Install the S66 block onto
the S89-type bracket.
S66M1-50 Installation Instructions
Route the horizontal, or
backbone cables inside the
S89 bracket and feed the cables
out either the right or the left side
of the bracket as needed.
2
Terminate each conductor
using an S814 impact tool or
equivalent.
Note: It is important to keep the S814 tool
perpendicular to the block when terminat-
ing the conductors. Twisting of the S814
tool while terminating can result in bent
pins and subsequent damage to the S66
block.
6
Label each block on the fan-
ning strip, designation
strips, or cover as appropriate.
7
Cross-connect wires should
be installed through the
same slot in the fanning strip as
the horizontal or backbone cable
pairs.
8
3
Route each pair through the
same slot in the fanning strip
in its mated state. Separate the con-
ductors of each pair inside the fanning
strip and place in the appropriate
quick clips. Pair twist must be main-
tained to within .05 in. of the point of
termination for category 5e installa-
tions. Check the conductor sequence
at this point and correct any miswires
or reversals.
5
Strip back only as much
cable jacket as is necessary
to terminate the conductors.
Note: Common practice prior to the emer-
gence of category 5/5e cable was to strip
back the cable jacket to the side of the
block so that no jacket was visible. This
practice is not recommended when
installing systems where category 5e per-
formance is required. The cable jacket
should be left on the cable as close to point
of termination as possible.
4
Mount an S89-type bracket
firmly on a properly prepared
plywood wall using two wood
screws; or alternately mount on a
Siemon cross-connect frame.
1
INS_100.2777_G_S66M1_50_G 2/12/15 9:54 AM Page 1