Generac PowerPact Series G0065190 Manuel utilisateur

Taper
Manuel utilisateur
Owners Manual
For
Automatic Transfer Switch
PowerPact™ Home Standby Generator
MODEL NUMBER: _________________________
SERIAL NUMBER: _________________________
DATE PURCHASED:________________________
WWW.GENERAC.COM
1-888-GENERAC
(1-888-436-3722)
Para español , visita:
http://www.generac.com/service-support/product-support-lookup
Pour le français, visiter : http://www.generac.com/service-support/product-support-lookup
SAVE THIS MANUAL FOR FUTURE REFERENCE
ii Automatic Transfer Switch Owner’s Manual
(000005)
WARNING
California Proposition 65. This product contains or
emits chemicals known to the state of California to
cause cancer, birth defects, and other reproductive
harm.
(000004)
WARNING
California Proposition 65. Engine exhaust and some
of its constituents are known to the state of California
to cause cancer, birth defects, and other reproductive
harm.
Table of Contents
PowerPact™ Automatic Transfer Switch Owner’s Manual iii
Section 1: Introduction and Safety
Introduction ..........................................................1
Safety Rules .........................................................1
Safety Symbols and Meanings ...........................2
General Hazards ..................................................3
Section 2: General Information
Unpacking ............................................................5
Equipment Description .......................................5
Transfer Switch Features ....................................5
Specifications ......................................................5
Transfer Switch Data Decal ................................5
Transfer Switch Enclosure .................................6
Safe Use of Transfer Switch ...............................6
Section 3: Installation
Introduction ..........................................................7
Mounting ...............................................................7
Connecting Power Source and Load Lines .......7
2-Pole Mechanism ...............................................8
Connecting Start Circuit Wires ...........................8
Circuit Breaker Wiring .........................................9
Section 4: Operation
Functional Tests and Adjustments ..................11
Manual Operation ..............................................11
Close to Normal Source Side ....................................11
Close to Emergency Source Side .............................11
Return to Normal Source Side ..................................12
Voltage Checks ..................................................12
Utility Voltage Checks ...............................................12
Generator Voltage Checks ........................................12
Generator Tests Under Load ............................13
Checking Automatic Operation ........................13
Shutting Generator Down While Under Load ..13
Installation Summary ........................................13
Section 5: Drawings and Diagrams
Installation Diagram .......................................... 15
(Drawing 0K8843-A) ..................................................15
Interconnection Drawing .................................. 16
(Drawing 0K8844-B) ..................................................16
Table of Contents
Table of Contents
iv PowerPact™ Automatic Transfer Switch Owner’s Manual
This page intentionally left blank.
Introduction and Safety
PowerPact™ Automatic Transfer Switch Owner’s Manual 1
Section 1: Introduction and Safety
Introduction
Thank you for purchasing a Generac Power Systems Inc.
product. This unit has been designed to provide high-
performance, efficient operation, and years of use when
maintained properly.
Read this manual thoroughly and understand all of the
instructions, cautions, and warnings before using this
equipment. If any section of the manual is not
understood, contact your nearest authorized dealer, or
contact Generac Customer Service at 1-888-436-3722
(1-888-GENERAC), or www.generac.com with any
questions or concerns.
The owner is responsible for proper maintenance and
safe use of the equipment. Before operating or servicing
this transfer switch:
Study all warnings in this manual and on the
product carefully.
Become familiar with this manual and the unit
before use.
Refer to the Installation section of the manual for
instructions on final assembly procedures. Follow
the instructions completely.
Save these instructions for future reference. ALWAYS
supply this manual to any individual that will use this
machine.
THE INFORMATION CONTAINED HEREIN WAS
BASED ON MACHINES IN PRODUCTION AT THE
TIME OF PUBLICATION. GENERAC RESERVES THE
RIGHT TO MODIFY THIS MANUAL AT ANY TIME.
Safety Rules
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and on tags and decals affixed to the unit
are, therefore, not all inclusive. If using a procedure, work
method or operating technique that the manufacturer
does not specifically recommend, verify that it is safe for
others. Also make sure the procedure, work method or
operating technique utilized does not render the
equipment unsafe.
Throughout this publication, and on tags and decals
affixed to the transfer switch, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel
to special instructions about a particular operation that
may be hazardous if performed incorrectly or carelessly.
