O & M Manual for the EGS Automatic
Transfer Switch with RTC-50 Control
and Integral Loadcenter - 100 Amp
Instructional Booklet
New Information
Description Page
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Receiving, Handling, and Storage . . . . . . . . . . . . . . . . 5
3. Equipment Description. . . . . . . . . . . . . . . . . . . . . . . . 5
4. Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . 7
5. Functional Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6. Adjustments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7. Maintenance and Component Replacement. . . . . . . . . . 13
For more information visit: www.eaton.com IB70-8671
Instructional Booklet
Page 2 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
.
Figure 1. Typical Automatic Transfer Switch Equipment
Nameplate.
All possible contingencies that may arise during installation, opera-
tion, or maintenance, and all details and variations of this equip-
ment do not purport to be covered by these instructions. If
further information is required by the purchaser regarding a partic-
ular installation, application, or maintenance activity, please con-
tact an authorized Eaton sales representative or the installing
contractor.
SECTION 1: INTRODUCTION
1.1 Preliminary Comments and Safety Precautions
This technical document is intended to cover most aspects associ-
ated with the installation, application, operation, and maintenance
of the Automatic Transfer Switch (ATS). It is provided as a guide
for authorized and qualified personnel only. Please refer to the
specific WARNING and CAUTION in Section 1.1.2 before proceed-
ing. If further information is required by the purchaser regarding a
particular installation, application, or maintenance activity, please
contact an authorized Eaton sales representative or the installing
contractor.
1.1.1 Warranty and Liability Information
No warranties, expressed or implied, including warranties of fit-
ness for a particular purpose of merchantability, or warranties aris-
ing from course of dealing or usage of trade, are made regarding
the information, recommendations, and descriptions contained
herein. In no event will Eaton be responsible to the purchaser or
user in contract, in tort (including negligence), strict liability, or
otherwise for any special, indirect, incidental or consequential
damage, or loss whatsoever, including but not limited to damage
or loss of use of equipment, plant or power system, cost of capi-
tal, loss of power, additional expenses in the use of existing
power facilities, or claims against the purchaser or user by its cus-
tomers resulting from the use of the information and descriptions
contained herein.
1.1.2 Safety Precautions
All safety codes, standards, and/or regulations must be strictly
observed in the installation, application, operation, and mainte-
nance of this device.
WARNING
READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREIN-
AFTER BEFORE ATTEMPTING TO UNPACK, ASSEMBLE, OPERATE,
OR MAINTAIN THIS EQUIPMENT.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH
ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL
INJURY. FOLLOW PROPER INSTALLATION, OPERATION, AND MAIN-
TENANCE PROCEDURES TO AVOID THESE VOLTAGES.
THE TRANSFER SWITCH EQUIPMENT COVERED BY THIS INSTRUC-
TION BOOK IS DESIGNED AND TESTED TO OPERATE WITHIN ITS
NAMEPLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS
MAY CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH, SERI-
OUS BODILY INJURY, AND/OR PROPERTY DAMAGE. ALL RESPON-
SIBLE PERSONNEL SHOULD LOCATE THE DOOR MOUNTED
EQUIPMENT NAMEPLATE AND BE FAMILIAR WITH THE INFORMA-
TION PROVIDED ON THE NAMEPLATE. A TYPICAL EQUIPMENT
NAMEPLATE IS SHOWN IN FIGURE 1.
L050412234
Cat No: EGS100L24R ENCL TYPE: 3R
Style No: ITEM: 001
GO No: ABC0123 PIECE: 001
OF: 001
Volts: 240 Amps: 100 Hertz: 60
Poles: 2 Phase: 1 Wire: 3
30-43465
WARNING
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO-
CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONAL SAFETY
AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE
OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO
FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION.
THIS WILL HELP TO ENSURE THAT PERSONNEL ARE ALERT TO
WARNINGS, WHICH APPEAR THROUGHOUT THE DOCUMENT. IN
ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE.
CAUTION
READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOC-
UMENT BEFORE ATTEMPTING INSTALLATION, APPLICATION, OPER-
ATION, OR MAINTENANCE OF THE EQUIPMENT. IN ADDITION,
ONLY QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM
ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING
INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL-
LOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMA-
NENT EQUIPMENT DAMAGE.
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 3
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
1.2 General Information
ATSs are used to protect critical electrical loads against loss of
power. The load’s utility power source is backed up by a genera-
tor power source. An ATS is connected to both the utility and
generator power sources and supplies the load with power from
one of these two sources. In the event that power is lost from the
utility power source, the ATS transfers the load to the generator
power source. Once the utility power is restored, the load is auto-
matically transferred back to the utility power source (Figure 2).
Figure 2. Typical Load Transfer Switch (Contactor) Schematic.
An intelligence system initiates the transfer when the utility power
source fails or falls below a preset voltage. An engine start is
then initiated by the generator and the ATS transfers to the gener-
ator power source when sufficient generator voltage is available.
When the utility power source is restored, the ATS automatically
transfers back and the generator will shut down after a time delay.
In the event the utility power source fails and the generator
power source does not appear, the ATS remains connected to the
utility power source until the generator power source does appear.
Conversely, if connected to the generator power source and the
generator power source fails while the utility power source is still
unavailable, the ATS remains connected to the generator power
source.
ATSs automatically perform the transfer function, and include
three basic elements.
1. Main contacts to connect and disconnect the load to and from
the source of power.
2. Solenoids to make the transfer of the main contacts from
source to source.
3. Intelligence/supervisory circuits to constantly monitor the con-
dition of the power sources and thus provide the intelligence
necessary for the switch and related circuit operation.
