuel tank outdoors.
DO NOT overfill tank. Allow space for fuel
expansion. If the tank is overfilled, fuel
can overflow onto a hot engine and cause fire
or explosion. Wipe up any spilled fuel
immediately.
If fuel spills, wait until it evaporates before
starting engine.
Keep fuel away from sparks, open flames,
pilot lights, heat, and other ignition sources.
Check fuel lines, tank, cap and fittings
frequently for cracks or leaks. Replace if
necessary.
DO NOT light a cigarette or smoke when
filling the fuel tank.
1.Clean area around fuel fill cap, remove cap.
2.Slowly add unleaded fuel to fuel tank. Be
careful not to fill above the red fuel level
indicator . This allows adequate space for
fuel expansion.
3.Install fuel cap and let any spilled fuel
evaporate before starting engine or wipe up
any spilled gasoline.
CAUTION
Slowly add unleaded gasoline to fuel tank.
Do not overfill tank.
Do not fill above top of fuel screen. This
will all expansion in hot weather and
prevent overflow.
Operation at High Altitude
At altitudes over 5,000 feet(1524 meters), a
minimum 85 octane / 85 AKI (89 RON) gasoline
is acceptable.
The density of air at high altitude is lower
than at sea level. Engine power is reduced
as the air mass and air-fuel ratio decrease.
Engine power and generator output will be
reduced approximately 3.5% for every 1000 feet
of elevation above sea level. This is a
natural trend and cannot be changed by
adjusting the engine. At high altitudes
increased exhaust emissions can also result
due to the increased enrichment of the air
fuel ratio.
Other high altitude issues can include hard
starting, increased fuel consumption and
spark plug fouling. To alleviate high
altitude issues other than the natural
power loss, FIRMAN can provide a high
altitude carburetor main jet. The alternative
English Customer Service: 1-844-FIRMAN1
Page 13
Altitude main jet 1
Altitude main jet 2
208cc
335717002
335717003
Altitude
3000-6000Feet
6000-8000Feet
OPEN
WARNING
Grounding
The National Electric Code requires your generator
must be properly connected to an appropriate
ground to help prevent electric shock.
Failure to properly ground the
generator can result in electric
shock.
WARNING
THERE IS A PERMANENT CONDUCTOR BETWEEN
THE GENERATOR (STATOR WINDING) AND THE
FRAME.
Use approved transfer equipment to prevent
backfeed by isolating generator from electric
utility workers.
When using generator for backup power, notify
utility company.
Use a ground fault circuit interrupter (GFCI) in
any damp or highly conductive area, such as
metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords
which are worn,frayed, bare or otherwise
damaged.
DO NOT operate generator in the rain or wet
weather.
DO NOT handle generator or electrical cords
while standing in water, while barefoot, or
while hands or feet are wet.
DO NOT allow unqualified persons or children
to operate or service generator.
Connecting to a Building's Electrical System
WARNING
Generator voltage could cause
electrical shock or burn resulting
in death or serious injury.
The part number and recommended minimum
altitude for the application of the high
altitude carburetor main jet is listed in the
table below.
main jet and installation instructions can be
obtained by contacting Customer Support.
Installation instructions are also available in the
Technical Bulletin area of the FIRMAN internet site.
English Customer Service: 1-844-FIRMAN1
OPERATION
Page 14
Generator Location
Make sure you review each warning in order to
prevent fire hazard.
Keep area clear of inflammables or other
hazardous materials.
Select a site that is dry, well ventilated and
protected from the weather.
Keep exhaust pipe clear of foreign objects.
Keep generator away from open flame.
Keep generator on a stable and level surface.
WARNING
Surge Protection
Voltage fluctuation may impair the proper
functioning of sensitive electronic equipment.
WARNING
POISONOUS GAS HAZARD.
Do not block generator air vents with paper or
other material.
CAUTION
Tilting can cause fuel spillage.
CAUTION
English Customer Service: 1-844-FIRMAN1
Page 15
Starting the Generator
1. Before starting the generator, check for loose
or missing parts and for any damage which
may have occurred during shipment.
2. Check oil level and fuel.
6. Move the choke lever to the “START” position.
5. Flip the engine switch to the “ON(l) position.
8. Do not over-choke. As soon as engine starts
and warms up, move the choke lever to the
RUN” position.
9. Allow generator to run at no load for few
minutes upon each initial start-up to permit
engine and generator to stablize.
WARNING
When starting engine, pull cord slowly until
resistance is felt and then pull rapidly to avoid
kickback.
4. Turn the fuel valve to the “ON” (l)position.
7. Pull the starter cord slowly until resistance is
felt and then pull rapidly.
3. Disconnect all electrical loads from the
generator. Never start or stop the generator
with electrical devices plugged in or turned
on.
English Customer Service: 1-844-FIRMAN1
Keep choke lever in “START” position for only 1
pull of the recoil starter. After first pull, move
choke lever to the “RUNposition for up to the
next 3 pulls of the recoil starter. Too much
choke leads to sparkplug fouling/engine
flooding due to the lack of incoming air. This
