Simplicity 071075-00 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Not for
Reproduction
10 Circuit 50 Amp
Pre-wired Automatic Transfer Switch
Installation Manual
Copyright © Briggs & Stratton Corporation
Milwaukee, WI, USA. All Rights Reserved.
80006789
Revision A
Not for
Reproduction
2 BRIGGSandSTRATTON.COM
Thank you for your purchase of this Briggs & Stratton® automatic transfer switch. This product is designed for use with
specific home standby generators and may not function with generators produced by other manufacturers. Seek a qualified
electrical professional to determine applicability of this equipment to generators manufactured by others. When operated and
maintained according to the instructions in this manual, your system will provide many years of dependableservice.
This manual contains safety information to make you aware of the hazards and risks associated with this system and how to
avoid them. We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation
is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be
achieved. We do not know all possible hazards and/or the results of each possible method or procedure. It is important that
you read and understand these instructions thoroughly before attempting to install or operate this equipment. Save these
instructions for future reference.
This transfer switch requires professional installation before use. Refer to the Installation section of this manual for
instructions on installation procedures. Only licensed electrical contractors should install transfer switches. Installations must
strictly comply with all applicable federal, state and local codes, standards and regulations. Your installer should follow the
instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages.
There are many authorized service dealers who provide quality service. You can also contact Technical Service by phone at
800-732-2989 between 8:00 AM and 5:00 PM CT, or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a
list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Transfer Switch
Model Number
Revision
Serial Number
Date Purchased
Not for
Reproduction
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................5
Owner Orientation ............................................5
Installing Dealer/Contractor Responsibilities ........................5
Mounting Guidelines ..........................................7
Power Wiring Interconnections ..................................7
System Setup................................................8
System Test .................................................8
Operation .................................... 10
Maintenance .................................. 11
Troubleshooting................................ 11
Schematic Diagram ..........................................12
Wiring Diagram .............................................13
Product Specifications ........................... 14
Not for
Reproduction
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the equipment.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol
may be used to represent the type of hazard. The signal
word NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the equipment unsafe.
Electrical Shock Read Manual
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
SAVE THESE INSTRUCTIONS
WARNING Only qualified electricians should attempt
installation of this equipment, which must strictly comply
with applicable codes, standards and regulations.
WARNING Failure to properly ground equipment
could cause electrocution resulting in death or
seriousinjury.
Do not touch bare wires.
Do not use equipment with worn, frayed, bare or
otherwise damaged wiring.
Do not handle electrical cords while standing in water,
while barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand
on an insulated dry surface to reduce shock hazard.
Do not allow unqualified persons or children to operate or
service equipment.
In case of an accident caused by electrical shock,
immediately shut down all sources of electrical power
and contact local authorities. Avoid direct contact with
the victim.
NOTICE Improper treatment of equipment can damage it
and shorten its life.
Use equipment only for intended uses.
If you have questions about intended use, ask dealer or
contact Briggs & Stratton Power Products.
Do not expose equipment to excessive moisture, dust,
dirt, or corrosive vapors.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
If connected devices overheat, turn them off and turn off
their circuit breaker/fuse.
WARNING Shock Hazard. Installing low and high voltage
wire in same conduit could result in death or serious
injury.
Do not run low and high voltage wire in the same conduit unless
the insulation rating on ALL wiring is rated for 600V. See NEC
for more information.
WARNING Shock Hazard. Equipment contains high
voltage that could cause electrocution resulting in
death or serious injury.
Do Not operate this equipment imprudently or neglect its
maintenance.
Not for
Reproduction
5
Installation
We sincerely appreciate your patronage. For this reason,
we have made significant effort to provide for a safe,
streamlined and cost-effective installation. Because each
installation is unique, it is impossible to know of and advise
the trade of all conceivable procedures and methods by
which installation might be achieved. Neither could we
know of possible hazards and/or the results of each method
orprocedure.
For these reasons, only current licensed electrical should
attempt system installations. Installations must strictly
comply with all applicable codes, industry standards
andregulations.
Your equipment is supplied with this Installation Manual
and a separate Operator’s Manual. These are important
documents and should be retained by the owner after the
installation has been completed.
