Airwell SCW 45 2T Installation and Maintenance Manual

Catégorie
Climatiseurs split-system
Taper
Installation and Maintenance Manual
English Français EspañolDeutsch Italiano
IOM KOG 02-N-8GB
Part number / Code / Teil Nummer / Codice / Código : 3990269GB
Supersedes / Annule et remplace / Annulliert und ersetzt /
Annulla e sostituisce / Anula y sustituye : IOM KOG 02-N-7GB
Installation and maintenance manual
Manuel d’installation et de maintenance
Installations- und Wartungshandbuch
Manuale di installazione e di manutenzione
Manual de instalación y de mantenimiento
CHILLED OR HEATED WATER CASSETTE
CASSETTE EAU GLACEE OU EAU CHAUDE
KALTWASSER ODER GEHEIZTESWASSER -KASSETTE
CASSETTA ACQUA GHIACCIATA O RISCALDATA
CASETE AGUA HELADA O CALENTADA
IOM KOG 02-N-8
Part number / Code / Teil Nummer / Codice / Código : 3990269
Supersedes / Annule et remplace / Annulliert und ersetzt /
Annulla e sostituisce / Anula y sustituye : IOM KOG 02-N-7
K 30 OG 2T
K 45 OG 2T
K 45 OG 4T
ECF 30 OG 2T
ECF 45 OG 2T
ECF 45 OG 4T
SCW 30 2T
SCW 45 2T
SCW 45 4T
WKW 30 2T
WKW 45 2T
WKW 45 4T
INSTALLATION INSTRUCTION
NOTICE D’INSTALLATION
INSTALLATIONSHANDBUCH
ISTRUZIONI INSTALLAZIONE
INSTRUCCIONES DE INSTALACIÓN
2
Chilled Water Cassette
Contents
1 SAFETY PRECAUTIONS ............................................................................................ 3
2 DESCRIPTION .......................................................................................................... 4
2.1 PACKAGE CONTENTS ..................................................................................................................................... 4
2.2 2 PIPES CASSETTE DIMENSIONS .................................................................................................................... 4
2.3 WEIGHTS........................................................................................................................................................ 4
2.4 4 PIPES CASSETTE DIMENSIONS .................................................................................................................... 5
2.5 WEIGHTS........................................................................................................................................................ 5
3 GENERAL ................................................................................................................. 6
3.1 ELECTRICAL SPECIFICATION ..........................................................................................................................6
3.2 OPERATING LIMITS .........................................................................................................................................6
AIR TEMPERATURE LIMITS ......................................................................................................................................................................6
WATER TEMPERATURE LIMITS ................................................................................................................................................................. 6
3.3 INSPECTION AND HANDLING ....................................................................................................................... 7
4 INSTALLATION......................................................................................................... 8
4.1 INSTALLATION LOCATION ............................................................................................................................. 8
4.2 CEILING MOUNTING ..................................................................................................................................... 8
4.3 CASSETTE FITTING ......................................................................................................................................... 9
4.4 CASSETTE INSTALLATION ............................................................................................................................... 9
5 CONNECTIONS ..................................................................................................... 10
5.1 CONDENSATE EVACUATION ....................................................................................................................... 10
5.2 HYDRAULIC CONNECTIONS ........................................................................................................................ 10
6 ELECTRICAL CONNECTION ................................................................................... 11
6.1 ELECTRICAL CONNECTION ............................................... ........................................................................... 11
6.2 CHANGE OVER SENSOR CONNECTION (MODELS 2T) ................................................................................11
THERMOSTAT INSTALLATION ............................................................................................................................................................... 11
WATER TEMPERATURE PROBE INSTALLATION .......................................................................................................................................11
6.3 ELECTRIC HEATING ...................................................................................................................................... 12
6.4 FAULT WARNING REPEATER ......................................................................................................................... 12
6.5 VENTILATION SPEEDS .................................................................................................................................. 12
6.6 WIRING DIAGRAM ....................................................................................................................................... 12
7 ELECTRICITY .......................................................................................................... 13
7.1 THERMOSTAT LOCATION ............................................................................................................................. 13
7.2 CONTROL .................................................................................................................................................... 13
