Simplicity 01656 Manuel utilisateur

Catégorie
Accessoires pour véhicules automobiles
Taper
Manuel utilisateur
Owner’s Manual / Manuel de l'Utilisateur
Questions? Help is just a moment away!
Vous avez des questions? Vous n'avez pas besoin d'aller loin pour trouver de l'aide!
Call: Generac Generator Helpline / Appelez la ligne d'assistance de Generac Motor - 1-800-270-1408 M-F 8-5 CT
Model No. 1656-1 (4,000 Watt AC Generator) Manual No. 191519GS Revision 7 (02/22/2005)
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
JEFFERSON,WISCONSIN, U.S.A.
Generac Portable Products is a licensed trademark of Briggs & Stratton Power Products.
Generac Portable Products est une marque déposéee autorisée de Briggs & Stratton Power Products.
Before using this product, read this manual and follow all
Safety Rules and Operating Instructions.
CAUTION
Avant d’utiliser ce produit, veuillez lire le manuel et suivre
toutes les directives relatives à la sécurité et à l’utilisation.
ATTENTION
2
4000EXL Extended Life Generator
TABLE OF CONTENTS
Safety Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Know Your Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-14
Product Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
EQUIPMENT
DESCRIPTION
Read this manual carefully and become familiar
with your generator. Know its applications, its
limitations and any hazards involved.
This generator is an engine–driven, revolving field,
alternating current (AC) generator. It was designed to
supply electrical power for operating compatible electrical
lighting, appliances, tools and motor loads.The generator’s
revolving field is driven at about 3,600 rpm by a single-
cylinder engine.
CAUTION! DO NOT exceed the generator’s
wattage/amperage capacity. See “Don’t Overload
Generator”.
Every effort has been made to ensure that information in
this manual is accurate and current. However, we reserve
the right to change, alter or otherwise improve the product
and this document at any time without prior notice.
The Emission Control System for this generator is
warranted for standards set by the Environmental
Protection Agency. For warranty information refer to the
engine owner’s manual.
SAFETY RULES
This is the safety alert symbol. It is used to
alert you to potential personal injury hazards.
Obey all safety messages that follow this
symbol to avoid possible injury or death.
The safety alert symbol ( ) is used with a signal word
(DANGER, CAUTION,WARNING), a pictorial and/or a
safety message to alert you to hazards. DANGER indicates
a hazard which, if not avoided, will result in death or
serious injury. WARNING indicates a hazard which, if not
avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, might
result in minor or moderate injury. CAUTION, when used
without the alert symbol, indicates a situation that could
result in equipment damage. Follow safety messages to
avoid or reduce the risk of injury or death.
Hazard Symbols and Meanings
The engine exhaust from this product contains
chemicals known to the State of California to cause
cancer, birth defects, or other reproductive harm.
WARNING
Fire
Explosion
Toxic Fumes
Kickback
Electrical Shock
Electrocution
Electrical Shock
Explosive Pressure
Chemical Burn
Hot Surface
Copyright © 2005 Briggs & Stratton Power Products
Group, LLC. All rights reserved. No part of this material
may be reproduced or transmitted in any form by any
means without the express written permission of Briggs &
Stratton Power Products Group, LLC.
4000EXL Extended Life Generator
3
When using generator for backup power, notify utility
company. Use approved transfer equipment to isolate
generator from electric utility.
Use a ground fault circuit interrupter (GFCI) in any damp or
highly conductive area, such as metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
DO NOT operate generator in the rain.
DO NOT handle generator or electrical cords while standing
in water, while barefoot, or while hands or feet are wet.
DO NOT allow unqualified persons or children to operate or
service generator.
Generator produces powerful voltage.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.
WARNING
This generator does not meet U. S. Coast Guard Regulation
33CFR-183 and should not be used on marine applications.
Failure to use the appropriate U. S. Coast Guard approved
generator could result in bodily injury and/or property
damage.
WARNING
DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
Wear protective goggles, rubber apron, and rubber gloves.
Storage batteries give off explosive hydrogen gas
during recharging.
Hydrogen gas stays near battery for a long time
after battery has been charged.
Slightest spark will ignite hydrogen and cause
explosion.
You can be blinded or severely injured.
Battery electrolyte fluid contains acid and is
extremely caustic.
Contact with battery fluid will cause severe
chemical burns.
DANGER
Operate generator ONLY outdoors.
Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes or other openings.
DO NOT operate generator inside any building or enclosure,
including the generator compartment of a recreational vehicle (RV).
Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea,
fainting or death.
WARNING
WHEN ADDING OR DRAINING FUEL
Turn generator OFF and let it cool at least 2 minutes before
removing fuel cap. Loosen cap slowly to relieve pressure in
tank.
Fill or drain fuel tank outdoors.
DO NOT overfill tank.Allow space for fuel expansion.
Keep fuel away from sparks, open flames, pilot lights, heat, and
other ignition sources.
DO NOT light a cigarette or smoke.
WHEN STARTING EQUIPMENT
Ensure spark plug, muffler, fuel cap and air cleaner are in place.
DO NOT crank engine with spark plug removed.
If fuel spills, wait until it evaporates before starting engine.
WHEN OPERATING EQUIPMENT
Do not tip engine or equipment at angle which causes fuel to
spill.
This generator is not for use in mobile equipment or marine
applications.
