Simplicity 040608-01 Manuel utilisateur

Taper
Manuel utilisateur
Not for
Reproduction
Page | i
Operation Instructions
GC1031 GENSET Controller
Instrucciones de operación
Controlador de GRUPO
ELECTRÓGENO GC1031
Directives d’utilisation
GC1031 GENSET Contrôleur
Copyright © Briggs &Stratton Corporation 80086364
Milwaukee, WI USA. All Rights Reserved. Revision B
Not for
Reproduction
Page | ii
Safety Definitions
For your safety, the safety of others, and to protect the performance of equipment, obey the
warnings in the manual before operation, during operation, and during maintenance procedures.
indicates a potential personal injury hazard.
DANGER
indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
indicates a situation which can cause damage to the equipment, personal property and/or the
environment, or cause the equipment to operate incorrectly.
WARNING
Failure to read, understand and obey the instructions in this manual could result in death or se-
rious injury. Read, understand and obey the instructions in this manual before operating this
product.
Not for
Reproduction
Page | iii
List of Abbreviations and Acronyms
This list contains the abbreviations and acronyms used in this document. Refer to this list for
their respective description.
Acron
y
m Description
AC Alternating Current
ACK Acknowledge
ALT Alternator
AMF Auto Mains Failure
AUX Auxiliary
AVR Automatic Voltage Regulator
CHG Charging
CKT Circuit
CT Current Transformer
DC Direct Current
DIG IN Digital Input
EGov Electronic Governor
ENG TEMP Engine Temperature
GCU Genset Control Unit
Genset Generator Set
GND Ground
GST Gain Schedule Trigger
HMI Human Machine Interface
HSD High Side Driver
HWT High Water Temperature
ID Identifier
LCD Liquid Crystal Display
LED Light Emitting Diode
LIM Low Idle Mode
LLOP Low Lube Oil Pressure
LOP Lube Oil Pressure
LVL Level
MCP Manual Control Panel
MPU Magnetic Pickup Unit
OV Over Voltage
PF Power Factor
PID Proportional Integral Derivative
PWM Pulse Width Modulation
RMS Root Mean Square
RPM Revolutions Per Minute
RTC Real Time Clock
R-Y-B Red-Yellow-Blue
SCP Sensor Common Point
SMD State Machine Diagram
TEMP Temperature
USB Universal Serial Bus
UV Under Voltage
PF Power Factor
AVR Automatic Voltage Regulator
Not for
Reproduction
Page | iv
Table of Contents
Key Highlights of the Product ..................................................................................................... 1
Installation .............................................................................................................................. 1
1
Terminal Description ....................................................................................................... 1
1.1
Description of Control Keys ................................................................................................. 4
2
Functions of Control Keys ............................................................................................. 4
2.1
Configuration of GCU ............................................................................................................ 5
3
List of Parameters ........................................................................................................... 5
3.1
Operating Modes .................................................................................................................. 14
4
Auto Mode ...................................................................................................................... 14
4.1
Auto Mains Failure (AMF)......................................................................................... 14
4.1.1
Remote Start/Stop (2 Wire) ...................................................................................... 16
4.1.2
Auto Exercise Mode ................................................................................................. 16
4.1.3
Manual Mode .................................................................................................................. 17
4.2
Low Idle Mode (LIM) ................................................................................................. 18
4.2.1
Alarms ................................................................................................................................... 19
5
Troubleshooting ................................................................................................................... 21
6
Notes ............................................................................................................................................ 24
Not for
Reproduction
Page | v
List of Figures
Figure 1: GC1031 Genset controller from the backside ................................................................. 1
Figure 2: Control key function ........................................................................................................ 4
Figure 3: Configuration mode screen ............................................................................................. 5
Figure 4: Configuration mode authentication page screen ............................................................ 5
Figure 5: Saving settings screen .................................................................................................... 5
Figure 6: SMD for AMF mode ....................................................................................................... 15
Figure 7: SMD for auto exercise mode ........................................................................................ 17
Figure 8: SMD for manual mode .................................................................................................. 18
Not for
Reproduction
Page | vi
List of Tables
Table 1: Voltage input terminology ................................................................................................. 2
Table 2: Details of the GC1031 terminals ....................................................................................... 2
Table 3: Control keys in different modes ........................................................................................ 4
Table 4: Parameters ....................................................................................................................... 5
Table 5: Alarm actions .................................................................................................................. 19
Table 6: Alarms and their causes ................................................................................................. 19
Table 7: Common faults and their remedial actions ..................................................................... 21
Not for
Reproduction
Page | 1
Key Highlights of the Product
Auto, Manual and Remote Start /Stop Modes for 1-phase & 3-phase gensets
Electronic governor controller integration
RPM sensing using frequency and MPU
Supports Auto Exercise Modes
Real time clock-based event logs
PC connectivity via USB port, RS485, CAN J1939 protocol
Backlit and full graphics display with power saving feature
Installation
1
Terminal Description
1.1
The figure that follows shows the rear view of the controller.
