DigiTrace RAYSTAT-CONTROL-10 Manuel utilisateur

Taper
Manuel utilisateur
RAYSTAT-CONTROL-10
Control thermostat
Thermostat
Thermostat de contrôle
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:141
ENGLISH
Table of contents ........................................................................................................... 2
Description & Technical data..................................................................................... 6
Functional description .................................................................................................. 7
Display ................................................................................................................................. 7
Installation description ................................................................................................. 8
Operational description ................................................................................................ 11
Testing, commissioning and maintenance ......................................................... 14
Wiring diagrams .............................................................................................................. 37
Commissioning sheet ................................................................................................... 39
DEUTSCH
Inhaltsverzeichnis ......................................................................................................... 2
Beschreibung & technische Daten .......................................................................... 16
Funktionsbeschreibung ................................................................................................ 17
Display ................................................................................................................................. 18
Montage .............................................................................................................................. 18
Programmierung ............................................................................................................. 22
Test, Inbetriebnahme und Wartung........................................................................ 25
Anschlussdiagramme.................................................................................................... 37
Inbetriebnahmeprotokoll ............................................................................................. 39
FRANÇAIS
Table des matières ....................................................................................................... 2
Description & caractéristiques techniques ......................................................... 26
Fonctionnement ............................................................................................................... 27
Afficheur .............................................................................................................................. 28
Installation .......................................................................................................................... 29
Paramétrage ...................................................................................................................... 33
Test, mise en service et entretien ............................................................................ 36
Schémas électriques ..................................................................................................... 37
Fiche de mise en service.............................................................................................. 39
RAYSTAT-CONTROL-10
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:142
DEUTSCH
A1.Thermostatgehäuse
2, 3, 4, 5. Einführungen
(2 x M25, 1 x M20, 1 x M16)
6. Temperatursensor Pt 100
7. Sensorkabel
8. Steuerungstasten
9. Digitales Display
FRANÇAIS
A1.Boîtier du thermostat
2, 3, 4, 5. Entrées de câbles
(2 x M25, 1 x M20, 1 x M16)
6. Sonde de température Pt 100
7. Câble de la sonde
8. Touches de programmation
9. Afficheur numérique
ENGLISH
A1.Thermostat enclosure
2, 3, 4, 5 Cable entries
(2 x M25, 1 x M20, 1 x M16)
6. Temperature sensor Pt 100
7. Sensor cable
8. Push buttons
9. Digital display
B1.Schraubendreher 3 mm,
Längsschlitz
2. Schraubendreher 5 mm,
Kreuzschlitz
3. Kabelmesser
4, 5, 6. Schraubenschlüssel
(27 mm, 24 mm, 19 mm)
B1.Terminal screwdriver 3 mm
2. Posi-drive screwdriver 5 mm
3. Trimming knife
4, 5, 6. Spanners
(27 mm,
24 mm, 19 mm)
5
B1.Tournevis 3 mm
2. Tournevis 5 mm
3. Cutter
4, 5, 6. Clés
(27 mm, 24 mm, 19 mm)
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:143
V
D
E
A
8
3
2
4
6
7
5
9a
1
10 20 30 40 50 60 70 80 90
0
9b
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:144
90
100 110 120 130 140 150
160 170 180
mm
B
1.
2.
3.
4.
5.
6.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:145
6
Description
RAYSTAT-CONTROL-10 is an electronic Pt 100 control thermostat with dis-
play, advanced alarm facilities and the capability of switching large currents
(25 A). The RAYSTAT-CONTROL-10 is designed to control Tyco Thermal
Controls heating cable systems. Heating cable can be controlled (switched
ON/OFF) either directly by the RAYSTAT-CONTROL-10 or via a contactor.
Direct switching of heating cables is possible for heating loads up to 25 A.
For heating loads greater than 25 A indirect switching via a suitably rated
contactor controlled by a RAYSTAT-CONTROL-10 is necessary.