Every effort has been made to make sure that the information
in this manual is both accurate and current. However, the
manufacturer reserves the right to change, alter or otherwise
improve the system at any time without prior notice.
Home Owner Responsibilities
To help you make informed choices and communicate
effectively with your installation contractor(s), read and
understand Owner Orientation before contracting or
starting your equipment installation.
To arrange for proper installation, contact the store at which
you purchased your equipment, your dealer, or your utility
power provider.
The equipment warranty is VOID unless the system is
installed by licensed electrical professionals.
Owner Orientation
The illustrations provided are for typical circumstances and
are meant to familiarize you with the installation options
available with your system.
Local codes, appearance, and distances are the factors that
must be considered when negotiating with an installation
professional. As the distance from the existing electrical
service increases, compensation in wiring materials must
be allowed for. This is necessary to comply with local codes
and overcome electrical voltage drops.
These factors will have a direct effect on the overall price
of your equipment installation.
Your installer must check local codes AND obtain permits
before installing the system.
Read and follow the instructions given in this manual.
Follow a regular schedule in caring for and using your
equipment, as specified in this manual.
Installing Dealer/Contractor Responsibilities
Read and observe the safety rules.
Read and follow the instructions given in this manual.
Consult with home generator owner(s) to discuss their
selection of “Essential Circuits.”
The installer may need to provide appropriate rated
contactors based on loads to be controlled.
Check federal, state and local codes and authority
having jurisdiction, for questions on installation.
Ensure generator is not overloaded with selected loads.
If you need more information about the transfer switch, call
800-732-2989, between 8:00 AM and 5:00 PM CT.
Equipment Description
The transfer switch is designed to transfer the selected
loads found in normal residential installations to generator
power in the event of a utility power failure. The load is
connected either to utility power (normal) or home standby
power (generator). The transfer switch monitors utility and
generator voltages and will automatically connect to the
appropriate source of power.
Major components of the transfer switch are 2 pole
contactor switches, control circuit board, fused utility
terminals and interconnecting wiring. There is also a pre-
wired, wire whip that allows for easy connection to the main
distribution panel.
The transfer switch is coil-operated from utility or generator
inputs and contains suitable electrical interlock switches to
eliminate the possibility of connecting the utility service to
the generator output.
The control board has active circuits sensing utility and
generator voltages. It creates a signal for the generator start-
up, switch transfer, retransfer when utility is restored and
generator cool down periods.
Not for
Reproduction
6 BRIGGSandSTRATTON.COM
Delivery Inspection
After opening the carton, carefully inspect the transfer
switch components for any damage that may have occurred
duringshipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss
or damage. If loss or damage is noted after delivery, contact
the carrier for claim procedures. Missing or damaged parts
are not warranted.
Shipment contents
Pre-wired automatic transfer switch (1)
Full complement of branch circuit breakers
Installation manual (1)
Operator’s manual (1)
To be supplied by installer:
Connecting wire and conduit
Various specialty tools/equipment
Essential Circuit Isolation
Essential electrical loads are loads that will be powered by
the home generator. Essential loads are grouped together
and wired into the transfer switch.
TO THE INSTALLER: Consult with home generator owner(s)
to discuss their selection of “Essential Circuits”.
Ensure that the total of the selected load circuits fed by this
transfer switch are within the generator’s rated capacity.
The following requirements apply to this type of
isolationsystem:
The automatic transfer switch is installed after the main
distribution panel.
The automatic transfer switch has a load rating of
50Amps. This is the maximum load rating of the total
essential load.
All wiring must conform to national, state and
localcodes.
The illustration below depicts the system installation and
assumes the utility is supplying 120/240Volt, single-phase
electrical service.
To Utility Power
Watt-Hourrmeter
Main Distribution Panel
To Air Conditioner (240V)
To Other Circuits (120V)
To Range
To Water Heater
240V
To generator
120V To Microwave
120V To Bathroom
240V To Well Pump
120V To Sump Pump
Neutral
120V
To Furnace Blower
To Lights
To Refrigerator
120V To Freezer
Automatic Transfer Switch
(in normal position)
Not for
Reproduction
7
Mounting Guidelines
The system circuitry is enclosed in a NEMA Type 3R
enclosure suitable for indoor/outdoor use. Guidelines for
mounting the enclosure include:
Install enclosure on a firm, sturdy supporting structure.