Observe them carefully. Their definitions are as follows:
NOTE: Notes contain additional information important to
a procedure and will be found within the regular text of
this manual.
These safety warnings cannot eliminate the hazards that
they indicate. Common sense and strict compliance with
the special instructions while performing the action or
service are essential to preventing accidents.
(000001)
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
Introduction and Safety
2 PowerPact™ Automatic Transfer Switch Owner’s Manual
Safety Symbols and Meanings
(000129)
DANGER
Electrocution. High voltage is present at
transfer switch and terminals. Contact with live
terminals will result in death or serious injury.
(000104)
DANGER
Electrocution. Water contact with a power
source, if not avoided, will result in death
or serious injury.
(000145)
DANGER
Electrocution. In the event of electrical accident,
immediately shut power OFF. Use non-conductive
implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will
result in death or serious injury.
(000131a)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator when electrical utility is the primary
power source. Failure to do so will result in death,
serious injury, and equipment damage.
(000195)
DANGER
Electrocution, equipment and property damage.
Handle transfer switches carefully when installing.
Never install a damaged transfer switch. Doing so
could result in death or serious injury, equipment
and property damage.
(000123)
DANGER
Electrocution. Turn utility supply OFF before
working on utility connections of the transfer
switch. Failure to do so will result in
death or serious injury.
(000157)
DANGER
Electrocution. Do not disable or modify the
connection box door safety switch. Doing so
will result in death or serious injury.
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000191)
DANGER
(000119)
Equipment malfunction. Installing a dirty or damaged
transfer switch will cause equipment malfunction and
will result in death or serious injury.
DANGER
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
(000155)
WARNING
Only a trained and licensed electrician should perform
wiring and connections to unit. Failure to follow proper
installation requirements could result in death, serious
injury, and damage to equipment or property.
(000120)
CAUTION
Equipment damage. Verify all conductors are
tightened to the factory specified torque value.
Failure to do so could result in damage
to the switch base.
(000121)
CAUTION
Equipment damage. Perform functional tests in the
exact order they are presented in the manual.
Failure to do so could result in equipment damage.
(000134a)
CAUTION
Equipment damage. Exceeding rated voltage
and current will damage the auxiliary contacts.
Verify that voltage and current are within specification
before energizing this equipment.
Introduction and Safety
PowerPact™ Automatic Transfer Switch Owner’s Manual 3
General Hazards
Any AC generator that is used for backup power if
a NORMAL (UTILITY) power source failure occurs
must be isolated from the NORMAL (UTILITY)
power source by means of an approved transfer
switch. Failure to properly isolate the NORMAL
and STANDBY power sources from each other
may result in injury or death to electric utility
workers, due to backfeed of electrical energy.
Extremely high power and dangerous voltages are
present inside an installed transfer switch. Any
contact with high voltage terminals, contacts or
wires can result in LETHAL electric shock, while
arc flash can cause blindness and severe burns.
DO NOT WORK ON THE TRANSFER SWITCH
UNTIL YOU HAVE CONFIRMED THAT ALL
POWER SUPPLIES TO THE SWITCH ARE
TURNED OFF.
Competent, qualified personnel should install,
operate and service this equipment. Adhere strictly
to local, state and national electrical and building
codes. When using this equipment, comply with
regulations the National Electrical Code (NEC),
CSA Standard; C22.1 Canadian Electric Code and
Occupational Safety and Health Administration
(OSHA) have established.
Never handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
Because jewelry conducts electricity, wearing it
may cause dangerous electrical shock. Remove all
jewelry (such as rings, watches, bracelets, etc.)
before working on this equipment.
If working on this equipment while standing on
metal or concrete, place insulative mats over a dry
wood platform. Work on this equipment only while
standing on such insulative mats.
Never work on this equipment while physically or
mentally fatigued.
Keep the transfer switch enclosure door closed
and bolted at all times. Only qualified personnel
should be permitted access to the switch interior.
When an automatic transfer switch is installed for a
standby generator set, the generator engine may
crank and start at any time without warning. To
avoid possible injury that might be caused by such
sudden start-ups, the system’s automatic start
circuit must be disabled before working on or
around the generator or transfer switch. Then
place a “DO NOT OPERATE” tag on the transfer
switch and on the generator.
Any voltage measurements should be performed
with a meter that meets UL3111 safety standards,
and meets or exceeds overvoltage class CAT III.