INFRA RED VERSION - INFRA RED REMOTE CONTROL ......................................................................................................................... 13
USE ........................................................................................................................................................................................................................13
ROOM THERMOSTAT TRM-VP AND TRM-FA .........................................................................................................................................15
USE ........................................................................................................................................................................................................................15
SWITCHES ..............................................................................................................................................................................................................15
DIMENSIONS .........................................................................................................................................................................................................15
ELECTRICAL CONNECTIONS ..................................................................................................................................................................................15
WALL MOUNTING ..................................................................................................................................................................................................15
TECHNICAL CHARACTERISTICS ...............................................................................................................................................................................15
FINAL OPERATIONS ................................................................................................................................................................................................16
TAE20 ROOM THERMOSTAT ...............................................................................................................................................................17
FIELDS OF APPLICATION .........................................................................................................................................................................................17
DESCRIPTION .........................................................................................................................................................................................................17
ADJUSTMENT AND CONTROL ELEMENTS ...............................................................................................................................................................17
8 AIR DISTRIBUTION ................................................................................................ 18
8.1
AIR DISTRIBUTION MODULE FITTING .............................................................................................................................18
8.2 FILTER INSTALLATION .................................................................................................................................. 18
9 COMMISSIONING ................................................................................................. 19
9.1 CHECKS BEFORE COMMISSIONING ............................................................................................................. 19
9.2 GENERAL INSTALLATION ............................................................................................................................ 19
9.3 ELECTRICAL ELEMENTS ................................................................................................................................ 19
3
Chilled Water Cassette
THE MANUFACTURER’S WARRANTY WILL NOT APPLY IF THE INSTALLATION
RECOMMENDATIONS LISTED IN THIS MANUAL ARE NOT FOLLOWED.
WARNING !
The installation, commissioning and maintenance of these
units should be performed by qualified personnel having
a good knowledge of standards and local regulations,
as well as experience of this type of equipment.
WARNING !
Any wiring produced on site must comply with local
electrical regulations.
WARNING !
Ensure that the electrical supply corresponds to the
specification indicated on the unit’s maker’s plate before
proceeding with the connection in accordance with the
wiring diagram supplied.
WARNING !
The unit must be EARTHED to avoid any risks caused by
insulation defects.
WARNING !
No wiring must come in contact with the heat source or
the fan rotating parts.
NOTE: PLEASE REFER TO THE TECHNICAL MANUAL FOR THE LIMITATIONS OF USE AND TECHNICAL
CHARACTERISTICS.
ELECTRICAL POWER MUST BE SWITCHED OFF BEFORE
STARTING ANY WORK ON CONTROL BOXES
The aim of this manual is to provide cassette users with instructions for installation, commissioning, operation and
maintenance.
It does not contain the complete description of all the maintenance operations guaranteeing the unit’s long life and reliability.
Only the services of a qualified technician can guarantee the unit’s safe operation over a long service life.
1
safety preCautions
Take care !
The unit should be handled using lifting and handling
equipment appropriate to the unit’s size and weight.
Take care !
It is forbidden to start any work on the electrical
components without switching off the electrical supply
to the unit.
Take care !
It is forbidden to start any work on the electrical
components if water or high humidity is present on the
installation site.
Take care !
When the unit is being connected, ensure that no
impurities are introduced into the pipe work and the
water circuits.
Take care !
A device to disconnect all the power conductors with an
approved minimum opening distance must be included
in the mains power supply according to best installation
practices.
Take care !
The units may contain a small amount of oil incompatible
with plastic polyethylene piping (PER/HTA/PVC). The coil
should be rinsed out before use to avoid any problem.It is
the installer’s responsibility to contact their pipe supplier
and take into account the general instructions for the use
of plastic pipes (PER/HTA/PVC).
