Simplicity 071150-00 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

Not for Reproduction
100/150/200 Amp Automatic
Transfer Switch
with Utility
Service Disconnect
Installation and Operator’s Manual
Questions?
Help is just a moment away!
Call: Transfer Switch Helpline
800-732-2989 Monday - Friday 8:00 AM - 5:00 PM Central Time
Copyright © Briggs & Stratton Corporation
Milwaukee, WI USA. All Rights Reserved.
80020772
Revision B
Not for Reproduction
2 BRIGGSandSTRATTON.COM
Thank you for your purchase of this Briggs & Stratton® automatic transfer switch. This product is designed for use with specific home
standby generators and may not function with generators or remote modules produced by other manufacturers. Seek a qualified electrical
professional to determine applicability of this equipment to equipment manufactured by others. When operated and maintained according to
the instructions in this manual, your system will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with this system and how to avoid them.
We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation is unique, it is impossible
to know of and advise of all conceivable procedures and methods by which installation might be achieved. We do not know all possible
hazards and/or the results of each possible method or procedure. It is important that you read and understand these instructions thoroughly
before attempting to install or operate this equipment. Save these original instructions for future reference.
This transfer switch and optional remote modules require professional installation before use. Refer to the Installation section of this manual
and the installation instructions packaged with the remote modules for instructions on installation procedures. Only licensed electrical
contractors should install transfer switches and remote modules. Installations must strictly comply with all applicable federal, state and local
codes, standards and regulations. Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages. There are many
authorized service dealers who provide quality service. You can also contact Technical Service by phone at 800-743-4115 between 8:00 AM
and 5:00 PM CT, or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Not for Reproduction
3
Table of Contents
Important Safety Instructions ...........................4
Installation ...........................................5
Home Owner Responsibilities .....................................5
Owner Orientation ...............................................5
Installing Dealer/Contractor Responsibilities .........................5
Equipment Description ...........................................5
Delivery Inspection ..............................................6
Mounting Guidelines .............................................6
Power Wiring Interconnections ....................................7
System Setup .................................................10
Testing the Automatic Transfer Switch .............................11
Controls ............................................12
Operation ...........................................12
Enclosure Door ................................................12
Troubleshooting .....................................13
Transfer Switch Schematic Diagram ....................14
Transfer Switch Wiring Diagram........................15
Product Specfications ................................16
Not for Reproduction
4 BRIGGSandSTRATTON.COM
Save These Instructions
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the equipment.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal injury
hazard. A signal word (DANGER, WARNING, or CAUTION) is used
with the alert symbol to designate a degree or level of hazard
seriousness. A safety symbol may be used to represent the type of
hazard. The signal word NOTICE is used to address practices not
related to personal injury.
DANGER indicates a hazard which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazard which, if not avoided, could result
in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could result
in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in this
manual, and the tags and decals affixed to the unit are, therefore,
not all-inclusive. If you use a procedure, work method or operating
technique that the manufacturer does not specifically recommend,
you must satisfy yourself that it is safe for you and others. You
must also make sure that the procedure, work method or operating
technique that you choose does not render the equipment unsafe.
NOTICE Only qualified electricians should attempt installation
of this equipment, which must strictly comply with applicable
codes, standards and regulations.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
NOTICE Improper treatment of equipment could damage it and
shorten its life.
Use equipment only for intended uses.
If you have questions about intended use, ask dealer or contact
Briggs & Stratton Power Products.
Do not expose equipment to excessive moisture, dust, dirt, or
corrosive vapors.
Remain alert at all times while working on this equipment. Never
work on the equipment when you are physically or
mentally fatigued.
If connected devices overheat, turn them off and turn off their
circuit breaker/fuse.
Electrical Shock Read Manual
WARNING Shock Hazard. Installing low and high voltage
wire in same conduit could result in death, serious injury
and/or property damage.
Do not run low and high voltage wire in the same conduit unless
the insulation rating on ALL wiring is rated for 600V. See NEC
for more information.