WHEN TRANSPORTING OR REPAIRING
EQUIPMENT
Transport/repair with fuel tank EMPTY or with fuel shutoff
valve OFF.
Disconnect spark plug wire.
WHEN STORING FUEL OR EQUIPMENT WITH FUEL
IN TANK
Store away from furnaces, stoves, water heaters, clothes
dryers or other appliances that have pilot light or other
ignition source because they can ignite fuel vapors.
Fuel and its vapors are extremely flammable and
explosive.
Fire or explosion can cause severe burns or
death.
WARNING
4000EXL Générateur Qui Dure Longtemps
4
DO NOT tamper with governed speed. Generator supplies
correct rated frequency and voltage when running at governed
speed.
DO NOT modify generator in any way.
Excessively high operating speeds increase risk of injury
and damage to generator.
Excessively low speeds impose a heavy load.
CAUTION
See “Don’t Overload Generator”.
Start generator and let engine stabilize before connecting
electrical loads.
Connect electrical loads in OFF position, then turn ON for
operation.
Turn electrical loads OFF and disconnect from generator
before stopping generator.
Exceeding generators wattage/amperage capacity can
damage generator and/or electrical devices connected
to it.
CAUTION
Use generator only for intended uses.
If you have questions about intended use, ask dealer or call
1-800-270-1408.
Operate generator only on level surfaces.
DO NOT expose generator to excessive moisture, dust, dirt,
or corrosive vapors.
DO NOT insert any objects through cooling slots.
If connected devices overheat, turn them off and disconnect
them from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
Improper treatment of generator can damage it and
shorten its life.
CAUTION
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
Disconnect the spark plug wire from the spark plug and place
the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug removed.
Unintentional sparking can result in fire or
electric shock.
WARNING
DO NOT touch hot surfaces.
Allow equipment to cool before touching.
The generator must be at least 5 feet from structures having
combustible walls and/or other combustible materials.
Keep at least 3 feet of clearance on all sides of generator for
adequate cooling, maintenance and servicing.
In the State of California a spark arrester is required by law
(Section 4442 of the California Public Resources Code). Other
states may have similar laws. Federal laws apply on federal
lands. If you equip the muffler with a spark arrester, it must be
maintained in effective working order.
Running engines produce heat.Temperature of
muffler and nearby areas can reach or exceed
150°F (65°C).
Severe burns can occur on contact.
Combustible debris, such as leaves, grass, brush,
ect. can catch fire.
WARNING
When starting engine, pull cord slowly until resistance is felt
and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices plugged in
and turned on.
Rapid retraction of starter cord (kickback) will
pull hand and arm toward engine faster than
you can let go.
Broken bones, fractures, bruises or sprains could
result.
WARNING
5
4000EXL Générateur Qui Dure Longtemps
KNOW YOUR GENERATOR
Read this owner’s manual and safety rules before operating your generator.
Compare the illustrations with your generator, to familiarize yourself with the locations of various controls and
adjustments. Save this manual for future reference.
120 Volt AC, 20 Amp
Duplex Receptacle
Fuel Tank
Idle Control Switch
Choke Lever
Recoil Starter
12 Volt DC, 10 Amp
Receptacle
Run/Stop Switch
120 Volt AC, 30 Amp
Receptacle
Double Pole Circuit
Breaker (AC)
120/240 Volt AC,
20 Amp Receptacle
Spark Arrester Muffler
Air Cleaner
Grounding Fastener
Start Button
12 Volt DC,10 Amp Receptacle — Recharge a discharged
12 Volt automotive type battery through this receptacle.
120 Volt AC, 20 Amp Duplex Receptacle — May be used to
supply electrical power for the operation of 120 Volt AC, 20 Amp,
single phase, 60 Hz electrical lighting, appliance, tool and motor
loads.
120 Volt AC, 30 Amp Receptacle — May be used to supply
electrical power for the operation of 120 Volt AC, 30 Amp, single
phase, 60 Hz electrical lighting, appliance, tool and motor loads.
120/240 Volt AC, 20 Amp Receptacle — May be used to
supply electrical power for the operation of 120 and/or 240 Volt
AC, 20 Amp, single phase, 60 Hz electrical lighting, appliance, tool
and motor loads.
Air Cleaner — Protects engine by filtering dust and debris out
of intake air.
Choke Lever — Used when starting a cold engine.
Circuit Breaker (AC) The 120 Volt AC, 30 Amp receptacle is
provided with a "push to reset" circuit breaker to protect the
generator against electrical overload.
Double Pole Circuit Breaker (AC) A double pole circuit
breaker is provided to protect all the receptacles and generator
against electrical overload.
Fuel Tank — Capacity of 4.5 U.S. gallons.
Grounding Fastener — Used for proper grounding of unit.
Idle Control Switch With this switch set to ON, printed
circuit board in control panel automatically reduces engine speed
when no load is connected and increases engine to proper speed
when load is applied. However, be sure switch is OFF when
starting engine.
Oil Fill Cap Add oil to engine here.
Recoil starter — Used to start the engine manually.
Run/Stop Switch — Set this switch to "Run" before using
recoil starter. Set switch to "Stop" to switch OFF engine.
Spark Arrester Muffler — Exhaust muffler lowers engine noise
and is equipped with a spark arrester screen.
Start Button When pressed, cranks engine to start.