The enclosure must be installed with minimum
NEMA3R hardware for conduit connections.
To prevent switch contact distortion, level and plumb
the enclosure. This can be done by placing washers
between the enclosure and the mounting surface.
NEVER install the switch where any corrosive
substance might drip onto the enclosure.
Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and
corrosivevapors.
A typical indoor transfer switch installation is depicted
below. Discuss layout suggestions/changes with the owner
before beginning the system installation process.
NOTICE Before drilling conduit entry holes, or any
other holes, cover and protect the switch and electronics
to prevent dirt and metal fragments from entering the
mechanical and electrical components. Failure to do so may
result in damage or malfunction of the switch.
NOTICE Use a vacuum to clean any dirt or metal
shavings inside the transfer switch. Do not use a blower or
compressed air to clean the inside of the transfer switch
because debris may become lodged in the electrical and
mechanical components causing damage or malfunction.
Power Wiring Interconnections
All wiring must be the proper size, properly supported and
protected by conduit, if applicable. All wiring should be done
per applicable federal, state and local codes, standards and
regulations. Obey wire type and torque specifications printed
on terminal blocks and neutral/ground connectors.
NOTICE Improper installation can cause damage to the
circuit boards and shorten their life. Installing circuit boards
in live circuits will damage the board and is not covered by
warranty. ALWAYS disconnect ALL sources of power prior to
servicing.
Remove all power prior to installing this equipment.
Failure to do so could cause internal damage to the
board when making electrical connections.
Turn generator to OFF position.
All wiring furnished with the transfer switch is sized
for the circuit breakers shipped with the unit. If circuit
breakers are replaced with larger ones, replace wires
to properly match the circuit breaker amperage per
applicable federal, state and local codes, standards and
regulations.
1. Set generator’s circuit breaker to OFF (open) position.
2. Remove 15 Amp fuse from system control panel.
3. Turn off utility power to the standby generator and
transfer switch.
NOTICE When moving circuit locations from main electrical
panel to the transfer switch, balance must be maintained.
Circuits sharing a neutral wire should be moved
together to adjacent positions in the transfer switch or
not moved.
If unsure of the proper procedure, contact a licensed
electrician.
Circuits being moved must be protected by the same
size breaker.
4. Remove main distribution panel cover.
5. Remove the appropriate size knockout from the main
distribution panel.
6. Locate the pre-wired whip on the transfer switch
and remove the threaded lock nut from the conduit
coupling.
7. Feed all wires through the knockout into the main
distribution panel.
8. Slip lock nut over wires and tighten securely onto
coupling.
9. Work with the home owner to determine which circuits
to power up during a power outage.
10. Once the circuits are identified, remove the black
(hot) wire from the circuit breaker and wire nut it to
the matching wire from the circuit breaker of the load
center in the transfer switch.
11. Trace the black (hot) wire, that was wired in the
previous step, back to the Romex cable and wire nut
the white (neutral) wire to the same size white (neutral)
wire from the load center in the transfer switch.
Automatic
transfer
switch
Main
distribution
panel
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
WARNING Shock Hazard. Installing low and high voltage
wire in same conduit could result in death or serious
injury.
Do not run low and high voltage wire in the same conduit unless
the insulation rating on ALL wiring is rated for 600V. See NEC
for more information.
Not for
Reproduction
8 BRIGGSandSTRATTON.COM
12. Repeat Steps 10 and 11 for all selected circuits.
NOTICE Both grounded and ungrounded conductors must
be moved to the load center and connected to the new wiring
in the transfer switch.
13. Install a double-pole circuit breaker into the main
distribution panel. This circuit breaker is used to
provide utility power for the transfer switch. The
maximum current rating for this circuit breaker is 50
Amps.
NOTICE It may be necessary to reposition remaining
breakers in the main distribution panel to accommodate
the installation of the double-pole breaker. The double-pole
breaker must be compatible with the main distribution panel.
14. Connect the black and red wires from the pre-wired
whip to the double-pole circuit breaker.