WARNING Failure to properly ground equipment could cause
electrocution resulting in death or seriousinjury.
Do not touch bare wires.
Do not use equipment with worn, frayed, bare or otherwise
damaged wiring.
Do not handle electrical cords while standing in water, while
barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce shock hazard.
Do not allow unqualified persons or children to operate or
service equipment.
In case of an accident caused by electrical shock, immediately
shut down all sources of electrical power and contact local
authorities. Avoid direct contact with the victim.
WARNING Shock hazard. Equipment contains high voltage
that could result in death, serious injury and/or
property damage.
DO NOT operate this equipment imprudently or neglect its
maintenance.
Not for Reproduction
5
Installation
We sincerely appreciate your patronage and have made significant effort
to provide for a safe, streamlined and cost-effective installation. Because
each installation is unique, it is impossible to know of and advise the
trade of all conceivable procedures and methods by which installation
might be achieved. Neither could we know of possible hazards and/or the
results of each method
or procedure.
For these reasons, only current licensed electrical professionals should
attempt system installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Your equipment is supplied with this Installation Manual and a separate
Operator’s Manual. These are important documents and should be
retained by the owner after the installation has
been completed.
Every effort has been made to make sure that the information in this
manual is both accurate and current. However, the manufacturer reserves
the right to change, alter or otherwise improve the system at any time
without prior notice.
Home Owner Responsibilities
To help you make informed choices and communicate effectively with
your installation contractor(s), read and understand Owner Orientation
before contracting or starting your
equipment installation.
To arrange for proper installation, contact the store at which you
purchased your equipment, your dealer, or your utility
power provider.
The equipment warranty is VOID unless the system is installed by
licensed electrical professionals.
Owner Orientation
The illustrations provided are for typical circumstances and are meant to
familiarize you with the installation options available with your system.
Local codes, appearance, and distances are the factors that must be
considered when negotiating with an installation professional. As the
distance from the existing electrical service increases, compensation in
wiring materials must be allowed for. This is necessary to comply with
local codes and overcome electrical voltage drops.
These factors will have a direct effect on the overall price of your
equipment installation.
Your installer must check local codes AND obtain permits before installing
the system.
• Read and follow the instructions given in this manual.
• Follow a regular schedule in caring for and using your equipment,
as specified in this manual.
Installing Dealer/Contractor Responsibilities
• Read and observe the Important Safety Instructions.
• Read and follow the instructions given in this manual.
• The installer may need to provide appropriate rated contactors
based on loads to be controlled.
• Discuss with owner their load priority preferences to decide on
remote module priority settings.
• Check federal, state and local codes and authority having
jurisdiction, for questions on installation.
• Ensure generator is not overloaded with selected loads.
If you need more information about the transfer switch, call
800-732-2989, between 8:00 AM and 5:00 PM CT.
Equipment Description
The transfer switch is designed to transfer selected loads found in normal
residential installations to standby power in the event of a primary power
outage. The load is connected either to utility power (normal) or home
standby power (generator). The generator controller monitors utility and
generator voltages, and automatically controls the transfer switch board
to connect load to the appropriate source of power.
Only a licensed electrician should complete a home standby installation.
Service conduit and conductors can be wired directly from the watt-hour
meter to the transfer switch. A separate service entrance disconnect and
associated wiring is not required when installed per applicable federal,
state and local codes, standards andregulations.
Major components of the transfer switch are a 2 pole utility disconnect
circuit breaker, a 2 pole double throw transfer switch, transfer switch
board, fused utility terminals and interconnecting wiring. All of these
components are housed in a NEMA3R enclosure that is suitable for both
indoor and outdoor installations.
The transfer switch is solenoid-operated from utility or generator inputs
and contain suitable mechanical and electrical interlock switches to
eliminate the possibility of connecting the utility service to the generator
output. It has ratings capable of switching full utility power into the
residence. In addition, a manual override lever is provided for the transfer
function.