4
Chilled Water Cassette
2.1 PACKAGE CONTENTS
1 Cassette
2 Angle attachment fittings
1 Fastener bag: Angle brackets + screws
Rubber shock absorbing pads
Treated air distribution frame screws
Fascia clips
2.2 2 PIPES CASSETTE DIMENSIONS 2.3 WEIGHTS
2
DesCription
1 Documentation bag
1 Fascia assembly
1 Suspended ceiling
2 T bar (suspended ceiling)
3 Evaporator
4 Fan
5 Intake grille
6 Electrical connection
7 Condensate evacuation Ø 15
MODELS 30 2T 45 2T
WEIGHTS (kg) 49 55
Dimensions in mm
8 Water intake RC1"
9 Water outlet RC1"
10 Opening for ducted air distribution into the adjacent
room (ready to punch out)
11 Port for fresh air succion (ready to punch out)
12 Air vent
5
Chilled Water Cassette
2.4 4 PIPES CASSETTE DIMENSIONS
2.5 WEIGHTS
2
DesCription ContinueD
1 Suspended ceiling
2 T bar (suspended ceiling)
3 Evaporator
4 Fan
5 Intake grille
6 Electrical connection
7 Condensate evacuation Ø 15
8 Hot water outlet RC1/2"
8a Hot water intake RC1/2"
9 Cold water outlet RC1"
9a Cold water intake RC1"
10 Opening for ducted air distribution into the adjacent
room (ready to punch out)
11 Port for fresh air succion (ready to punch out)
12 Cold water air vent
MODELS 45 4T
WEIGHTS (kg) 55
Dimensions in mm
6
Chilled Water Cassette
3.1 ELECTRICAL SPECIFICATION
* Minimum cable diameter to be determined in accordance with installation conditions and local
standards.
** aM or C curve trip switch
1 thermostat for each cassette or installation with the 7ACEL1207 kit for a MAXIMUM of 4 Cassettes.
3
General
Models 30 2P 45 2P
with heating without heating with heating without heating
Nominal current A 19 7.4 0.9 8.8 0.96
Maximal current A 22.6 8.5 1.27 10.6 1.35
Fuse rating gG A 25 10 2 ** 16 2 **
Fuse rating ASE / VDE A 25 10 2 16 2
Power supply 230V 50Hz 3N ~ 400V - 50Hz 230V 50Hz 3N ~ 400V - 50Hz 230V 50Hz
Cable section mini* mm² 3G4 5G1.5 3G1.5 5G1.5 3G1.5
Electric heating capacity W 4300 4300 / 5400 /
Models 45 4P
Nominal current A 0.96
Maximal current A 1.35
Fuse rating aM ** A 2
Fuse rating ASE / VDE A 2
Power supply 230V 50Hz
Cable section mini* mm² 3G1.5
3.2 OPERATING LIMITS
Standard unit
Cooling Heating
Minimum ambient temperature (wb) 13 °C /
Minimum ambient temperature (db) 17 °C /
Maximum ambient temperature (wb) 22 °C 22 °C
Maximum ambient temperature (db) 32 °C 32 °C
Standard unit
Cooling Heating
2T / 4T 2T with heating
Minimum water inlet temperature 3 °C / /
Maximum water inlet temperature 18 °C 70 °C 35 °C
AIR TEMPERATURE LIMITS
Please consult us for operating conditions exceeding these temperatures.
WATER TEMPERATURE LIMITS
db: dry bulb wb: wet bulb
7
Chilled Water Cassette
3.3 INSPECTION AND HANDLING
In the event of shipping damage, write precise
details of the damage on the shipper’s delivery note
and send a registered letter with acknowledgement
of receipt to the shipper within 48 hours, clearly
stating the damage caused. Forward a copy of the
letter to the manufacturer or their representative.
N.B. Writing “subject to unpacking” on the delivery note is
not sufficient for the shipper’s insurance company.
IIt is recommended to place the cassette as near as possible
to the final installation site before unpacking.
Avoid placing heavy tools or weights on top of the packed
cassette.
On opening the carton, check that all the accessories
required for installation are present.
Keep the fascia grille in its packaging until it is to be finally
installed.
DO NOT LIFT THE CASSETTE BY THE
CONDENSATE EVACUATION TUBE
The sharp edges and surfaces of the coils can
cause injury. Avoid contact with them.
WARNING !
3
General ContinueD
8
Chilled Water Cassette
4.1 INSTALLATION LOCATION
Installing the cassette will be easier with the use of a fork
lift truck. Use the packing base by placing it between the
cassette and the truck forks.