Figure 1: GC1031 Genset controller from the backside
Not for
Reproduction
Page | 2
Table 1: Voltage input terminology
Sr. No. System Terminology 1 Terminology 2
1
1 Phase 2 wire R-N L1-N
2
1 Phase 3 wire R-Y-N L1-L2-N
3
3 Phase 4 wire R-Y-B-N L1-L2-L3-N
Table 2: Details of the GC1031 terminals
Sr.
No.
Name Description
1
BATT - Battery negative
2
BATT + Battery positive
3
OUT A High side driver output – A
4
OUT B High side driver output – B
5
OUT C High side driver output – C
6
OUT D High side driver output – D
7
D+ CHG ALT Reserved
8
OUT E High side driver output – E
9
OUT F High side driver output – F
10
DIG_IN A Input from switch – A
11
DIG_IN B Input from switch – B
12
DIG_IN C Input from switch – C
13
CAN H CAN high
14
CAN L CAN low
15
RS485_B RS485 – B
16
RS485_A RS485 – A
17
GOV_ACT – OUT1 Output for the Actuator – 1
18
GOV_ACT – OUT4 Output for the Actuator – 4
19
GOV_ACT – OUT2 Output for the Actuator – 2
20
GOV_ACT – OUT3 Output for the Actuator – 3
21
DIG_IN D Input from switch – D
22
DIG_IN E Input from switch – E
23
ANLG_V IN Analog input 4-20mA for LOP or 2.5 ± 2V
24
ANLG_IN ENG_TEMP
Analog input from Engine Temperature
Sensor
25
ANLG_IN Fuel Level Analog input from Fuel Level Sensor
26
ANLG_IN LOP
Analog input from Lube Oil Pressure
Sensor
27
GEN_V IN NTRL Voltage input from Gen Neutral
28
GEN_V IN B Voltage input from Gen B / L3
29
GEN_V IN Y Voltage input from Gen Y / L2
30
GEN_V IN R Voltage input from Gen R / L1
31
MAINS_V IN NTRL Voltage input from Mains Neutral
32
MAINS_V IN B Voltage input from Mains Phase B / L3
33
MAINS_V IN Y Voltage input from Mains Phase Y / L2
34
MAINS_V IN R Voltage input from Mains Phase R / L1
Not for
Reproduction
Page | 3
Sr.
No.
Name Description
35
CT – IN B1 CT input 1 from Phase B / L3
36
CT – IN B2 CT input 2 from Phase B / L3
37
CT IN Y1 CT input 1 from Phase Y / L2
38
CT IN Y2 CT input 2 from Phase Y / L2
39
CT – IN R1 CT input 1 from Phase R / L1
40
CT – IN R2 CT input 2 from Phase R / L1
41
SENSOR COMM Sensor common point
42
MPU I/P (Speed
Sensor)
Input from engine speed sensor (Inductive)
Not for
Reproduction
Page | 4
Description of Control Keys
2
Figure 2: Control key function
1. Menu Navigation Up key
2. Menu Navigation Down key
3. Stop/Config key
4. Start/Select key
5. Auto/Manual Mode selection key
Functions of Control Keys
2.1
The table that follows gives a brief overview of different functions of control keys in different modes.