Installation and all wiring must be in accordance with applicable regulations.
The device must be installed in non hazardous areas only.
Tyco Thermal Controls offers other controls for use in hazardous areas.
Technical data
Supply voltage: 230 Vac. +10%/–10%, 50/60 Hz (6V leakproof
maintenance-free non-rechargeable battery
incl. for programming without power supply)
Main relay: max. 25 A, 250 Vac. Resistive
Heater operation on
sensor error: programmable: ON or OFF
Hysteresis: programmable: 1K to 5K
Set point T range: 0°C to + 150°C
Accuracy: ±0,5 K at 5°C
Operating Temperature: –40°C to +40°C ambient
User interface: 4 x 7 segment digital display
4 push buttons
alarm relay, max. 2 A, 250 Vac. (Potential free)
Power terminals: 3 x 0,75 mm
2
to 4 mm
2
Alarm terminals: (3 + ) x 0,75 mm
2
to 2,5 mm
2
Sensor terminals: (3 + ) x 0,75 mm
2
to 2,5 mm
2
Heater terminals: (2 + ) x 0,75 mm
2
to 4 mm
2
Enclosure
Exposure Temperature: –40°C to +80°C
Ingress Protection: IP 65
Entries: 2 x M25, 1 x M20, 1 x M16
Size: 120 x 160 x 90 (mm)
Weight: approx. 800 gr.
Material: polycarbonate
Lid fixing: 4 captive screws
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:146
7
Mounting: on a wall or directly on the pipe using support
brackets, SB-100 / SB-101
T sensor /
Type: 3-wire Pt 100 according to IEC Class B
Sensor head: 50 mm x 5 mm
Cable length: 3 m*
Cable diameter: 4 mm
Cable exposure T: –40°C to +150°C
(+215°C intermittent 1000h)
* The sensor cable can be extended with a 3-core shielded cable of 20
max. per conductor (e.g. up to 150 m with a 3x1.5 mm
2
cable).
The shield shall be earthed on the controller side only.
Functional description
During normal operation, the display alternates between the measured tem-
perature and the set point temperature.
When the measured pipe temperature exceeds the programmed setpoint
value plus hysteresis, the switching contact opens and the heating cable is
switched off.
When the measured pipe temperature falls below the setpoint value minus
hysteresis, the switching contact closes. A LED in the display indicates that
the heating cable is switched on.
In the event of an error, the alarm relay switches and an error code shows on
the display. It is possible to program the status of the heating cable (on or
off) in case of a sensor error.
The unit is fitted with a battery so that programming can be done on the
bench prior to mounting in the working location (see Operational description,
page 11).
Display
RAYSTAT-CONTROL-10 has a digital display. The three left hand digits 9a
are the value display and the right hand digit 9b is the status display.
There are 4 different display modes possible:
1. In the normal operation mode (no error condition), the measured tem-
perature or the set point temperature value are displayed in the value dis-
play (alternating).
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:147
8
During the time that the actual measured temperature is shown in the
value display, the X
T
LED in the status display lights up.
When the set point temperature is shown, the W
T
LED in the status dis-
play lights up.
Also during normal operation, the middle horizontal LED in the status dis-
play lights up for the time that the heater (main relay) is ON ( ).
For example: means 20°C measured temperature and heater is
switched on, means set point temperature 24°C and heater is
switched on.
2. In case an error is detected, the value display shows “ ” (flashing)
and the status display indicates the error number (see Errors).
3. Programming is done by means of the push buttons (see Operational de-
scription). In the programming mode, the status display will indicate the
code of the parameter that is selected. The value display indicates the
value for the parameter.
4. When power is initially applied, all display segments will illuminate for a
short period. This will also occur if no mains power is available and the
battery button is pressed. Do not push the battery button when the unit is
powered, as this will shorten battery life.
Installation description
1. Installation of heating cable
For design and selection of heating cables in sanitary applications, follow the
Technical Handbook.
