DLM Skylight Photocell
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24817 – 05/21 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPS-6000
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
This unit is pre-set for Plug n’ Go™ operation, adjustment is optional.
For full operational details, adjustment and more features of the product, see the DLM
System Installation Guide provided with Wattstopper room controllers, and also available
at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and NEC
codes. Wire connections shall be rated suitable for the wire size (lead and building
wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2 power source
only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.
SPECIFICATIONS:
Footcandle range LMPS-6000 ........................24 - 6000 fc
Calibration ............... None, controlled by system software
Input voltage ...........................................................24VDC
Sensor output ......................................................1-10VDC
Peak current ...........................................4.5 mA Maximum
Slew rate ............... 1 minute full scale response time filter
Operating temperature ...... -40�F to 140�F (-40�C to 60�C)
Wire color code
Red ........................................Input Voltage +24 VDC
Black .......................... Input Return/Output Common
Yellow ...................................1-10VDC Output Signal
Housing
UV stabilized plastic with dome lens
Mounting .............................................. ½" NPT x .69" stem
Overall dimensions .............................2.55"L x 1.28"D
DESCRIPTION
The LMPS-6000 is a daylight sensor specifically designed to be used in conjunction with an LMIN-104 Digital Interface Module or
LMIO-301 DLM Photocell Input Module. The LMIN-104/LMIO-301 converts the 10 VDC signal from the photocell sensor to a digital
signal that is shared across the DLM Local Network. The signal is forwarded as a BACnet object via a DLM network bridge to the
segment network for load control via a DLM segment manager or BACnet compatible Building Automation System (BAS).
INSTALLATION
Install the sensor on the side wall of the skylight well as shown in the Wiring diagram. The sensor housing is equipped with a ½” NPT
nipple and will thread into any suitable box or fitting, or mount into a ½” knockout. This sensor is also suitable for use in atrium or
clerestory applications where high sunlight levels are common.
WIRING
Connect the sensor to the LMIN-104
or LMIO-301 as shown.
#20 AWG up to 250 feet
#18 AWG up to 1000 feet
Class 2 wiring
Common (Black)
4
57
8
9
1610
2
3
+24VDC Input Voltage (Red)
1-10VDC Output Signal (Yellow)
LMIO-301 Terminals
LMPS-6000
Skylight Photocell
Skylight
Well
Vertical
Orientation
Option
#20 AWG up to 250 feet
#18 AWG up to 1000 feet
Class 2 wiring
4
57
8
9
1610
2
3
1-10VDC Output Signal (Yellow)
LMIO-301 Terminals
LMPS-6000
Skylight Photocell
Skylight
Well
Vertical
Orientation
Option
Common (Black)
+24VDC Input Voltage (Red)
(Inputs 5, 6, 7, or 8 may be used)