Table 3: Control keys in different modes
# Mode Key input Function
1
Manual
Start Starts the engine in LIM
Start+Start Exits LIM and operates at normal speed
2
Manual
Auto Enters Auto Mode
Stop Stops the engine when engine is running
Stop (long pressed) Enters Configuration Mode
Stop + Down (long pressed) Enters Programming Mode
3
Auto Stop Stops the engine and enters Manual Mode
4
Manual/Auto/
Configuration
Up/Down Scrolls the screens/parameter
5
Manual/Auto Up + Down Acknowledges and clears the alarm
6
Configuration
Start Selects/saves the parameter
7
Up + Down (long pressed) Enters on event log page
8
Stop (long pressed) Back to Manual Mode
9
Event log Up + Down (long pressed) Back to Configuration Mode
10
Programming Up + Down (long pressed) Controller enters in Application Mode
1
3
2
4
5
Not for
Reproduction
Page | 5
Configuration of GCU
3
To configure the controller, please do the instructions that follow:
To enter the configuration mode, push and hold the “STOP” key for at least 3 seconds. The
following screen will appear on the GCU:
Figure 3: Configuration mode screen
If you want to only view the configuration, push the “STOP” key on the GCU. If you wish to
change the configuration, push the “START” key on the GCU.
Figure 4: Configuration mode authentication page screen
The GCU will ask for a password (0000). Enter the password by using the up & down arrow key
for changing the digit and the “START” key for selecting the digit. The 4 digits will start blinking
individually as each one is selected. Press the “START” button as mentioned earlier to enter the
correct digit.
After completion of the parameter configuration, push and hold the “STOP” key to exit from
configuration mode. Before exiting from the configuration mode the controller will show the
following screen:
Figure 5: Saving settings screen
List of Parameters
3.1
The table that follows gives a brief overview of configurable parameters in GC1031 controller.
Table 4: Parameters
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
Module
(MODULE)
General
(GENERAL)
* Power On Mode
(POWER ON MODE)
Manual/Auto
* Power On Lamp Test
(POWER ON LAMP TEST)
Disable/Enable
Load Histogram
(LOAD HISTOGRAM)
Disable/Enable
Auto-Clear Warning Alarm
(WARNING AUTO CLEAR)
Disable/Enable
Language
(LANGUAGE)
English
Not for
Reproduction
Page | 6
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
Display
(DISPLAY)
Contrast
(CONTRAST)
0 – 100 %
Power Save Mode
(POWER SAVE MODE)
Disable/Enable
Communication
(COMMUNICATION)
Communication Mode
(COMM MODE)
None/MODBUS
* Slave ID
(MODBUS SLAVE ID)
1 – 247
* Baudrate
(MODBUS BAUDRATE)
1200/2400/4800/9600/19200/
38400/57600/115200 bps
* Parity Bit
(PARITY BIT)
None/Even/Odd
Auto Exercise
(AUTO EXERCISE)
Exercise Option
(EXER OPTN)
No Exercise/Standard
Exercise
Cycle
(EXER CYCLR)
No run/0.1/5/10/15/20 min run
Event Occurence