Not for Reproduction
6 BRIGGSandSTRATTON.COM
The generator controller has active circuits sensing utility and
generator voltages. The generator controller controls when the
generator starts up and when the transfer switch transfers to utility
or generator power. Status LEDs indicate the position the transfer
switch contactor is at
Delivery Inspection
After opening the carton, carefully inspect the transfer
switch components for any damage that may have occurred
duringshipment.
If loss or damage is noted at time of delivery, have the person(s)
making delivery note all damage on the freight bill and affix his
signature under the consignor’s memo of loss or damage. If loss
or damage is noted after delivery, contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Shipment contents:
• Automatic transfer switch
• Installation and operator’s manuals
To be supplied by installer:
• Connecting wire and conduit
• Various specialty tools/equipment
Mounting Guidelines
The transfer switch system circuitry is enclosed in a NEMA Type3R
enclosure suitable for indoor/outdoor use. Guidelines for mounting
the enclosure include:
• Install enclosure on a firm, sturdy supporting structure.
• The transfer switch enclosure must be installed with
minimum NEMA3R hardware for conduit connections.
• To prevent switch contact distortion, level and plumb the
enclosure. This can be done by placing washers between the
enclosure and the mounting surface.
• NEVER install the switch or remote modules where any
corrosive substance might drip onto the enclosure.
• Protect the switch at all times against excessive moisture,
dust, dirt, lint, construction grit and corrosivevapors.
A typical automatic transfer switch installation is depicted below
and on the next few pages. Examples of remote module installations
are also shown. It is best if the transfer switch is mounted near the
utility meter, either inside or outside. Discuss layout suggestions/
changes with the owner before beginning the system installation
process
NOTICE Before drilling conduit entry holes, or any other holes,
cover and protect the switch and electronics to prevent dirt and
metal fragments from entering the mechanical and electrical
components. Failure to do so may result in damage or malfunction
of the switch. Wiring to generator must be enclosed in conduit.
NOTICE Use a vacuum to clean any dirt or metal shavings inside
the transfer switch. Do not use a blower or compressed air to clean
the inside of the transfer switch because debris may become lodged
in the electrical and mechanical components causing damage or
malfunction.
Main
Distribution
Panel
Transfer Switch
w/ Service
Disconnect
Hot Water
Heater
Air
Conditioner
Generator
Watt -
Hourmeter
Service Disconnect
Branch
Circuits
Not for Reproduction
7
Power Wiring Interconnections
NOTICE Improper installation could cause damage to the circuit
boards and shorten their life. Installing circuit boards in live
circuits will damage the board and is not covered by warranty.
ALWAYS disconnect ALL sources of power prior to servicing.
Remove all power prior to installing this equipment. Failure to
do so could cause internal damage to the board when making
electrical connections.
Turn generator to OFF position.
Turn off utility power to the standby generator and
transferswitch.
All wiring must be the proper gauge, properly supported and
protected by conduit. All wiring should be done per applicable
federal, state and local codes, standards and regulations. Obey
wire type and torque specifications printed on the terminal blocks,
neutral/ground connectors, and installation instructions.
Use installer supplied 600VAC or greater copper or aluminum wire
of a gauge that complies with the latest version of the National
Electric Code to complete the following connections between utility
power, transfer switch, generator, main distribution panel, and
optional remote modules. Apply the necessary correction factors
and wire size calculations.
1. Set generator’s circuit breaker to OFF position.
2. Set generator’s system switch to OFF position.
3. Remove 15 Amp fuse from generator control panel.
4. Turn off utility power to the standby generator and
transfer switch.
5. Connect utility service to transfer switch’s utility
service disconnect circuit breaker terminals marked
“UTILITYCONNECTION”.
6. Connect utility service neutral to transfer switch
neutralterminal.
7. Connect main distribution panel feeder conductors to transfer
switch terminals marked “LOADCONNECTION”.