Introduction and Safety
4 PowerPact™ Automatic Transfer Switch Owner’s Manual
This page intentionally left blank.
General Information
PowerPact™ Automatic Transfer Switch Owner’s Manual 5
Section 2: General Information
Unpacking
Carefully unpack the transfer switch. Inspect closely for
any damage that might have occurred during shipment.
The purchaser must file with the carrier any claims for
loss or damage incurred while in transit.
Check that all packing material is completely removed
from the switch prior to installation.
Equipment Description
This automatic transfer switch is used for transferring
critical electrical load from a utility (normal) power source
to a generator (standby) power source. Such a transfer of
electrical loads occurs automatically when the utility
power source has failed or is substantially reduced and
the generator source voltage and frequency have
reached an acceptable level. The transfer switch
prevents electrical feedback between two different power
sources (such as the utility and generator sources) and,
for that reason, codes require it in all standby electric
system installations.
The transfer switch consists of a transfer mechanism, a
control relay, a terminal strip and fuse holder for
connection of sensing wires.
This switch is suitable for control of motors, electric
discharge lamps, tungsten filament and electric heating
equipment and the tungsten load does not exceed 30%
of the switch rating.
This UL listed transfer switch is for use in optional
standby systems only (NEC article 702).
A 50A rated switch is suitable for use on circuits capable
of delivering not more than 10,000 RMS symmetrical
amperes, 250 VAC maximum, when protected by a 50A
maximum circuit breaker (Siemens types QP or BQ) or
50A maximum circuit breaker (Square D Q2,
Westinghouse CA-CAH, General Electric TQ2 and
Siemens QJ2).
Transfer Switch Features
Utilizes standard Siemens components
UL listed to U.S.A. and Canadian safety standards
Single panels are compatible with single-phase
generators rated up to 50 Amps/12 kW
Flush or Surface Mount NEMA 1 enclosure
This switch is listed for use with the following one inch
breakers:
Siemens*
Murray*
Eaton
Square D
*Including GFCI, AFCI and tandem breakers up to 50
amps.
NOTE: For branch circuits over 50 amps, only listed
Siemens or Murray circuit breakers shall be used.
Specifications
Transfer Switch Data Decal
A data decal is permanently affixed to the transfer switch
enclosure. Use this transfer switch only with the specific
limits shown on the data decal and on other decals and
labels that may be affixed to the switch. This will prevent
damage to equipment and property.
When requesting information or ordering parts for this
equipment, make sure to include all information from the
data decal.
For future reference, record the Model and Serial
numbers in the space provided on the front cover of this
manual.
Enclosure NEMA Type 1, Surface or Flush
Mount, general purpose, painted
metal, for interior use only
Transfer Switch Generator Lugs (E1, E2)
Transfer Switch Wire
Size
Load Lugs (T1, T2)
Ground Lug #12–20
Neutral Bar #4–14 AWG
Ground Fault or Arc
Fault Circuit Breaker
QPF or QAF Siemens
Withstand Rating Main
Bus (Amps)
10,000
Meets NEC Wire
Bending Space
Yes
UL Listed and CSA Yes
Weight:
Without Whips
With Whips
20 lbs (9.1 kg)
39 (17.7 kg)
Operating Temperature –20°F to 140°F (-29°C to 60°C)
General Information
6 PowerPact™ Automatic Transfer Switch Owner’s Manual
Figure 2-1. Panelboard With Operator
Transfer Switch Enclosure
The standard switch enclosure is a National Electrical
Manufacturer’s Association (NEMA) UL Type 1.
Safe Use of Transfer Switch
Before installing, operating or servicing this equipment,
read Introduction and Safety carefully. Comply strictly
with all information presented in Introduction and
Safety to prevent accidents and/or damage to the
equipment. The manufacturer recommends that a copy
of Introduction and Safety be posted near the transfer
switch. Also, be sure to read all instructions and
information found on tags, labels and decals affixed to
the equipment.
Two publications that outline the safe use of transfer
switches are the following:
NFPA 70; National Electrical Code
NFPA 70E: Standard for Electrical Safety in the
Workplace
UL 1008: Standard for Safety—Automatic Transfer
Switches
UL 97: Standard for Safety—Panelboard
NOTE: It is essential to use the latest version of any
standard to verify correct and current information.
001482
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
Installation
PowerPact™ Automatic Transfer Switch Owner’s Manual 7
Section 3: Installation
Introduction
This equipment has been wired and tested at the factory.
Installing the switch includes the following procedures:
Mounting the enclosure.
Connecting power source and load leads.
Connecting the generator start and sensing circuit.
Testing functions.
Mounting
Mounting dimensions for the NEMA Type 1 Transfer
Switch enclosure are in this manual. Enclosures are
typically wall-mounted. See Drawings and Diagrams.
Protect the switch against impact at all times, and against
construction grit and metal chips.
1. Locate automatic transfer switch with built-in
emergency load center in close proximity to the
main distribution panel. The transfer switch can be
located to the left or right of the main distribution
panel. One (1) foot (0.3 m) is the suggested
distance.
NOTE: The transfer switch may be located a different
distance from the main panel depending on available
mounting area. Using the two (2) foot (0.61 m) conduit
connected straight across to the main panel is another
option. Always adhere to local electrical codes during
installation.
2. Hold transfer switch against the mounting surface.
Level the transfer switch and mark the mounting
holes.
3. Drill the appropriate size pilot holes.
4. Mount transfer switch with built-in load center to
mounting surface with appropriate fasteners.
NOTE: See Figure 3-1. Transfer switch MUST be
mounted vertically as shown.
Figure 3-1. Mount Transfer Switch
5. Switch service main circuit breaker to the OFF
(OPEN) position prior to removal of cover or
removal of any wiring of the main electrical
distribution panel. The wires connected to the
service main circuit breaker remain LIVE or HOT.
Avoid contact with these wires and the service
main circuit breaker connection lugs.
NOTE: This switch may be equipped with 2 foot (0.67 m)
or 30 foot (9.1 m) whips. If not provided, size conductors
and conduits according to NEC codes.
Connecting Power Source and Load Lines
Installation and interconnection diagrams are provided in
this manual.
NOTE: All installations must comply with national, state
and local codes. It is the responsibility of the installer to
perform an installation that will pass the final electrical
inspection.
(000195)
DANGER
Electrocution, equipment and property damage.
Handle transfer switches carefully when installing.
Never install a damaged transfer switch. Doing so
could result in death or serious injury, equipment
and property damage.
(000119)
Equipment malfunction. Installing a dirty or damaged
transfer switch will cause equipment malfunction and
will result in death or serious injury.
DANGER
001483
(000213)
DANGER
Electrocution. Only authorized personnel should
access transfer switch interior. Transfer switch doors
should be kept closed and locked. Failure to do so
will result in death or serious injury.
Electrocution. Turn utility and emergency
power supplies to OFF before connecting
power source and load lines. Failure to do so
will result in death or serious injury.
(000116)
DANGER
(000155)
WARNING
Only a trained and licensed electrician should perform
wiring and connections to unit. Failure to follow proper
installation requirements could result in death, serious
injury, and damage to equipment or property.
Installation
8 PowerPact™ Automatic Transfer Switch Owner’s Manual
2-Pole Mechanism
See Figure 3-2. These switches are used with a single-
phase system when the single-phase NEUTRAL line is to
be connected to a Neutral Lug and is not to be switched.
Figure 3-2. Typical 2-Pole Transfer Mechanism
Solderless, screw-type terminal lugs are standard.
Conductor sizes must be adequate to handle the
maximum current to which they will be subjected, based
on the 167° F (75°C) column of tables, charts, etc. used
to size conductors. The installation must comply fully with
all applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove any
surface oxides from the cable ends with a wire brush. All
power cables should enter the switch next to transfer
mechanism terminals.
NOTE: If aluminum conductors are used, apply corrosion
inhibitor to conductors. After tightening terminal lugs,
carefully wipe away any excess corrosion inhibitor.
Tighten terminal lugs to the torque values as noted on the
decal located on the inside of the door. After tightening
terminal lugs, carefully wipe away any excess corrosion
inhibitor.
Connect power source and load conductors to clearly
marked terminal lugs on transfer mechanism as follows:
1. Connect utility (normal) power source cables to
utility service disconnect circuit breaker.
2. Connect the generator (standby) source power
cables to transfer switch terminals E1, E2., and E3
3. Connect customer LOAD leads to switch terminals
T1 and T2.
Conductors must be properly supported, of approved
insulative qualities, protected by approved conduit, and
of the correct wire gauge size in accordance with
applicable codes.
Be sure to maintain proper electrical clearance between
live metal parts and grounded metal. Allow at least one-
half inch (13 mm) for 100-400 amp circuits.