1.2.1 Design Configuration
The Eaton Residential ATS is a rugged, compact design that uti-
lizes power contactors to transfer essential loads from one power
source to another (see Figure 3). The Residential ATS contains
suitable mechanical and/or electrical interlock switches to elimi-
nate the possibility of connecting the utility service to the genera-
tor output. In addition, a manual override lever is provided for the
transfer function.
Figure 3. EGS100L24R (100 A).
1.2.2 Load Shed Contacts
Two sets of contacts are available and can be used to control
large connected loads on the generator (i.e. air conditioners, hot
tubs, etc.). The contacts are rated for 250 Vac, 5 amps maxi-
mum.
1.3 Transfer Switch Catalog Number Identification
ATS equipment catalog numbers provide a significant amount of
relevant information pertaining to a specific piece of equipment.
The Catalog Number Identification Table (see Table 1) provides
the required interpretation information.
Utility
Generator
Load
WARNING
DO NOT MANUALLY TRANSFER THE SWITCH WHILE UNDER LOAD.
For more information visit: www.eaton.com IB70-8671
Instructional Booklet
Page 4 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
Table 1. ATS Catalog Numbering System
1.4 Environmental and Operational Conditions
Normally, an ATS is applied indoors in an electrical equipment
room. It can also be used for normal outdoor applications (with
standard NEMA 3R enclosure) where the equipment is subject to
falling rain, freezing temperatures, and 95% humidity (non-con-
densing). The ambient temperature range for operation is
between -20 and 70°C (-4 and 158°F).
1.5 Glossary
With respect to their use within this document and as they relate
to transfer switch and controller operation, the following terminol-
ogy is defined.
Available
A source is defined as “available” when it is within its undervolt-
age setpoint ranges for the nominal voltage setting.
Connected
Connected is defined as when the input is shorted by an external
contact or connection.
Failed or Fails
A source is defined as “failed” when it is outside of the applicable
voltage setpoint ranges for the nominal voltage and for a time
exceeding 0.5 seconds after the time delay emergency fail (TDEF)
time delays expires.
Failsafe
Failsafe is a feature that prevents disconnection from the only
available power source and also forces a transfer or re-transfer
operation to the only available power source.
Re-Transfer
Re-transfer is defined as a change of the load connection from the
Generator to the Utility.
Utility
Utility is the primary source (normal source, normal power source,
or normal).
Generator
Generator is the secondary source (generator emergency source,
emergency power source, emergency, standby, or backup
source).
Utility: Failed or Fails
Utility is defined as “failed” when it is outside of its undervoltage
setpoint ranges for the nominal voltage and frequency setting.
Generator: Failed or Fails
Generator is defined as “failed” when it is outside of its undervolt-
age/underfrequency/overfrequency (if applicable) setpoint ranges
for the nominal voltage and frequency setting for a time exceeding
0.5 seconds after the Time Delay Emergency Fail (TDEF) time
delay expires.
Transfer
Transfer is defined as a change of the load connection from the
Utility to the Generator power source.
Unconnected
Unconnected is defined as when the input is not shorted by an
external contact or connection.
100
100 = 100 A
Loadcenter
L24 - 24 Circuit
L 24
R
Enclosure Type
R = Type 3R
Eaton
Generator
Switch
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 5
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
SECTION 2: RECEIVING, HANDLING, AND
STORAGE
2.1 Receiving
Every effort is made to ensure that the ATS equipment arrives at
its destination undamaged and ready for installation. The packing
is designed to protect the internal components as well as the
enclosure. Care should be exercised, however, to protect the
equipment from impact at all times. Do not remove the protective
packaging until the equipment is at the installation site and ready
to be installed.
When the ATS equipment reaches its destination, the customer
should inspect the shipping container for any obvious signs of
rough handling and/or external damage that occurred during trans-
portation. Record any external and internal damage for reporting
to the transportation carrier and to the Eaton sales representative,
once a thorough inspection is complete. All claims should be as
specific as possible and include the Shop Order and General Order
numbers.
A shipping label affixed to the shipping container includes a vari-
ety of equipment and customer information, such as General
Order and catalog numbers. Make certain that this information
matches the other shipping paper information.
Each ATS enclosure is packaged in its own box. Do not discard
the packing material until the equipment is ready for installation.
Once the packaging is removed from the shipment, the enclosure
door can be opened. A plastic bag of documents will be found in
the enclosure. Important documents, such as wiring diagrams and
appropriate instruction leaflets are enclosed within the bag and
should be filed in a safe place.
2.2 Handling
As previously mentioned, ATS equipment is packaged in its own
box. Protect the equipment from impact at all times and do not
double stack. Once the equipment is at the installation site and
ready to be installed, the packaging material can be removed.
Refer to Section 4 of this manual for specific installation instruc-
tions.
2.3 Storage
Although well packaged, this equipment is not suitable for outdoor
storage. The equipment warranty will not be applicable if there is
evidence of outdoor storage. If the equipment is to be stored
indoors for any period of time, it should be stored with its protec-
tive packaging material in place. Protect the equipment at all
times from excessive moisture, construction dirt, corrosive condi-
tions, and other contaminants. It is strongly suggested that the
package-protected equipment be stored in a climate-controlled
environment of -20 to 70°C (-4 to 158°F), with a relative humid-
ity of 80% or less. Do not, under any circumstance, stack other
equipment on top of an ATS equipment enclosure, whether pack-
aged or not.
SECTION 3: EQUIPMENT DESCRIPTION
3.1 Introduction
The Eaton Residential ATS is assembled and tested at the factory.