15. Connect the ground (green) wire from the pre-wired
whip to the ground bar at the main distribution panel.
16. Connect the neutral (white) wire from the pre-wired
whip to the neutral bar at the main distribution panel.
17. Reinstall the main distribution panel cover.
NOTICE All circuit wires are color coded for ease of
identification and installation. If colors are not clear, use a
multi-meter to test for correct positions.
System Setup
You must perform the following before operating the system:
• When generator is installed in an area regularly subjected to
temperatures above 40°F (4°C), select a 20 second warm-
up time by installing jumper JP2 on transfer switch control
board. Unit is shipped with JP2 installed (factory default).
• When generator is installed in an area regularly subjected to
temperatures below 40°F (4°C), select a 50 second warm-up
time by removing jumper JP2 installed on transfer switch
control board.
System Test
With the generator system switch in AUTO, turn the
50Amp circuit breaker feeding the transfer switch to the
OFF position. After a few minutes the generator will start
and the transfer switch will transfer essential loads to
generatorpower.
To return to utility power, turn the 50Amp circuit breaker
feeding the transfer switch ON.
L 1
L 2
L
1
L 2
N
N
G
L 1
L 2
1
3
5
7
9
2
4
6
8
10
G
N
LINE2
LINE1
Automatic Transfer Switch
Install 2-pole circuit breaker.
(MAX current ratings of 50 Amps.)
Utility Connection
JP2
Generator
Connection
To Watt-
Hourmeter
Neutral
Bus
Neutral
Bus
Neutral
Bus
Ground
Bus
Ground
Bus
Main Distribution Panel
B&S Generator
NOTICE:
All circuit
conductors
are not
shown.
Detail View B
on page 9.
Detail View A
on page 9.
Not for
Reproduction
9
10
8
6
4
2
1
3
5
7
9
CIRCUITS FROM
TRANSFER SWITCH
SPLICE USING WIRE NUT
TO HOUSE CIRCUITS
NOTICE All circuit wires (1-10) are color coded.
View B
View A
Not for
Reproduction
10 BRIGGSandSTRATTON.COM
Operation
To select automatic transfer operation, do the following:
1. Set 50 Amp circuit breaker feeding the transfer switch
to “ON” position.
2. Install 15 Amp fuse in generator’s control panel.
3. Set generator’s circuit breaker to “ON” position.
4. Set generator’s system switch to “AUTO” position.
The system will now be in automatic operation mode.
NEMA 3R Enclosure Door
To open door, press the spring-load door lock to the right
and pull down on the door.
To close and latch door, push door closed against enclosure.
While in this position, push door upwards. This will cause
spring-load door lock to engage and latch door in place.
Enclosure door MUST be closed and latched at all times
except when system is being serviced.
Testing the Automatic Transfer Switch
Turn the 50 Amp utility disconnect circuit breaker in the
main distribution panel to the “OFF” position. The automatic
sequence will follow. To go back to utility power, turn the
50Amp utility disconnect circuit breaker “ON”.
Automatic Sequence
Utility Fail
Utility voltage sensor senses when utility voltage is below
70% of nominal. Engine start sequence is initiated after
10second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer. Use
jumper on control board to select delay of 20 seconds or
50seconds.
Transfer
Transfer from utility to generator supply occurs after
generator voltage is above set levels. Minimum engine run
time is 5 minutes after transfer.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from generator to utility power is approximately
10 seconds after utility voltage supply is above pickup level
and minimum run time is completed.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
Not for
Reproduction
11
Troubleshooting
Problem Cause Correction
Au tomatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Reset generator circuit breaker.
2. Refer to generator manual.
Au tomatic transfer switch does not
transfer to utility
1. Main distribution panel breaker open.
2. Utility voltage not acceptable.
1. Reset main distribution panel breaker.
2. Wait for utility voltage to return
tonormal.
Ge nerator is still running after switch
transfers to utility power
Engine cool down period. Engine should stop after 1 minute.
Ge nerator is still running after utility
power is restored
1. Minimum engine run time has
notelapsed.
2. Fuse(s) in transfer switch is defective.
1. Wait five minutes for transfer switch
to retransfer to utility power.
