200 Amp Automatic Transfer Switch
with Service Disconnect and AC Control Module™
Installation & Operator’s Manual
NOT
for
REPRODUCTION
2 BRIGGSandSTRATTON.COM
Copyright © 2013. Briggs & Stratton Power Products Group, LLC
Milwaukee, WI, USA. All rights reserved.
Briggs & Stratton Power Products is a registered
trademark of Briggs & Stratton Corporation
Milwaukee, WI, USA
Thank you for your purchase of this Briggs & Stratton® Power Products automatic transfer switch. This product is designed
for use with specific home standby generators and may not function with generators produced by other manufacturers. Seek
a qualified electrical professional to determine applicability of this equipment to generators manufactured by others. When
operated and maintained according to the instructions in this manual, your power management system will provide many
years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with this system and how to
avoid them. We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation
is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be
achieved. We do not know all possible hazards and/or the results of each possible method or procedure. It is important that
you read and understand these instructions thoroughly before attempting to install or operate this equipment. Save these
instructions for future reference.
This transfer switch requires professional installation before use. Refer to the Installation section of this manual for
instructions on installation procedures. Only licensed electrical contractors should install transfer switches. Installations must
strictly comply with all applicable federal, state and local codes, standards and regulations. Your installer should follow the
instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages.
There are many authorized service dealers who provide quality service. You can also contact Technical Service by phone at
(800)743-4115 between 8:00 AM and 5:00 PM CT, or on the Internet at BRIGGSandSTRATTON.COM.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Model Number
Revision
Serial Number
Date Purchased
ORIGINAL INSTRUCTIONS (ENGLISH)
NOT
for
REPRODUCTION
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................5
Owner Orientation ............................................5
Installing Dealer/Contractor Responsibilities ........................5
Mounting Guidelines ..........................................6
Power Wiring Interconnections ..................................7
Controls ..................................... 10
Operation .................................... 10
Maintenance .................................. 11
Troubleshooting................................ 12
Schematic Diagram ..........................................13
Wiring Diagram .............................................14
Warranty..................................... 15
Product Specifications ........................... 16
NOT
for
REPRODUCTION
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the equipment.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol
may be used to represent the type of hazard. The signal
word NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the equipment unsafe.
Electrical Shock Read Manual
Save These Instructions
WARNING Only qualified electricians should attempt
installation of this equipment, which must strictly comply
with applicable codes, standards and regulations.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
WARNING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
• Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
WARNING Failure to properly ground equipment can
result in electrocution.
• Do not touch bare wires.
• Do not use equipment with worn, frayed, bare or
otherwise damaged wiring.
• Do not handle electrical cords while standing in water,
while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand
on an insulated dry surface to reduce shock hazard.
• Do not allow unqualified persons or children to operate or
service equipment.
• In case of an accident caused by electrical shock,
immediately shut down all sources of electrical power
and contact local authorities. Avoid direct contact with
the victim.
WARNING Equipment contains high voltage that can
cause personal injury or death.
• Despite the safe design of the system, operating this
equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
NOTICE Improper treatment of equipment can damage it
and shorten its life.
• Use equipment only for intended uses.
• If you have questions about intended use, ask dealer or
contact Briggs & Stratton Power Products.
• Do not expose equipment to excessive moisture, dust,
dirt, or corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• If connected devices overheat, turn them off and turn off
their circuit breaker/fuse.
NOT
for
REPRODUCTION
5
Installation
We sincerely appreciate your patronage. For this reason,
we have made significant effort to provide for a safe,
streamlined and cost-effective installation. Because each
installation is unique, it is impossible to know of and advise
the trade of all conceivable procedures and methods by
which installation might be achieved. Neither could we know
of possible hazards and/or the results of each method or
procedure. For these reasons,
Only current licensed electrical should attempt system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Your equipment is supplied with this combined “Installation
and Operator’s Manual”. This is an important document and
should be retained by the owner after the installation has
been completed.
Every effort has been made to make sure that the information
in this manual is both accurate and current. However, the
manufacturer reserves the right to change, alter or otherwise
improve the system at any time without prior notice.