It is designed to be used in conjunction with standby power distri-
bution equipment to provide an alternate source of power to criti-
cal circuits in the event that the primary power source is
interrupted.
This ATS monitors both utility and generator power sources and
automatically transfers critical load circuits between the two
sources, depending on which source is available. The utility
power source is preferred and will remain connected to the switch
if it is available.
3.2 Power Panel
The power panel is used for making load, power, and neutral con-
nections. The power contactor is mounted on a steel baseplate
(Figure 4).
Figure 4. Typical Power Panel for 100 A.
3.2.1 Main Contacts
This ATS incorporates power contactors as the main switching
device. The main contacts connect and disconnect the load to and
from the different power sources. The power contactor is
mechanically interlocked to prevent the two sets of main contacts
from being closed simultaneously.
For more information visit: www.eaton.com IB70-8671
Instructional Booklet
Page 6 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
3.3 RTC-50 Logic Panel
The RTC-50 is a microprocessor-based transfer switch logic con-
trol package. The hardware and software of the controller contain
the intelligence/supervisory circuits that constantly monitor the
condition of the power sources. It provides the intelligence neces-
sary for the operation of the ATS (Figure 5).
Figure 5. RTC-50 Logic Control Panel.
The RTC-50 controller has an operating temperature of
-20 to 70°C (-4 to 158°F).
The controller circuit board is protected by an insulating conformal
coating.
The specifications, under normal operating conditions, are as fol-
lows:
Tolerance for voltage sensing function: ±1% of full scale
3.4 EGS ATS Features
A variety of standard and optional features are available for Eaton
ATSs. All features or combinations of features may not be avail-
able on specific ATSs. All features and/or accessories are Under-
writers Laboratories (UL) listed unless noted.
3.4.1 Standard Features
The following is a list of the standard features for the RTC-50
Controlled ATS.
1. Time Delay Normal to Emergency (TDNE)
This feature provides a time delay when transferring from the
Utility to the Generator power source. Timing begins when
the Generator becomes available. It permits controlled trans-
fer of the load circuit to the Generator.
Jumper selectable at 20 seconds or 50 seconds. Default is
20 seconds.
3. Time Delay Emergency to Normal (TDEN)
This feature provides a time delay of the re-transfer opera-
tion to permit stabilization of Utility. Timing begins when the
Utility becomes available. If the Generator fails during tim-
ing, then re-transfer is delayed for up to 6 seconds to allow
the generator to recover.
Fixed at 10 Seconds.
5. Generator Monitoring and Protection
This feature provides monitoring and protection based on the
Generator voltage setpoints. All feature functions are Fail-
safe operations.
5J. All Phase Undervoltage Protection
Undervoltage:
Dropout: 70% of nominal
Pickup: 80% of nominal
12. Power Source Annunciation
This feature provides LEDs to give power source availability
indications.
Switch Position
Provides LEDs to indicate the switch position
Power Source Availability
Provides LEDs to indicate if a power source is available.
LEDs may be integral or separate from the controller.
12G. Utility - Available
This feature provides a green LED that, when lit, indicates
the Utility is available.
12H. Generator - Available
This feature provides an red LED that, when lit, indicates
the generator is available.
15M. Load Shed
Two sets of contacts are available and can be used to con-
trol large connected loads on the generator (i.e. air condi-
tioners, hot tubs, etc.). The contacts are rated for 250 Vac,
5 amps.
26. Utility - Monitoring and Protection
This feature provides Utility monitoring and protection func-
tions. If the Utility power supply fails, then the RTC-50 will
begin the sequence of operations necessary to transfer the
load circuit to the Generator power supply. All Feature 26
monitoring and protection functions are Failsafe operations.
26P. All Phase Undervoltage Protection
Undervoltage:
Dropout: 70% of nominal
Pickup: 80% of nominal
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 7
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
3.5 Standards
Eaton ATS equipment is listed for application by UL. In addition,
Eaton ATSs are listed in File E316586 by Underwriters Laborato-
ries, Inc. under Standard UL 1008 and UL 67. This standard cov-
ers the requirements for ATSs intended for use in ordinary
locations to provide lighting and power as follows:
a. In standby systems, in accordance with article 702 of the
National Electrical Code.
Eaton ATSs are available to meet NFPA 110 for standby power
systems.
Eaton ATS equipment are listed for application by CSA. In addi-
tion, Eaton ATSs are listed in the Legacy File LR96245 Master
Contract 163545 by Canadian Standards Association under Stan-
dard 22.2 #178-1978
SECTION 4: INSTALLATION AND WIRING
4.1 General
Eaton ATSs are factory wired and tested. Installation requires sol-
idly mounting the enclosed unit and connecting the power cables
and the auxiliary sensing circuits. Physical mounting procedures
and power cable connections are covered in this section.
Once a transfer switch is properly installed and wired, it should be
mechanically and electrically checked for proper installation and
operation. The procedures for these initial mechanical and electri-
cal checks are outlined in Section 5 of this manual.
4.2 Mounting Location
Choose a location that offers a flat, rigid mounting surface capa-
ble of supporting the weight of the enclosed ATS equipment (see
Figure 6). Protect the transfer switch at all times against exces-
sive moisture, dust, dirt, lint, and corrosive vapors.
Figure 6. Dimensions and Plan View of a Standard EGS (in.) (100 A) Type 3R Enclosure.