Connecting Start Circuit Wires
Control system interconnections (Electrical Data section)
consist of UTILITY 1 (N1), UTILITY 2 (N2) and LOAD
(T1), and leads 23 and 194. Recommended wire gauge
sizes for this wiring depends on the length of the wire, as
recommended in the following chart:
Exception: Conductors of AC and DC circuits, rated
1000 volts nominal or less, shall be permitted to occupy
the same equipment, cable, or conduit. All conductors
shall have an insulation rating equal to at least the
maximum circuit voltage applied to any conductor within
the equipment, cable, or conduit. See NEC 300.3(C)(1).
A. Utility Lugs (N1 & N2)
B. Generator Lugs (E1 & E2)
C. Load Lugs (T1 & T2)
Switch Rating Wire Range Conductor
Tightening Torque
50A 1/0–14 AWG 50 in.lbs. (5.65 Nm)
001488
A
C
B
(000120)
CAUTION
Equipment damage. Verify all conductors are
tightened to the factory specified torque value.
Failure to do so could result in damage
to the switch base.
Maximum Wire Length Recommended Wire Size
1–115 ft (1–35 m) No. 18 AWG
116–185 ft (36–56 m) No. 16 AWG
186–295 ft (57–89 m) No. 14 AWG
296–460 ft (90–140 m) No. 12 AWG
Installation
PowerPact™ Automatic Transfer Switch Owner’s Manual 9
Circuit Breaker Wiring
NOTE: Balance must be maintained when moving circuit
locations from main electrical distribution panel to
emergency load center. Circuit breaker positions
alternate buss bars vertically. Circuits sharing a neutral
wire should either be moved together to adjacent
positions in emergency load center or not moved. If
unsure of the proper procedure or if the installation differs
from that described in this guide, consult a licensed
professional at this time.
1. Remove the main electrical distribution panel
cover.
2. Remove appropriate size knockout from the right
side of the main panel. (If provided, a two foot (0.67
m) flexible conduit is pre-wired from the transfer
switch with built-in load center).
3. Remove threaded lock nut from conduit coupling.
Feed all wires through knockout into main panel.
Slip lock nut over wires and tighten securely onto
conduit coupling.
NOTE: Circuits to be moved must be protected by same
size breaker. For example, a 15 amp 120 volt circuit in
emergency load center will replace a 15 amp 120 volt
circuit in main electrical distribution panel.
4. In the main panel, remove the black (hot) wire from
the circuit breaker that protects a circuit to be
powered in the event of a power failure. Wire nut
the black wire to the matching circuit lead wire from
the emergency circuit breaker in the load center in
the transfer switch. (All circuit wires are color
coded and labeled for easy identification). UL listed
wire locknuts are included in installation kit.
5. Trace each black (hot) wire connected and wire nut
the white (neutral) wire from the same Romex
cable (circuit) to the matching circuit number on the
white (neutral) wire from the emergency load
center. Repeat for each circuit.
6. Repeat this process with the remaining circuits to
be powered by the generator.
NOTE: Both grounded and ungrounded conductors must
be moved to the emergency panel and connected to the
new wiring from the emergency panel using supplied wire
nuts.
7. Install the 50 amp double pole breaker; 7 kW
(purchased or supplied separately), into main
electrical distribution panel. This circuit breaker
must be compatible with the main electrical
distribution panel. It may be necessary to
reposition remaining circuit breakers or remove
circuit breakers that have been disconnected to
accommodate the insertion of the 50 amp double
pole circuit breaker.
8. Connect white wire to the main distribution panel
neutral bar.
9. Connect solid green wire to main electrical panel
ground bar.
10. Connect the black and red wires to the 50 amp
double pole circuit breaker.
11. Reinstall the main distribution panel cover.
Installation
10 PowerPact™ Automatic Transfer Switch Owner’s Manual
This page intentionally left blank.
Operation
PowerPact™ Automatic Transfer Switch Owner’s Manual 11
Section 4: Operation
Functional Tests and Adjustments
Following transfer switch installation and interconnection,
inspect the entire installation carefully. A competent,
qualified electrician should inspect it. The installation must
comply strictly with all applicable codes, standards, and
regulations. When absolutely certain the installation is
proper and correct, complete a functional test of the system.