For selection of industrial heating cables, follow the Selection Guide for In-
dustrial Trace-Heating Systems or use the latest version of TraceCalc or con-
tact your Tyco Thermal Controls representative.
Follow the design guidelines and install the system in accordance with the
system specifications.
Follow the “Product Safety Notice” supplied with the heating cable.
Residual current device (RCD 30 mA) is required.
The RAYSTAT-CONTROL-10 is a sensitive electronic device, and should be
installed taking care of common guidelines for EMC interference.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:148
9
2. Mounting of the enclosure
The RAYSTAT-CONTROL-10 can be installed indoor or outdoor.
Do not install the thermostat under the thermal insulation.
A. Wall mounting
Mount the enclosure using wall fasteners (screws) via the four,
4 mm holes.
B. Mounting on a pipe
Tyco Thermal Controls offers different support brackets (not included) to
mount the RAYSTAT-CONTROL-10 on a pipe: SB-100, SB-101.
3. Wiring
Remove the terminal protection cover to access the terminals.
Power cable:
Enter a single phase (230 Vac.) power cable through the M25 gland 2
(see drawing A ) and wire according to the wiring diagram (page 37).
Wiring the heating cable can be done either:
A. Via junction box or contactor or when using RayClic with the cold cable
through the M25 gland 3 .
B. Directly into RAYSTAT-CONTROL-10.
In this case, the M25 gland 3 , which is delivered pre-mounted to the
RAYSTAT-CONTROL-10, is to be replaced by an appropriate kit.
Follow instructions supplied with the kit for installation.
Important: For Voltage Free Operation, the wire links (W1) and (W2) need to
be removed. Failure to remove the wire links can result in damage to the unit
or to other connected equipment. Wiring of RAYSTAT-CONTROL-10 to a re-
mote alarm is optional through the M20 gland 4 . It is strongly recom-
mended to use a remote alarm for critical operations (e.g. when extreme low
temperatures (lower than –25°C) can be expected or for critical processes).
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:149
10
90°
A
B
C
D
20 mm
4. Installation of the sensor
Location
as indicated in the system design documentation
not on valves, flanges, supports, pumps or other heat sinks
at the top of the pipe for thermally sensitive pipe contents (A)
on lower quadrant of pipe 90° for single heating cable (B)
on lower quadrant of pipe centrally between the heating cables if they
are two or more (C)
Attachment of the sensor
–fix sensor firmly on surface with adequate fixing tape (same tape as
used to fix heater to the pipe) in two places (D)
–fix sensor parallel to pipe (D)
route sensor cable and eventual extension cable to avoid damage in use.
Fix to pipe with adequate tape where appropriate.
Warning: Do not install sensor at ambient temperatures below –20°C. Do not
bend sensor (last 50 mm), keep it straight under all circumstances. Min.
bending radius for sensor cable: 10 mm.
Wiring sensor to RAYSTAT-CONTROL-10
Enter the sensor cable through the indicated M16 gland 5 and wire as
shown in the wiring diagram (page 37). Please pay attention to color coding
of the wiring.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1410
11
Remark: The sensor cable can be extended up to 150 m when a cross section
of 3 x 1,5 mm
2
is used (max. 20 per conductor). The connection between
sensor cable and sensor extension can be made in junction box JB-86 or
equivalent. Use a shielded cable for extension to avoid interference. The
shielding braid is to be earthed in the thermostat.
5. Complete installation
A
A
A
Put the terminal protection cover back in place.
If RAYSTAT-CONTROL-10 is not yet programmed, please do so as described
in Operational description (page 11) and onwards.
Close the lid of the unit.
Ensure that the pipe and sensor are thermally insulated and clad to the de-
sign specification after installation of thermostat.
Seal cladding with sealant (A).
Operational description
1. Introduction
The RAYSTAT-CONTROL-10 parameters are configured via a menu system.
