DESCRIPTION
These instructions will guide the experienced installer in
converting an existing nVent RAYCHEM NGC-UIT2-HAZ
installation to an nVent RAYCHEM NGC-UIT3-EX installation.
TOOLS REQUIRED
• 5/16 in (8mm) nut driver
• 3/8 in (10mm) nut driver
KIT CONTENTS
Qty Description Manufacturer
Manufacturer
Part Number
3 Alarm Relay Sockets TE Connectivity RT78724
3
12V SPDT Alarm
Relays
TE Connectivity RTB14012F
1 NGC-UIT3-EX nVent 10332-034
12 6/32 in KEP nuts 10332-013
1
UIT2-HAZ to UIT3-EX
Adapter Plate
nVent T1213129
1
UIT2-HAZ to UIT3-EX
Gasket
nVent T1213130
4 Terminal Block Phoenix Contact 3031364
2
Grounding Terminal
Block
Phoenix Contact 3031380
2 End Cover Phoenix Contact 3030420
1
15' Shielded Twisted
Pair RS-485 wire
T0000929
Refer to the nVent RAYCHEM NGC-UIT3-EX installation manual for
full specications.
WARNING: IMPORTANT:
CERTIFICATIONS / APPROVALS
TYPE 4X, IP65 protection on front panel
FCC Part15 Subpart B/ICES 003 Class A
CE marking
Low Voltage Directive (2014/35/EU) EN 62368-1:2014 / A11:2017
EMC Directive (2014/30/EU) EN 55032:2015 EN 55035:2017
Conforms to UL 62368-1, 2nd Ed, 2014-12-01; CAN/CSA C22.2
No. 62368-1-14, 2nd Ed, Issued: 2014-12-01; UL 60950-1, 2nd Edition,
2019-05-09 ; CAN/CSA C22.2 No. 60950-1-07, 2nd Edition, 2014-10
ATEX Directive (2014/34/EU)
EN 60079-0:2017
EN 60079-11:2012
EN 60079-7: 2015 +A1:2018
IECEx
IEC 60079-0 2017
IEC 60079-11 2012
IEC 60079-7, 5.1 Ed
II 3 G Ex ic ec IIC T5 Gc
RoHS
Do not connect/disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
Ne débranchez pas l'equipement tant que l'alimentation est
coupée ou que la zone est connue pour être non dangereux.
Use appropriately classified and listed Power Supply
(Limited Power Source, or LPS). Follow all applicable
wiring codes and regulations.
Peripheral equipment must be suitable for the location
in which it is used.
There are no non-incendive circuits or non-incendive
field wiring within or associated with the unit.
Only technically qualified service personnel are
permitted to install or service the equipment.
Do not disassemble the system - no user-serviceable
parts inside.
Do not operate the equipment if it has been damaged.
Utilisez une source d'alimentation correctement classée
et répertoriée (source dénergie limitée ou LPS). Suivez
tous les codes et normes de câblage applicables.
L'équipement périphérique doit être adapté à
l'emplacement dans lequel il est utilisé.
Il n'y a pas de circuits non incendiaires ni de câbles de
terrain non incendiaires à l'intérieur ou associés avec
léquipment.
Seul le personnel qualifié est autorisé à installer ou à
entretenir l'équipement.
Ne pas démontez le système - aucune pièce interne ne
peut être réparée par l'utilisateur.
N'utilisez pas l'équipement s'il a été endommagé.
2 | nVent.com/RAYCHEM
NGC-UIT3-EX Connection Diagram
Front view
Side View
Top view
Bottom View
Back view
nVent.com/RAYCHEM | 3
Removing the NGC-UIT2-HAZ and Related Components
NGC-UIT2-HAZ mounted on panel door
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
Field
Port
3 2 1
Wh Bk G Wh Bk G
3 2 1
Remote
CRM(S)
AC Power Cord
RS-485 Cables
DIN Rail
Terminals
To other
CRM(S)
RMM2
PLI
A = Gnd
B = Data +
C = Data –
Remote
Port
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y ) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
3 2 1
ADAM 4069
Relay Output
Module
8 Outputs
9 Pin to
RS-485
Converters
RS-485-1
RS-485-(IN)
1. Prior to removing the existing UIT2-HAZ from the panel door, disconnect the AC power and remove the power cord.
Disconnect the two RS-485 cables from the unit as shown in the illustration below.