Home Owner Responsibilities
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation before contracting
or starting your equipment installation.
To arrange for proper installation, contact the store at which
you purchased your equipment, your dealer, or your utility
power provider.
The equipment warranty is VOID unless the system is
installed by licensed electrical professionals.
Owner Orientation
The illustrations provided are for typical circumstances and
are meant to familiarize you with the installation options
available with your system.
Local codes, appearance, and distances are the factors that
must be considered when negotiating with an installation
professional. As the distance from the existing electrical
service increases, compensation in wiring materials must
be allowed for. This is necessary to comply with local codes
and overcome electrical voltage drops.
These factors will have a direct effect on the overall price
of your equipment installation.
NOTE: Your installer must check local codes AND obtain
permits before installing the system.
 • Readandfollowtheinstructionsgiveninthismanual.
 • Followaregularscheduleincaringforandusingyour
equipment, as specified in this manual.
Installing Dealer/Contractor Responsibilities
 • Readandobservethesafetyrules.
 • Readandfollowtheinstructionsgiveninthismanual.
 • Theinstallermayneedtoprovideappropriaterated
contactors based on loads to be controlled.
 • Checkfederal,stateandlocalcodesandauthority
having jurisdiction, for questions on installation.
 • Ensuregeneratorisnotoverloadedwithselectedloads.
If you need more information about the transfer switch, call
(800) 743-4115, between 8:00 AM and 5:00 PM CT.
Equipment Description
The transfer switch is designed to transfer the selected loads
found in normal residential installations when used with the
supervisory contacts provided. The load is connected either
to utility power (normal) or home standby power (generator).
The transfer switch monitors utility and generator voltages
and will automatically connect to the appropriate source
ofpower.
These switches make it easy for a licensed electrician to
complete a home standby installation. Service conduit and
conductors can be wired directly from the hour-meter to the
transfer switch. A separate disconnect and associated wiring
are not required when installed per applicable federal, state
and local codes, standards and regulations.
Major components of the transfer switch are a 2 pole utility
disconnect circuit breaker, a 2 pole generator disconnect
circuit breaker, a 2 pole double throw transfer switch, control
circuit board, fused utility terminals and interconnecting
wiring. The control board also has two inputs for current
transformers that sense generator current. These
components are housed in a NEMA 3R enclosure that is
suitable for both indoor and outdoor installations.
The transfer switch is solenoid-operated from utility or
generator inputs and contain suitable mechanical and
electrical interlock switches to eliminate the possibility of
connecting the utility service to the generator output. It
has ratings capable of switching full utility power into the
residence. In addition, a manual override lever is provided
for the transfer function.
The control board has active circuits sensing utility and
generator voltages. It creates a signal for the generator
start-up, switch transfer and retransfer when utility is
restored. The control board also contains red and green
LED’s indicating the power sources available and two
relay operated contacts that provide supervisory control of
external loads.
NOT
for
REPRODUCTION
6 BRIGGSandSTRATTON.COM
Delivery Inspection
After opening the carton, carefully inspect the transfer
switch components for any damage that may have occurred
duringshipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor’s
memo of loss or damage. If loss or damage is noted after
delivery, contact the carrier for claim procedures. Missing or
damaged parts are not warranted.
Shipment Contents
 • Automatictransferswitch(1)
 • Installationandoperator’smanual(1)
 • Currenttransformers(2)
To be supplied by installer:
 • Connectingwireandconduit
 • Variousspecialtytools/equipment
NOT
for
REPRODUCTION
7
Main
Distribution
Panel
Transfer
Switch
Hot Water
Heater
Air
Conditioner
Contactor
Disconnect Switch
Generator
Watt -
Hourmeter
Branch
Circuits
Emergency Branch
Circuits
— — — — — — Control Wiring
Emergency
Load
Center
Alternate
Typical
Main
Distribution
Panel
Transfer Switch
w/ Service
and Generator
Disconnect
Hot Water
Heater
Air
Conditioner
Generator
Watt -
Hourmeter
— — — — — — Control Wiring
Disconnect Switch
Contactor
Branch Circuits
Mounting Guidelines
The system circuitry is enclosed in a NEMA Type 3R
enclosure suitable for indoor/outdoor use. Guidelines for
mounting the enclosure include:
 • Installenclosureonafirm,sturdysupportingstructure.
 • Theenclosuremustbeinstalledwithminimum
NEMA3R hardware for conduit connections.
 • Levelandplumbtheenclosure.Thiscanbedone
by placing washers between the enclosure and the
mounting surface.
 • NEVERinstalltheswitchwhereanycorrosive
substance might drip onto the enclosure.
 • Protecttheswitchatalltimesagainstexcessive
moisture, dust, dirt, lint, construction grit and
corrosivevapors.
A typical installation of the automatic transfer switch is
depicted below. An alternative installation is also depicted.
It is best if the transfer switch is mounted near the utility
meter, either inside or outside. Discuss layout suggestions/
changes with the owner before beginning the system
installation process.
NOTICE Before drilling conduit entry holes, or any
other holes, cover and protect the switch and electronics
to prevent dirt and metal fragments from entering the
mechanical and electrical components. Failure to do so may
result in damage or malfunction of the switch.
NOTICE Use a vacuum to clean any dirt or metal
shavings inside the transfer switch. Do not use a blower or
compressed air to clean the inside of the transfer switch
because debris may become lodged in the electrical and
mechanical components causing damage or malfunction.
NOT
for
REPRODUCTION
8 BRIGGSandSTRATTON.COM
Power Wiring Interconnections
All wiring must be the proper size, properly supported
and protected by conduit. All wiring should be done per
applicable federal, state and local codes, standards and
regulations. Obey wire type and torque specifications printed
on the terminal blocks and neutral/ground connector.
Approved for copper and aluminum conductors.
Complete the following connections between the transfer
switch, main distribution panel, utility power and generator.
Useunstaller-supplied300VACorgreaterwirethatcomplies
with Table 310.16 in the National Electric Code. Apply the
necessary correction factors and wire size calculations.
1. Set generator’s system switch to OFF position.
2. Set generator’s circuit breaker to OFF (open) position.
3. Turn off utility power to the standby generator and
transfer switch.
4. Connect utility service to transfer switch service
disconnect circuit breaker terminals marked
“UTILITYCONNECTION”.
5. Connect utility service neutral to transfer switch
neutralterminal.
6. Connect main distribution panel feeder
conductors to transfer switch terminals marked
“LOADCONNECTION”.
7. Connect main distribution panel neutral conductor to
transfer switch neutral terminal.
8. Connect main distribution panel ground conductor to
transfer switch “GND” terminal.
NOTE: Assure grounding electrode conductor is connected
and bonded per applicable federal, state and local codes,
standards and regulations.
9. Connect feeder conductors from transfer switch
breaker “GENERATOR CONNECTION” terminals to
generator control panel breaker. Each conductor
must pass through hole of current transformer before
makingconnection.
10. Plug current transformer leads into “CT1” and “CT2”
terminals on control module.
11. Connect conductor from transfer switch neutral
terminal to generator control panel neutral terminal.
12. Connect conductor from transfer switch “GND” terminal
to generator control panel “GROUND” terminal.
NOTE: Assure generator equipment grounding conductor
is connected per applicable federal, state and local codes,
standards and regulations.
13. Connectthetransferswitch“UTILITY240VAC”
terminalstogenerator’s“240VAC”terminalsusing
installersupplied300VACorgreaterwire,minimum
#14 AWG conductors via supplied two-poleconnector.
14. Connect “GND” and “T/R” terminals on transfer
switch control board (B) to the generator’s control
panel (A) “TxRx” and “TxRx GND” terminals using
#18 AWG twisted pair conductors, no greater than
200 ft in length, 300 volt 75°C-90°C via supplied
ten-pole connector.
15. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torque values.