The unit is delivered with a battery so that the operating parameters can be
set up without any need for the power supply to be connected. This is useful
for setting units on the bench prior to mounting in their working location or
on site when power isn’t available.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1411
12
Please note that the Battery key ( ) must not be pressed whilst the unit
has the power supply connected. It will cause the battery to discharge imme-
diately. The battery will be disconnected automatically when the last para-
meter has been set.
Once programmed, the settings will be retained even in case of power loss.
2. Activating and navigating the Menu in Set-Up mode
In order to activate the Set-up mode when the unit is not connected to a
mains power supply, press the Battery key ( ) for about 2 sec.
This action will immediately light up all segments of the display, so correct
functioning of the display can be verified. The display will then shortly show
, and switch to the first parameter to be changed.
In order to activate the Set-up mode when the unit is connected to a mains
power supply (the display alternates between the setpoint and actual meas-
ured temperature), press the MENU key for about 2 sec. The display will
shortly show , and switch to the first parameter to be changed.
Stepping through the complete parameter list can be done by successively
pressing the MENU key. When the last parameter has been set, the display
will show , and return to normal operation. In case the unit is not con-
nected to a power supply, the battery will be disconnected.
If the unit is in Set-up mode, but no keys are activated, it will return to the
normal operation (or switch the battery off when the battery is used) after
about 30 sec.
To alter any parameter shown in the display, press the + or – keys. This
will allow the parameter to be raised or lowered to the maximum or the mini-
mum in integer steps.
If you require to reset all parameters to their default value, press the + and
– keys together for about 2 sec. If this is succesful, the display will show
.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1412
13
3. Parameters
The first parameter to show up during Set-up mode is the Set Point. Other
parameters, their default, minimum and maximum values are shown in the
below table:
Parameter Default Displayed Min. Max.
Value Code
Set Point (°C) 5 0 150
Hysteresis (K) 1 1 5
Low Temperature Alarm
0 –40 148
1
Threshold
1
(°C)
High Temperature
65 2
2
150
3
Threshold (°C)
Heater Operation if
10 (OFF) 1 (ON)
Sensor Error
Voltage Free Operation 0 0 (NO) 1 (YES)
1
Max. Low Temp. Alarm is always smaller than Set Point minus hysteresis.
2
Min. High Temp. Alarm is always larger than Set Point plus hysteresis.
3
Consider also max. exp. temp. of heating cable in table,to select an
appropriate High Temp. Alarm value. If one does not want the High Temp.
Alarm to be active, set the value to , which comes after 150.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1413
14
4. Errors
Error Code Description Remedy
Short Circuit Sensor Replace sensor
(or very low resistance)
Open Circuit Sensor Connect sensor cable or
replace sensor
Low Temperature Verify heating system &
Threshold Alarm sensor fixation
High Temperature
1
Verify heating system
Threshold Alarm
Output Voltage Error
2
Relay or triac malfunction /
replace unit
Supply below 207 Vac.
3
Verify supply voltage
1
Detection of this error is disabled if High Temperature Alarm is set off.
2
Detection of this error is disabled in Voltage Free Mode.
3
Unit is not active when supply voltage is below approx. 190 Vac.
All alarms are on the same alarm relay.
An alarm will clear automatically as soon as the error condition is gone.
There is no need to reset; all settings are maintained.
If multiple alarms are active, the alarms are shown with the following priority:
(Highest), , , , , (Lowest)
Testing, commissioning and maintenance
Test heating cable when thermostat installation is complete as directed in the
Tyco Thermal Controls instructions applicable for the heating cable. Fill out
the commisioning sheet (page 39).
Maintain thermostat during normal plant maintenance.
Check: Mounting is firm
Exposed sensor cable is not damaged
Glands are tightened firmly
Thermostat operation is correct (no error code displayed)
Thermostat settings suits application
Lid is closed firmly.
