Johnson Controls NS Series Installation Instructions Manual

Taper
Installation Instructions Manual

Ce manuel convient également à

Part No. 24-11256-00007, Rev. —
1
NS8000 Series
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors
Part No. 24-11256-00007, Rev. —
Issue Date February 2019
Installation Instructions
*241125600007Rev-*
Important (USA, Canada)
The NS Series Network Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or
malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property,
additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or
alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
Le NS Series Network Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales
de fonctionnement. Lorsqu’une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou
d’endommager l’équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs
de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d’autres dispositifs, tels que des systèmes de
supervision ou d’alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d’avertissement ou de protection en
cas de défaillance ou de dysfonctionnement du network sensor.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the
interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Mounting
The NS Series Network Sensor can be surface mounted or wallbox mounted. For wallbox-mounted installations,
mount the NS Series Network Sensor on a vertically roughed-in wallbox only. Do not attempt to mount the sensor on a
horizontally roughed-in wallbox.
Johnson Controls does not supply the required hardware for mounting.
Software terms
Use of the software that is in (or constitutes) this product or access to the cloud or hosted services applicable to this product,
if any, is subject to applicable terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an
agreement to such terms. If you do not agree to be bound by such terms, you may return the unused product
to your place of purchase.
Note:
Part No. 24-11256-00007, Rev. —
2
NS8000 Series
Location considerations
Note:
48 in (1.2 m)
°C
MAX MIN
50°C
122°F
0°C
32°F
MAX 90% RH
MIN 10% RH
85°F (29°C) MAX DP
Locate the network sensor away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled),
or sources of electrical interference.
Height requirements may vary depending on the site.
Network sensors without CO
2
sensing are shock and vibration resistant, but not shock and vibration proof. Be careful not
to drop the unit or mount it where it could be exposed to excessive vibration. Dropping a CO
2
network sensor may result
in readings outside of the specied accuracy tolerance.
Special tools (only one type needed)
Johnson Controls T-4000-119 Allen-head adjustment tool
JC 5309 Allen-head exible tool
1/16 in (1.5 mm) Allen wrench
Part No. 24-11256-00007, Rev. —
3
NS8000 Series
2
1
Installation
21
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l’alimentation avant de réaliser tout raccordement électrique an d’éviter tout risque de décharge électrique.
IMPORTANT: Do not insert tools into the housing. Be careful not to damage any components when pushing the tabs on either side
of the sensor.
IMPORTANT: Do not remove the printed circuit board (PCB). Removing the PCB voids the product warranty.
IMPORTANT: Failure to adhere to these wiring details causes the network sensor to function incorrectly. You will not be able to
connect to the system using the Bluetooth® Wireless Comissioning Converter (BTCVT), Mobile Access Portal Gateway (MAP), or
the handheld VAV balancing tool, and you will not be able to expand the system with future offerings.
Notes:
IMPORTANT: Do not connect the SA bus ground, the modular phone jack GND or the screw terminal COM, to the negative
communication terminal SA–.
IMPORTANT: Do not connect the Sensor/Actuator (SA) connection at the controller until the cables have completely
been terminated.
Do not use both the modular phone jack and screw terminal connections on the same SA bus segment
at the same time.
The modular phone jack and screw terminal connections cannot be used simultaneously.
Part No. 24-11256-00007, Rev. —
4
NS8000 Series
5
2
1
4
15 VDC
COM
15 VDC
1 2 5 643
COM
SA +
SA -
SA +
SA –
COM
15 VDC
3
Part No. 24-11256-00007, Rev. —
5
NS8000 Series
Applications
Icon Description
1 Humiditiy indicator icon
2 Humidity measurement
3 CO
2
measurement
4 Configurable setpoint or current temperature
5 Setpoint indicator icon
6 Fahrenheit icon
7 Celsius icon
8 Percent relative humidity icon
9 Fan speed bars
10 Fan icon
11 Automatic fan speed icon
12 Up adjustment or navigation icon
13 SA bus online indicator
14 Down adjustment or navigation icon
15 Menu or enter icon
16 Occupancy indicator
17 Default display value (setpoint, zone temperature, relative humidity)
1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
9
10
Table 1: Display icons
Part No. 24-11256-00007, Rev. —
6
NS8000 Series
Setup and adjustments
Adjusting the temperature setpoint
1. To view the current setpoint value, press the Up or Down icon once.
2. To increase or decrease the temperature setpoint by 0.5 degrees Fahrenheit or Celsius, press the Up or Down icon again.
3. To save the new settings, press the Menu icon once to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
4. Optional: Press and hold the Up or Down icon to continuously increase or decrease the temperature setpoint.
Adjusting the fan speed
1. To view the current fan speed, press the Fan icon once.
2. To adjust the fan speed, continue to press the Fan icon to cycle through the automtic, off, low, medium or
high fan speed settings.
3. To save the new settings, press the Menu icon once to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
Viewing the SA bus sensor address and the rmware version
