1/3
Altivar
Fan Kits VZ3V3101, VZ3V3102
W9 1598347 01 14 A04
02 - 2018
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility
is assumed by Schneider Electric for any consequences arising out of the use of this product.
© 2018 Schneider Electric. All Rights Reserved.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other
pertinent product documentation and who have received safety training to recognize and avoid hazards involved are
authorized to work on and with this drive system. Installation, adjustment, repair, and maintenance must be
performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as well
as all other applicable regulations with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use
only electrically insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block
the motor shaft to prevent rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of
the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the
absence of DC bus voltage that can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals (PA/+ and PC/-) using a properly rated
voltmeter to verify that the voltage is <42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative. Do
not repair or operate the product.
• Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
00159834714048