2. Check fuse(s) and replace
ifnecessary
Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks
should be made on a regular basis. Maintenance will consist
mainly of keeping the transfer switch clean.
Visual inspections should be done at least once a month.
Access to transfer switch must not be obstructed. Keep
3feet (92 cm) clearance around transfer switch. Check
for an accumulation of dirt, moisture and/or corrosion
on and around the enclosure, loose parts/hardware,
cracks and/or discoloration to insulation, and damaged or
discoloredcomponents.
Exercise the transfer switch at least once every three months
as described in Testing the Automatic Transfer Switch
unless a power outage occurs and home generator has gone
through an automatic sequence. Allow generator to run for at
least 30 minutes.
Contact a licensed electrical professional to inspect and clean
the inside of the enclosure and other components of your
home generator system at least once a year.
When Calling for Assistance
You must have the Model Number and Serial Number from
the unit ID label at hand if it is necessary to contact a local
service center regarding service or repair of this unit. Obtain
this information from the unit ID label located on or inside
the enclosure.
To contact Briggs & Stratton call 800-732-2989 between
8:00 AM and 5:00 PM CT.
Installation Inspection
Before placing the system into service, inspect the entire
installation carefully.
Complete the ”Installation Checklist” as you make the
inspection. Ensure all items have been filled-in and all
signatures have been obtained. Instruct the owner to mail
the white copy to the address shown on the checklist.
Not for
Reproduction
12 BRIGGSandSTRATTON.COM
Schematic Diagram
8
7
4
31
2
5
6
9
10
T1
T2
Not for
Reproduction
13
To Main Breaker Panel
10
8
6
4
2
9
7
5
3
1
Wiring Diagram
Not for
Reproduction
14 BRIGGSandSTRATTON.COM
Product Specifications
Enclosure ................................................................ NEMA 3R
Rated Maximum Load Current*
(at 25°C/77°F) ........................................................50 Amps
Rated AC Voltage .................................................... 250 Volts
Poles .................................................................................... 2
Frequency ..................................................................... 60 Hz
Fault Current Rating ......... 5,000 RMS Symmetrical Amperes
Normal Operating Range .... -20°F (-28.8°C) to 104°F (40°C)
Weight ............................................................40 lbs (18 kg).
* This transfer switch is certified in accordance with UL (Underwriters
Laboratories) 1008 (transfer switch equipment). Short circuit rating is
limited to the lowest capacity of any device installed.
Automatic Transfer Switch
Not for
Reproduction
Interruptor de transferencia automática
precableado de 50 amperios y 10 circuitos
Manual de instalación
ydeloperario
80006789
Modificación (A)
Copyright © Briggs & Stratton Corporation
Milwaukee, WI, USA. Todos los derechos reservados.
Not for
Reproduction
2 BRIGGSandSTRATTON.COM
Gracias por comprar este conectador automático de Briggs & Stratton®. Este producto está diseñado para utilizarse con
generadores de reserva domésticos específicos y puede no funcionar con generadores producidos por otros fabricantes.
Recurra a un electricista profesional cualificado para determinar la aplicabilidad de este equipo en generadores fabricados por
terceros. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, su sistema le proporcionará muchos años
de funcionamiento fiable.
Este manual contiene información de seguridad para que usted conozca los peligros y riesgos propios de este sistema y
cómo evitarlos. Se ha realizado el máximo esfuerzo para que la instalación resulte segura, sencilla y económica. Debido a que
cada instalación es única, es imposible conocer y recomendar todos los procedimientos y métodos posibles para efectuarla.
No conocemos todos los riesgos y/o resultados posibles de cada método o procedimiento existente. Es importante que lea
y comprenda perfectamente estas instrucciones antes de intentar instalar o utilizar este equipo. Guarde estas instrucciones
para futuras consultas.
Este el conectador requiere instalación profesional antes de utilizarse. Consulte las instrucciones sobre los procedimientos
de instalación en la sección Instalación del presente manual. Los conectador sólo deben ser instalados por electricistas con
licencia. Las instalaciones deben cumplir estrictamente la totalidad de los códigos, estándares y regulaciones federales,
estatales y locales vigentes. El instalador debe seguir las instrucciones detalladamente.
Ubicación
Nunca debe ir demasiado lejos para encontrar el soporte y servicio de Briggs & Stratton para su sistema. Consulte las
Páginas Amarillas. Existen múltiples distribuidores de servicio autorizados que ofrecen un servicio de calidad. También
puede comunicarse con el Servicio técnico por teléfono al 800-732-2989 de 8:00 a. m. a 5:00 p. m. Hora del Centro, hora del
centro de los EE. UU; o haga clic en Buscar un distribuidor en BRIGGSandSTRATTON.COM para que aparezca una lista de
distribuidores autorizados.
Para futuras consultas
Llene la siguiente información y conserve su factura para facilitar la identificación de la unidad en caso de que surjan
problemas relacionados con la compra en el futuro.
Conectador automático
Número de modelo
Revisión
Número de serie
Fecha de compra
Not for
Reproduction
3
Tabla de contenido
Instrucciones importantes deseguridad ................4
Instalación ....................................5
Orientación al propietario.......................................5
Responsabilidades del distribuidor / técnicoinstalador................5
Pautas de montaje ............................................7
Interconexión de los cables de alimentación ........................7
Configuración del sistema ......................................9
Prueba del sistema............................................9
Funcionamiento................................ 11
Mantenimiento ................................ 12
Resolución de problemas ......................... 13
Especificaciones del producto ...................... 14
Not for
Reproduction
4 BRIGGSandSTRATTON.COM
Instrucciones importantes
deseguridad
GUARDE ESTAS INSTRUCCIONES - Este manual contiene
instrucciones importantes que se deben seguir durante la
instalación y el mantenimiento delequipo.
Símbolos sobre la seguridad y significados
El símbolo de alerta de seguridad indica un posible riesgo
para su integridad física. Se utiliza una palabra de señalización
(PELIGRO, ADVERTENCIA o ATENCIÓN) junto con el símbolo de
alerta para designar un grado o nivel de gravedad de riesgo. Se
puede utilizar un símbolo de seguridad para representar el tipo
de riesgo. La palabra de señalización AVISO se utiliza para hacer
referencia a una práctica no relacionada con una lesión física.
PELIGRO indica un riesgo que, de no evitarse, provocará la
muerte o lesiones de gravedad.
ADVERTENCIA indica un riesgo que, de no evitarse, podría
provocar la muerte o lesiones de gravedad.
ATENCIÓN indica un riesgo que, de no evitarse, podría provocar
lesiones leves o moderadas.
AVISO hace referencia a una práctica no relacionada con una lesión
física.
El fabricante no puede prever toda circunstancia que conlleve
un riesgo potencial. Por tanto, las advertencias de este manual,
así como las etiquetas y calcomanías adheridas a la unidad, no
incluyen todos los riesgos posibles. Si utiliza un procedimiento,
método de trabajo o técnica de uso no recomendado
específicamente por el fabricante, deberá asegurarse de que es
seguro tanto para usted como para otras personas. También deberá
asegurarse de que el procedimiento, método de trabajo o técnica de
uso que elija no hace que el equipo sea inseguro.
Guarde estas instrucciones
ADVERTENCIA Peligro de descarga. La instalación de un
cable de baja y alta tensión en el mismo conducto podría
provocar lesiones graves o incluso la muerte.
No tienda un cable de baja y alta tensión en el mismo conducto
a menos que el valor nominal de aislamiento en TODO el
cableado sea de 600 V. Para obtener más información, consulte
el NEC.
ADVERTENCIA Una conexión a tierra defectuosa del equipo
podría provocar electrocución, así como lesiones graves
o incluso la muerte.
No toque los cables pelados.
No utilice el equipo con cables desgastados, deshilachados o
deteriorados de cualquier otra forma.
No manipule los cables eléctricos si se encuentra en una zona
húmeda, está descalzo o tiene las manos o los piesmojados.
Si tiene que trabajar junto a una unidad en funcionamiento,
manténgase en una superficie aislada y seca para reducir el
riesgo de descarga eléctrica.
No permita que personas no cualificadas o niños utilicen o
reparen el equipo.
En caso de accidente provocado por una descarga eléctrica,
desconecte inmediatamente todos los suministros de energía
eléctrica y póngase en contacto con las autoridades locales.