(EXER EVENT OCCR)
Weekly/Monthly
Event Day
(EXER EVENT DAY)
Weekdays/1 – 28 days
Start Time
(EXER START TIME)
00:00 – 23:59 hour
Exercise Skip Enable
(EXER SKIP ENABLE)
Yes/No
45 min Burn Off
(45 MIN BURN OFF)
45 min Burn Off
(45 MIN BURN OFF)
Disable/Enable
Event Month
(EVENT MONTH 1)
March/April/May/None
Event Day
(EVENT DAY 1)
1 - 28
Start Time
(EVENT START TIME 1)
00:00 – 23:59 hour
Event Month
(EVENT MONTH 2)
August/September/
October/None
Event Day
(EVENT DAY 2)
1 - 28
Start Time
(EVENT START TIME 2)
00:00 – 23:59 hour
Digital Inputs
(INPUTS)
Digital Input X
(DIG IN X)
X= A/B/C/D/E
* Source
(SOURCE)
* Polarity
(POLARITY)
Close to Activate/Open to
Activate
* Action
(ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Activation
(ACTIVATION)
Never/From Engine Start/
From Monitoring On/Always
* Activation Delay
* (ACTIVATION DELAY)
1 – 60 sec
Analog Inputs
Analog Input 1
* Use Input As
Not used/Digital Input G/Anlg
Not for
Reproduction
Page | 7
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
(AMB TEMP/DIG G) (USE INPUT AS) In Amb Temp
* Circuit Fault Action
(CKT FAULT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Ambient Temperature Sensor
Calibration Table
Analog Input 2
(FUEL LVL/DIG H)
* Use Input As
(USE INPUT AS)
Not used/Digital Input H/Anlg
In Fuel LVL
* (Digital) Source
((DIG) SOURCE)
* (Digital) Polarity
((DIG) POLARITY)
Close to Activate/Open to
Activate
* (Digital) Action
((DIG) ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* (Digital) Activation
((DIG) ACTIVATION)
Never/From Engine Start/
From Monitoring On/Always
* (Digital) Activation Delay
((DIG) ACTIVATION DELAY)
1 – 60 sec
* Low Fuel Level Shutdown
(SHUTDOWN)
Disable/Enable
* Low Fuel Level Shutdown
Threshold
(SHUTDOWN THRESHOLD)
0 – 78 %
* Low Fuel Level Notification
(NOTIFICATION)
Disable/Enable
* Low Fuel Level Notification
Threshold
(NOTIFICATION THRESH)
2 – 80 %
* Fuel Tank Capacity
(FUEL TANK CAPACITY)
2 – 1000 litre
* Fuel Theft Warning
(FUEL THEFT ALARM)
Disable/Enable
* Fuel Theft Alarm Threshold
(FUEL THEFT THRESHOLD)
1 – 100 % per hour
* Circuit Fault Action
(CKT FAULT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Fuel Sensor Reference
(FUEL SENSOR REFERENCE)
Engine Body/Battery Negative
* Fuel Level Sensor Calibration
Table
Analog Input 3
(LOP RES/ DIG F)
* Use Input As
(SENSOR SELECTION)
Not used/Digital Input F/Anlg
In LOP
* (Digital) Source
((DIG) SOURCE)
* (Digital) Polarity
((DIG) POLARITY)
Close to Activate/Open to
Activate
* (Digital) Action
((DIG) ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* (Digital) Activation
((DIG) ACTIVATION)
Never/From Engine Start/
From Monitoring On/ Always
* (Digital) Activation Delay
1 – 60 sec
Not for
Reproduction
Page | 8
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
((DIG) ACTIVATION DELAY)
* Low Level Shutdown
(SHUTDOWN)
Disable/Enable
* Low Level Shutdown Threshold
(SHUTDOWN THRESHOLD)
0.0 – 9.8 bar
* Low Level Warning
(WARNING)
Disable/Enable
* Low Level Warning Threshold
(WARNING THRESHOLD)
0.2 – 10.0 bar
* Circuit Fault Action
(CKT FAULT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Lube Oil Pressure Sensor
Calibration Table
Analog Input 4
(LOP CURR/ DIG I)
* Use Input As
(SENSOR SELECTION)
Not used/Digital Input I/Anlg
In LOP(4 – 20mA)
* (Digital) Source
((DIG) SOURCE)
* (Digital) Polarity
((DIG) POLARITY)
Close to Activate/Open to
Activate
* (Digital) Action
((DIG) ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* (Digital) Activation
((DIG) ACTIVATION)
Never/From Engine Start/
From Monitoring On/ Always
* (Digital) Activation Delay
((DIG) ACTIVATION DELAY)
1 – 60 sec
* Shutdown
(SHUTDOWN)
Disable/Enable
* Shutdown Threshold
(SHUTDOWN THRESHOLD)
0.0 – 9.8 (0.0 – 9.8 Bar)
* Warning
(WARNING)
Disable/Enable
* Warning Threshold
(WARNING THRESHOLD)
0.2 – 10.0 (0.2 – 10.0 Bar)
* Circuit Fault Action
(CKT FAULT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Lube Oil Pressure Sensor
Calibration Table
Outputs
(OUTPUTS)
Output X
(OUT X)
X= A/B/C/D/E/F
* Source
(SOURCE)
* On Activation
(ON ACTIVATION)
Energize/De-energize
Timers
(TIMERS)
Cranking
(CRANKING
TIMER)
* Crank Hold Time
(CRANK HOLD TIME)
3 – 15 sec
* Crank Rest Time
(CRANK REST TIME)
2 – 60 sec
* Manual Start Delay
(MANUAL START DELAY)
0 – 30 sec
* Auto Start Delay
(AUTO START DELAY)
0 – 43200 sec
General Timer
* Safety Monitoring Delay
10 – 60 sec
Not for
Reproduction
Page | 9
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
(GENERAL TIMER)
(SAFETY MONITOR DELAY)
Mains Detect Delay
(MAINS DETECT DELAY)
1 – 300 sec
* Alternator Detect Delay
(ALT DETECT DELAY)
1 – 60 sec
Warm-Up Delay
(WARM UP DELAY)
0 – 60 sec
Return To Mains Delay
(RETN-TO-MAINS DELAY)
0 – 600 sec
* Engine Cooling Time
(ENG COOL TIME)
0 – 300 sec
* Stop Action Time
(STOP ACTION TIME)
10 – 120 sec
* Additional Stopping Time
(ADDN STOPPING TIME)
0 – 120 sec
Load Transfer Delay
(LOAD TRANSFER DELAY)
0 – 60 sec
Power Save Mode Delay
(PWR SAVE MODE DELAY)
5 – 1800 sec
Sounder Alarm Time
(SOUNDER ALARM TIMER)
1 – 300 sec
Auto Exit Config Mode
(AUTO EXIT CNFG TMR)
10 – 1800 sec
Generator
(GENERATOR)
Alternator
Configuration
(ALT CONFIG)
* Alternator Present
(ALT PRESENT)
No/Yes
* Number Of Poles
(NUMBER OF POLES)
2/4/6/8
* AC system
(ALT AC SYSTEM)
Single Phase 2 Wire/ Single
Phase 3 Wire/ Three Phase 4
Wire (1Ph 2 wire/1Ph 3
wire/3Ph 4 wire)
* Min Healthy Voltage
(MIN HEALTHY VOLT)
50 – 350 Volt Ph-N
* Min Healthy Frequency
(MIN HEALTHY FREQ)
10 – 75 Hz
* Phase Reversal Detection
(PHASE REVERSE DETECT)
Disable/Enable
* Phase Reversal Action
(PHASE REVERSE ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Auto Load Transfer
(AUTO LOAD TRANSFER)
Disable/Enable
* Genset Nominal Voltage
(NOMINAL VOLTAGE (L-L))
100 – 650 Volt L-L