8. NOTE: Connect main distribution panel neutral to transfer
switch neutral terminal.
9. Connect main distribution panel ground to transfer switch
“GND” terminal.
Assure grounding electrode conductor is connected and
bonded per applicable federal, state and local codes,
standards and regulations.
10. Connect feeder conductors from transfer switch
“GENERATOR CONNECTION” terminals to generator circuit
breaker LINE1 and LINE2 terminals.
33
240V
11
22
44
11
22
44
120V
120V
0
Neutral
Ground
To Transfer Switch
Line 1 Neutral
Ground
Line 2
Generator
Circuit
Breaker
WARNING Shock Hazard. Installing low and high voltage
wire in same conduit could result in death, serious injury
and/or property damage.
Do not run low and high voltage wire in the same conduit unless
the insulation rating on ALL wiring is rated for 600V. See NEC
for more information.
WARNING Shock Hazard. Failure to properly wire equipment could
cause electrocution resulting in death or seriousinjury.
DO NOT connect the ground conductor to the neutral connection in the
remote module.
All modules must have a dedicated neutral connection.
D3
J9
J10
GND 7
4
8
T/R
+12VDC
Generator
Mode
B B A A
Generator
Mode
From
generator
Not for Reproduction
8 BRIGGSandSTRATTON.COM
11. Connect conductor from transfer switch neutral terminal to
generator NEUTRAL terminal. Observe generator control panel
labeling for terminalidentification.
12. Connect conductor from transfer switch “GND” terminal to
generator control panel “GROUND” terminal.
Assure generator equipment grounding conductor is connected per
applicable federal, state and local codes, standards and regulations.
13. Using minimum #14 AWG conductors, connect the transfer switch
“UTILITY 240 VAC” terminals to generator’s “240 VAC” terminals
via two-pole connector supplied with generator.
14. Using minimum #18 AWG twisted pair copper or aluminum
conductors for GND and T/R and for+12VDC a single #18 AWG.
Refer to table below for maximum wire length per wire gauge sizes:
Maximum Wire Length Wire Gauge
1 - 200 ft
(1 - 60 m)
18
201 - 300 ft
(61 - 91 m)
16
301 - 500 ft
(92 - 152 m)
14
Torque Terminal
J7 = 2.5 lb/in.
Generator Control Panel:
NOTICE: For this system to work, the generator controller needs
to have hardware and software version as mentioned below:
Hardware Revision or Higher
Software
Revision or
Higher
E3 E1.00
When upgrading to ACCM board and Symphony 2
®
Power
Management System TxRx and TxRxGnd wires cannot be more
than 200 ft. in length between transfer switch control board and
generator control panel.
15. Tighten all wire connections/fasteners to proper torque. See label
inside transfer switch enclosure or values listed in remote module
installation instructions for proper
torque values.
The illustration on the following page shows a completed transfer switch
installation. Your actual layout will vary.
Illustration callouts are:
A - From utility watt-hour meter
B - Optional generator disconnect circuit breaker
C - Transfer switch enclosure
D - T/R and GND to Generator
E - TRCM
F - Neutral terminal
G - Neutral bus
H - Ground bus
J - Main distribution panel
K - UTILITY 240VAC to Generator
L - Two pin connector or Two pin terminal block at generator
M - Ten pin connector or Eight pin terminal block at generator
N - Generator circuit breaker
P - Generator
R - Generator Neutral terminal
S - Generator Ground terminal
T - Transfer switch ground terminal
U - Load connection to distribution panel
V - Utility disconnect circuit breaker
W - Utility connection
X - Generator connection (if no generator disconnect present)
Torque Table
Utility 250 lb-in.
Generator
50 lb-in.
(100A)
250 lb-in.
(150/200A)
Neutral 250 lb-in.
Ground 50 lb-in.
Fuse Block 12 lb-in.
Control
12 lb-in.
(J10)
2.5 lb-in.
(J7)
16. NOTE: Wires between generator and transfer switch need to be
enclosed in conduit.