Evite el contacto directo con la víctima.
AVISO Un tratamiento inadecuado del equipo podría estropearlo
y acortar su vida útil.
Utilice el equipo sólo para los usos previstos.
En caso de dudas sobre su uso, diríjase al distribuidor o a Briggs
& Stratton Power Products.
No exponga el equipo a un exceso de humedad, polvo, suciedad
o vapores corrosivos.
Manténgase alerta en todo momento cuando utilice este equipo.
Nunca lo utilice ni manipule en condiciones de fatiga física o
mental.
Si se calientan excesivamente los dispositivos conectados,
apáguelos y abra sus interruptores o quite sus fusibles.
ADVERTENCIA Riesgo de descarga. Este equipo contiene
alta tensión que puede ocasionar la electrocución y, por
tanto, la muerte o lesiones graves.
No utilice este equipo de un modo imprudente o con negligencia
en cuanto a su mantenimiento.
ADVERTENCIA La instalación de este equipo debe
cumplir estrictamente la totalidad de los códigos,
estándares y regulaciones vigentes, por lo que sólo debe
ser llevada a cabo por un electricista cualificado.
ADVERTENCIA Determinados componentes en
este producto y los accesorios relacionados contienen
sustancias químicas declaradas cancerígenas, causantes
de malformaciones, y otros defectos congénitos por el
Estado de California. Lávese las manos después de
manipular estos elementos.
Descarga eléctrica Lea el manual
Not for
Reproduction
5
Instalación
Realmente valoramos que nos haya elegido. Por este
motivo, se ha realizado un esfuerzo importante para que
la instalación resulte segura, sencilla y económica. Debido
a que cada instalación es única, es imposible conocer y
recomendar todos los procedimientos y métodos posibles
para efectuarla. Tampoco conocemos todos los riesgos y/o
resultados posibles de cada método o procedimiento.
Por tanto, la instalación del sistema sólo puede ser
llevada a cabo por un electricista con licencia vigente.
Las instalaciones deben cumplir estrictamente la
totalidad de los códigos, estándares de la industria y
regulacionesvigentes.
Su equipo incluye este manual de instalación y un
manual del usuario independiente. Estos documentos son
importantes y el propietario debe conservarlos incluso
después de haber realizado la instalación.
Se ha realizado el máximo esfuerzo para reunir en este
manual la información más precisa y actualizada. No
obstante, el fabricante se reserva el derecho de modificar,
alterar o mejorar de cualquier otra forma el sistema en
cualquier momento y sin previo aviso.
Responsabilidades del propietario
Para tomar decisiones bien fundadas y comunicarse
eficazmente con el técnico instalador, lea y comprenda la
sección Orientación al propietario antes de contratar o
iniciar la instalación del equipo.
Para solicitar la instalación, póngase en contacto con la
tienda en la que adquirió el equipo, con su distribuidor o con
la compañía eléctrica.
La garantía del equipo quedará ANULADA a menos
que electricistas profesionales con licencia instalen
elsistema.
Orientación al propietario
Las ilustraciones incluidas corresponden a circunstancias
habituales y tienen por objeto familiarizarle con las opciones
de instalación del sistema.
La normativa local, la apariencia y las distancias son los
aspectos que deberán tenerse en cuenta al negociar la
instalación con un profesional. Al aumentar la distancia
desde el servicio eléctrico, se deberá prever una
compensación en cables y otros materiales necesarios
para cumplir la normativa local vigente y evitar caídas de
tensióneléctrica.
Estos factores tendrán un efecto directo en el precio total
de la instalación del equipo.
El instalador deberá comprobar la normativa local Y obtener
los permisos correspondientes antes de instalar elsistema.
Lea y siga las instrucciones que se indican en
estemanual.
Siga un plan regular de cuidado y uso del equipo, como
se indica en este manual.
Responsabilidades del distribuidor /
técnicoinstalador
Lea y respete las normas de seguridad.
Lea y siga las instrucciones que se indican en
estemanual.
Consulte con el propietario del generador doméstico
para seleccionar los “circuitos esenciales”.
Es posible que el instalador tenga que proporcionar
contactores nominales adecuados con base en las
cargas que van a controlarse.