* Genset Nominal Frequency
(NOMINAL FREQUENCY)
10.0 – 75.0 Hz
Voltage Monitoring
(VOLT MONITOR)
* Under-voltage Shutdown
(UNDER VOLT SHUTDOWN)
Disable/Enable
* Under-voltage Shutdown
Threshold
(UV SHUTDWN THRESHLD)
50 – 295 Volt Ph-N
Not for
Reproduction
Page | 10
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
* Under-voltage Warning
(UNDER VOLT WARNING)
Disable/Enable
* Under-voltage Warning
Threshold
(UV WARNING THRESHOLD)
55 – 300 Volt Ph-N
* Over-voltage Shutdown
(OVER VOLT SHUTDOWN)
Disable/Enable
* Over-voltage Shutdown
Threshold
(OV SHUTDWN THRESHLD)
105 – 350 Volt Ph-N
* Over-voltage Warning
(OVER VOLT WARNING)
Disable/Enable
* Over-voltage Warning
Threshold
(OV WARNING THERSHOLD)
100 – 345 Volt Ph-N
Frequency
Monitoring
(FREQ MONITOR)
* Under-frequency Shutdown
(UNDER FREQ SHUTDOWN)
Disable/Enable
* Under-frequency Shutdown
Threshold
(UF SHUTDWN THRESHLD)
10.0 – 59.0 Hz
* Under-frequency Warning
(UNDER FREQ WARNING)
Disable/Enable
* Under-frequency Warning
Threshold
(UF WARNING THRESHOLD)
11.0 – 60.0 Hz
* Over-frequency Shutdown
(OVER FREQ SHUTDOWN)
Disable/Enable
* Over-frequency Shutdown
Threshold
(OF SHUTDWN THRESHLD)
26.0 – 75.0 Hz
* Over-frequency Warning
(OVER FREQ WARNING)
Disable/Enable
* Over-frequency Warning
Threshold
(OF WARNING THRESHOLD)
25.0 – 74.0 Hz
Current Monitoring
(CURRENT
MONITOR)
* CT Ratio
(CT RATIO)
0 – 8000 / 5
* Over-current Action
(OVER CURR ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Over-current Threshold
(OVER CURR THRESHOLD)
5 – 10000 Amp
* Over-current Delay
(OVER CURR DELAY)
1 – 600 sec
* CT Location
(CT LOCATION)
On Load Cable/On Alt Output
Cable
Load Monitoring
(LOAD MONITOR)
* Generator Rating
(GEN RATING)
0 – 8000 kW
* Over-load Action
(OVERLOAD ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Over-load Threshold
(OVERLOAD THRESHOLD)
50 – 150 %
Not for
Reproduction
Page | 11
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
* Over-load Monitoring Delay
(OVERLOAD MON DELAY)
1 – 600 sec
* Unbalanced Load Action
(UNBAL LOAD ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Unbalanced Load Threshold
(UNBAL LOAD THRESHOLD)
5 – 200 %
* Unbalanced Load Delay
(UNBAL LOAD DELAY)
1 – 600 sec
* Extended Over-load Trip
(EXT OL TRIP)
Disable/Enable
* Extended Over-load Trip
Threshold
(EXT OL THRESHOLD)
50 – 150 %
Mains
(MAINS)
Configuration
(MAINS CONFIG)
Mains Monitoring
(MAINS MONITORING)
Disable/Enable
* Mains AC system
(MAINS AC SYSTEM)
Single Phase 2 Wire/Single
Phase 3 Wire/Three Phase 4
Wire (1Ph 2 wire/1Ph 3 wire
/3Ph 4 wire)
* Phase Reversal Detection
(PHASE REVERSE DETECT)
Disable/Enable
* Phase Reversal Action
(PHASE REVERSE ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
Under-voltage
Monitoring
(UNDER VOLT
MON)
* Under-voltage
(ENABLE)
Disable/Enable
* Trip
(TRIP)
50 – 298 Volt Ph-N
* Return
(RETURN)
52 – 300 Volt Ph-N
Over-voltage
Monitoring