Oil Fill Cap
Circuit Breaker (AC)
6
4000EXL Extended Life Generator
ASSEMBLY
IMPORTANT: Read entire owner’s manual before you
attempt to assemble or operate your new generator.
Carton Contents
Parts included:
Generator
Wheel kit
Battery
Battery charge cables
Battery float charger
Locking 20 Amp plug
Locking 30 Amp plug
Engine oil
Two packets of fuel stabilizer
Owner's manual
Engine manual
If any of the above parts are missing or damaged, call the
generator helpline at 1–800–270–1408.
Attach Negative Battery Wire
The sealed battery on the generator is fully charged and
pre–installed except for the negative (black) battery cable.
To install:
1. Cut off tie wrap securing loose end of negative (black)
cable.
2. Connect negative (black) battery cable to negative (–)
terminal on battery (Figure 1).
3. Verify that connections to battery and generator are
correct and secure.
Install Handle
To install the handle you need the following tools:
2 - 13 mm (1/2”) box, open end, or socket wrenches
Install handle as follows:
1. Remove hardware from bracket on handle.
2. Place lifting handle on alternator end of cradle so that
handle falls between the two twistlock receptacles as
shown in Figure 2.Attach handle with provided cap
screws and hex nuts.Tighten with 13mm wrenches.
Figure 1 — Negative Battery Connection
Positive
battery cable
Negative
battery cable
Figure 2 — Install Handle
Capscrew
Handle
Hex
Nut
4000EXL Extended Life Generator
7
BEFORE STARTING THE
ENGINE
Add Engine Oil
Place generator on a level surface.
Refer to engine owner’s manual and follow oil
recommendations and instructions.
NOTE: Check oil often during engine break–in. Refer to
engine owner’s manual for recommendations.
NOTE: The generator assembly rotates on a prelubricated
and sealed ball bearing that requires no additional
lubrication for the life of the bearing.
Add Fuel
NOTE: This gasoline engine is certified to operate on
gasoline. Exhaust Emission Control System: EM (Engine
Modifications).
1. Use clean, fresh, regular UNLEADED fuel with a
minimum of 85 octane with equipment. DO NOT use
fuel which contains Methanol. DO NOT mix oil with
fuel.
2. Clean area around fuel fill cap, remove cap.
3. Slowly add regular unleaded fuel to fuel tank. Be careful
not to fill above the baffle.This allows adequate space
for fuel expansion (Figure 3).
4. Install fuel cap and wipe up any spilled fuel.
CAUTION
Refer to engine manual for oil fill information.
Damage to equipment resulting from failure to follow this
instruction will void warranty.
Any attempt to crank or start the engine before it has
been properly filled with the recommended oil will result
in equipment failure.
WHEN ADDING FUEL
Turn generator OFF and let it cool at least 2 minutes before
removing fuel cap. Loosen cap slowly to relieve pressure in tank.
Fill fuel tank outdoors.
DO NOT overfill tank.Allow space for fuel expansion.
Keep fuel away from sparks, open flames, pilot lights, heat, and
other ignition sources.
DO NOT light a cigarette or smoke.
Fuel and its vapors are extremely flammable and
explosive.
Fire or explosion can cause severe burns or
death.
WARNING
FUEL
TANK
Figure 3 — Typical Fuel Expansion Space
Baffle
8
4000EXL Extended Life Generator
USING THE GENERATOR
System Ground
The generator has a system ground that connects the
generator frame components to the ground terminals on
the AC output receptacles.The system ground is connected
to the AC neutral wire (the neutral is bonded to the
generator frame).
Special Requirements
There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes, or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction.
In some areas, generators are required to be registered
with local utility companies.
If the generator is used at a construction site, there may
be additional regulations which must be observed.
Connecting to a Building’s Electrical
System
Connections for standby power to a building’s electrical
system must be made by a qualified electrician.The
connection must isolate the generator power from utility
power, and must comply with all applicable laws and
electrical codes.
Generator Location
Generator Clearance
The generator must be at least 5 ft. (152 cm) from
structures having combustible walls and/or other
combustible materials. Leave at least 3 ft. (92 cm) all around
generator including overhead, for adequate cooling,
maintenance and servicing.
Place generator in a well ventilated area, which will allow
for removal of deadly exhaust gas. DO NOT place
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow
exhaust gas to collect in a confined area (Figure 4).
Prevailing winds and air currents should be taken into
consideration when positioning generator.
When using generator for backup power, notify utility
company. Use approved transfer equipment to isolate
generator from electric utility.
Use a ground fault circuit interrupter (GFCI) in any damp or
highly conductive area, such as metal decking or steel work.
DO NOT touch bare wires or receptacles.
DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
DO NOT operate generator in the rain.
DO NOT handle generator or electrical cords while standing
in water, while barefoot, or while hands or feet are wet.
DO NOT allow unqualified persons or children to operate or
service generator.
Generator produces powerful voltage.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.
WARNING
Operate generator ONLY outdoors.
Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes or other openings.
DO NOT operate generator inside any building or enclosure,
including the generator compartment of a recreational vehicle (RV).
Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea,
fainting or death.
WARNING
Figure 4 — Generator Clearance
Exhaust Port
Typical Generator Shown
4000EXL Extended Life Generator
9
OPERATING THE
GENERATOR
IMPORTANT: Always unplug the battery float charger
before starting the generator.