Consulte la normativa vigente en caso de dudas sobre
la instalación.
Asegúrese de que las cargas seleccionadas no
sobrecargan el generador.
Si necesita más información sobre el conectador, llame al
800-732-2989, de 08:00 a 17:00 CT.
Descripción del equipo
El conectador está diseñado para transferir las cargas
seleccionadas de una instalación residencial normal
al suministro del generador en caso de un fallo en el
suministro de alimentación de la red pública. La carga
se conecta al suministro de servicio general (normal)
o al suministro doméstico de reserva (generador). El
conectador monitoriza las tensiones de la red pública y del
generador y conecta automáticamente la carga a la fuente de
alimentación apropiada.
Los componentes principales del conectador son los
interruptores de contacto bipolares, la tarjeta de circuito
impreso de control, los terminales con fusibles de tensión de
la red pública y el cableado de interconexión. También existe
una conexión flexible precableada que permite una fácil
conexión del panel de distribución principal.
El conectador es accionado por una bobina alimentada
desde entradas de la red pública o del generador y tiene
interruptores de enclavamiento eléctricos, adecuados para
eliminar la posibilidad de conectar la red pública a la salida
del generador. Sus valores nominales son suficientes para
conectar la potencia del generador a la residencia.
La tarjeta de circuito impreso del módulo de control tiene
circuitos activos que detectan las tensiones de la red pública
y del generador. Genera una señal para el arranque del
generador, conectador, retransferencia cuando se restablece
la tensión en la red pública y períodos de enfriamiento
delgenerador.
Not for
Reproduction
6 BRIGGSandSTRATTON.COM
Inspección en el momento de la entrega
Después de abrir la caja de cartón, con cuidado inspeccione
el contenido para detectar cualquier daño que pudiera haber
ocurrido durante el envío.
Si detecta faltas o daños en el momento de la entrega,
solicite a la persona que realiza la entrega que anote
todos los daños en Ia nota de entrega y que la firme bajo
el área de pérdidas y daños del remitente. Si se detectan
faltas o daños después de la entrega, póngase en contacto
con el transportista para solicitar información sobre el
procedimiento de reclamación. La garantía no cubre las
partes faltantes o dañadas.
Contenido del paquete
Interruptor de transferencia automática precableado (1)
Complemento completo de disyuntores de circuitos
derivados esenciales
Manual de instalación (1)
Manual de instrucciones (1)
No incluye:
Cable y conducto de conexión.
Herramientas/equipos especiales diversos
Aislamiento de los circuitos fundamentales
Las cargas eléctricas fundamentales son aquellas que
serán alimentadas mediante el sistema de generador. Las
cargas fundamentales se agrupan y se conectan dentro del
compartimiento del conmutador de transferencia automático.
AL INSTALADOR: Consulte con el propietario del
sistema de generador para analizar la “Selección de los
circuitosfundamentales”.
Asegúrese de que el total de los circuitos de carga
seleccionados para ser alimentados por este conmutador de
transferencia se encuentre dentro de la capacidad nominal
del generador.
Los siguientes requisitos se aplican a este tipo de sistema
deaislamiento:
El conmutador de transferencia automático se instala
después de instalar el panel de distribución principal.
El conmutador de transferencia automático tiene un
valor nominal de carga de 50 Amperios. Este es el valor
nominal máximo para las cargas fundamentals totales.
Todas las conexiones de cableado deben cumplir con
lo establecido en el nacional, todos los códigos locales
yestatales.
La ilustración muestra el sistema de generador y supone
que la compañía proveedora de electricidad entrega
120/240Voltios, con corriente monofásica.
A la energía de la compañía proveedora de electricidad
Vatímetro
Panel de distribución principal
Al acondicionador de aire (240V)
A otros circuitos (120V)
A la cocina
Al calentador de agua
240V
A la generador
120V al horno de microondas
120 V al cuarto de baño
240V A la bomba de pozo
120V A la bomba de sumidero
Neutro
120V
Al soplador de caldera
A las luces
Al refrigerador
120V al freezer
Conmutador de transferencia
automático (en posición normal)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Simplicity 071075-00 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à