will cause the engine not to start.
Page 16
Connecting Electrical Loads
1.Let engine stabilize and warm up for a few
minutes after starting.
2.Ensure circuit breaker on control panel is in
on position.
Stopping the Engine
1. Turn off and remove entire electrical loads.
Never start or stop the generator with
electrical devices plugged in or turned on.
This unit has been pretested and adjusted to
handle its full capacity. Before starting the
generator, disconnect all load. Apply load only
after generator is running. Voltage is regulated
via the engine speed adjusted at the factory for
correct output. Readjusting will void warranty.
CAUTION
When applying a load, do not exceed the maximum
wattage rating of the generator when using one or
more receptacles. Also, do not exceed the amperage
rating of any one receptacle.
Do not apply heavy electrical load during break-in
period (the first five hours of operations).
Let the generator run at no-load for two
minutes to stabilize internal temperatures
of the engine and generator.
2. Press the engine switch to the “OFF(O) position.
3. Turn the fuel valve to the “OFF(O) position.
Do not leave the generator until it has
completely stopped.
English Customer Service: 1-844-FIRMAN1
4.Plug in and turn on the desired 120 or 240 Volt
AC, single phase, 60Hz electrical loads. It is
better to attach the item with largest load first.
3. Turn on voltage selector to desired 120 Volt or
240 Volt. When voltage selector is 120 Volt position,
120 Volt is supplied to 120 Volt outlets including
TT-30R and 5-20R outlets (items 5 and 6 in Control
Panel Section). When voltage selector is in 240 Volt
position, 120/240 Volt is supplied just to outlet
L14-30R (item 3 in Control Panel Section).
Page 17
Do Not Overload Generator
DO NOT stop engine by moving choke control
to “START” position.
Important: Always ensure that the Fuel Valve
and the Engine Switch are in the “OFF” position
when the engine is not in use.
If the engine will not be used for a period of two
weeks or longer, please see the Storage section
for proper engine and fuel storage.
Low Oil Shutdown
If the engine oil drops below a preset level, an
oil switch will stop the engine. Check oil level
with dipstick.
If oil level is between LOW and HIGH mark on
dipstick:
1.DO NOT try to restart the engine.
2.Contact an Authorized FIRMAN Service Dealer.
3.DO NOT operate engine until oil level is
corrected.
If oil level is below LOW mark on dipstick:
1.Add oil to bring level to HIGH mark.
2.Restart engine and if the engine stops again
a low oil condition may still exist. DO NOT try
to restart the engine.
3.Contact an Authorized FIRMAN Service Dealer.
4.DO NOT operate engine until oil level is
corrected.
Overloading a generator in excess of its rated
wattage capacity can result in damage to the
generator and to connected electrical devices.
To prolong the life of your generator and
attached devices, follow these steps to add
electrical load:
1. Start the generator with no electrical load
attached.
2. Allow the engine to run for several minutes
to stabilize.
3. Plug in and turn on the first item. It is best to
attach the item with the largest load first.
4. Allow the engine to stabilize.
5. Plug in and turn on the next item.
6. Allow the engine to stabilize.
7. Repeat steps 5-6 for each additional item.
WARNING
If a cover is used, do not install until unit has cooled.
Fuel and its vapors are extremely flammable
and explosive which could cause burns, fire or
explosion resulting in death, serious injury
and/or property damage.
English Customer Service: 1-844-FIRMAN1
MAINTENANCE AND STORAGE
MAINTENANCE SCHEDULE
Page 18
ITEM NOTES
Daily(Before
operation)
Initial
25 hours
Every
50 hours
Every
100 hours
(or annual)
Fittings/
Fasteners
Spark Plug
Engine Oil
Air Filter
Fuel Filter
Fuel Line
Exhaust
System
Carburetor
Starting
System
Check condition. Adjust gap
and clean. Replace if necessary.
Check oil level.
Clean, replace if necessary.
Clean fuel filter and fuel tank
strainer. Replace if necessary.
Check for leakage. Retighten or
replace gasket if necessary.
Check choke operation.
Check recoil starter operation.
Check. Replace if necessary.
Check fuel hose for cracks or other
damage. Replace if necessary.
General Recommendations
Regular maintenance will improve the performance and extend the life of the generator. See any
authorized dealer for service.
The generator's warranty does not cover items that have been subjected to operator abuse or
negligence. To receive full value from the warranty, the operator must maintain the generator as
instructed in this manual.
Some adjustments will need to be made periodically to properly maintain your generator.
All service and adjustments should be made at least once each season. Follow the requirements
in the Maintenance Schedule chart above.
Notice Once a year you should clean or replace the spark plug and replace the air filter. New
spark plugs and clean air filter assure proper fuel-air mixture and help your engine run better
and last longer.
Replace.
Check spark arrester screen.
Clean/Replace if necessary.
English Customer Service: 1-844-FIRMAN1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102

Firman P03611 Le manuel du propriétaire

Catégorie
Groupes électrogènes
Taper
Le manuel du propriétaire

dans d''autres langues