WARNING
BE CERTAIN THAT THE DEADFRONT IS PROPERLY INSTALLED
BEFORE THE TRANSFER SWITCH EQUIPMENT IS PUT INTO SER-
VICE. THE DEADFRONT PROVIDES PROTECTION FROM DANGER-
OUS VOLTAGES AT THE LINE AND LOAD TERMINALS WHEN THE
EQUIPMENT IS IN OPERATION. FAILURE TO DO SO COULD RESULT
IN PERSONAL INJURY OR DEATH.
14.462
5.321
7.154
2.633
19.005
5.198
3.154
2.496
8.000
14.462
14.308
5.321
29.332
Instructional Booklet
Page 8 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
For more information visit: www.eaton.com IB70-8671
Check to ensure there are no pipes, wires, or other mounting haz-
ards in the immediate mounting area that could create a problem.
Carefully remove all packing material from the ATS enclosure at
the installation site. Even though an equipment inspection was
performed when the equipment was received, make another care-
ful inspection of the enclosure and the ATS mechanism as the
packing material is removed and the enclosure readied for mount-
ing. Be especially alert for distorted metal, loose wires, or dam-
aged components.
4.3 Mounting Procedure
With the enclosed ATS equipment unpacked and ready for mount-
ing, proceed with the following steps.
For Type 3R:
Step 1: Depress the padlockable catch at the bottom of the door
and slide the door downward (see Figure 7). Open the
door and remove the deadfront.
Figure 7. Location of the Door Latch.
Step 2: Utilize the 5-point hanging system to mount..
Step 3: Mount the switch to a rigid structure as close to the elec-
trical loads as possible.
4.4 Power Cable Connection
Test all power cables prior to connection to the unit to ensure that
the conductors or cable insulation has not been damaged while
being pulled into position.
Power cables are to be connected to solderless, screw type lugs
located on the automatic transfer switching devices. Verify that
the lugs supplied will accommodate the power cables being used.
Also verify that the cables comply with all local electrical codes.
Standard ATS equipment, as supplied from the factory, will
accommodate the wire sizes shown in Table 2.
Table 2. Wire Sizes for ATSs.
Carefully strip the insulation from the power cables to avoid nick-
ing or ringing of the conductor strands. Prepare the stripped con-
ductor termination end by cleaning it with a wire brush. If
aluminum conductors are used, apply an appropriate joint com-
pound to the clean conductor surface area.
Note:Tighten the cable lugs to the torque identified on the label affixed to
the unit.
Step 1: Connect cables as follows (see Figure 8 and Table 2):
The utility power cables to the utility lugs;
The generator power cables to the generator lugs;
The customer load cables to the distribution panel;
The neutral cables to the neutral bar; and
The ground wires to the ground bar.
CAUTION
EXTREME CARE SHOULD BE TAKEN TO PROTECT THE ATS FROM
DRILL CHIPS, FILINGS, AND OTHER CONTAMINANTS WHEN MAK-
ING THE CABLE ENTRY HOLES AND MOUNTING THE ENCLOSURE
TO PREVENT COMPONENT DAMAGE OR A FUTURE MALFUNCTION.
NOTICE
THE INSTALLATION MUST FULLY COMPLY WITH ALL APPLICABLE
CODES, STANDARDS, AND REGULATIONS.
NOTICE
FOR CONTROL WIRING (GENERATOR ENGINE START WIRING), THE
WIRES MUST BE ISOLATED FROM BOTH THE UTILITY AND GENERA-
TOR POWER SOURCE CABLES.
WARNING
POWER CONDUCTORS MAY HAVE VOLTAGE PRESENT THAT CAN
CAUSE SEVERE PERSONAL INJURY OR DEATH. DE-ENERGIZE ALL
POWER OR CONTROL CIRCUIT CONDUCTORS TO BE CONNECTED
TO THE ATS EQUIPMENT BEFORE BEGINNING TO WORK WITH THE
CONDUCTORS AND/OR TERMINATING THEM TO THE EQUIPMENT
CAUTION
TO HELP PREVENT COMPONENT DAMAGE OR FUTURE MALFUNC-
TIONS, USE EXTREME CARE TO KEEP CONTAMINANTS OUT OF
THE ATS EQUIPMENT WHEN MAKING THE POWER CABLE CONNEC-
TIONS.
TRANSFER SWITCH
AMP RATING
CONTACTOR WIRE
SIZE RANGE
NUMBER OF CABLES
PER PHASE
100 #14 –2/0 1
CAUTION
IMPROPER POWER CABLE CONNECTIONS CAN CAUSE EXCESSIVE
HEAT AND SUBSEQUENT EQUIPMENT FAILURE.
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 9
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
.
Figure 8. Cable Connection Locations (100 A).
Step 2: The generator utility sensing connections are located on
the fuse block that is installed at the bottom of the power
panel. The utility sensing wires, required for proper gener-
ator operation, are connected at this point. See Section
4.7 for more detailed information on connecting the gen-
erator utility sensing wires.
Figure 9. Generator Utility Sensing Wires Connection.
Step 3: Tighten all cables and wiring to specifications.
GEN LUGS
UTILITY
LUGS
GENERATOR
LOAD LUGS
UTILITY LUGS
LUGS
UTILITY SENSING WIRE CONNECTION
UTILITY
LUGS
LOAD
LUGS
GENERATOR
LUGS
GROUND
NEUTRAL
For more information visit: www.eaton.com IB70-8671
Instructional Booklet
Page 10 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
4.5 Wiring
4.6 Installation
In a typical installation for critical loads (see Figure 10), the ATS
(1) and the generator (2) are connected to the power supply. The
ATS and emergency distribution panel (1) receive utility power
from a dedicated breaker in the utility service panel (3). The ATS
and emergency panel receive generator power from the generator
(2). Power from the utility feeds the utility panel.
