NGC UIT2-HAZ to UIT3-EX
Conversion instructions
NGC-UIT3-EX
installed in a panel
DESCRIPTION
These instructions will guide the experienced installer in
converting an existing nVent RAYCHEM NGC-UIT2-HAZ
installation to an nVent RAYCHEM NGC-UIT3-EX installation.
TOOLS REQUIRED
• 5/16 in (8mm) nut driver
• 3/8 in (10mm) nut driver
KIT CONTENTS
Qty Description Manufacturer
Manufacturer
Part Number
3 Alarm Relay Sockets TE Connectivity RT78724
3
12V SPDT Alarm
Relays
TE Connectivity RTB14012F
1 NGC-UIT3-EX nVent 10332-034
12 6/32 in KEP nuts 10332-013
1
UIT2-HAZ to UIT3-EX
Adapter Plate
nVent T1213129
1
UIT2-HAZ to UIT3-EX
Gasket
nVent T1213130
4 Terminal Block Phoenix Contact 3031364
2
Grounding Terminal
Block
Phoenix Contact 3031380
2 End Cover Phoenix Contact 3030420
1
15' Shielded Twisted
Pair RS-485 wire
T0000929
Refer to the nVent RAYCHEM NGC-UIT3-EX installation manual for
full specications.
WARNING: IMPORTANT:
CERTIFICATIONS / APPROVALS
• TYPE 4X, IP65 protection on front panel
• FCC Part15 Subpart B/ICES 003 Class A
• CE marking
Low Voltage Directive (2014/35/EU) EN 62368-1:2014 / A11:2017
EMC Directive (2014/30/EU) EN 55032:2015 EN 55035:2017
• Conforms to UL 62368-1, 2nd Ed, 2014-12-01; CAN/CSA C22.2
No. 62368-1-14, 2nd Ed, Issued: 2014-12-01; UL 60950-1, 2nd Edition,
2019-05-09 ; CAN/CSA C22.2 No. 60950-1-07, 2nd Edition, 2014-10
• ATEX Directive (2014/34/EU)
EN 60079-0:2017
EN 60079-11:2012
EN 60079-7: 2015 +A1:2018
• IECEx
IEC 60079-0 2017
IEC 60079-11 2012
IEC 60079-7, 5.1 Ed
II 3 G Ex ic ec IIC T5 Gc
RoHS
Do not connect/disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
Ne débranchez pas l'equipement tant que l'alimentation est
coupée ou que la zone est connue pour être non dangereux.
• Use appropriately classified and listed Power Supply
(Limited Power Source, or LPS). Follow all applicable
wiring codes and regulations.
• Peripheral equipment must be suitable for the location
in which it is used.
• There are no non-incendive circuits or non-incendive
field wiring within or associated with the unit.
• Only technically qualified service personnel are
permitted to install or service the equipment.
• Do not disassemble the system - no user-serviceable
parts inside.
• Do not operate the equipment if it has been damaged.
• Utilisez une source d'alimentation correctement classée
et répertoriée (source dénergie limitée ou LPS). Suivez
tous les codes et normes de câblage applicables.
• L'équipement périphérique doit être adapté à
l'emplacement dans lequel il est utilisé.
• Il n'y a pas de circuits non incendiaires ni de câbles de
terrain non incendiaires à l'intérieur ou associés avec
léquipment.
• Seul le personnel qualifié est autorisé à installer ou à
entretenir l'équipement.
• Ne pas démontez le système - aucune pièce interne ne
peut être réparée par l'utilisateur.
• N'utilisez pas l'équipement s'il a été endommagé.