(OVER VOLT MON)
* Over-voltage
(ENABLE)
Disable/Enable
* Trip
(TRIP)
102 – 350 Volt Ph-N
* Return
(RETURN)
100 – 348 Volt Ph-N
Under-frequency
Monitoring
(UNDER FREQ
MON)
* Under-frequency
(ENABLE)
Disable/Enable
* Trip
(TRIP)
10.0 – 59.0 Hz
* Return
(RETURN)
11.0 – 60.0 Hz
Over-frequency
Monitoring
(OVER FREQ MON)
* Over-frequency
(ENABLE)
Disable/Enable
* Trip
(TRIP)
26.0 – 75.0 Hz
* Return
(RETURN)
25.0 – 74.0 Hz
Engine
(ENGINE)
Crank Disconnect
(CRANK DISCON)
* Start Attempts
(START ATTEMPTS)
1 – 9
* Disconnect On Oil Pressure
Disable/Enable
Not for
Reproduction
Page | 12
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
Sensor
(DISCONN ON LOP SENS)
* Pressure Sensor Monitoring
Threshold
(DISCONN LOP THRESH)
0.5 – 10.0 bar
* Monitor Pressure Switch Before
Crank
(MON LLOP BEFR CRANK)
Disable/Enable
* Monitor Pressure Sensor Before
Crank
(MON LOP BEFR CRANK)
Disable/Enable
* Disconnect On Oil Pressure
Switch
(DISCONN ON LLOP SW)
Disable/Enable
* Pressure Switch Transient Time
(LLOP SW TRANS TIME)
0.0 – 3.0 sec
* Crank Disconnect At Alt
Frequency
(DISCONN AT ALT FREQ)
10 – 70 Hz
* Crank Disconnect At Engine
Speed
(DISCONN AT ENG SPEED)
150 – 4000 rpm
Speed Monitoring
(SPEED MONITOR)
* Engine Speed Sense Source
(SPEED SENSE SOURCE)
Sensor input only/
Alternator output only/
Primary Sensor/Secondary
Alternator/
Primary Alternator/Secondary
Sensor
* Flywheel Teeth
(FLYWHEEL TEETH)
1 – 300
* Under-speed Shutdown
(UNDER SPEED SHUTDOWN)
Disable/Enable
* Under-speed Threshold
(UNDER SPD THRESHOLD)
0 – 3600 rpm
* Under-speed Delay
(UNDER SPD DELAY)
1 – 60 sec
* Over-speed Threshold
(OVER SPD THRESHOLD)
700 – 4500 rpm
* Over-speed Delay
(OVER SPEED DELAY)
0.1 – 20 sec
* Gross Over-speed Threshold
(GROSS OS THRESHOLD)
100 – 200 %
Battery Monitoring
(BATTERY
MONITOR)
* Low Battery Voltage Action
(LOW VOLT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
* Low Battery Voltage Threshold
(LOW VOLT THRESHOLD)
8.0 – 31.0 volt
* Low Battery Voltage Delay
(LOW VOLT DELAY)
5 – 1800 sec
* High Battery Voltage Action
(HIGH VOLT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
Not for
Reproduction
Page | 13
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
* High Battery Voltage Threshold
(HIGH VOLT THRESHOLD)
9.0 – 32.0 volt
* High Battery Voltage Delay
(HIGH VOLT DELAY)
5 – 1800 sec
Maintenance
(MAINTENANCE)
Maintenance Alarm
(MAINT ALARM)
Alarm Action
(ACTION)
Notification/Warning
Due At Engine Hours
(DUE AT ENGINE HOURS)
10 – 65000 Hrs
Alarm Due Date
(ALARM DUE
DATE)
Alarm Due Date DD/MM/YYYY
Rotary Actuator
(ROTARY
ACTUATOR)
General
(GENERAL)
* Actuator Application
(ACTUATOR APPLN)
As E-Governor/As Start / Stop
Device
* Actuator Speed
(ACTUATOR SPEED)
1 – 10 x 25 Hz
* Actuator Direction
(ACTUATOR DIRECTION)
(Clockwise/Anti–Clockwise) to
Stop
Engine Start
Strategy
(ENG START
STRGY)
* Cranking Steps
(CRANKING STEPS)
5 – 5000
* Initial Low Speed Delay
(INIT LOW SPEED DELAY)
0 – 180 sec
* Initial Low Speed
(INIT LOW SPEED)
500 – 1800 RPM
* PID Trigger Speed
(PID TRIGGER SPEED)
20 – 2800 RPM
* Ramp Up Time
(RAMP UP TIME)
1 – 180 sec
* PID on Time
(PID ON TIME)
1 – 180 sec
* LIM P Gain
(LIM P GAIN)
0 – 1000
* LIM I Gain
(LIM I GAIN)
0 – 2000
* LIM D Gain
(LIM D GAIN)
0 – 1000
* Cold Sweep Enable
(COLD SWEEP ENABLE)
Yes/No
* Cold Sweep Angle
(COLD SWEEP ANGLE)
0 – 180 Deg
Generator EGov
Configuration
(GEN EGOV CNFG)
* Set Speed Selection
(SET SPEED SELECTION)
Fixed Speed(0% Droop)/
Speed Bias Input (0-5 V)/
Load Based Droop
* Droop
(DROOP)
0 – 4 %
* Target Speed
(TARGET SPEED)
500 – 4000 RPM
* Proportional Gain (Kp)
(PROPORTIONAL GAIN)
0 – 1000
* Integral Gain (Ki)
0 – 2000
Not for
Reproduction
Page | 14
Level 0 Level 1 (On screen) Level 2 (On screen) Parameters (On screen)
(INTEGRAL GAIN)
* Derivative Gain (Kd)
(DERIVATIVE GAIN)
0 – 1000
* Friction Setoff
(FRICTION SETOFF)
0 – 1000
* Gain Schedule Trigger
(GAIN SCHEDULE TRIGGER)
0.0 – 100.0 %
* Loading Factor
(LOADING FACTOR)
0 – 1000
* Unloading Factor
(UNLOADING FACTOR)
0 – 1000
Start/Stop
Configuration
(STR/STP DEV
CNFG)
* Running Steps
(RUNNING STEPS)
0 – 500
(MISC SETTINGS)
PASSWORD 1
* ####
0 – 9 for each digit
PASSWORD 2 #### 0 – 9 for each digit
PASSWORD 3 #### 0 – 9 for each digit
(RESET
COUNTERS)
(GENSET)
* (RUN TIME)
(In hours)
(NO. OF STARTS) (In numbers)
(NO. OF TRIPS) (In numbers)
(SELECT PROFILE)
(SELECT PROFILE) (Profile Name) A – Z, 0 – 9
(DATE AND TIME)
(DATE) (DD / MM / YYYY) 0 – 9 for each digit
(TIME) (Hours) (In hours)
(ACTUATOR TEST)
(ACTUATOR TEST)
(ENABLE) Yes/No
(TEST DURATION) 0 – 10 sec
* Note: Certain parameters can only be changed by the dealer while others can only be changed by the
manufacturer (designated by an *). Some default parameters are subject to change during firmware updates
per the manufacturer. The dealer password is available on the Briggs and Stratton
®
Power Portal.
Operating Modes
4
There are two modes of operation:
Auto Mode
Manual Mode
Auto Mode
4.1
To enter Auto Mode, push the “AUTO” key. While in Auto Mode, the generator will start and run under
any one of these conditions:
Auto Mains Failure (AMF)
Remote Start/Stop (2 Wire)
Auto Exercise
Auto Mains Failure (AMF)
4.1.1
When the Mains Monitoring is enabled (default setting) in the Mains configuration and the controller is
in the Auto Mode, AMF mode gets activated.
In this mode, if the Mains is healthy, the genset remains in the OFF condition. When the Mains voltage
drops below a certain threshold, the controller gives a start command. Once the genset is started and
its loading parameters reach the threshold values, the genset contactor is latched and the load is
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

Simplicity 040608-01 Manuel utilisateur

Taper
Manuel utilisateur