• Whenconnectingtocircuitboardterminalblocks,
fasten only one wire to each connector screw.
• Torqueterminalblockscrewsto12in-lb
(13.5Newton meter).
The illustration on page 8 shows a typical completed
installation. The actual layout will vary.
WARNING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
• Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
NOTICE Improper installation can cause damage to the
circuit boards and shorten their life. Installing circuit
boards in live circuits will damage the board and is not
covered by warranty. ALWAYS disconnect ALL sources of
power prior to servicing.
• Remove all power prior to installing this equipment.
Failure to do so could cause internal damage to the board
when making electrical connections.
• Turn generator to OFF position.
• Turn off utility power to the standby generator and
transfer switch.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
A
B
NOT
for
REPRODUCTION
9
Generator
To Utility
Ground
Terminal
Load
Connection
Main Distribution Panel
Neutral
Terminal
Supervisory
Contacts
Generator
Connection
Utility
Connection
Wireways
CT
CT
UTILITY240VACtoGenerator
T/R and GND to
Generator
Ground Bus
Neutral Bus
NOT
for
REPRODUCTION
10 BRIGGSandSTRATTON.COM
Supervisory Control Wiring
An air conditioner can be used with the supervisory contacts
on either terminals A-A or B-B. Terminals A-A can only be
used with supervisory control. Large loads can only be used
with contactor control on terminals B-B. Examples of each
system are described below.
1. The terminal strip on control module in transfer switch
has four connections for customer use. There are two
sets of “Normally Closed” contacts available. They will
be activated when generator power is required. These
can be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator power available.
NOTE: There are two wireways provided to keep the
supervisory loads separated from each other.
2. Terminals “A-A” on control module are rated for
24VACandairconditionercontactorcontrol.Contacts
are connected in series with the air conditioner
contactor control circuit.
3. Terminals “B-B” on control module are rated for 1Amp
125VACandinstallersuppliedcontactortocontrol
a large load, such as an electric hot water heater.
Contacts are connected in series with the contactor
controlcircuit.
4. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torquevalues.
System Setup
You must perform the following before operating the system:
• Ifgeneratorisinstalledinanarearegularlysubjectedto
temperatures below 40°F (4°C), select a 50 second warm up
time by moving jumper JP2 (C) installed on transfer switch
control board from ‘20’ position to ‘50’position.
• SettheDPSW1(A) and DPSW2 (B) dipswitches on the
transfer switch control board to match the kW rating of the
standby generator, as described in SettingDipswitches.
Setting Dipswitches
Dipswitches are used to adjust control board operation based
on generator capacity. DPSW1 and DPSW2 switches are set to
correspond to total system kW rating. Dipswitch DPSW1 (A) has
units of 1,000 watts; Dipswitch DPSW2 (B) has units of
10,000 watts.
Set dipswitches with utility and generator power removed from
the transfer switch to ensure proper control system operation.
If dipswitches are set when power is present at transfer switch,
a power reset needs to be performed before the new dipswitch
settings will take effect. Power reset is when all power is removed
from the transfer switch and then reintroduced after 30 seconds.
NOTICE An FC_8 will occur on standby generator control board if
dipswitches are not properly established as noted above.
A
A
Air Conditioner Contactor
24VAC
B
B
Contactor
Neutral
120VAC
NOTICE Use extreme caution when setting dipswitches or
damage to control board will result.
• Use a pencil or small piece of plastic to set the dipswitch.
• NEVERuseascrewdriveroranytypeofmetalobjectto
set dipswitches.
DPSW
1
DPSW2
JP2
A
B
C
NOT
for
REPRODUCTION
11
The “On” position for the dipswitches is the switch number ON
THE TRANSFER SWITCH CONTROL BOARD, not on the switch. For
example, for an 18,000 watt generator, set DPSW2 dipswitch 10 to
“On” position. Set DPSW1 dipswitch 8 to “On” position. 10,000 plus
8000 equals 18,000 watts.
Set only one switch to “On” position
on DPSW1 andDPSW2.
Refer to following chart for proper switch selection(s).
NOTICE
Air density is less at high altitudes, resulting in less
available engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1% for each 10°
F (5.6°C) above 77°F (25°C). Generators located in these conditions
must have the transfer switch programmed appropriately for this
power decrease.
System Test
With the generator system switch in AUTO, turn the service
disconnect feeding the transfer switch contactor to the OFF
position. After a few minutes the generator will start and the
transfer switch will transfer to generator power.
To return to utility power, turn the service disconnect feeding
the transfer switch to the ON position.
Controls
Other than a Manual Override lever, there are no operator
controls because this is an automatic transfer switch. The
manual override is to be used only by licensed professionals.
Operation
To select automatic transfer operation, do the following:
1. Set service disconnect switch that sends utility power
to transfer switch contactor to “On” position.
2. Install 15 Amp fuse in generator’s control panel.
3. Set generator’s circuit breaker to “On” position.
4. Set generator’s system switch to “AUTO” position..
The system will now be in automatic operation mode.
When the generator is providing power to the transfer
switch, the control module is constantly monitoring
generator power. If the air conditioner is called to run, and
there is sufficient generator power available, the controller
will close contacts “A-A” to air conditioner contactor.
Contacts “B B” will open before contacts A-A close. If loads
are too great for the generator, contacts A-A and/or B-B will
open. When air conditioning is not needed, A-A will open. If
enough power is available, B-B will close.
kW Rating
of
Generator
DPSW
#1 “ON”
Position
DPSW
#2 “ON”
Position
7kW 7 0
8kW 8 0
9kW 9 0
10kW* 0 10
11kW* 1 10
12kW 2 10
13kW* 3 10
14kW 4 10
15kW 5 10
16kW 6 10
17kW 7 10
18kW 8 10
19kW 9 10
20kW 0 20
30kW 0 30
45kW 5 40
48kW 8 40
50kW 0 50
60kW 0 60
* For generators with a rating that includes 500 Watts, round
down to next lowest rating
(example: 13.5 kW set to 13kW)
NOT
for
REPRODUCTION
12 BRIGGSandSTRATTON.COM
Enclosure Door
To open door, press the spring-load door lock to the right
and pull down on the door.
To close and latch door, push door closed against enclosure.
While in this position, push door upwards. This will cause
spring-load door lock to engage and latch door in place.
NOTE: Enclosure door MUST be closed and latched at all
times except when system is being serviced.
Testing the Automatic Transfer Switch
Turn the service disconnect feeding the transfer switch
contactor to the “Off” position. The system’s automatic
sequence will initiate. To return to utility power, turn the
service disconnect to the “On” position.
Utility Fail
The generator senses when utility voltage is below
70percent of nominal. Engine start sequence is initiated
after 6 second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer. Use
jumper on control board to select delay of 20 seconds or
50seconds.
Transfer
Transfer from utility to generator supply occurs after voltage
is above set levels. Minimum engine run time is 5 minutes
after transfer.
Utility Pickup
Voltagepickuplevelis80percentofnominalvoltage.
Retransfer
Retransfer from generator to utility power is approximately
10 seconds after utility voltage supply is above pickup level
and minimum run time is completed.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks
should be made on a regular basis. Maintenance will consist
mainly of keeping the transfer switch clean.
Visualinspectionsshouldbedoneatleastonceamonth.
Access to transfer switch must not be obstructed. Keep
3feet (92 cm) clearance around transfer switch. Check
for an accumulation of dirt, moisture and/or corrosion
on and around the enclosure, loose parts/hardware,
cracks and/or discoloration to insulation, and damaged or
discoloredcomponents.
Exercise the transfer switch at least once every three months
as described in Testing the Automatic Transfer Switch unless
a power outage occurs and home generator system has gone
through an automatic sequence. Allow generator to run for at
least 30 minutes.
Contact a licensed electrical professional to inspect and clean
the inside of the enclosure and other components of your
home generator system at least once a year.
When Calling for Assistance
You must have the Model Number and Serial Number from
the unit ID label at hand if it is necessary to contact a local
service center regarding service or repair of this unit. Obtain
this information from the unit ID label located on or inside
the enclosure.