1. Press the Menu icon once to view the SA bus sensor address. See Table 2 for setting the SA bus sensor address
2. Press the Menu icon a second time to view the rmware version.
3. Press the Menu icon a third time to return to the home screen or wait for ten seconds for the screen to return to the
home screen automatically.
Adjusting the temperature unit
To change the temperature units from Fahrenheit to Celsius or Celsius to Fahrenheit, complete the following steps:
1. On the home screen, press and hold the Up and Down icons for ve seconds until the middle display disappears and the
Celsius and Fahrenheit indicator icons blink.
2. To toggle between Fahrenheit and Celsius, press the Up or Down icon.
3. To save the new settings, press the Menu icon six times to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
Changing the home screen default value
Choose whether you want to display current temperature or the setpoint value in the middle of the home screen. To change which
value displays in the middle of the home screen, complete the following steps:
1. Press and hold the Up and Down icons for ve seconds until the Fahrenheit and Celsius indicator icons start to blink. All icons
are visible on the display.
2. Press the Menu icon once.
3. To select and switch between current temperature or setpoint value, press the Up or Down icon.
4. To save the new settings, press the Menu icon ve times to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
Selecting the setpoint display value
To change whether current or setpoint temperature displays in the upper-right corner, complete the following steps:
1. Press and hold the Up and Down icons for ve seconds until the Fahrenheit and Celsius indicator icons start to blink.
2. Press the Menu icon twice.
3. To select and switch between current temperature or setpoint value, press the Up or Down icon.
4. To save the new settings, press the Menu icon four times to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
Selecting the maximum fan speed settings
The fan speed is set to high speed by default. To change the value of the maximum fan speed that displays on the home screen,
complete the following steps:
1. Press and hold the Up and Down icons for ve seconds until the Fahrenheit and Celsius indicator icons start to blink.
2. Press the Menu icon three times.
3. To increase or decrease the maximum fan speed, press the Up or Down icon.
4. To save the new settings, press the Menu icon three times to return to the home screen or wait for ten seconds for the screen
to return to the home screen automatically.
Changing the decimal separator
1. Press and hold the Up and Down icons for ve seconds until the Fahrenheit and Celsius indicator icons start to blink.
2. Press the Menu icon four times.
3. To switch between decimal point or decimal comma, press the Up or Down icon.
4. To save the new settings, press the Menu icon twice to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
Notes:
To activate the home screen when the backlight is off, touch the screen to turn the backlight back on for ten seconds.
All icons are visible on the home screen during conguration.
Part No. 24-11256-00007, Rev. —
7
NS8000 Series
4 2 1
On
Off
DIP switch SA bus address Switch 4 Switch 2 Switch 1
199 Off Off Off
200 Off Off On
201 Off On Off
202 Off On On
203 On Off Off
204 On Off On
205 On On Off
206 On On On
CO
2
altitude compensation
The Johnson Controls® NS Series CO
2
Network Sensors ship from the factory calibrated for an altitude range of 0 ft to 2,000 ft
(0 m to 600 m) without compensation.
For altitudes above 2,000 ft (600 m) where optimum accuracy of the CO
2
concentration measurement is essential, modify the
offset property of the NS Series CO
2
Network Sensors (Zone Quality [ZN-Q] Analog Input [AI]). The offset represents the local
atmospheric pressure in hectopascals (hPa). Set the offset to the known local pressure or use the local altitude value listed in
Table 3. The factory default value is 978 hPa.
As of Release 5.3 of the Controller Conguration Tool (CCT) and Facility Explorer® Programmable Controller Tool (FX-PCT)
software, the NS Series CO
2
Network Sensors (Zone Quality [ZN-Q] Analog Input [AI]) automatically change the hPa value entered
from Table 3 into the correct offset value in the CCT and FX-PCT software. The offset value for the SA bus device is labeled ppm;
however, it is the proper eld to enter the hPa value found in Table 3. Refer to the Controller Tool Help (LIT-12011147) for more
details.
Note: Enter the pressure value only in units of hPa. The sensor reads the value entered as hPa. The CO
2
present value may
require several minutes to settle after changing the offset value.
See Table 3 for local altitude values.
Network sensor addressing
Table 2: Network sensor addressing
Figure 1: Three-position switch
Hiding icons on the home screen
1. Press and hold the Up and Down icons for ve seconds until the Fahrenheit and Celsius indicator icons start to blink.
2. Press the Menu icon ve times.
3. To go through each icon on the display, press the Down icon.
4. When the icon you want to hide blinks, press the Up icon to hide it.
5. To save the new settings, press the Menu icon ve times to return to the home screen or wait for ten seconds for the screen to
return to the home screen automatically.
Activating and deactivating the screen lockout
Lock the screen to prevent users from making setpoint changes or entering the commissioning mode. To activate and deactivate
the screen lockout, complete the following steps:
1. Press and hold the Menu icon for ten seconds until the Up and Down icons vanish on the display
to activate the screen lockout.