Figure 10. Typical Installation of a Residential ATS.
The ATS (1) and generator (2) are connected to the power supply.
The automatic transfer switch is located between the generator
and the utility panel (3).
When the utility power fails, the ATS will sense the failure, the
generator will start, and when sufficient generator voltage is avail-
able, the ATS will switch all loads to the emergency panel. All
emergency loads will receive power from the generator. A line
breaker is required between the generator power source and the
transfer switch (see Figure 11). When utility power returns, the
ATS will switch all power back to the utility panel and the genera-
tor will shut down.
Figure 11. Diagram of a Typical Installation (Critical Loads Only).
4.7 Generator Utility Sensing Connection
The generator utility sensing connections are located on the fuse
block that is installed at the bottom of the power panel. The utility
sensing wires, required for proper generator operation, are con-
nected at this point.
Note: Prior to making the generator utility sensing connection to the ATS,
set the generator control selector switch to the OFF position to prevent an
unwanted generator start. Control wiring, such as the generator utility
sensing wires, must be run separately from the power cables.
Use the proper wire size as listed by the generator set (Genset)
manufacturer.
This ATS is intended for use on generators with built in auto start
features. These generators sense, and react to, utility power.
Remote starting contacts are not provided in this transfer switch.
WARNING
POWER CONDUCTORS AND CONTROL WIRING MAY HAVE VOLT-
AGE PRESENT THAT CAN CAUSE SEVERE PERSONAL INJURY OR
DEATH. DE-ENERGIZE ALL POWER OR CONTROL CIRCUIT CONDUC-
TORS BEFORE BEGINNING TO PERFORM ANY WIRING ACTIVITY TO
OR WITHIN THE ATS EQUIPMENT.
CAUTION
CHECK THE ATS EQUIPMENT NAMEPLATE FOR RATED VOLTAGE.
IT SHOULD BE THE SAME AS THE UTILITY AND GENERATOR LINE
VOLTAGES. OPERATING THE EQUIPMENT ON IMPROPER VOLTAGE
CAN CAUSE EQUIPMENT DAMAGE.
Generator
(Source 2)
Circuit Breaker
(typically included
in Genset)
EDitibtiPl
Critical
Loads
Utility
(Source 1)
Watt-Hour
Meter
Non-Critical
Loads
Utility Panel
Transfer
Switch
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 11
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
4.8 Preliminary Checks
After the ATS enclosure is installed and power cables are con-
nected to the equipment, thoroughly inspect the unit to ensure
that no tools were left inside and that the cabinet is free of debris.
If necessary, use a vacuum cleaner to remove any and all con-
struction or installation debris from the equipment.
Read and understand all labels on the equipment. Review and
understand the wiring diagrams supplied with the equipment.
Note any optional accessories that may have been furnished with
this unit and review their operation.
Verify that the phase-to-phase line voltages of both the utility and
generator power sources are the same and that they match the
rated voltage as indicated on the ATS ratings label.
4.9 Protection
For Catalog # EGS100L24R only
When protected by one of the following circuit breakers rated not
more than 150 amperes, this transfer switch is rated for use on a
circuit capable of delivering not more than 25,000 RMS symmetri-
cal amperes, 240 volts maximum, but not more than the interrupt-
ing capacity of the selected circuit breaker.
Eaton/Cutler-Hammer
BR CH FDC CSR CSH
BW BWH
Siemens
CED6 ED6 ED4 HED6 HED4
When protected by circuit breakers without adjustable short-time
response only or by fuses this transfer switch is rated for use on a
curcuit capable of delivering not more than 10,000 RMS symmet-
rical amperes at 240V AC.
MANUFACTURER-ANY
BREAKER-ANY
TYPE-ANY
AMPS MAX-PER NEC
SECTION 5: FUNCTIONAL TESTING
5.1 Preliminary Checks
Step 1: Check all loads connected to the ATS to ensure that they
are ready to be energized.
5.2 Energize the Switch
Step 1: Close the upstream utility power source breaker or
switch to connect the ATS to the utility power source
voltage.
Step 2: Using a voltmeter, measure the line-to-line and the line-
to-neutral voltages across the utility line terminals to
ensure the utility voltage is correct.
Step 3: If the voltage is acceptable, the solenoid will engage and
the contactor will automatically switch to the UTILITY
position.
Step 4: Position the generator control selector switch, located on
the standby generator, to the AUTOSTART position. (It
may also be labeled REMOTE START or AUTO.)
5.3 Operational Checks
Step 1: Open the upstream utility breaker originally closed in
Step 1 of Section 5.2.
Step 2: After a time delay (based on the generator settings), the
standby generator engine will start.
Step 3: Using a voltmeter, measure the line-to-line and line-to-
neutral voltages across the generator line terminals to
ensure that the generator emergency voltage is correct.
If necessary, make adjustments to the voltage regulator
on the generator according to the manufacturer’s recom-
mendations to correct any voltage deviations. The ATS
will only respond to the correct voltage from the genera-
tor power source.
Step 4: Close the upstream generator power source breaker or
switch to connect the ATS to the generator power supply
source.
CAUTION
SEVERE EQUIPMENT DAMAGE CAN RESULT IF THE UNIT IS NOT
APPLIED AT PROPER VOLTAGE. DO NOT ENERGIZE THE EQUIP-
MENT IF THE SUPPLY VOLTAGES DO NOT MATCH EQUIPMENT
RATINGS LABEL.