To contact Briggs & Stratton call (800)743-4115, between
8:00 AM and 5:00 PM CT.
Installation Inspection
Before placing the system into service, inspect the entire
installation carefully.
NOT
for
REPRODUCTION
13
Troubleshooting
Problem Cause Correction
Automatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Reset generator circuit breaker.
2. Refer to generator manual.
Automatic transfer switch does not
transfer to utility
1. Service disconnect breaker open.
2. Utility voltage not acceptable.
1. Reset service disconnect breaker.
2. Wait for utility voltage to return
tonormal.
Generator is still running after switch
transfers to utility power
Engine cool down period. Engine should stop after 1 minute.
Generator or supervised loads (air
conditioner, etc.) are operating
improperly when generator is
supplyingpower
1. A-A or B-B contacts not
operatingcorrectly.
2. Too much load on generator.
3. Current transformer not connected.
4. Broken current transformer.
1. Check A-A or B-B contacts for
proper operation and/or check
control wiring to external load.
2. Decrease load to generator.
3. Plug CT connectors into
controlmodule.
4. Contact local authorized
servicecenter.
Generator is still running after utility
power is restored
1. Minimum engine run time has
notelapsed.
2. Fuse(s) in transfer switch
isdefective.
1. Wait five minutes for transfer switch
to retransfer to utility power.
2. Check fuse(s) and replace
ifnecessary.
200 Amp Automatic Transfer Switch
Product Specifications
Rated Maximum Load Current* (at 25°C/77°F) ........200 Amps
RatedACVoltage ................................250Volts
Poles................................................2
Frequency .........................................60 Hz
Fault Current Rating ......... 25,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24VoltAC
B-B Terminals . . . . . . . . . . . . . . . .1Amp,125VoltAC,PilotDuty
Normal Operating Range ........-20°F (-28.8°C) to 104°F (40°C)
Weight ....................................63 lbs. (29 kg)
*This transfer switch is certified in accordance with UL (Underwriters Laboratories)
1008 (transfer switch equipment).
NOT
for
REPRODUCTION
14 BRIGGSandSTRATTON.COM
2 AMP SLO-BLO
or 10 AMP FUSE
Schematic Diagram
NOT
for
REPRODUCTION
15
Wiring Diagram
NOT
for
REPRODUCTION
16 BRIGGSandSTRATTON.COM
Warranty
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC TRANSFER SWITCH OWNER WARRANTY POLICY
LIMITED WARRANTY
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or
workmanship or both. Transportation charges on product submitted for repair or replacement under this warranty must be borne by purchaser. This
warranty is effective for the time periods and subject to the conditions stated below. For warranty service, find the nearest Authorized Service Dealer in
our dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED WARRANTIES ARE
EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some
states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you specific legal rights and you
may also have other rights which vary from state to state or country to country.
The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time stated in the
table above. “Consumer use” means personal residential household use by a retail consumer. “Commercial use” means all other uses, including use for
commercial, income producing or rental purposes. Once equipment has experienced commercial use, it shall thereafter be considered as commercial use for
purposes of this warranty. Equipment used for prime power in place of utility are not applicable to this warranty.
NOWARRANTYREGISTRATIONISNECESSARYTOOBTAINWARRANTYONBRIGGS&STRATTONPRODUCTS.SAVEYOURPROOFOFPURCHASE
RECEIPT.IFYOUDONOTPROVIDEPROOFOFTHEINITIALPURCHASEDATEATTHETIMEWARRANTYSERVICEISREQUESTED,THEMANUFACTURING
DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty
repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if
equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper installation. Similarly, the
warranty is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered or modified. During
the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal
use and service. This warranty will not cover the following repairs and equipment:
• Normal Wear: Outdoor Power Equipment, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not cover
repair when normal use has exhausted the life of a part or the equipment.
• Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation
or alteration and modification, misuse, negligence, accident, overloading, improper maintenance, repair or storage so as, in our judgment, to adversely
affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments, cleaning and fuse replacement.
• Other Exclusions: This warranty excludes wear items or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or
improper servicing. Accessory parts are excluded from the product warranty. This warranty excludes failures due to acts of God and other force
majeure events beyond the manufacturers control. Also excluded is used, reconditioned, and demonstration equipment. 198180E, Rev. C, 12/31/2006
Effective November 1, 2005 replaces all undated Warranties and all Warranties dated before November 1, 2005
3 years
None
Consumer Use
Commercial Use
WARRANTY PERIOD
NOT
for
REPRODUCTION
Interruptor de transferencia automática
de 200 amperios
con módulo de control de energía eléctrica de CA™
Manual de instalación ydeloperario
NOT
for
REPRODUCTION
2 BRIGGSandSTRATTON.COM
Gracias por comprar este conectador automático de Briggs & Stratton® Power Products. Este producto está diseñado para
utilizarse con generadores de reserva domésticos específicos y puede no funcionar con generadores producidos por otros
fabricantes. Recurra a un electricista profesional cualificado para determinar la aplicabilidad de este equipo en generadores
fabricados por terceros. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, su sistema le proporcionará
muchos años de funcionamiento fiable.
Este manual contiene información de seguridad para que usted conozca los peligros y riesgos propios de este sistema y
cómo evitarlos. Se ha realizado el máximo esfuerzo para que la instalación resulte segura, sencilla y económica. Debido a que
cada instalación es única, es imposible conocer y recomendar todos los procedimientos y métodos posibles para efectuarla.
No conocemos todos los riesgos y/o resultados posibles de cada método o procedimiento existente. Es importante que lea
y comprenda perfectamente estas instrucciones antes de intentar instalar o utilizar este equipo. Guarde estas instrucciones
para futuras consultas.
Este el conectador requiere instalación profesional antes de utilizarse. Consulte las instrucciones sobre los procedimientos
de instalación en la sección Instalación del presente manual. Los conectador sólo deben ser instalados por electricistas con
licencia. Las instalaciones deben cumplir estrictamente la totalidad de los códigos, estándares y regulaciones federales,
estatales y locales vigentes. El instalador debe seguir las instrucciones detalladamente.
Ubicación
Nunca debe ir demasiado lejos para encontrar el soporte y servicio de Briggs & Stratton para su sistema. Consulte las
Páginas Amarillas. Existen múltiples distribuidores de servicio autorizados que ofrecen un servicio de calidad. También puede
comunicarse con el Servicio técnico por teléfono al (800) 743 4115 de 8:00 a. m. a 5:00 p. m. Hora del Centro, o a través de
Internet en BRIGGSandSTRATTON.COM.
Para futuras consultas
Llene la siguiente información y conserve su factura para facilitar la identificación de la unidad en caso de que surjan
problemas relacionados con la compra en el futuro.
Conectador automático
Número de modelo
Versión
Número de serie
Fecha de compra
Copyright © 2012. Briggs & Stratton Power Products Group, LLC
Milwaukee, WI, USA. Reservados todos los derechos.
Briggs & Stratton Power Products es una marca
registradas de Briggs & Stratton Corporation
Milwaukee, WI, USA
NOT
for
REPRODUCTION
3
Tabla de contenido
Instrucciones importantes deseguridad ................4
Instalación ....................................5
Orientación al propietario.......................................5
Responsabilidades del distribuidor/ técnicoinstalador ................5
Pautas de montaje ............................................6
Interconexión de los cables de alimentación ........................7
Controles .................................... 10
Funcionamiento................................ 10
Mantenimiento ................................ 11
Resolución de problemas ......................... 12
Garantía . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Especificaciones del producto ...................... 14
NOT
for
REPRODUCTION
4 BRIGGSandSTRATTON.COM
Conserve estas instrucciones
Instrucciones importantes
deseguridad
GUARDE ESTAS INSTRUCCIONES - Este manual contiene
instrucciones importantes que se deben seguir durante la
instalación y el mantenimiento del equipo.