Starting the Engine
Disconnect all electrical loads from the generator. Follow
these start instruction steps in numerical order:
1. Turn fuel valve to On” position (Figure 5).
2. Make sure Idle Control switch is in Off” position
(Figure 6).
3. Start engine according to instructions given in engine
owner’s manual.
NOTE: If engine still fails to start after 3 pulls, check for
proper oil level in crankcase.This unit is equipped with a
Low Oil Shutdown System. See engine manual.
Connecting Electrical Loads
Let engine stabilize and warm up for a few minutes after
starting.
Plug in and turn on the desired 120 and/or 240 Volt AC,
single phase, 60 Hz electrical loads.
DO NOT connect 240 Volt loads to the 120 Volt
receptacles.
DO NOT connect 3–phase loads to the generator.
DO NOT connect 50 Hz loads to the generator.
DO NOT OVERLOAD THE GENERATOR. See
“Don’t Overload Generator”.
Figure 5 — Fuel Shut-off Valve
Figure 6 — Idle Control Switch
See “Don’t Overload Generator”.
Start generator and let engine stabilize before connecting
electrical loads.
Connect electrical loads in OFF position, then turn ON for
operation.
Turn electrical loads OFF and disconnect from generator
before stopping generator.
Exceeding generators wattage/amperage capacity can
damage generator and/or electrical devices connected
to it.
CAUTION
DO NOT touch hot surfaces.
Allow equipment to cool before touching.
The generator must be at least 5 feet from structures having
combustible walls and/or other combustible materials.
Keep at least 3 feet of clearance on all sides of generator for
adequate cooling, maintenance and servicing.
In the State of California a spark arrester is required by law
(Section 4442 of the California Public Resources Code). Other
states may have similar laws. Federal laws apply on federal
lands. If you equip the muffler with a spark arrester, it must be
maintained in effective working order.
Running engines produce heat.Temperature of
muffler and nearby areas can reach or exceed
150°F (65°C).
Severe burns can occur on contact.
Combustible debris, such as leaves, grass, brush,
ect. can catch fire.
WARNING
When starting engine, pull cord slowly until resistance is felt
and then pull rapidly to avoid kickback.
NEVER start or stop engine with electrical devices plugged in
and turned on.
Rapid retraction of starter cord (kickback) will
pull hand and arm toward engine faster than
you can let go.
Broken bones, fractures, bruises or sprains could
result.
WARNING
10
4000EXL Extended Life Generator
Stopping the Engine
1. Turn OFF and unplug ALL electrical loads from
generator panel receptacles. NEVER start or stop engine
with electrical devices plugged in and turned ON.
2. Move idle control switch to Off” position.
3. Let engine run at no-load for several minutes to
stabilize internal temperatures of engine and generator.
4. Turn engine off according to instructions given in the
engine owner’s manual.
5. Move fuel valve to Off” position.
Operating Automatic Idle Control
This switch is designed to greatly improve fuel economy.
When this switch is turned ON, the engine will only
run at its normal high governed engine speed when
electrical loads are connected.When an electrical load is
removed, the engine will run at a reduced speed.
With the switch off, the engine will run at the normal
high engine speed. Always have the switch off when
starting and stopping the engine.
Charging a Battery
Your generator has the capability of recharging a
discharged 12 Volt automotive or utility style storage
battery. DO NOT use the unit to charge any 6 Volt
batteries. DO NOT use the unit to crank an engine having
a discharged battery.
To recharge 12 Volt batteries, proceed as follows:
1. Check fluid level in all battery cells. If necessary, add
ONLY distilled water to cover separators in battery
cells. DO NOT use tap water.
2. If battery is equipped with vent caps, make sure they
are installed and are tight.
3. If necessary, clean battery terminals.
4. Connect battery charge cable connector plug to panel
receptacle identified by the words “12-VOLTS D.C.”.
5. Connect battery charge cable clamp with red handle
to the positive (+) battery terminal (Figure 7).
6. Connect battery charge cable clamp with black handle
to the negative (–) battery terminal (Figure 7).
7. Start engine. Let engine run while battery recharges.
8. When battery has charged, shut down engine.
NOTE: Use an automotive hydrometer to test battery state
of charge and condition. Follow the hydrometer
manufacturer’s instructions carefully. Generally, a battery is
considered to be at 100% state of charge when specific gravity
of its fluid (as measured by hydrometer) is 1.260 or higher.
COLD WEATHER
OPERATION
Under certain weather conditions (temperatures below
40°F [4°C] combined with high humidity), your generator
may experience icing of the carburetor and/or the
crankcase breather system.To reduce this problem, you
need to perform the following:
1. Make sure generator has clean, fresh fuel.
2. Open fuel valve (turn valve to open position).
3. Use SAE 5W-30 oil (synthetic preferred, see engine
manual).
4. Check oil level daily or after every eight (8) hours of
operation.
Figure 7 — Battery Connections
DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
Wear protective goggles, rubber apron, and rubber gloves.
Storage batteries give off explosive hydrogen gas
during recharging.
Hydrogen gas stays near battery for a long time
after battery has been charged.
Slightest spark will ignite hydrogen and cause
explosion.
You can be blinded or severely injured.
Battery electrolyte fluid contains acid and is
extremely caustic.
Contact with battery fluid will cause severe
chemical burns.
DANGER
4000EXL Extended Life Generator
11
5. Maintain generator following “Maintenance Schedule”
in engine manual.