(1) No
(2) Comm
(3) NC
(4) TxRx
(5) TxRx Gnd
(6) + LED
(7) Gnd
(8) 12v DC
UTILITY A
UTILITY B
(1) No
(2) Comm
(3) NC
(4) TxRx
(5) TxRx Gnd
(6) + LED
(7) Gnd
(8) 12v DC
UTILITY A
UTILITY B
C1
12VDC
TCRM
Located at
Transfer Switch
Not for Reproduction
9
Typical Transfer Switch shown
G
LINE1
LINE2
N
240
VAC
L
1
L
2
N
G
L
1
L
2
N
OR
D3
J9
J10
GND 7
4
8
T/R
+12VDC
Generator
Mode
B B A A
GND
7
4
8
T/R
+12VDC
A
D
E
F
S
R
G
T
L
W
N
M
X
J H
U
P
CB
K
V
L
M
Not for Reproduction
10 BRIGGSandSTRATTON.COM
*ONLY APPLICABLE ON SOME MODELS
*
SOFTWARE VERSION
DISPLAYED
E-Governor
Check
Transfer Switch
Utility Dropout
Utility Pickup
Warm-up Time
KW
HZ
PHASE
VOLTS
KW
FLASHING
50/60 Hz
FLASHING
SINGLE
or
THREE
FLASHING
VOLTS
FLASHING
ACCM
or
TRCM
70%
or
80%
80%
or
90%
20 Seconds
or
50 Seconds
ACCM
TRCM
Stepper Motor
will sweep through throttle
range for dealer
visual verification
or
or
or
or
or
or
or
or
or
or
or
or
or
or
or
or
or
or
or
"ADVANCED SETTINGS"
WILL SCROLL
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
System Setup
1. TCRM board. This is only applicable to
Briggs & Stratton
®
generator controller
software version E1 or higher,
hardware E4 or higher.
• Go to the generator control panel.
• Access advanced menu/screen
settings. For explanation on how to do
this, read the Control Panel section of
the generator manual.
• In the advanced menu, scroll to
transfer switch settings as shown.
• Set to TRCM and press OK.
2. You must perform the following before
operating the system:
• If generator is installed in an area
regularly subjected to temperatures
below 40°F(4°C), select a 50 second
warm up time at the advanced menu
settings. Factory default is set to a 20
second warm up.
• Insert the 15A ATO fuse into
the fuse holder of the generator
controller. Measure voltage across
terminal labeled GND and +12V DC
at generator electrical box. Voltage
measured should be around +12V DC.
• If no voltage is measure across
terminal labeled GND and 12V DC
check to make sure hardware revision
of control panel is E4 or higher.
Not for Reproduction
11
Supervisory Control Wiring (A-A and B-B)
1. A-A and B-B are NC contacts that are used as lockouts when
the transfer switch is switched to generator power.
NOTE: There are two circuits provided to keep the supervisory
loads separated from each other.
2. Air conditioning control wiring or larger loads can be
connected to A-A or B-B.
3. A-A and B-B are rated 120V AC, 1A
4. A-A and B-B wire range 12 - 22 AWG. Torque 12 lb/in.
Testing the Automatic Transfer Switch
Turn the utility service disconnect circuit breaker feeding the transfer
switch contactor to the OFF position. The system’s automatic sequence
described below will initiate. To return to utility power, turn the utility
service disconnect circuit breaker to the ON position.
Utility Fail
The generator senses when utility voltage is below 70percent of nominal.
Engine start sequence is initiated after 6second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer. Select delay of
20seconds or 50 seconds.
Transfer
Transfer from utility to generator supply occurs after voltage is above set
levels, the generator control board will send a transfer signal (12 VDC)
to TRCM board. At this time the red LED will turn on and transferswitch
switches to generator power. Minimum engine run time is 5 minutes after
transfer.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from generator to utility power is approximately 10 seconds
after utility voltage supply is above pickup level and minimum run time is
completed.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
A
A
120V AC
120V AC
B
B
LOAD
LOAD NEUTRAL
NEUTRAL
Not for Reproduction
12 BRIGGSandSTRATTON.COM
Controls
Other than a Manual Override lever, there are no operator controls
because this is an automatic transfer switch. The manual override
is to be used only by licensed professionals. Information on handle
use can be obtained by calling Technical Service at 800-732-2989.
Operation
To select automatic transfer operation, do the following:
1. In transfer switch, set utility disconnect circuit breaker
to ON position.
2. Set generator disconnect circuit breaker to ON position.
3. Install 15 Amp fuse in generator’s control panel.
4. Set generator’s system switch to AUTO position.
Enclosure Door
To open the transfer switch door, remove the two exterior
thumb screws (A) and carefully lift off door.
To close and secure the door, push door closed against
enclosure making sure that the tab on the enclosure fits into
the slot on the door. While in this position, the door can
rest on the tab (B) at the bottom of the enclosure. Reinstall
both thumb screws to finger tight. Enclosure door MUST be
closed and secured at all times except when system is being
serviced.
When Calling for Assistance
You must have the Model Number and Serial Number from each
transfer switch or remote module ID label at hand if it is necessary
to contact a local service center regarding service or repair. Obtain
this information from the unit ID labels located on or inside device.
For convenience, record the information on the inside front cover of
this manual.
To contact Briggs & Stratton call 800-732-2989, between 8:00 AM
and 5:00 PM CT.
Installation Inspection
Before placing the system into service, inspect the entire installation
carefully.
WARNING Shock Hazard. Equipment contains high voltage
that could cause electrocution resulting in death or
serious injury.
Testing must only be performed by qualified personnel.
Do not operate this equipment imprudently, carelessly or neglect
its maintenance.
A
B
Not for Reproduction
13
Troubleshooting
Problem Cause Correction
Automatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
3. Transfer signal (12VDC) not present
1. Reset generator circuit breaker.
2. Refer to generator manual.
3. Check for transfer signal (12VDC) at
generator controller and TRCM
Automatic transfer switch does not
transfer to utility
1. Utility disconnect circuit breaker open in
transfer switch.
2. Utility voltage not acceptable.
1. Reset utility disconnect circuit breaker in
transfer switch.
2. Wait for utility voltage to return tonormal.
Generator is still running after switch
transfers to utility power
Engine cool down period. Engine should stop after 1 minute.
Generator or supervised loads (air
conditioner, etc.) are operating
improperly when generator is
supplyingpower
1. A-A or B-B contacts not
operatingcorrectly.
1. Check A-A or B-B contacts for
proper operation and/or check
control wiring to external load.
Generator is still running after utility
power is restored
1. Minimum engine run time has notelapsed.
2. Fuse(s) in transfer switch isdefective.
1. Wait five minutes for transfer switch to
retransfer to utility power.
2. Contact local authorized servicecenter.
Not for Reproduction
14 BRIGGSandSTRATTON.COM
Transfer Switch Schematic Diagram
Optional generator
disconnect circuit
breaker
Not for Reproduction
15
Transfer Switch Wiring Diagram
Not for Reproduction
16 BRIGGSandSTRATTON.COM
Automatic Transfer Switch
Product Specfications
Model 071200
Series 200SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........25,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Model 071100
Series 100SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................100 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........22,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................13 kg (29 lbs)
This transfer switch is a UL Listed device.
Model 071150
Series 200SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................150 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ............................................................................................... 2
Frequency ................................................................................60 Hz
Fault Current Rating ..........25,000 RMS Symmetrical Amperes on Utility Side
................................. 10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ...............-28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Not for Reproduction
Interruptor de transferencia
automática de 100/150/200
amperios
con
Desconexión de servicio de la red pública
Manual de instalación y del operador
¿Preguntas?
¡La ayuda está muy cerca!