Símbolos sobre la seguridad y significados
El símbolo de alerta de seguridad indica un posible
riesgo para su integridad física. Se utiliza una palabra de
señalización(PELIGRO,ADVERTENCIAoATENCIÓN)junto
con el símbolo de alerta para designar un grado o nivel
de gravedad de riesgo. Se puede utilizar un símbolo de
seguridad para representar el tipo de riesgo. La palabra de
señalizaciónAVISOseutilizaparahacerreferenciaauna
práctica no relacionada con una lesión física.
PELIGRO indica un riesgo que, de no evitarse, provocará
la muerte o lesiones de gravedad.
ADVERTENCIA indica un riesgo que, de no evitarse,
podría provocar la muerte o lesiones de gravedad.
ATENCIÓN indica un riesgo que, de no evitarse, podría
provocar lesiones leves o moderadas.
AVISO hace referencia a una práctica no relacionada con una
lesión física.
El fabricante no puede prever toda circunstancia que conlleve
un riesgo potencial. Por tanto, las advertencias de este
manual, así como las etiquetas y calcomanías adheridas a
la unidad, no incluyen todos los riesgos posibles. Si utiliza
un procedimiento, método de trabajo o técnica de uso no
recomendado específicamente por el fabricante, deberá
asegurarse de que es seguro tanto para usted como para
otras personas. También deberá asegurarse de que el
procedimiento, método de trabajo o técnica de uso que elija
no hace que el equipo sea inseguro.
Descarga eléctrica Lea el manual
ADVERTENCIA La instalación de este equipo debe
cumplir estrictamente la totalidad de los códigos,
estándares y regulaciones vigentes, por lo que sólo debe
ser llevada a cabo por un electricista cualificado.
ADVERTENCIA Determinados componentes en
este producto y los accesorios relacionados contienen
sustancias químicas declaradas cancerígenas, causantes
de malformaciones, y otros defectos congénitos por el
Estado de California. Lávese las manos después de
manipular estos elementos.
ADVERTENCIA Los cables de baja tensión no se
pueden instalar en el mismo conducto que los
cables de suministro de energía.
• Si no se respeta esta indicación pueden producirse
lesiones, daños y/o fallos de funcionamiento del equipo.
ADVERTENCIA Una conexión a tierra defectuosa del
equipo puede provocar la electrocución.
• No toque los cables pelados.
• No utilice el equipo con cables desgastados,
deshilachados o deteriorados de cualquier otra forma.
• No manipule los cables eléctricos si se encuentra en
una zona húmeda, está descalzo o tiene las manos o los
piesmojados.
• Si tiene que trabajar junto a una unidad en
funcionamiento, manténgase en una superficie aislada y
seca para reducir el riesgo de descarga eléctrica.
• No permita que personas no cualificadas o niños utilicen
o reparen el equipo.
• En caso de accidente provocado por una descarga
eléctrica, desconecte inmediatamente todos los
suministros de energía eléctrica y póngase en contacto
con las autoridades locales. Evite el contacto directo con
la víctima.
ADVERTENCIA El equipo contiene alta tensión que
puede provocar lesiones o la muerte.
• A pesar de la seguridad del diseño del sistema, si éste se
utiliza con imprudencia, ignorando su mantenimiento o
sin las debidas precauciones, se pueden producir lesiones
o incluso la muerte.
AVISO Un tratamiento inadecuado del equipo puede
estropearlo y acortar su vida útil.
• Utilice el equipo sólo para los usos previstos.
• En caso de dudas sobre su uso, diríjase al distribuidor o a
Briggs & Stratton Power Products.
• No exponga el equipo a un exceso de humedad, polvo,
suciedad o vapores corrosivos.
• Manténgase alerta en todo momento cuando utilice este
equipo. Nunca lo utilice ni manipule en condiciones de
fatiga física o mental.
• Si se calientan excesivamente los dispositivos conectados,
apáguelos y abra sus interruptores o quite sus fusibles.
NOT
for
REPRODUCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Simplicity 071046-01 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur