16
Low Voltage (Generator, FC_3)
This fault is indicated by fault code FC_3 and three blinks on
the LED indicator. This condition is caused by a restriction
in the fuel flow, a broken or disconnected signal lead, a
failed alternator winding, the control panel circuit breaker is
open, or the generator is overloaded.To remedy the problem,
contact your installer or a GE Authorized Dealer.
Engine Fail To Start (FC_4)
This fault is indicated by fault code FC_4 and four blinks on
the LED indicator. This feature prevents the generator from
damaging itself if it continually attempts to start in spite
of another problem, such as no fuel supply. Each time the
system is directed to start, the unit will crank for 10 seconds,
pause for 10 seconds, and repeat. If the system does not
begin producing electricity after approximately 2 minutes,
the unit will stop cranking and the LED will blink.
Check to make sure the generator’s circuit breaker is in the
ON position in order for the sensing leads to verify that the
unit is running.
The most likely cause of this problem is no fuel supply. Check
the internal and external fuel shut off valves to ensure they
are fully open. Other causes could be failed spark plug(s),
failed engine ignition, or the engine air filter is clogged. You
may need to contact your installer for assistance if you can’t
remedy these problems.
Low Frequency (FC_5)
This fault is indicated by fault code FC_5 and five blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if the
engine runs slower than 55 Hz for three seconds.
This condition is caused by a failed engine component or by
excessive loads on the generator. To remedy the problem,
contact your installer or an authorized dealer.
Engine Overspeed (FC_6)
This fault is indicated by fault code FC_6 and six blinks on the
LED indicator. This feature protects devices connected to the
transfer switch by shutting the generator down if the engine
happens to run faster than the preset limit.
The overspeed fault is detected as follows:
• Ifthegeneratoroutputfrequencyis65-70Hz,after
three seconds, the generator will shut down.
• Ifthegeneratoroutputfrequencyisgreaterthan
70 Hz, the generator will shut down immediately.
This condition is caused by a failed engine component.
To remedy the problem, contact your installer or an
authorized dealer.
High Temperature (FC_7)
This fault is indicated by fault code FC_7 and seven blinks on
the LED indicator. The contacts of the temperature switch
are normally open. If the engine temperature exceeds
approximately 115°C (240°F), the fault is detected and the
engine shuts down.
Common causes for this condition include running the
unit with all access doors removed, obstructed air inlet or
exhaust port, low oil or coolant level, or debris in the engine
compartment or radiator.
To resolve the problem, let the engine cool down and remove
any accumulated debris and obstructions. Ensure that the
access doors are installed whenever the unit is running.To
remedy the problem, contact your installer or an
authorized dealer.
Transfer Switch Fault (FC_8)
This fault is indicated by fault code FC_8 and eight blinks
on the LED indicator (if transfer switch is equipped with
fault detection).
The most likely cause of this fault is a blown fuse in the
transfer switch. To remedy the problem, contact your installer
or an authorized dealer.
Over Voltage (FC_9)
This fault is indicated by fault code FC_9 and nine blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if the
generator output voltage happens to increase above the
preset limit.
The overvoltage fault is detected as follows:
•Ifthegeneratoroutputvoltageisover264voltsfor
240VAC, the generator will shut down immediately.
This condition is most likely caused by a failed voltage
regulator, alternator excitation circuit or a load imbalance. To
remedy the problem, contact your installer or an
authorized dealer.
ENG-
The engine is equipped with on-board diagnostics that
monitor the operation of emission related components. If
an emission related problem has been detected, the system
control panel display will alternate between run hours and
ENG- in three second intervals while the generator is running.
If ENG- displays while the generator is running, a diagnostic
trouble code may be set or a problem may exist in the
system which has caused the engine emissions to go outside
the standards certified by the Environmental Protection
Agency. It is the responsibility of the operator to contact an
authorized service technician to repair this condition.