6. Shelter unit from elements.
In an emergency, use the original shipping carton as a
temporary shelter:
7. Cut off all carton flaps.
8. Cut out one long side of carton to expose muffler side
of unit as shown in Figure 8.
IMPORTANT: The generator must be at least 5 ft.
(152 cm) from structures having combustible walls and/or
other combustible materials. Leave at least 3 ft. (92 cm) all
around generator including overhead, for adequate cooling,
maintenance and servicing.
9. Cut appropriate slots to access receptacles of unit.
10. Start unit, then place carton over it.
IMPORTANT: Remove shelter when temperatures are
above 40°F [4°C].
For a more permanent shelter, build a structure that will
enclose three sides and the top of the generator.
7. Make sure entire muffler-side of generator is exposed,
as shown in Figure 8.
IMPORTANT: The generator must be at least 5 ft.
(152 cm) from structures having combustible walls and/or
other combustible materials. Leave at least 3 ft. (92 cm) all
around generator including overhead, for adequate cooling,
maintenance and servicing.
8. Face exposed end away from wind and elements.
9. Structure should hold enough heat created by the
generator to prevent icing problem.
10. Start and run engine outdoors.
11. Keep exhaust gas from entering a confined area
through windows, doors, ventilation intakes or other
openings.
12. DO NOT enclose generator any more than shown in
Figure 8.
13. Remove shelter when temperatures are above 40°F
[4°C].
14. Turn engine OFF and let cool two (2) minutes before
refueling.
Figure 8 — Permanent Cold Weather Shelter
Wind
DO NOT touch hot surfaces.
Allow equipment to cool before touching.
The generator must be at least 5 feet from structures having
combustible walls and/or other combustible materials.
Keep at least 3 feet of clearance on all sides of generator for
adequate cooling, maintenance and servicing.
Remove shelter when temperatures are above 40°F [4°C].
Running engines produce heat.Temperature of
muffler and nearby areas can reach or exceed
150°F (65°C).
Severe burns can occur on contact.
Combustible debris, such as leaves, grass, brush,
ect. can catch fire.
WARNING
Operate generator ONLY outdoors.
Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes or other openings.
DO NOT operate generator inside any building or enclosure,
including the generator compartment of a recreational vehicle
(RV).
Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea,
fainting or death.
WARNING
12
4000EXL Extended Life Generator
HOW TO USE THE
BATTERY CHARGER
Use battery float charger jack to keep the starting battery
charged and ready for use. Battery charging should be done
in a dry location, such as inside a garage.
1. Plug charger into unit’s “Battery Float Charger” jack,
which is located on the starter switch (Figure 9). Plug
battery charger into a 120 Volt AC wall receptacle.
2. Unplug charger from unit and wall outlet when
generator is being started and while in operation.
3. Keep charger plugged in when generator is not in use
to prolong battery life.The charger has a built in float
equalizer and will not overcharge battery, even when
plugged in for an extended period of time.
IMPORTANT: See “Battery Maintenance” on page 16 for
additional information.
RECEPTACLES
120/240 Volt AC, 20 Amp Locking
Receptacle
Use a NEMA L14-20 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volts at 20 Amps (or greater)
(Figure 10).You can use the same 4-wire cord if you plan to
run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 2,000 watts of power at
16.6 Amps for 120 Volts; 4,000 watts of power (4.0 kW) at
16.6 Amps for 240 Volts.The outlet is protected by a
double pole circuit breaker.
Figure 9 — Battery Charger Jack
NEVER attempt to power a device requiring more amperage
than generator or receptacle can supply.
DO NOT overload the generator. See “Don’t Overload
Generator”.
Receptacles may be marked with rating value greater
than generator output capacity.
CAUTION
Figure 10 — 120/240 Volt AC, 20 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-20
Ground (Green)
4000EXL Extended Life Generator
13
120 Volt AC, 30 Amp Locking
Receptacle
Use a NEMA L5-30 plug with this receptacle. Connect a
3-wire cord set rated for 125 Volts AC at 30 Amps to the
plug (Figure 11).
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts (3.6 kW) of power
at 30 Amps.The outlet is protected by a double pole circuit
breaker and a 30 Amp push-to-reset circuit breaker.
120 Volt AC, 15 Amp Duplex
Receptacle
Each of these outlets is protected against overload by a
double pole circuit breaker (Figure 12).
Use each outlet to operate 120 Volt, 60 Hz, single phase
loads requiring 1,800 (1.8 kW) watts at 15 Amps of current.
12 Volt DC, 10 Amp Receptacle
This receptacle allows you to recharge a 12 Volt
automotive or utility style storage battery with the battery
charge cables provided (Figure 13).
This receptacle can not recharge 6 Volt batteries and can
not be used to crank an engine having a discharged battery.
See the section “Charging a Battery” (page 10) before
attempting to recharge a battery.
Figure 11 — 120 Volt AC, 30 Amp, Locking Receptacle
3-Wire Cord Set
Neutral
120V
Hot
Ground (Green)
NEMA L5-30
Figure 13 — 12 Volt DC, 10 Amp Receptacle
Figure 12 — 120 Volt AC, 15 Amp Duplex Receptacle
14
4000EXL Extended Life Generator
DON'T OVERLOAD
GENERATOR
Capacity
You must make sure your generator can supply enough
rated (running) and surge (starting) watts for the items you
will power at the same time. Follow these simple steps:
1. Select the items you will power at the same time.
2. Total the rated (running) watts of these items.This is
the amount of power your generator must produce to
keep your items running. See Figure 14.