2. Remove the (12) 5/16" nut driver that secure the NGC-UIT2-HAZ to the panel door. Save the mounting hardware - it will be
needed later to secure the adapter plate to the panel.
3. Disconnect the RS-485 communications wiring from the two RS-232 to RS-485 converters, from the Adam Relay Output
module and the DIN rail terminals. Carefully tag the RS-485 wiring coming from the CRM(s) and Remote connections, as these
will need to be re-connected once the new components and NGC-UIT3-EX have been installed.
4 | nVent.com/RAYCHEM
4. Next, disconnect the 12Vdc wiring from the Adam module.
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
Field
Port
Power
Supply
Connections
To + 12 Vdc
power supply used to
power the CRM(S) boards
Remote
Port
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
+
+
ADAM 4069
Relay Output
Module
8 Outputs
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
Field
Port
Refer to panel drawings for
location of Terminal Blocks (TB)
for landing relay wiring.
To optional Alarm Lamp/Switch
mounted on Panel door.
N
TB-X
TB-X
TB-X
TB-X
TB-X
TB-X
Line
Fuse
A = Gnd
B = Data +
C = Data –
Remote
Port
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
AR
ADAM 4069
Relay Output
Module
8 Outputs
5. Disconnect any alarm relay wiring from the Adam module. Be sure to carefully label each set of wires (relay number, as well as
NO, NC, and Common signals), as these will be reconnected to the new NGC-UIT3-EX once installed.
nVent.com/RAYCHEM | 5
6. Remove components mounted to the DIN rail (Adam module, RS-232 to RS-485 converters).
7. Note that the four wiring terminals formerly used to connect the RS-485 signals should be retained since they will be re-used to
distribute the 12Vdc power to various components so they do not need to be removed. Further details are provided later in this
document.
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y ) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
ADAM 4069
Relay Output
Module
8 Outputs
Two position jumpers
8. Install the new components onto the DIN rail as shown below. Note that the specic location or orientation of the
components is not critical – choose the placement that makes wiring connections easiest to complete.
6 | nVent.com/RAYCHEM
1
2
3
4
5
6
7
8
9
10
11
12
Not to Scale
9. Install the NGC-UIT3-EX into the cutout in the adapter plate using the twelve 6-32 KepNuts supplied with the unit. Tighten
the nuts to 0.56 N-m (5 in-lbs) of torque using the 5/16 in nut driver in the sequence shown in the diagram below to
ensure proper sealing.
10. Next, install the NGC-UIT3-EX and Adapter plate combination into the existing panel opening. Ensure that the gasket
supplied with the kit is installed in between the Adapter plate and the panel opening.
11. Secure the Adapter plate using the twelve 10-32 nuts/lockwashers retained when the original NGC-UIT-HAZ was removed
in Step 2 above.
12. Tighten the nuts to 0.9 N-m (8 in-lbs) of torque using the 3/8 in nut driver in the sequence shown in the diagram below to
ensure proper sealing.
Installing the NGC-UIT3-EX and Adapter Plate into the Panel
Adapter Plate
NGC-UIT3-EX
Weld Stud
(x12)
Gasket
Heat Trace Panel
Adapter Plate
Mounting Nuts
10-32 (x12)
6-32 Nut
(x12)
nVent.com/RAYCHEM | 7
Reconnect 12Vdc Power to Components
NO
C
NC
NO
C
NC
NO
C
NC
Alarm Relays
NGC-UIT3-EX
Connect to +12Vdc power
supply used to power the
CRM(s) boards
Two position jumpers
Common (-)
Common (-)
+12Vdc
+12Vdc
1 3 42
13. Connect the 12Vdc from the power supply used to power the CRM(s) boards to the DIN rail terminals as shown below.
Be sure to connect the +12V to the rst terminal and the negative (common) to the third terminal. The jumpers installed
in between terminals 1 & 2 as well as 3 & 4 should remain in place.
14. Connect the 12Vdc from terminal 1 to each of the alarm relays as shown in the diagram below.
15. Connect 12Vdc to the male power connector located on the left side of the NGC-UIT3-EX. The “+” lead should go from
DIN terminal 2 to UIT3-EX terminal marked “9-30Vdc” and the “-“ lead should go from DIN terminal 4 to the UIT3-EX
terminal marked “GND”. Ensure that the cables are routed through the cable clamp as shown.