It is recommended to install the cassette, as far as is possible,
in the centre of the room, in order to optimise treated air
distribution.
For the chosen location, check that the distribution grilles
can be removed and that there is sufficient space available
for access for maintenance and repairs.
When fitting the angle attachment fittings in the low position,
remove the insulating foam from around the mounting
nuts.
The possibility of fitting the angle attachment fittings
at different heights, leaves the installer the choice of
mounting them on the cassette in the high or low position.
Mounting them in the low position provides for more flexible
installation.
Do not tighten the nuts or lock nuts. This will be done only
after having set the cassette in its final horizontal position,
when are the connections have been completed.
4.2 CEILING MOUNTING
Mark the position of each support rod.
Refer to Chapter 2“Dimensions”
The cassettes must not be positioned above
electrical equipment in order to avoid exposure
to water leaks which may occur under extreme
conditions.
107
270
1220
1220
510
510
4
installation
Fit the angle attachment fittings supplied with the cassette
onto the threaded rods (not supplied). Recommended Ø 6
mm maximum Ø 8 mm. Take care to distance them from
the suspended ceiling by 270 mm or 107 mm.
Take care !
Do not install the cassette in a room where gasses, acids or
inflammable products are stored, in order to avoid damage
to the aluminium and copper evaporators and the internal
plastic parts.
Do not install the cassette in a workshop or a kitchen. Oil
vapour attracted by the treated air could form deposits on
the cassette evaporators and modify their performance or
damage the cassette’s internal plastic parts.
Do not install the cassette in a laundry, or a room where
steam is produced.
It is recommended to insure a sufficient ventilation around
the cassette.
The cassette is designed to be built into a suspended
ceiling with panels dimensions of 60 x 60 cm, or multiples
thereof.
9
Chilled Water Cassette
4.4 CASSETTE INSTALLATION
Side openings are provided for installing separate ducts for
outside air intake and treated air distribution to an adjacent
room.
Use a punch to remove the condensation protection insulation
and the pre-punched panels from the openings.
TAKE CARE not to damage the heat exchanger coil
located behind the openings.
Plug the gaps between the ducts and the opening edge with
anti-condensation insulation.
Use material which can withstand a continuous operating
temperature of 60° C. The ducts can be of the flexible type
with a spring core or of corrugated aluminium, covered
inside with an insulating material (12 to 25 mm thick glass
fibre).
If it is intended to install ducting to an adjacent room, refer to § 4.4 for
removal of the pre-punched panel before installing the cassette.
4.3 CASSETTE FITTING
To make the assembly easier the electrical box can be
disassembled by removing 2 screws, and disconnect the
multipoints connectors (15 pts connector for the main
connection, 12 pts connector for the electric heating) and
small connector for the infra-red.
Fix the cassette, connect the multipoints connectors, place
the cassette into is final position and reset the electric box
with 2 screws
Fix the screws to fix the corner irons
In the event that the suspended ceiling is 300 mm from the
ceiling (minimum permitted height), it might be necessary
to temporarily remove some of the suspended ceiling T
supports.
Position the cassette on the suspended ceiling support
rods, and start by tightening the side mounting bolts, then
the threaded rods nuts and lock nuts, after having set the
cassette level, maintaining a gap of around 10 mm between
the metal chassis and the suspended ceiling.
Decompression grille
When the installation is finished, all the surfaces of the
non-insulated ducts must be covered with anti-condensation
insulation material (6 mm thick expanded polystyrene or
expanded neoprene). Fireproofing classification: M1)
IF THE ABOVE INSTRUCTIONS ARE NOT FOLLOWED,
CONDENSATE LEAKS MAY OCCUR.
Distributing air to an adjacent room requires one or two
of the corresponding ducts’ air distribution flaps to be
closed.
A decompression grille must be fitted in the partition between
the air conditioned room (where the cassette is installed)
and the adjacent room.
New air
intake
Treated air
distribution
WARNING !
4
installation ContinueD
10
Chilled Water Cassette
The condensate evacuation pipe must be heat insulated
to a thickness of 5 to 10 mm with insulating material such
as polyurethane, propylene or neoprene (Fireproofing
classification: M1) to prevent condensation.