3. Estimate how many surge (starting) watts you will
need. Surge wattage is the short burst of power
needed to start electric motor-driven tools or
appliances such as a circular saw or refrigerator.
Because not all motors start at the same time, total
surge watts can be estimated by adding only the
item(s) with the highest additional surge watts to the
total rated watts from step 2.
Example:
Total Rated (Running) Watts = 3075
Highest Additional Surge Watts = 1800
Total Generator Output Required = 4875
Power Management
To prolong the life of your generator and attached devices,
it is important to take care when adding electrical loads to
your generator.There should be nothing connected to the
generator outlets before starting it's engine.The correct
and safe way to manage generator power is to sequentially
add loads as follows:
1. With nothing connected to the generator, start the
engine as described in this manual.
2. Plug in and turn on the first load, preferably the largest
load you have.
3. Permit the generator output to stabilize (engine runs
smoothly and attached device operates properly.
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load.
NEVER add more loads than the generator capacity.Take
special care to consider surge loads in generator capacity,
as described above.
*Wattages listed are approximate only. Check tool or
appliance for actual wattage.
Tool or Appliance
Rated (Running)
Watts
Additional Surge
(Starting) Watts
Window Air
Conditioner
1200 1800
Refrigerator 800 1600
Deep Freezer 500 500
Television 500 -
Light (75 Watts) 75 -
3075 Total
Running Watts
1800 Highest
Surge Watts
Tool or Appliance
Rated*
(Running)
Watts
Additional
Surge
(Starting)
Watts
Essentials
Light Bulb - 75 watt 75 -
Deep Freezer 500 500
Sump Pump 800 1200
Refrigerator/Freezer - 18 Cu. Ft. 800 1600
Water Well Pump - 1/3 HP 1000 2000
Heating/Cooling
Window AC - 10,000 BTU 1200 1800
Window Fan 300 600
Furnace Fan Blower - 1/2 HP 800 1300
Kitchen
Microwave Oven - 1000 Watt 1000 -
Coffee Maker 1500 -
Electric Stove - Single Element 1500 -
Hot Plate 2500 -
Family Room
DVD/CD Player 100 -
VCR 100 -
Stereo Receiver 450 -
Color Television - 27” 500 -
Personal Computer w/17” monitor 800 -
Other
Security System 180 -
AM/FM Clock Radio 300 -
Garage Door Opener - 1/2 HP 480 520
Electric Water Heater - 40 Gallon 4000 -
DIY/Job Site
Quartz Halogen Work Light 1000 -
Airless Sprayer - 1/3 HP 600 1200
Reciprocating Saw 960 960
Electric Drill - 1/2 HP 1000 1000
Circular Saw - 7 1/4” 1500 1500
Miter Saw - 10” 1800 1800
Planer/Jointer - 6” 1800 1800
Table Saw/Radial Arm Saw - 10” 2000 2000
Air Compressor - 1-1/2 HP 2500 2500
Figure 14 - Wattage Reference Chart
4000EXL Extended Life Generator
15
SPECIFICATIONS
Maximum Surge Watts . . . . . . . . . . . . . . . . . . 6,600 Watts
Continuous Wattage Capacity . . . . . . . . . . . . 4,000 Watts
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0
Rated Maximum Continuous Load Current
At 120 Volts . . . . . . . . . . . . . . . . . . . . . . . . . 33.3 Amps
At 240 Volts . . . . . . . . . . . . . . . . . . . . . . . . . 16.6 Amps
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-phase
Rated Frequency . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hertz
Fuel Tank Capacity . . . . . . . . . . . . . . . . . . . . 4.5 U.S. gallons
Shipping Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 lbs.
GENERAL MAINTENANCE
RECOMMENDATIONS
The Owner/Operator is responsible for making sure that
all periodic maintenance tasks are completed on a timely
basis; that all discrepancies are corrected; and that the unit
is kept clean and properly stored. NEVER operate a
damaged or defective generator.
NOTE: If equipped with inflatable tires, make sure tires
are inflated to the value marked on the tire or within
15 and 40 psi.
NOTE: Should you have questions about replacing
components on your Generac Portable Products generator,
please call 1-800-270-1408 for assistance.
Engine Maintenance
See engine owner’s manual for instructions.
KEEP OUT OF REACH OF CHILDREN. DON'T
POLLUTE. CONSERVE RESOURCES. RETURN
USED OIL TO COLLECTION CENTERS.
Generator Maintenance
Generator maintenance consists of keeping the unit clean
and dry. Operate and store the unit in a clean dry
environment where it will not be exposed to excessive
dust, dirt, moisture or any corrosive vapors. Cooling air
slots in the generator must not become clogged with
snow, leaves or any other foreign material.
NOTE: DO NOT use a garden hose to clean generator.
Water can enter engine fuel system and cause problems. In
addition, if water enters generator through cooling air slots,
some of the water will be retained in voids and cracks of
the rotor and stator winding insulation.Water and dirt
buildup on the generator internal windings will eventually
decrease the insulation resistance of these windings.
Fuel Valve Maintenance
The fuel valve is equipped with a fuel sediment cup, screen,
retaining ring and o-ring that need to be cleaned every
6 months or 100 hours (whichever occurs first).