IMPORTANT: Before proceeding with functional tests,
read and make sure all instructions and information in
this section is understood. Also read the information and
instructions of labels and decals affixed to the switch.
Note any options or accessories that might be installed
and review their operation.
Manual Operation
See Figure 4-1. A manual transfer handle (D) is shipped
with the transfer switch. Manual operation must be
checked BEFORE the transfer switch is operated
electrically. To check manual operation, proceed as
follows:
1. Verify the generator is in the OFF mode.
2. Turn OFF or OPEN both UTLITY and
EMERGENCY power supplies to the transfer
switch, with whatever means provided (such as the
main line circuit breakers).
3. Note position of transfer mechanism main contacts
by observing the movable contact carrier arm.
Manual operation handle towards the top of switch
mechanism—LOAD terminals (T1, T2) are
connected to STANDBY terminals (E1, E2
).
• Manual operation handle towards the bottom of
switch mechanism—LOAD terminals (T1, T2) are
connected to UTILITY terminals (N1, N2).
Close to Normal Source Side
See Figure 4-1. Before proceeding, verify the position of
the switch by observing the position of the manual
transfer handle (D).
Figure 4-1. Actuating Transfer Switch
If the handle is down, the contacts are closed in the
normal position. No further action is required. If the
handle is UP, proceed.
With the handle inserted into the actuating shaft, move
handle DOWN. Be sure to hold on to the handle as it will
move quickly after the center of travel.
Close to Emergency Source Side
See Figure 4-1. Before proceeding, verify the position of
the switch by observing the position of the manual
transfer handle (D).
If the handle is UP, the contacts are closed in the
EMERGENCY (Standby) position. No further action is
required. If the handle is down, proceed.
With the handle inserted into the actuating shaft, move
the handle UP. Be sure to hold on to the handle as it will
move quickly after the center of travel.
(000121)
CAUTION
Equipment damage. Perform functional tests in the
exact order they are presented in the manual.
Failure to do so could result in equipment damage.
(000132)
DANGER
Electrocution. Do not manually transfer under load.
Disconnect transfer switch from all power sources
prior to manual transfer. Failure to do so will result
in death or serious injury, and equipment damage.
(000122)
CAUTION
Equipment damage. Do not use excessive force
while manually operating the transfer switch.
Doing so could result in equipment damage.
A. Load connected to standby power source
B. Load connected to utility power source
C. Transfer switch operating lever
D. Manual transfer handle
001484
A
B
C
D
Operation
12 PowerPact™ Automatic Transfer Switch Owner’s Manual
Return to Normal Source Side
Manually actuate switch to return manual operating
handle to the DOWN position.
Voltage Checks
Utility Voltage Checks
1. Turn ON the UTILITY power supply to the transfer
switch with whatever means provided (such as the
UTILITY main line circuit breaker).
2. With an accurate AC voltmeter, check for correct
voltage. Measure across ATS terminal lugs N1 and
N2; N1 to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is
correct and compatible with transfer switch ratings,
turn OFF the UTILITY supply to the transfer switch.
Generator Voltage Checks
1. On the generator panel, select the MANUAL mode
of operation. The generator should crank and start.
2. Let the generator stabilize and warm up at no-load
for at least five minutes.
3. Set the generator main circuit breaker (CB1) to ON
or CLOSED.
4. With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
Measure across ATS terminal lugs E1 to E2; E1 to
NEUTRAL and E2 to NEUTRAL.
5. When certain that generator supply voltage is
correct and compatible with transfer switch ratings,
turn OFF the generator supply to the transfer
switch.
6. Set the generator main circuit breaker (CB1) to
OFF or OPEN.
7. On the generator panel, select the OFF mode to
shut down the generator.
NOTE: Do NOT proceed until generator AC output
voltage and frequency are correct and within stated
limits. If the no-load voltage is correct but no-load
frequency is incorrect, the engine governed speed may
require adjustment. If no-load frequency is correct but
voltage is not, the voltage regulator may require
adjustment.
(000129)
DANGER
Electrocution. High voltage is present at
transfer switch and terminals. Contact with live
terminals will result in death or serious injury.
(000123)
DANGER
Electrocution. Turn utility supply OFF before
working on utility connections of the transfer
switch. Failure to do so will result in
death or serious injury.