WARNING
YOU ARE READY TO ENERGIZE THE EQUIPMENT. VOLTAGES
WITHIN THE ENCLOSURE ARE CAPABLE OF CAUSING SEVERE PER-
SONAL INJURY OR DEATH. USE EXTREME CAUTION TO AVOID
CONTACT WITH ENERGIZED EQUIPMENT.
WARNING
CONTACT WITH ENERGIZED COMPONENTS WILL CAUSE ELECTRI-
CAL SHOCK CAPABLE OF PRODUCING SEVERE PERSONAL INJURY
OR DEATH. USE EXTREME CAUTION TO AVOID CONTACT WITH
ENERGIZED COMPONENTS WHEN USING A METER FOR VOLTAGE
CHECKS.
NOTICE
THIS WILL SIMULATE AN INTERRUPTION OF THE UTILITY POWER
SOURCE.
For more information visit: www.eaton.com IB70-8671
Instructional Booklet
Page 12 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
Step 5: The ATS Time Delay Normal (Utility) to Emergency (Gen-
erator) (TDNE) will begin to time after the generator
engine begins to run. After time out, the solenoid will
engage and the contactor will automatically switch from
the UTILITY to the GENERATOR position.
Step 6: Close the utility breaker described in Step 1 of
Section 5.2.
Step 7: The ATS Time Delay Emergency (Generator) to Normal
(Utility) (TDEN) timer will begin timing, and the solenoid
will engage and automatically switch from the GENERA-
TOR to the UTILITY position and the generator will shut
down after a cool down period.
SECTION 6: ADJUSTMENTS
6.1 General
Refer to IB00405004E-70-8664, supplied with the ATS for
RTC-50 controller adjustments and functions.
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 13
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
SECTION 7: MAINTENANCE AND
COMPONENT REPLACEMENT
7.1 Introduction
In general, ATS equipment is designed to be relatively mainte-
nance free under normal usage. However, because of the variabil-
ity of application conditions and the importance placed on
dependable operation by this type of equipment, inspection and
maintenance checks should be made on a regularly scheduled
basis. Since equipment maintenance will consist mainly of keep-
ing the equipment clean, the frequency of maintenance will
depend, to a large extent, on the cleanliness of its surroundings.
If a significant amount of dust or foreign matter is present, a more
frequent maintenance schedule should be followed.
It is suggested that visual inspections of the equipment be made
on a regular basis, not just during regularly scheduled periods.
Always be alert for an accumulation of dirt in and around the
structure, loose parts and/or hardware, cracks and/or discolora-
tion to insulation, and damaged or discolored components.
Figure 12 is the wiring diagram for the EGS 100 Amp ATS switch.
Note:Only qualified and experienced personnel should attempt any diag-
nostic work using this diagram.
Figure 12. Wiring Diagram for the EGS100L24R ATS (Shown Deenergized).
WARNING
HIGH VOLTAGES ARE PRESENT IN AND AROUND TRANSFER
SWITCH EQUIPMENT. BEFORE INSPECTING OR MAINTAINING THIS
EQUIPMENT, DISCONNECT THE LINE POWER FROM THE EQUIP-
MENT BEING SERVICED BY OPENING AND LOCKING OUT, IF POSSI-
BLE, THE NEXT HIGHEST DISCONNECT DEVICE. FAILURE TO
FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL
INJURY AND/OR DEATH.
Instructional Booklet
Page 14 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
For more information visit: www.eaton.com IB70-8671
7.2 Procedures
A suggested maintenance procedure to be followed is outlined in Table 3.
Table 3. Recommended Periodic Maintenance Procedures.
STEP ACTION
a. Make the transfer switch equipment safe for inspection and/or maintenance. Disconnect the line power from the equipment being serviced by opening next highest disconnect
device. Make certain that any accessory control power is switched off.
b. Inspect the structure area for safety hazards or potential maintenance problems. Inspect the area, especially where the contactor is installed, for any safety hazards, including per-
sonal safety and fire hazards. Exposure to certain chemical vapors can cause deterioration of the
electrical connections.
Inspect for accumulated dirt, loose hardware, or physical damage.
Examine the primary insulation for evidence of cracking or overheating. Overheating will show as
discoloration, melting, or blistering of the conductor insulation, or as pitting or melting of the con-
ductor surfaces due to arcing.
Inspect the secondary control connections for damage, and control wiring for insulation integrity.
c. Inspect the contactor for dust, dirt, soot, grease, moisture, or corrosion. Remove dust, dirt, soot, grease, moisture, and corrosion contamination from the surface of the
switching device using a dry, soft lint-free cloth, dry soft bristle brush, and vacuum cleaner. Do
not blow debris into the contactor. If contamination is found, look for the source and fix the prob-
lem.
d. Check for material integrity, uneven wear, discoloration, or loose hardware. Severe material cracking will require replacement and loose hardware will need to be tightened.
e. Check the terminals and connectors for looseness or signs of overheating. Overheating will show as discoloration, melting, or blistering of the conductor insulation.
Connections that do not have signs of looseness or overheating should not be disturbed.
f. Exercise the contactor if it is not often exercised while in operation. This will permit the wiping
action by the contacts.
If a switching device is used for frequent switching during normal operation, this step can be disre-
garded.
g. Return the transfer switch equipment to service. Make certain all barriers are in place and the door is closed. Re-apply generator and utility power.
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 15
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
7.3 Maintenance Log
DATE ACTION
Example: 01/01/04 Inspected and cleaned.
Instructional Booklet
Page 16 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
For more information visit: www.eaton.com IB70-8671
7.4 Component Replacement
Certain components within the ATS are field replaceable. Table 4 lists the part numbers to use when ordering replacement components.