Llame a: Línea de ayuda del interruptor de transferencia
800-732-2989 Lunes a viernes de 8:00 a. m. a 5:00 p. m. hora del Centro
Copyright © Briggs & Stratton Corporation
Milwaukee, WI, EE. UU. Todos los derechos reservados.
80020772
Modificación B
Not for Reproduction
2 BRIGGSandSTRATTON.COM
Gracias por comprar este interruptor de transferencia automática de Briggs & Stratton®. Este producto está diseñado para usarlo con
generadores de reserva residenciales específicos y es posible que no funcione con generadores o módulos remotos producidos por
otros fabricantes. Busque a un electricista profesional calificado para determinar la aplicabilidad de este equipo en equipos fabricados
por terceros. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, el sistema le proporcionará muchos años de
funcionamiento fiable.
Este manual contiene información de seguridad para advertirle sobre los peligros y riesgos asociados con este sistema y cómo evitarlos.
Hemos realizado todos los esfuerzos para garantizar una instalación segura, simplificada y rentable. Cada instalación es única y por ello es
imposible conocer y brindar consejos con respecto a todos los métodos y procedimientos posibles mediante los cuales se puede lograr la
instalación. Tampoco conocemos todos los posibles peligros o resultados de cada método o procedimiento posible. Es importante que lea
y comprenda totalmente estas instrucciones antes de tratar de instalar u operar este equipo. Conserve estas instrucciones originales para
consultas a futuro.
Este interruptor de transferencia y los módulos remotos opcionales requieren una instalación profesional antes de su uso. Consulte la
sección Instalación de este manual y las instrucciones de instalación incluidas con los módulos remotos para obtener instrucciones sobre
los procedimientos de instalación. Solo contratistas eléctricos con licencia deberían instalar los interruptores de transferencia y los módulos
remotos. Las instalaciones deben cumplir estrictamente con todos los códigos, las normas y los reglamentos federales, estatales y locales
correspondientes. Su instalador debe seguir completamente las instrucciones.
Dónde puede encontrarnos
Nunca deberá buscar demasiado para encontrar la asistencia y el servicio de Briggs & Stratton para su sistema. Consulte las Páginas
Amarillas. Existen muchos distribuidores de servicio autorizados que ofrecen asistencia de calidad. También puede comunicarse con
Servicio Técnico por teléfono al 800-743-4115 entre las 8:00a.m. y las 5:00p.m. hora del Centro, o bien, puede hacer clic en Find a Dealer
(Encontrar un distribuidor) en BRIGGSandSTRATTON.COM, donde obtendrá una lista de distribuidores autorizados.
Para futuras consultas
Complete la información a continuación y guárdela con su recibo para permitir la identificación de la unidad para futuros asuntos de
compras.
Not for Reproduction
3
Table of Contents
Instrucciones de seguridad importantes..................4
Instalación ...........................................5
Responsabilidades del propietario de la vivienda .....................5
Orientación para el propietario.....................................5
Responsabilidades del distribuidor o contratista de instalación ..........5
Descripción del equipo ...........................................5
Inspección de entrega ...........................................6
Pautas de montaje ..............................................6
Interconexiones del cableado eléctrico..............................7
Configuración del sistema .......................................10
Prueba del interruptor de transferencia automática ...................11
Controles ...........................................12
Operación...........................................12
Puerta de la caja ...............................................12
Detección de fallas ...................................13
Diagrama esquemático del interruptor de transferencia ...14
Diagrama de cableado del interruptor de transferencia ....15
Especificaciones del producto .........................16
Not for Reproduction
4 BRIGGSandSTRATTON.COM
Conserve estas instrucciones
Instrucciones de seguridad importantes
CONSERVE ESTAS INSTRUCCIONES - Este manual
contiene instrucciones importantes que se deben seguir
durante la instalación y el mantenimiento del equipo.