If several cassettes are installed in the room, the evacuation
system can be designed as illustrated below.
THE CASSETTE MUST ALWAYS REMAIN
CONNECTED TO ELECTRICAL SUPPLY TO ALLOW
THE DRAINAGE OF WATER CONDENSATS.
5.1 CONDENSATE EVACUATION
To ensure effective condensate evacuation, the downward
slope must be 1 cm per metre without any restricted or
ascending section.
600 mm
MAXI
1cm/m
50 mini
Ø
16max
OK
NO
5
ConneCtions
WARNING !
The condensate extraction height is limited to a maximum
of 0.60 metre.
For heights above 0.60 m, an auxiliary condensate pump
with a level regulator should be installed.Furthermore, a
siphon with a height of at least 50 mm must be provided
to avoid any unpleasant odours in the room.
5.2 HYDRAULIC CONNECTIONS
For the system to operate in complete safety,
regulating valves must be fitted, if they are not
already fitted at the factory.
The regulation valves are installed
inside the cassettes. A lock spanner
must be used for tightening the
pipe work.
The first time the cassettes are filled with water
to check the tightness of the circuits, they can
be filled on a temporary basis, without power
being connected to the unit. If, on the other hand,
continuous water circulation is planned, the units
must be connected to the power supply to ensure
condensate drainage by the draining pump and
to avoid the condensate tray overflowing.
WARNING !
WARNING !
For connecting the coils the use of stop cock valves with
flexible pipes is recommended.
It is imperative to envisage a support of these pipings
independently of the cassette.
The connection must not be over tightened.
The hot water coil air vent must be done through the water
outlet connection (8).
It should be noted that over tightening the connections can
cause excessive material constraints during high temperature
operation.
The use of regulation valves (factory-fitted, supplied as an
accessory or by the client) is mandatory to ensure that the
appliance operates correctly.
The installation and operating conditions require the
MANDATORY fitting of a valve ON the unit OR/AND
upstream in the hydraulic circuit. This is to prevent
chilled water from circulating in the appliance when
the fan is not operational (condensation issue) or to
prevent the simultaneous circulation of chilled water
and hot water in a 4-pipes exchanger.
11
Chilled Water Cassette
6.1 ELECTRICAL CONNECTION
6
eleCtriCal ConneCtion
Take care !
Before starting any electrical connection, check
that the electrical supply corresponds to the
specification indicated on the unit’s maker’s plate.
Each cassette in equipped with a terminal block
located inside the cassette cabinet.
Connection to the electrical network must comply with
current electrical standards.
The unit must be earthed.
The manufacturer and their representatives decline all
responsibility for any accidents caused by inadequate or
non-existent earthing of the installation.
All the cassettes are intended to operate on a normal voltage
of 230V ± 10% / 1 phase / 50Hz + Earth or 3N~400V
± 10% / 50Hz.
The wiring diagram affixed to the unit illustrates the
connections to be made.
6.2 CHANGE OVER SENSOR
CONNECTION (MODELS 2T)
Depending on the season, the cassette units are either
supplied with hot water in winter or with chilled water in
summer and during the mid season periods. A 3-way
valve must be installed on the water circuit supplying
the unit.
Summer and mid-season: The 3 way valve is controlled
by the thermostat to obtain cooling.
Winter: The 3 way valve is controlled by the thermostat
to obtain heating.
CHANGE OVER SENSOR
The change over sensor supplied in the unit is to be located
on the water inlet pipe. It enables the thermostat action to
be reversed in relation to water temperature.
THERMOSTAT INSTALLATION
WARNING:
The thermostat is already wired up at the factory.
1. Shut off the unit’s electrical power supply.
2. Fit the thermostat on the water inlet pipe.
3. Cover the connection with a protective
sheath.
WATER TEMPERATURE PROBE INSTALLATION
The SW probe supplied in the unit is to be located on the
water inlet pipe.
WARNING:
The SW probe is already wired at the factory.
1. Cut the power supply to the unit.
2. Fit the probe onto the water inlet pipe.
3. Cover the connection with a protective
sheath.