To order replacement components, contact an authorized Eaton sales representative.
Table 4. Field Replaceable Components.
7.4.1 Component Replacement Instructions
7.4.1.1 100 Ampere RTC-50 Controller
Figure 13. Controller Board Installed in a EGS ATS.
COMPONENT PART NUMBER ATS MODEL
Contactor 99-5638 100 A
RTC-50 Controller RTC50 100 A
Harness EGS 99-5638-3 100 A
Service Entrance Breaker 99-5638-4 100 A
Ground Bar 99-5638-15 100 A
Lugs 99-5638-6 100 A
Neutral Bar 99-5638-17 100 A
SurgTel DHW4PT 100 A
SurgCable DCXCAB2 100 A
TVSS 99-5638-10 100 A
WARNING
HIGH VOLTAGES ARE PRESENT IN AND AROUND TRANSFER
SWITCH EQUIPMENT. BEFORE ATTEMPTING TO REPLACE ANY
COMPONENT, DISCONNECT THE LINE POWER FROM THE EQUIP-
MENT BEING SERVICED BY OPENING AND LOCKING OUT, IF POSSI-
BLE, THE NEXT HIGHEST DISCONNECT DEVICE. FAILURE TO
FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL
INJURY AND/OR DEATH.
ALWAYS TURN THE UTILITY (SOURCE 1) POWER OFF AND TURN
THE GENERATOR (SOURCE 2) CONTROL SELECTOR SWITCH TO
THE “OFF” POSITION BEFORE ATTEMPTING TO REPLACE ANY COM-
PONENTS.
NOTICE
APPLY UTILITY (SOURCE 1) POWER AND PLACE THE GENERATOR
CONTROL SELECTOR SWITCH IN THE “AUTO” POSITION AFTER THE
COMPONENT HAS BEEN REPLACED. TEST THE SYSTEM FOR
PROPER FUNCTIONALITY.
RTC-50
Controller
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 17
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
Step 1:Turn the Generator Start select to “OFF” before attempt-
ing to replace the RTC-50 Controller. Ensure all sources of
power are removed.
Step 2: Disconnect the J1, J2, J3, J4, and J6 plugs from the con-
troller (see Figure 14).
Step 3: Disconnect the wires connected to J7 and J8.
Step 4: Remove the four (4) screws located at the corners of the
controller that secure it to the power panel. Remove the
controller (see Figure 14).
Figure 14. Removing the Controller Board
.
Step 5: Align the new controller with the mounting holes. Secure
the new controller board using the existing hardware.
Tighten the screws.
Step 6: Connect the J1, J2, J3, J4, and J6 plugs to their original
receptacles.
Step 7: Reconnect the wires to J7 and J8.
Step 8: Reapply power to the transfer switch.
Step 9: Place the generator control selector switch in the “AUTO”
position after the controller has been replaced. (The Gen-
erator may start but will shut down with in 5 minutes.)
Test the system for proper functionality.
7.4.1.2 100 A Neutral Bar
Figure 15. 100 A Neutral Bar.
Step 1: Turn the utility (Source 1) power off and turn the genera-
tor (Source 2) control selector switch to the “OFF” posi-
tion before attempting to replace the neutral bar.
Step 2: Disconnect all wire cables from the neutral bar.
Step 3: Remove the two screws in the black base using a blade
screwdriver or 0.375 in. socket or nut driver. Remove the
strap with a common straight blade screw driver and then
remove the neutral bar.
Figure 16. Replacing the 100 A Neutral Bar.
Step 4: Mount the neutral bar to the base plate using the hard-
ware supplied.
Step 5: Reattach the strap to the new neutral bar.
Step 6: Reconnect all wire cables to the neutral bar.
Step 7: Apply utility (Source 1) power and place the generator
control selector switch in the “AUTO” position after the
neutral bar has been replaced. Test the system for
proper functionality.
CONNECTORS
MOUNTING
SCREWS
J1-J4
J6
J7
J8
NEUTRAL BARS
SCREWS
Instructional Booklet
Page 18 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
For more information visit: www.eaton.com IB70-8671
7.4.1.3 Ground Bar
Figure 17. Replacing the Ground Bar.
Step 1: Turn the utility (Source 1) power off and turn the genera-
tor (Source 2) control selector switch to the “OFF” posi-
tion before attempting to replace the ground bar
Step 2: Disconnect all wire cables from the ground bar.
Step 3: Remove the screws securing the ground bar using a blade
screwdriver or 0.375 in. socket or nut driver (see
Figure 17). Remove the ground bar.
Step 4: Secure the new ground bar to the base plate using the
hardware supplied.
Step 5: Reconnect all wire cables to the ground bar.
Step 6: Apply utility (Source 1) power and place the generator
control selector switch in the “AUTO” position after the
ground bar has been replaced. Test the system for proper
functionality.
7.4.1.4. Replacing the Contactor
Figure 18. Replacing the Contactor.
Step 1: Turn the utility (Source 1) power off and turn the genera-
tor (Source 2) control selector switch to the “OFF” posi-
tion before attempting to replace the contactor.
Step 2: Note their location then disconnect the twelve (12) red
wires from the contactor (see Figure 18).
Note: All wires connected to the contactor are labeled to ease
identification.
Step 3: Remove the four (4) screws securing the contactor to the
base plate using a blade screwdriver or 0.25 in. socket or
nut driver. Remove the contactor.
Step 4: Following the replacement steps for the 100 A lugs (see
Sections 7.4.1.6), remove the lugs from the old contactor
then install the lugs on the new contactor.