2. Press and hold the Menu icon for ten seconds until the Up, Down and Fan icons reappear to deactivate the screen lockout.
Part No. 24-11256-00007, Rev. —
8
NS8000 Series
Repair Information
If the NS Series Network Sensor fails to operate within its specications, replace the unit. For a replacement NS Series Network
Sensor, contact the nearest customer service center or Johnson Controls representative.
Altitude above sea level Absolute pressure
Feet Meters hPa
-656 -200 1,038
0 0 1,013
656 200 989
1,312 400 966
1,969 600 943
2,625 800 921
3,281 1,000 899
3,937 1,200 877
4,593 1,400 856
5,249 1,600 835
5,906 1,800 815
6,562 2,000 795
7,218 2,200 775
7,874 2,400 756
8,530 2,600 738
9,186 2,800 719
9,843 3,000 701
Table 3: CO
2
altitude compensation
Part No. 24-11256-00007, Rev. —
9
NS8000 Series
Technical specications
Supply voltage 9.8 VDC to 16.5 VDC; 15 VDC nominal (from SA bus)
Current consumption Base current draw (all models) 3 mA maximum (non-transmitting)
CO
2
models 25 mA maximum additional current (during measurement)
Display models - backlight on 30 mA additional current
Note: SA bus applications are limited to a power load of 210 mA. The best practice when configuring
an SA bus is to limit the total available operating power consumption to 120 mA or less. This power
level allows you to connect a BTCVT Wireless Commissioning Converter temporarily or a DIS1710
Local Controller Display to the bus for commissioning, adjusting, and monitoring.
Terminations Modular jack and screw terminal block
Network sensor addressing All models DIP switch set from 199 to 206; factory set at 199
Wire size Modular jack models 24 AWG or 26 AWG (0.5 mm or 0.4 mm diameter); three twisted
pair (six conductors)
Screw terminal block models 18 AWG to 22 AWG (1 mm to 0.6 mm diameter); 22 AWG
(0.6 mm diameter)
Communication rate Auto-detect: 9.6 kbps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
Temperature measurement range 32.0°F/0°C to 104°F/40°C
Temperature sensor type Digital temperature sensor
Humidity sensor type Thin film capacitive sensor
Ambient conditions Operating 32°F to 122°F (0°C to 50°C); 10% to 90% RH, noncondensing;
85°F (29°C) maximum dew point
Storage Display models -40°F to 122°F (-40°C to 50°C); 5% to 95% RH, noncondensing
Non-display models -40°F to 185°F (-40°C to 70°C); 5% to 95% RH, noncondensing
Temperature resolution ±0.5°F/±0.5°C
Temperature accuracy NS Series Network Zone
Sensor
±1°F/±0.6°C
Temperature element only ±0.36°F/±0.2°C at 70°F/21°C
Humidity element accuracy NSB8BPN24x-0 models ±2% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±4% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F
(10°C to 35°C)
NSB8BHxxxx-0 models ±3% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±6% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F
(10°C to 35°C)
CO
2
sensor accuracy Accuracy ±30 ppm ±3% of CO
2
reading at 77°F (25°C) and 978 hPa
(1,000 ft/300 m)
Temperature dependence ±1.4 ppm/°F (± 2.5 ppm/°C)
Pressure dependence See Table 3 for CO
2
altitude compensation.
Time constant 10 minutes nominal at 10 fpm airflow
Default temperature setpoint adjustment range 50°F/10°C to 86°F/30°C in 0.5° increments
CO
2
sensor Operating 32°F to 122°F (0°C to 50°C)
Compliance United States UL Listed, File E107041, CCN PAZX,
Under UL 60730-1, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Canada cUL Listed, File E107041, CCN PAZX7,
Under CAN/CSA E60730-1, Signal Equipment
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls declares that this product is in
compliance with the essential requirements and other relevant
provisions of the EMC Directive and RoHS Directive.
Australia and New Zealand RCM Mark, Australia/NZ Emissions Compliant
China RoHS2
www.johnsoncontrols.com
Building Technologies & Solutions
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Johnson Controls
®
is registered trademark of Johnson Controls.
All other marks herein are the marks of their respective owners.
© Copyright 2019 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.
European Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
NA/SA Single Point of Contact:
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
APAC Single Point of Contact:
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142 - CHINA
NS8000 Series
UL conformity declaration information
Information Description
Purpose of control Operating control
Construction of control Independently mounted
Type 1 or Type 2 Action Type 1
External pollution situation Pollution degree 2
Rated impulse voltage 330 V
External power supply Intended for connection to Johnson Controls field controllers supporting the standard JCI SA Bus
implementation.
CO
2
sensor information The Model NSx8 Series Wall Mount sensors, sense, in part CO
2
. This functionality is intended to
provide an input to equipment under normal operating conditions. Where failure or malfunction of
the transmitter could lead to personal injury or property damage to the controlled equipment or other
property, additional precautions must be designed into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of
or protect against failure or malfunction of the sensor.
The performance specications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specications, consult the local Johnson Controls ofce. Johnson Controls shall not be liable for damages resulting from misapplication
or misuse of its products.
Dimensions (height x width x depth) 3.4 in. x 5 in. x 1.1 in. (85.3 mm x 127.55 mm x 26.8 mm)
Shipping weight 0.4 lb/0.18 kg
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Johnson Controls NS Series Installation Instructions Manual

Taper
Installation Instructions Manual
Ce manuel convient également à

dans d''autres langues