Frequency 60–62 Hz
Terminals E1 to E2 240–246 VAC
Terminals E1 to NEUTRAL 120–123 VAC
Terminals E2 to NEUTRAL 120–123 VAC
(000129)
DANGER
Electrocution. High voltage is present at
transfer switch and terminals. Contact with live
terminals will result in death or serious injury.
Operation
PowerPact™ Automatic Transfer Switch Owner’s Manual 13
Generator Tests Under Load
1. Turn OFF the utility power supply to the transfer
switch with whatever means provided (such as the
utility main line circuit breaker).
2. Set the generator main circuit breaker to OFF or
OPEN.
3. Manually actuate the transfer switch main contacts
to the emergency (Standby) position. See Manual
Operation. To start the generator, select the
MANUAL mode of operation. When engine starts,
let it stabilize for a few minutes.
4. Set the generator main circuit breaker to ON or
CLOSED. The generator now powers all LOAD
circuits. Check generator operation under load as
follows:
Turn on electrical loads to the full rated wattage/
amperage capacity of the generator. DO NOT
OVERLOAD.
With maximum rated load applied, check voltage
and frequency across transfer switch terminals E1
and E2. Voltage should be greater than 230 volts
(240 VAC system); frequency should be greater
than 59 Hz.
Let the generator run under rated load for at least
30 minutes. With unit running, listen for unusual
noises, vibration, overheating, etc., that might
indicate a problem.
5. When checkout under load is complete, set main
circuit breaker of the generator to the OFF or
OPEN position.
6. Let the generator run at no-load for several
minutes. Then, shut down by selecting the OFF
mode.
7. Move the main switch contacts back to UTILITY.
NOTE: See Manual Operation. Handle and operating
lever of transfer switch should be in down position.
8. Turn on the utility power supply to transfer switch,
using whatever means provided (such as a utility
main line circuit breaker). The utility power source
now powers the loads.
9. The system is now set for fully automatic operation.
Checking Automatic Operation
To check the system for proper automatic operation,
proceed as follows:
1. Verify generator is in OFF mode.
2. Install front cover of the transfer switch.
3. Turn the utility power supply to the transfer switch
ON, using the utility main line circuit breaker.
4. Set the generator main circuit breaker to ON.
5. On the generator panel, select AUTO. The system
is now ready for automatic operation.
6. Turn utility power supply to the transfer switch OFF.
With the generator ready for automatic operation, the
engine should crank and start when the utility source
power is turned OFF after a ten second delay (factory
default setting). After starting, the transfer switch should
connect load circuits to the standby side after a five (5)
second delay. Let the system operate through its entire
automatic sequence of operation.
Shutting Generator Down While Under Load
Important! To turn the generator off during utility outages
to perform maintenance, or conserve fuel, follow these
important steps:
To turn the generator OFF (while running in AUTO and
online):
1. Turn the main utility disconnect OFF.
2. Turn the main line circuit breaker (MLCB) on the
generator to OFF (OPEN).
3. Let the generator run at no-load several minutes.
4. Turn the generator OFF.
To turn the generator back ON:
1. Put the generator back into AUTO and allow to
start and warm-up for a few minutes.
2. Set the MLCB on the generator to ON.
The system will now be operating in its automatic mode.
The main utility disconnect can be turned ON (CLOSED).
NOTE: To shut the unit off, this complete process must
be repeated.
Installation Summary
1. Verify the installation has been properly performed
as outlined by the manufacturer and that it meets
all applicable laws and codes.
2. Verify proper operation of the system as outlined in
the appropriate Installation and Owner’s Manuals.
3. Educate the end user on the proper operation,
maintenance and service call procedures.
Operation
14 PowerPact™ Automatic Transfer Switch Owner’s Manual
This page intentionally left blank.
Drawings and Diagrams
PowerPact™ Automatic Transfer Switch Owner’s Manual 15
Section 5 Drawings and Diagrams
Installation Diagram
(Drawing 0K8843-A)
PP>@
PP>@
5PP>5@
5PP>5@
.12&.28768,7$%/()25
&21'8,76,=(
,))7:+,3127,1&/8'('
PP>@
PP>@
PP>@
PP>@
PP>@
PP>@
PP>@
PP>@
PP>@
PP>@
PP>@
001485
Drawings and Diagrams
16 PowerPact™ Automatic Transfer Switch Owner’s Manual
\Interconnection Drawing
(Drawing 0K8844-B)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78

Generac PowerPact Series G0065190 Manuel utilisateur

Taper
Manuel utilisateur