Step 5: Secure the contactor onto the base plate using the hard-
ware supplied.
Step 6: Reattach the twelve (12) red wires to the contactor.
Examine each wire to find the name then refer to Figure
18 for the correct connection point.
Step 7: Reconnect all wire cables to the contactor as per their
original connections.
Step 8: Apply utility (Source 1) power and place the generator
control selector switch in the “AUTO” position after the
contactor has been replaced. Test the system for proper
functionality.
MOUNTING
SCREWS
GROUND BAR
N2
N1
E2
E1
UTILITY
COIL
GENERATOR
COIL
GENERATOR AUX.
SWITCH
UTILITY AUX.
SWITCH
IB70-8671 For more information visit: www.eaton.com
Instructional Booklet
Effective: July 2008 Page 19
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
7.4.1.5 Wiring Harness
Figure 19. Wiring Harness Installed in a EGS ATS.
Step 1: Turn the utility (Source 1) power off and turn the genera-
tor (Source 2) control selector switch to the “OFF” posi-
tion before attempting to replace the wiring harness.
Step 2: Note their location then disconnect the red wires from the
contactor.
Note: All wires connected to the contactor are labeled to ease identifica-
tion.
Figure 20. Wires to Disconnect from the Contactor.
Step 3: Disconnect the J1, J2, J3, J4, J6, J7, and J8 plugs from
the controller (see Figure 14).
The wire harness is now free to be removed.
Step 4: Place the new wiring harness in the ATS.
Step 5: Connect the J1 through J8 plugs to the controller.
Step 6: Reattach the red wires to the contactor. Examine each
wire to find the name then refer to Figure 20 for the cor-
rect connection point.
Step 7: Apply utility (Source 1) power and place the generator
control selector switch in the “AUTO” position after the
wiring harness has been replaced. Test the system for
proper functionality.
7.4.1.6 Replacing the 100 A Lugs
Figure 21. Replacing the 100 A Lugs.
Step 1: Turn the utility (Source 1) power off and turn the genera-
tor (Source 2) control selector switch to the “OFF” posi-
tion before attempting to replace the lugs.
Step 2: Disconnect all wire cables from the contactor.
Step 3: Note their location then disconnect the red wires from the
contactor (see Figure 18).
Note: All wires connected to the contactor are labeled to ease
identification.
UTILITY COIL
CONNECTIONS
UTILITY
AUX
COM.
UTILITY
AUX
N.C.
GEN
AUX
N.C.
GEN
AUX
COM
GENERAL
COIL
CONNECTIONS
E1
E2
N1
N2
LOAD LUGS
GENERATOR
LUGS
UTILITY
LUGS
Instructional Booklet
Page 20 Effective: July 2008
O & M Manual for the EGS AutomaticTransfer Switch
with RTC-50 Control and Integral Loadcenter - 100 Amp
For more information visit: www.eaton.com IB70-8671
For All ATSs
Step 4: Remove the four (4) screws securing the contactor to the
base plate using a blade screwdriver or 0.25 in. socket or
nut driver.
Step 5: Remove the two (2) generator lugs and the two (2) load
lugs using a blade screwdriver (see Figure 21).
Step 6: Once the load lugs have been removed, insert a blade
screwdriver up through the circular hole in the load lug
bus and remove screws securing the two (2) generator
lugs.
Step 7: Place the new utility lugs on the utility bus so the anti-
turn protrusions fit in the holes. Once the lugs are in
place, take one (1) supplied control wire terminal and
hold it underneath the bus. Using one (1) screw and one
(1) washer supplied, tighten the control wire terminal and
lug to the utility bus. Repeat the process of the second
utility lug. Ensure that no gaps are present between the
lugs and bus.
Step 8: Place the new generator lugs on the generator bus.
Once the lugs are in place, take one (1) supplied control
wire terminal and hold it underneath the bus. Using one
(1) screw and one (1) washer supplied, tighten the con-
trol wire terminal and lug to the generator bus. Repeat
the process of the second generator lug. Ensure that no
gaps are present between the lugs and bus.
Step 9: Secure the load lugs to the load bus using the hardware
supplied.
Note: The load lugs do not require control wire terminals.
Step 10: Secure the contactor to the base plate using the four (4)
screws supplied.
Step 11: Reattach the red wires to the contactor. Examine each
wire to find the name then refer to Figure 21 for the cor-
rect connection point.
Step 12: Reconnect all cables to the contactor as per their original
connections.
Step 13: Apply utility (Source 1) power and place the generator
control selector switch in the “AUTO” position after the
lugs have been replaced. Test the system for proper
functionality.
7.5 Troubleshooting
Table 5 contains troubleshooting information for the EGS ATS. If
a problem still exists after completing the troubleshooting proce-
dures, contact an authorized Eaton sales representative.
Table 5. Troubleshooting Chart.
PROBLEM CAUSE CORRECTION
The automatic transfer switch does not transfer to the generator. 1. The generator breaker is open.
2. The generator voltage is not acceptable.
1. Reset the generator circuit breaker.
2. Refer to the generator User's Manual.
The automatic transfer switch does not transfer to the utility. 1. The service disconnect breaker is open.
2. The utility voltage is not acceptable.
1. Reset the service disconnect breaker.
2. Wait for the utility voltage to return to normal.
The generator is still running after the transfer switch transfers to the utility. Engine cool down period. The engine should stop after the cool down.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Eaton EGS100L24R Manuel utilisateur

Taper
Manuel utilisateur
Ce manuel convient également à

dans d''autres langues