English Customer Service: 1-844-FIRMAN1
06
FEATURES AND CONTROLS
6. 120/240V, 50A – (NEMA 14-50R) (Not GFCI protected)
A maximum of 38.75 Amps current for 240 Volts or two independent 120 Volt loads at 38.75 Amps current each.
7. 120/240V, 30A Twist Lock – (NEMA L14-30R) (Not GFCI protected)
Control Panel
NOTICE Total power drawn from all receptacles must not exceed the name plate rating.
A maximum of 30 Amps current for 240 Volts or two independent 120 Volt loads at 30 Amps current each.
9. 120V, 30A Twist Lock – NEMA L5-30R(Not GFCI protected)
A maximum of 30 Amps current may be drawn from this receptacle.
10. 120V, 20A Duplex GFCI (Ground Fault Circuit Interrupter)- NEMA 5-20R
A maximum of 20 Amps current may be drawn from this duplex receptacle.
1. Engine Start Switch – To start engine, press and hold the switch in the START (ll) position, the
engine will crank and attempt to start. When the engine starts, release the switch to the RUN (l) position.
2. 4-1 Data-Minder (Multi-Meter) – Push the SELECT button to show the Voltage, Hertz, running hours and
low oil alarm.
11. Ground Terminal – Consult an electrician or authority having jurisdiction for local grounding
requirements.
2345910
11
1
678
12
13
3. Battery Switch – Power the electric starter.
4. Remote Start Indicator Light - The light will light or flash depending on the status of the remote start
system.
5. Remote Start Program Button - Use this button along with the remote control to program the
generator to be started remotely. Your remote control is already programmed in factory for your
convenience. If remote start control is ever replaced you may need to program. Contact FIRMAN
customer service.
8. 120V, 30A RV – NEMA TT-30R(Not GFCI protected)
A maximum of 30 Amps current may be drawn from this receptacle.
12. Outlet Cover - Protect the receptacles from dust and debris.
13. Circuit Breakers – The receptacles are protected by AC circuit protectors. If the generator is
overloaded or an external short circuit occurs, a circuit protector may trip. If tripping occurs,
disconnect all electrical loads and determine the cause before attempting to continue using the
generator. Reset any tripped circuit protectors.
If multiple receptacles are used at the same time, the total current must be kept with-in the
portable generator nameplate rating.