INSULATE IMPERATIVELY
INSULATE IMPERATIVELY
A device to disconnect all the power conductors with
an approved minimum opening distance must be
included in the mains power supply according to
best installation practices.
Temperature effect: T° < 15 °C - T° > 30 °C.
12
Chilled Water Cassette
6.3 ELECTRIC HEATING
Each electric heating system is equipped with 2 SAFETY
DEVICES. One is reset automatically, the other is manually
reset. They cut off electrical supply to the heating resistances
as soon as an operating anomaly is detected.
The electrical coil must never operate without the
fan turning.
6.4 FAULT WARNING REPEATER
When the upper water level is reached (SB2 detector), the
pump electronic logic control shuts down ventilation, heating
and the cooling valve with one of its wires connected to
terminal 2.
A default relay (KD) or a warning light (I max 4A / 250 V) can
be connected to terminal 6 (230 V NEUTRAL potential).
Provide electrical supply to the system on the same
phase and coming from the same circuit protection
device as the cassette.
Manual reset
6.5 VENTILATION SPEEDS
The cassettes are supplied with 3 fan speeds, wired
according to the model. Depending on the application, it
is possible to select from the 6 speeds, by connecting the
motor wires on standby.
Take care !
Take care !
The disconnected, unused wire must be isolated in
accordance with best electrical wiring practices.
6
eleCtriCal ConneCtion ContinueD
6.6 WIRING DIAGRAM
This wiring diagram is correct at the time of
publication. Manufacturing changes can lead
to modifications. Always refer to the diagram
supplied with the product.
Take care !
SEE APPENDIX
13
Chilled Water Cassette
7
eleCtriCity
The unit must be installed and fitted in
accordance with current safety standards
by a qualified technician.
Fitting height: about 1.50 m above floor level.
Take care not to locate the thermostat in draughts created
by doors and windows.
7.1 THERMOSTAT LOCATION
Also ensure that the thermostat is located in the room’s
normal thermal currents and that it is not located in shelving
or covered by curtains.
Any source of parasitic heat negatively influences
temperature regulation accuracy. Therefore, avoid the sun’s
rays or proximity to portable heating devices, electric lights,
chimneys, televisions, etc...
INFRA RED VERSION - INFRA RED REMOTE CONTROL
USE
Three modes available:
² Cooling
² Heating
² Auto
For each of these modes, fan ventilation can be configured
in LS, MS, HS and Auto Ventilation modes.
7.2 CONTROL
14
Chilled Water Cassette
7
eleCtriCity ContinueD
ON / OFF key
Operating mode selection key for
COOLING
HEATING
AUTOMATIC COOLING / HEATING
REGULATION, FAN ONLY
I FEEL key: local detection of temperature
VENTILATION SPEED or AUTOMATIC
VENTILATION selection key
Set point increase key
Set point decrease key
SLEEP key (unoccupied mode)
"+" key: increases the operating time
"-" key: decreases the operating time
Liquid crystal diode display
I FEEL sensor
Infrared signal transmitter
ROOM key: display of the ambient temperature
LOCK key
SET key:Press for 5 seconds to set the time
RESET FUNCTION:
1. Remove one battery
2. Simultaneously press these 4 keys until the symbols are
no longer displayed
3. Reinstall the battery
NOTE :
Open the cover / flap to access the control keys.
The four keys to be pressed are:
The other buttons , , and of the
remote control are not active in this version.
"Timer" function is available only in option with
remote control µBMS/RCW2
The Timer function is not available with Aquanet.
15
Chilled Water Cassette
Medium speedHigh Speed
Lown Speed
ROOM THERMOSTAT TRM-VP AND TRM-FA
SWITCHES
Switch 0 - I
² ON "I"
² OFF "0"
Linear switch
Linear switch
² COOLING
² HEATING
7
eleCtriCity ContinueD
USE
The room thermostat of the air conditioner regulates the
room temperature. It is designed for closed, dry rooms such
as flats, offices, etc.
Maximum acceptable relative humidity of the air : 95%. This
value should not be exceeded.
Avoid condensation.
DIMENSIONS
WALL MOUNTING
² Remove the thermostat control knob, the
screw and the cover.