1. Move fuel valve to Off” position.
2. Remove sediment cup from fuel valve. Remove o-ring,
retaining ring and screen from fuel valve (Figure 15).
Figure 15 — Fuel Valve Maintenance
Sediment Cup
O-ring
Retaining Ring
Screen
Used motor oil has been shown to cause skin cancer in
certain laboratory animals.
Thoroughly wash exposed areas with soap and water.
Avoid prolonged or repeated skin contact with used
motor oil.
CAUTION
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
Disconnect the spark plug wire from the spark plug and place
the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug removed.
Unintentional sparking can result in fire or
electric shock.
WARNING
16
4000EXL Extended Life Generator
3. Wash sediment cup, o-ring, retaining ring, and screen in
a nonflammable solvent. Dry them thoroughly.
4. Place screen, retaining ring, and o-ring into fuel valve.
Install sediment cup and tighten securely.
5. Move fuel valve to On” position, and check for leaks.
Replace o-ring if there is any leakage.
Battery Maintenance
Other than float charging, described elsewhere, no
maintenance is required for the battery. Keep the battery
and terminals clean and dry.
IMPORTANT: Battery charging should be performed in a
dry location, such as inside a garage.
Generator Cleaning
Use a damp cloth to wipe exterior surfaces clean.
Use a soft bristle brush to loosen caked on dirt or oil.
Use a vacuum cleaner to pick up loose dirt and debris.
Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and opening on
generator.These openings must be kept clean and
unobstructed.
STORAGE
The generator should be started at least once every seven
days and allowed to run at least 30 minutes. If this cannot
be done and you must store the unit for more than
30 days, use the following guidelines to prepare it for
storage.
Generator Storage
Clean the generator as outlined in “Generator Cleaning”.
Check that cooling air slots and openings on generator
are open and unobstructed.
Engine Storage
See engine owner’s manual for instructions.
Other Storage Tips
To prevent gum from forming in fuel system or on
essential carburetor parts, empty all two supplied fuel
stabilizer containers into fuel tank and fill with fresh
gasoline. Run the unit for several minutes to circulate the
additive through the carburetor.The unit and fuel can
then be stored for up to 24 months.Additional fuel
stabilizer can be purchased locally.
DO NOT store gasoline from one season to another
unless it has been treated as described above.
Replace fuel container if it starts to rust. Rust and/or dirt
in fuel can cause problems if it's used with this unit.
Store in clean and dry area.
DO NOT expose generator to excessive moisture, dust, dirt,
or corrosive vapors.
DO NOT insert any objects through cooling slots.
Improper treatment of generator can damage it and
shorten its life.
CAUTION
DO NOT place a storage cover over a hot generator.
Let equipment cool for a sufficient time before placing the
cover on the equipment.
Storage covers can be flammable.
WARNING
4000EXL Extended Life Generator
17
TROUBLESHOOTING
Problem Cause Correction
No AC output is available, but
generator is running.
1. One of the circuit breakers is open.
2. Fault in generator.
3. Poor connection or defective cord
set.
4. Connected device is bad.
1. Reset circuit breaker.
2. Contact Authorized service facility.
3. Check and repair.
4. Connect another device that is in
good condition.
Generator runs good at no-load
but "bogs" down" when loads are
connected.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
1. Disconnect shorted electrical load.
2. See "Don't Overload Generator".
3. Contact Authorized service facility.
Generator will not start; or starts
and runs rough.
1. Failed battery.
2. Low oil level.
1. Replace battery.
2. Fill crankcase to proper level or
place generator on level surface.
Generator shuts down during
operation.
1. Out of gasoline.
2. Low oil level.
1. Fill fuel tank.
2. Fill crankcase to proper level or
place generator on level surface.
Generator lacks power. Load is too high. See "Don't Overload Generator".
18
4000EXL Extended Life Generator
NOTES
GENERAC PORTABLE PRODUCTS OWNER EQUIPMENT WARRANTY POLICY
Effective November 1, 2004
WARRANTY PERIOD*
* The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the
period of time stated in the table above. "Consumer use" means personal residential household use by a retail consumer.
"Commercial use" means all other uses, including use for commercial, income producing or rental purposes. Once equipment has
been used commercially, it shall thereafter be considered to be in commercial use for purposes of this warranty.
** The engine and starting batteries are warranted solely by the manufacturers of those products.
WARRANTY REGISTRATION IS NOT NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON POWER
PRODUCTS EQUIPMENT.SAVE YOUR PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE
INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED,THE MANUFACTURING DATE OF THE
EQUIPMENT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
About your equipment warranty:
We welcome warranty repair and apologize to you for being inconvenienced.Any Authorized service dealer may perform warranty
repairs. Most warranty repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For
example, warranty service would not apply if equipment damage occurred because of misuse, lack of routine maintenance, shipping,
handling, warehousing or improper installation. Similarly, the warranty is void if the manufacturing date or the serial number on the
equipment has been removed or the equipment has been altered or modified. During the warranty period, the Authorized service
dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use and service.This
warranty will not cover following repairs and equipment:
Normal Wear: Outdoor power equipment, like all mechanical devices, needs periodic parts, service and replacement to perform
well.This warranty does not cover repair when normal use has exhausted the life of a part or the equipment.
Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or
unauthorized installation or alteration and modification, misuse, negligence, accident, overloading, overspeeding, improper
maintenance, repair or storage so as, in our judgment, to adversely affect its performance and reliability.This warranty also does not
cover normal maintenance such as adjustments, fuel system cleaning and obstruction (due to chemical, dirt, carbon or lime, etc.).
Other Exclusions: Also excluded from this warranty are wear items such as quick couplers, oil gauges, belts, o-rings, filters,
pump packing, etc., pumps which have been run without water supplied or damage or malfunctions resulting from accidents,
abuse, modifications, alterations, or improper servicing or freezing or chemical deterioration.Accessory parts such as guns,
hoses, wands and nozzles are excluded from the product warranty.This warranty excludes failures due to acts of God and other
force majeure events beyond the manufacturers control.Also excluded is used, reconditioned, and demonstration equipment;
equipment used for prime power in place of utility power and equipment used in life support applications.
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
JEFFERSON,WISCONSIN, U.S.A.
LIMITED WARRANTY
"Generac Portable Products is a licensed trademark of Briggs & Stratton Power Products. Briggs & Stratton Power Products will
repair or replace, free of charge, any part, or parts of the equipment** that are defective in material or workmanship or both.
Transportation charges on parts submitted for repair or replacement under this warranty must be borne by purchaser.This
warranty is effective for the time periods and subject to the conditions provided for in this policy. For warranty service, find your
nearest Authorized service dealer by calling 1-800-270-1408.Warranty service may only be performed by a Briggs & Stratton
Power Products Authorized service dealer.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE,ARE LIMITED TO THE TIME PERIOD SPECIFIED, OR TO THE EXTENT PERMITTED
BY LAW.ANY AND ALL IMPLIED WARRANTIES ARE EXCLUDED. LIABILITY FOR CONSEQUENTIAL DAMAGES UNDER
ANY AND ALL WARRANTIES ARE EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some countries or
states do not allow limitations on how long an implied warranty lasts, and some countries or states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation and exclusion may not apply to you.This warranty gives
you specific legal rights and you may also have other rights that vary from country to country or state to state.
PRODUCTS** CONSUMER USE COMMERCIAL USE
Pressure Washer 1 year 90 days
Portable Generator 2 years (2nd year parts only) 1 year
20
4000EXL Extended Life Generator
TABLE DES MATIÈRES
Règles de Sécurité. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-22
Connaissez Votre Générateur . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Assemblage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-25
Opération . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-32
Caractéristiques du Produit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Entretien . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-34
Rangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Dépannage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Garantie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
DESCRIPTION DE L ÉQUIPEMENT
Lisez avec soin ce manuel et familiarisez-vous avec
votre générateur. Connaissez ses applications, ses
limitations et les dangers qu'il implique.
Ce générateur est un générateur entraîné par un moteur à champ
magnétique rotatif produisant du courant alternatif (c.a.). Il a été
conçu pour fournir du courant électrique pour faire marcher des
charges compatibles d'éclairage, d'appareils ménagers, d'outil et de
moteur. Le champ tournant du générateur est entraîné à
3,600 T/M par un moteur seul cylindrique.
ATTENTION! NE PAS dépasser la capacité en watts ou en
Ampères du générateur.Voir "Ne Pas Surcharger Générateur"
pour l'information spécifique.
Tout a été mis en oeuvre pour que les informations contenues
dans ce manuel soient exactes et à jour. Cependant, nous se
réserve le droit de changer, d'altérer ou d'améliorer le produit à
n'importe quel moment sans avis préalable.
Le Système de contrôle de l'émission du générateur est garanti
pour des normes établies par L'Agence de protection de
l'environnement. Pour des informations sur la garantie, se reporter
au manuel du moteur.
RÈGLES DE SÉCURITÉ
Ceci est la sûreté le symbole vif. Il est utilisé pour
vous alerter aux dangers de blessure personnels
potentiels. Obéir tous messages de sûreté qui suivent
ce symbole éviter la blessure ou la mort possibles.
Le symbole indiquant un message de sécurité est accompagné d'un
mot indicateur (DANGER,ATTENTION,AVERTISSEMENT), d'un
message illustré et/ou d'un message de sécurité visant à vous
avertir des dangers. DANGER indique un danger qui, s'il n'est pas
évité, provoquera des blessures graves, voire fatales.
AVERTISSEMENT indique un danger qui, s'il n'est pas évité, peut
provoquer des blessures graves, voire fatales. ATTENTION
indique un danger qui, s'il n'est pas évité, peut provoquer des
blessures mineures ou légères. Le mot ATTENTION, lorsqu'il est
utilisé sans le symbole d'alerte, indique une situation pouvant
endommager l'équipement. Suivez les messages de sécurité pour
éviter ou réduire les risques de blessures ou de mort.
Symboles de Danger et Moyens
L’échappement du moteur de ce produit contient des produits
chimiques que l’État de Californie considère comme causant le
cancer, des déformations à la naissance ou d’autres dangers
concernant la reproduction.
AVERTISSEMENT
Feu
Explosion
Emanations Toxiques
Surface Chaude
Choc Électrique
Électrocution
Choc Électrique
Pression Explosive
Brûlures Chimiques
Recul
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Simplicity 01656 Manuel utilisateur

Catégorie
Accessoires pour véhicules automobiles
Taper
Manuel utilisateur

dans d''autres langues