Cladding is sealed with sealant.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1414
15
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1415
16
Beschreibung
Der elektronische Thermostat RAYSTAT-CONTROL-10 ist mit einem digitalen
Display und umfassenden Alarmfunktionen ausgestattet. Er wurde speziell
für elektrische Beheizungen entwickelt und ist für das Schalten von großen
Stromen ausgelegt (25 A).
Die Heizleitung wird entweder direkt über den Thermostat oder über einen
Leistungsschütz ein- und ausgeschaltet. Bei einem Schaltstrom von weniger
als 25 A ist eine Schaltung über den Thermostaten RAYSTAT-CONTROL-10
zu empfehlen. Für einen Schaltstrom von mehr als 25 A enthält der
RAYSTAT-CONTROL-10 einen potentialfreien Kontakt zur Ansteuerung eines
Leistungsschützes.
Die Installation und der Anschluss der Steuerung müssen entsprechend den
örtlich geltenden Bestimmungen erfolgen.
Der Thermostat RAYSTAT-CONTROL-10 darf nicht in explosionsgefährdeten
Bereichen installiert werden. Für explosionsgefährdete Bereiche bietet Tyco
Thermal Controls spezielle Thermostate an.
Technische Daten
Betriebsspannung: AC 230 V, +10%/–10%, 50/60 Hz
(inkl. einem auslaufgeschützten, wartungs-
freien, nicht-wiederaufladbaren 6 V-Akku)
Nennstrom: max. 25 A bei AC 230 V, ohmsche Last
Heizleitung bei
Sensorfehler: Programmierbar: EIN oder AUS
Hysterese: Programmierbar: 1 bis 5 K
Temperaturbereich: 0°C bis +150°C
Schaltgenauigkeit: ±0,5 K bei 5°C
Umgebungstemperatur-
bereich: –40°C bis +40°C
Benutzerschnittstelle: Digitales Display
4 Tasten zur Programmierung
Alarmrelais, Wechlsler potentialfrei,
max. 2 A, AC 230 V
Stromanschluss: 3 Anschlussklemmen für 0,75 bis 4 mm
2
Alarmrelais-Anschluss: 3 Anschlussklemmen (+ ) für 0,75 mm
2
bis 2,5 mm
2
Sensorkabel-Anschluss: 3 Anschlussklemmen (+ ) für 0,75 mm
2
bis 2,5 mm
2
Steuerrelais-Anschluss: 2 Anschlussklemmen (+ ) für 0,75 mm
2
bis 4 mm
2
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1416
17
Gehäuse
Umgebungstemperatur-
bereich: –40°C bis +80°C
Schutzart: IP65
Bohrungen: 2 x M25, 1 x M20, 1 x M16
Abmessungen: 120 x 160 x 90 (mm)
Gewicht: ca. 800 g
Material: Graues Polycarbonat
Deckelbefestigung: 4 x M6, Zylinderkpfschrauben - rostfreier
Stahl, unverlierbar
Montage: Wandmontage oder auf Befestigungswinkel
SB-100, SB-101
Temperatursensor
Typ: in 3-leitertechnik Pt 100 (IEC Class B)
Sensorkopf: 50 mm x 5 mm
Kabellänge: 3 m*
Kabeldurchmesser: 4 mm
Umgebungstemperatur-
bereich: –40°C bis +150°C (kurzzeitig +215°C)
* Das Sensorkabel kann mit einem 3-adrigen abgeschirmten Kabel,
max. 20 je Leiter, verlängert werden
(bis zu 150 m bei einem Leiter-
querschnitt von 3 x 1,5 mm
2
).
Die Erdung ist nur am Thermosteten vorzunehmen.
Funktionsbeschreibung
Bei Normalbetrieb erscheinen im Display abwechselnd die Werte für die ge-
messene Umgebungstemperatur und die eingegebene Haltetemperatur.
Wenn die gemessene Rohrtemperatur die programmierte Haltetemperatur
plus Hysterese übersteigt, öffnet der Schaltkontakt, und die Heizleitung wird
ausgeschaltet.
Wenn die gemessene Rohrtemperatur unter die programmierte Halte-
temperatur minus Hysterese fällt, schließt der Schaltkontakt. Eine LED in der
Statusanzeige zeigt an, dass die Heizleitung eingeschaltet ist.
Bei einer Störung schaltet das Alarmrelais und in der Anzeige erscheint eine
Fehlermeldung. Sie können außerdem eingeben, ob das Heizsystem bei ei-
nem Sensorausfall abschalten oder weiter in Betrieb bleiben soll (EIN oder
AUS).Der Thermostat ist zusätzlich mit einer Batterie ausgestattet, so dass
die Programmierung auch ohne Spannungsversorgung direkt vor Ort vorge-
nommen werden kann (siehe „Programmierung“ auf Seite 21).
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1417
18
Display
Das Thermostat RAYSTAT-CONTROL-10 ist mit einem digitalen Display
ausgestattet. Das dreistellige Display links 9a gibt die Messwerte an, das
Display rechts 9b den Status.
Das Display gibt an, in welchen Betriebszustand sich die Beheizung befindet:
1. Bei normalem Betrieb werden die aktuelle Rohrtemperatur oder der Soll-
wert für die Haltetemperatur im linken Display abwechselnd angezeigt.
Solange die aktuelle Rohrtemperatur angezeigt wird, leuchtet die LED X
T
in der Statusanzeige rechts. Wenn die Haltetemperatur (Sollwert) im lin-
ken Display angezeigt wird, leuchtet die LED W
T
in der Statusanzeige. Im
Normalbetrieb leuchtet auch die LED in der Mitte. Sie zeigt an, dass die
Heizleitung (Hauptrelais) eingeschaltet ist ( ).
Beispiel: bedeutet, es werden aktuell 20°C gemessen, und die
Heizleitung ist eingeschaltet. bedeutet, die Haltetemperatur be-
trägt 24°C, und die Heizleitung ist eingeschaltet.
2. Im Falle einer Störung blinkt im linken Display die Meldung „ “, und
in der Statusanzeige erscheint ein Fehlercode (siehe „Fehlermeldungen“).
3. Die Programmierung erfolgt mit Hilfe der Bedientasten (siehe „Funktions-
beschreibung“). Während der Programmierung erscheint in der Statusan-
zeige der Code für den Parameter, der gerade programmiert wird. Im lin-
ken Display wird gleichzeitig der jeweilige Wert angezeigt.
4. Wird die Spannungsversorgung eingeschaltet, so leuchten alle Segmente
im Display kurzzeitig auf. Dies geschieht auch, wenn keine Spannungs-
versorgung angeschlossen ist und die Batterie-Taste gedrückt wird. Drük-
ken Sie die Batterie-Taste niemals, wenn eine Spannungsversorgung an-
geschlossen ist, da sich sonst die Lebensdauer der Batterie verkürzt.
Montage
1. Montage der Heizleitung
Informationen zur Auswahl und Auslegung von Frostschutzsystemen in der
Bautechnik finden Sie in unserem Technischen Handbuch.
Eine detaillierte Auswahlhilfe für industrielle Beheizungssysteme von Tyco
Thermal Controls finden Sie in unserer Projektierungsanleitung, bzw. in un-
serer speziell entwickelten Planungssoftware „TraceCalc“. Für Fragen zu in-
dividuellen Anwendungen wenden Sie sich bitte direkt an Ihre Tyco Thermal
Controls-Vertretung.
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1418
19
Um die ordnungsgemäße Funktion des Systems sicherzustellen, müssen die
Auslegungsvorschriften und die Montageanleitung exakt befolgt werden. Be-
achten Sie bitte auch das mitgelieferte Sicherheitsdatenblatt.
Hinweis:Es ist ein Fehlerstromschutzschalter (30mA) erforderlich.
Der RAYSTAT-CONTROL-10 ist ein empfindliches elektronisches Gerät und
sollte unter Berücksichtigung der allgemeinen Richtlinien zur elektromagneti-
schen Verträglichkeit (EMV) installiert werden.
Der Thermostat RAYSTAT-CONTROL-10 ist für max. 25 A ausgelegt, die
max.Heizkreislänge ist somit begrenzt. Größere Heizkreislängen können durch
einen potentialfreien Kontakt über ein Leistungsschütz geschaltet werden (es
sind nur entstörte Schütze zu verwenden).
2. Gehäusemontage
Der Thermostat RAYSTAT-CONTROL-10 kann im Freien oder innerhalb von
Gebäuden montiert werden. Montieren Sie das Gerät nicht unter der Wärme-
dämmung!
A. Wandmontage
Für die Wandmontage sind vier Löcher für M4-Schrauben im Gehäuse.
B. Montage auf der Rohrleitung
Tyco Thermal Controls bietet auch Befestigungswinkel (nicht im Lieferum-
fang enthalten) für die Montage auf der Rohrleitung an: SB-100 / SB-101.
3. Anschluss
Entfernen Sie zuerst die Gehäuseabdeckung.
Anschlusskabel
Führen Sie ein einphasiges Anschlusskabel (AC 230 V) durch die dafür vorge-
sehene M25-Verschraubung 2 (siehe Zeichnung A ) und schließen Sie das
Kabel entsprechend dem Anschlussdiagramm auf Seite 37 an.
Heizleitungsanschluss
A. Die Heizleitung kann über einen Anschlusskasten, ein Leistungsschütz oder
mit dem Kaltende des Anschlussmoduls RayClic direkt durch die M25-Ver-
schraubung 3 angeschlossen werden.
B. Die Heizleitung kann auch direkt im Thermostat angeschlossen werden. In
diesem Fall muss die M25-Verschraubung 3 , die bei der Lieferung bereits
an dem Thermostat montiert ist, durch eine entsprechende
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1419
20
Anschlussgarnitur ersetzt werden. Montieren Sie die Anschlussgarnitur
entsprechend der mitgelieferten Montageanleitung.
Hinweis: Für potentialfreien Betrieb müssen die Verbindungskabel (W1 und
W2) entfernt werden, da sonst der Thermostat oder andere, daran ange-
schlossene Komponenten beschädigt werden können. Bei kritischen
Prozessen oder extrem niedrigen Umgebungstemperaturen (unter -25°C)
wird die Verwendung einer externen Alarmeinheit empfohlen. Diese kann
über die M20-Verschraubung 4 direkt am Thermostaten angeschlossen
werden.
4. Sensormontage
Montageort des Sensors
–wie in der Projekt-Auslegung vorgesehen
–nicht in der Nähe von Ventilen, Flanschen, Rohrlagern, Pumpen oder
anderen wärmeabstrahlenden Komponenten, wenn diese ordnungsge-
mäss beheizt werden
bei temperaturempfindlichen Medien: oben auf der Rohrleitung (A)
bei einzelnen Heizleitungen: im unteren Quadranten der Rohrleitung, im
90°-Abstand zur Heizleitung (B)
bei zwei oder mehreren Heizleitungen: im unteren Quadranten der Rohr-
leitung in der Mitte zwischen den beiden Heizleitungen (C)
Befestigung des Sensors
Befestigen Sie den Sensor an zwei Stellen mit Klebeband auf der
Rohrleitung (D)
Befestigen Sie den Sensor parallel zur Rohrleitung (D)
90°
A
B
C
D
20 mm
Ray C F030793 RAYSTAT-Contr-N 18-09-2003, 10:1420
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

DigiTrace RAYSTAT-CONTROL-10 Manuel utilisateur

Taper
Manuel utilisateur