² On a flat surface, mount the control panel
using plugs and screws.
² Install the cover, the screw and the thermostat
control knob.
ELECTRICAL CONNECTIONS
Connection of the thermostat TRM-VP and TRM-FA.
Connections should be made according to the diagram
(SEE APPENDIX).
Max. cross-sectional area of wires : 2,5 mm
2
TECHNICAL CHARACTERISTICS
Operating voltage 230V 50Hz
Contact configuration SPDT
Temperature range 5 to 30°C
Switching current at 230V AC 6A (cos ϕ=1) / 3A (cos ϕ =0.6)
Switching differential approx. 0,5 K
Sensor system bimetal
Switches
ON / OFF
mode of operation
fan speed
16
Chilled Water Cassette
7
eleCtriCity ContinueD
FINAL OPERATIONS
ADJUSTMENT OF THE TEMPERATURE
RANGE
The room thermostat is set in the factory for a minimum
temperature of +5°C and a max. temperature of +30°C.
Two rings are provided inside the knob for reducing the
temperature range.
² Example: 12°C to 25°C.
ADJUSTMENT PROCEDURE
1. Setting the temperature range
e.g. max. 25°C, min. 12°C.
2. Remove the control knob.
3. Use a pointed object to align the mark on
the red ring (max. value) with the desired
maximum temperature (25°C), turning the
red index opposite the outside numbers
counterclockwise.
4. Use a pointed object to align the mark on
the blue ring (min. value) with the desired
minimum temperature (12°C), turning the
blue index opposite the inside numbers
clockwise.
5. Install the control knob.
The temperature ranges can be graduated in:
² degrees Celsius °C
from 5°C to 30°C
² number 1 to 6
1=5°C
2=10°C
3=15°C
4=20°C
5=25°c
6=30°C
17
Chilled Water Cassette
7
eleCtriCity ContinueD
TAE20 ROOM THERMOSTAT
FIELDS OF APPLICATION
² Regulating ambient temperature in rooms
heated or cooled.
² Opening and closing the valve.
² Cutting in and out the electric heating.
² Controlling the three fan speed.
DESCRIPTION
The unit comprises two parts:
² A plastic case, housing the electronics, the
controls and an internal ambience sensor.
² A mounting plate.
The case is hooked onto the fitted mounting plate, then
click fastened.
The screw terminal connections are located on the mounting
plate, with the DIP switches on the back of the case.
ADJUSTMENT AND CONTROL
ELEMENTS
² Operating mode switch "ON-OFF" and
manual fan speed selection).
² Electro-luminescent diodes for displaying the
heating and cooling modes and the fan.
² Minimum temperature setting limiter
(adjustable by increments of 1 K). Mechanical
stop accessible by removing the button 5.
² Maximum temperature setting limiter
(adjustable by increments of 1 K). Mechanical
stop accessible by removing the button 5.
² Ambient temperature setting adjustment
button.
² Set of DIP switches.
2 3 4
5 6 1
REFER TO SPECIAL TAE 20 ROOM THERMOSTAT MANUAL
18
Chilled Water Cassette
8.1
AIR DISTRIBUTION MODULE FITTING
Carefully unpack the module and fit the clips in the frame
corners.
For infra red models, connect the flat cable from the
receiver.
Present the frame to the unit, and apply pressure so that the
clips engage. Then screw it in place.
8.2 FILTER INSTALLATION
The seals are illustrated in the diagram below. They
avoid:
A Air by pass
B Treated air being distributed into the suspended
ceilling space.
After installation, check that the gap between the frame and
the suspended ceiling is less than 5 mm.
5 mm
install the central grille by twisting
Avoid distorsions of the frame caused by excessive traction;
the frame should be correctly centered in relation to the false
ceiling and it should especially ensure an airtight separation
between air succion and air discharge.
A B
8
air Distribution
Place the air intake grille hinges in the openings: rep A
Install the filter in the location provided: rep B
Close the grille with the locks on both sides.
A
A
B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42

Airwell SCW 45 2T Installation and Maintenance Manual

Catégorie
Climatiseurs split-system
Taper
Installation and Maintenance Manual

dans d''autres langues