Símbolos de seguridad y significados
El símbolo de alerta de seguridad indica un posible riesgo para
su integridad física. Se usa una palabra de señalización {PELIGRO,
ADVERTENCIA o PRECAUCIÓN) junto con el símbolo de alerta
para designar un grado o un nivel de gravedad de riesgo. Se puede
utilizar un símbolo de seguridad para representar el tipo de peligro.
La palabra de señalización AVISO se usa para designar prácticas no
relacionadas con lesiones corporales.
PELIGRO indica un riesgo que, si no se evita, ocasionará la
muerte o lesiones graves.
ADVERTENCIA indica un riesgo que, si no se evita, podría
ocasionar la muerte o lesiones graves.
PRECAUCIÓN indica un riesgo que, si no se evita, podría
ocasionar lesiones menores o moderadas.
AVISO hace referencia a una práctica no relacionada con una lesión
física.
El fabricante no puede anticipar cada circunstancia posible
que puede involucrar un peligro. Por lo tanto, las advertencias
incluidas en este manual, así como también las etiquetas y
calcomanías fijadas en la unidad, no son exhaustivas. Si emplea un
procedimiento, un método de trabajo o una técnica de operación
que el fabricante no recomienda específicamente, debe cerciorarse
de que sea seguro para usted y el resto del personal. También
debe asegurarse de que el procedimiento, el método de trabajo o la
técnica de operación que elija no pongan en riesgo la seguridad del
equipo.
AVISO La instalación de este equipo debe cumplir estrictamente
la totalidad de los códigos, estándares y regulaciones vigentes,
por lo que solo debe ser llevada a cabo por un electricista con
licencia.
ADVERTENCIA Determinados componentes de este
producto y los accesorios relacionados contienen sustancias
químicas reconocidas en el estado de California por producir
cáncer, defectos de nacimiento u otros daños que pueden ser
perjudiciales para la reproducción. Lávese las manos después de
manipular estos elementos.
AVISO Un tratamiento inadecuado del equipo podría estropearlo
y acortar su vida útil.
Utilice el equipo solo para sus usos previstos.
Si tiene preguntas acerca del uso previsto, consulte con el
distribuidor o comuníquese con Briggs & Stratton Power
Products.
No exponga el equipo a un ambiente con exceso de humedad,
polvo, suciedad o vapores corrosivos.
Permanezca alerta en todo momento mientras trabaja en el
equipo. Nunca trabaje en los equipos cuando esté mental o
físicamente fatigado.
Si los dispositivos conectados se sobrecalientan, apáguelos y
apague sus disyuntores o fusibles.
ADVERTENCIA Peligro de descarga eléctrica. Instalar
cables de alto y bajo voltaje en el mismo conducto
podría provocar la muerte, lesiones graves o daños a la
propiedad.
No pase cables de alto y bajo voltaje en el mismo conducto, a
menos que el aislamiento de TODO el cableado esté clasificado
para 600 V. Consulte el Código Eléctrico Nacional para obtener
más información.
ADVERTENCIA No conectar correctamente el equipo podría
causar electrocución, lo que provocará la muerte o
lesionesgraves.
No toque cables pelados.
No use equipos con cables desgastados, deshilachados, pelados
o de otro modo dañados.
No manipule los cables eléctricos mientras esté parado sobre
agua, descalzo o si sus manos o pies están mojados.
Si debe trabajar cerca de una unidad mientras está funcionando,
párese en una superficie seca y aislada para reducir el peligro
de descarga.
No permita que personas no calificadas o niños operen o
realicen mantenimiento al equipo.
En caso de un accidente por descarga eléctrica, corte
inmediatamente todas las fuentes de energía eléctrica y
comuníquese con las autoridades locales. Evite el contacto
directo con la víctima.
ADVERTENCIA Peligro de descarga eléctrica. El equipo
contiene alto voltaje que podría provocar la muerte,
lesiones graves y/o
daños a la propiedad.
NO opere el equipo de manera imprudente ni olvide realizar
mantenimiento.
Descarga eléctrica
Lea el manual
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Simplicity 071150-00 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à