8 | nVent.com/RAYCHEM
18. Connect the Alarm Relay contacts to the appropriate alarm wiring that was disconnected in Step 5. Ensure that the NO,
Common, and NC signals are assigned to the correct relays.
16. Connect 12Vdc power from the “VIN” terminal on the NGC-UIT3-EX Relay Driver Output connector to DIN terminal 2 and
connect from the "GND" terminal to DIN terminal 3 as shown in the diagram below.
17. Connect the relay output terminals 1, 2, and 3 of the NGC-UIT2-EX Relay Driver Output connector to the Alarm Relays on
the DIN rail as shown.
Reconnect the Alarm Relay Wiring
NO
C
N C
NO
C
N C
NO
C
N C
Alarm Relays
TB-X
TB-X
TB-X
TB-X
TB-X
TB-X
N
Line
Refer to panel drawings for
location of Terminal Blocks
(TB) for landing relay wiring.
To optional Alarm Lamp/Switch
mounted on Panel door.
Fuse
AR
1 3 42
Open Collector
ISOGND1
RS-485
TERM
PU
PD
TERM
PU
PD
DATA2-
ISOGND2
DATA1-
DATA1+
DATA2+
GND
VIN
3
2
1
4
RESET
TX
RX
TX
RX
GND
VIN
3
2
1
4
Door Mounted
+12 Vdc
These relays are shown
in the energized position
without an alarm condition.
+ 12 Vdc
0 Vdc
GND (–)
+12 Vdc
Input
NO
C
NC
NO
C
NC
NO
C
NC
3
4
Alarm
Lamp
12 Vdc
IDEC SWITCH/
LAMP
1
2
Relay Driver Output
Alarm Relays
Jumper switch
terminals 1, 4 and x2
nVent.com/RAYCHEM | 9
Reconnect the Communications Wiring
Data +
Data -
Shield
To host
computer
Data +
Data -
To CRM/S
RMM2 or
NGC-20
Shield
19. Connect the RS-485 Field and Remote communications ports using shielded twisted pair wire included with the kit. Be
sure to connect the Field Port terminals to the RS-485-1 serial port on the NGC-UIT3-EX, and the Remote port terminals
to the RS-485-2 serial port on the NGC-UIT3-EX as shown below.
20. Reconnect the RS-485 eld wiring (to/from the CRM(s) boards, RMMs, and other devices) that was disconnected in
Step 3. Be careful to observe the polarity of the connections as well as ensuring that the shield connections are
terminated as shown.
21. Repeat Step 20 for the Remote port (Host computer) connections.
10 | nVent.com/RAYCHEM
RS-485 configuration switches
The conguration switches are found on the bottom of
the NGC-UIT3-EX. Refer to the table below for settings.
Position
Switch On Off Comments
Pull-down (As-shipped default) RS-485 network “–”
signal is forced to a determinate state
when idle.
RS-485 network “–” signal is not
forced to a determinate state
when idle.
One device (typically this NGC-UIT3-EX) on the
RS-485 network should force the network “-“ signal
to a determinate state.
Pull-up (As-shipped default) RS-485 network “+”
signal is forced to a determinate state
when idle.
RS-485 network “+” signal is not
forced to a determinate state
when idle.
One device (typically this NGC-UIT3-EX) on the
RS-485 network should force the network “+“ signal
to a determinate state.
Termination (As-shipped default) RS-485 network is
terminated with 120-ohm resistor.
RS-485 network is not termi-
nated.
Terminate the device (NGC-UIT3-EX or other) that
is at each end of the RS-485 network, for a total of
two terminated devices. No other devices on the
network should be terminated.
Reset switch
The Reset switch can be found on the bottom of the NGC-UIT3-EX.
A pointed object is required to press the reset switch and restart the
NGC-UIT software.
Reset
Reset
nVent.com/RAYCHEM | 11
nVent.com/RAYCHEM
©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specications without notice.
RAYCHEM-IM-H60578-NGCUIT2HAZtoUIT3EX-EN-2104
North America
Tel +1 800 545 6258
Fax +1 800 527 5703
Europe, Middle East, Africa
Tel +32 16 213 511
Fax +32 16 213 604
Asia Pacific
Tel +86 21 2412 1688
Fax +86 21 5426 3167
Latin America
Tel +1 713 868 4800
Fax +1 713 868 2333
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Raychem NGC UIT2-HAZ to UIT2-EX Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues