KILLARK WLAL Series LED Luminaries Guide d'installation

Taper
Guide d'installation
P/N KIL00921486 FORM NO.K1486 ECO-6-063-18 R09/18
Sheet 1 of 4
HUBBELL ELECTRICAL PRODUCTS
A Division of HUBBELL
INCORPORATED (Delaware)
3940 Martin Luther King Drive
St. Louis, Missouri 63113 USA
INSTALLATION, OPERATION & MAINTENANCE DATA
SHEET
WLAL SERIES LED
LUMINAIRE
WLAL WLALFP
The WLAL is a rugged, high efficiency LED fixture suitable for use in wet locations. The WLAL has options for multiple
mounting positions. The WLALFP is an NSF version of the WLAL. The WLALFP has a smooth housing which enables its
use in food processing areas.
CAUTION: THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY
A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
CE PRODUIT DOIT ÊTRE INSTALLÉ SELON LE CODE D’INSTALLATION PERTINENT, PAR UNE PERSONNE QUI
CONNAÎT BIEN LE PRODUIT ET SON FONCTIONNEMENT AINSI QUE LES RISQUES INHÉRENTS.
Do not attempt installation until you are familiar with the following procedures. All installation must comply
with the applicable local and/or National Electrical Code and be performed by a qualified electrician.
Make sure that the circuit is de-energized before starting installation or maintenance.
Verify that luminaire is grounded. Failure to ground will create electrical shock hazards, which can cause serious
injury and or death.
ATTENTION: Ne pas tenter dentreprendre linstallation avant dêtre familiarisé avec les produres suivantes. Toute installation doit être
conforme au code électrique local et / ou national et être effectuée par un électricien qualifié.
Veiller à ce que le circuit soit mis hors tension avant de commencer l’installation ou la maintenance.
Vérifier si le luminaire est mis à la terre. S’il nest pas mis à la terre il pourrait causer des risques de choc électrique susceptibles dentraîner
des blessures graves ou la mort.
Note: Due to the surge protection provided in the fixture to protect the internal electronics and LEDs, a branch circuit
with the LED fixture may false fail a megohmmeter test (sometimes referred to as a megger test). If a megohmmeter
test is required, the LED fixture should be removed from the branch circuit.
Note: Multiple fluorescent or LED fixtures attached to a single Ground Fault Circuit Interrupter (GFCI) may cause
nuisance tripping of the GFCI. Regulatory agencies allow a small amount of leakage current because of the circuitry
required to mitigate possible issues with electromagnetic compatibility (reference UL8750 and EN61347). The
summation of these leakage currents from multiple fixtures may be enough to trip a GFCI.
P/N KIL00921486 FORM NO.K1486 ECO-6-063-18 R09/18
Sheet 2 of 4
WLAL INSTALLATION INSTRUCTIONS:
A. Channels are incorporated in the housing for 5/16” or M8 hex bolts or nuts. (See Figure 1)
1. 5/16” or M8 hex bolts can be slid into channels for direct mounting; or used to attach brackets which include
L- brackets, Wall Brackets, Ceiling Brackets, Beam Clamps, and Suspension Chains etc
2. 5/16” hex nuts or M8 hex nuts can be slid into channels and used with eyebolts, threaded rod
etcB. The End Caps also have provisions for surface or suspension mounting. (See Figure 2)
C. The Earthquake Safety Chain Tab” is incorporated into the endcap.
Figure 1 Figure 2 (Top View)
WLALFP FOOD PROCESSING INSTALLATION INSTRUCTIONS:
A. The WLALFP end caps have provisions for surface or suspension mounting. (See Figure 3)
B. The Earthquake Safety Chain Tab” is incorporated into the endcap.
Figure 3
IMPORTANT NOTE:
Turn off electricity to circuit at main fuse or at circuit breaker.
1. Connection to the black (Line), white (Neutral) and green (Ground/Earth) can be made with appropriate wire connectors
outside of the fixture, the connectors can be placed in the fixture through the hub. If the terminal blocks are going to be used,
loosen and remove the four (4) access plate screws. Remove access plate assembly to allow for entry into fixture.
2. If terminal blocks are used, discard the wires on the entry side of the terminal block. Run supply wire to fixture
through applicable hub. Make watertight joint using sealing fittings at appropriate hole. The hub in the endcap is for ¾-
14NPT (or 2 x M20 may be ordered).
3. Pull the supply wires into housing through the conduit hub and connect the appropriate leads using insulated wire
nuts or use the terminal blocks present. Fixtures with looping feature may have terminal blocks at both ends of the
fixture. See below for wiring battery backup fixtures.
4. Replace access plate screws if necessary.
5. Turn on electricity to verify fixture is operating properly.
P/N KIL00921486 FORM NO.K1486 ECO-6-063-18 R09/18
Sheet 3 of 4
Battery Backup Fixtures:
IMPORTANT: To turn the fixture completely off, an un-switched AC power source of 120VAC to 277VAC is required for the
yellow/black and white leads. If the yellow/black and white leads are attached to switched power, the fixture will go into battery
backup mode if the switch is turned off.
IMPORTANT: A switched or un-switched AC power source of 120VAC to 277VAC is acceptable for the black lead. Fixtures with
terminal blocks are shipped with a jumper between the terminals of the black and yellow/black wire. Remove the wire link
(jumper) and attach the yellow black wire to line voltage when local switching is required.
The battery must be charged for at least 12 hours prior to testing.
SELF DIAGNOSTIC INSTRUCTIONS / OPERATION: The self diagnostic feature is set from the factory. The
emergency LED driver will conduct a self check for thirty (30) minutes every thirty (30) days; and ninety (90) minutes
or one hundred eighty (180) minutes self check every 12 months. After every self check the LED indicator light will
indicate a status signal.
TABLE 1 Self Diagnostic Indications
LED Indicators Status
EM Driver Status/Mode
• Solid Green
System OK/AC OK(Self-diagnostic Enabled or Disabled).
• Slow Flashing Red, 4s on/1s off
Battery not Detected, Check Battery Switch Connection.
Flasing Red, 1s on/1s off
Battery Failure, Replace Battery.
Flashing Green, 1s on/1s off
Self-Diagnostic Test Underway.
Fast Flashing Red, 0.1s on/ 0.1s off
Abnormal Driver Performance, Replace Driver.
Very Slow Flashing Red, 4s on/4s off
Over Temperature.
None, Both LED's OFF
Normal Working EM Mode.
Green/Red Alternative Flashing, 1s Green/1s Red.
No Load or Output over Voltage Protection Triggered.
Battery Changing Procedure:
1. Remove one endcap from the main housing by removing the four screws
that hold the endcap to the housing.
2. Slide the gear tray out of the housing until the emergency driver is
exposed. Remove wires from lever nuts as necessary. To remove a wire
from a lever nut, fully push up the lever and remove the conductor.
3. Remove the two screws that hold the driver to the gear tray.
4. Remove the two screws that hold the battery compartment cover to the driver.
5. Disconnect the connector and replace the new battery.
6. Reassemble
The battery switch must be turned to the “ONposition for the fixture to operate correctly. The fixture will not light up in
battery backup mode until AC power is supplied once while the battery switch is in theONposition. Thereafter, the
fixture will operate in battery backup mode when the AC power is off.
Battery Back-Up Connection
with Terminal Block
New fixtures with batteries can be stored for 2 years in a -20°C to 30°C ambient without a need of recharge. A
fully discharged unit should not be stored more than 6 months without being recharged. There is low voltage
disconnect of the battery to the emergency drivers, however as the batteries still have self-discharge they should
be recharged within 6 months to prevent the cells from permanent capacity loss. For long term storage, turn the
battery switch to the “off” position to prevent the cells from permanent capacity loss.
P/N KIL00921486 FORM NO.K1486 ECO-6-063-18 R09/18
Sheet 4 of 4
MAINTENANCE INSTRUCTIONS:
CAUTION:
Disconnect the supplying circuit before opening fixture or removing optics. To maintain maximum light output, this fixture
should be cleaned periodically. Maintenance procedures sometimes require fixtures to be hosed down for good
housekeeping. The supply circuit must be turned OFF and the fixture lens must be allowed to cool to the ambient room
temperature before cleaning. Only mild, non-abrasive cleaning agents should be used. The force of water applied by a
hose must not exceed 65 gallons per minute coming from a 1” diameter hose applied at a distance of 10 feet. Caution:
Clean polycarbonate lenses with damp cloth only to reduce chances of static charge build up. These periodic
cleaning procedures are important to prevent the accumulation of dust and dirt which will impair the light output of the
fixture. The polycarbonate lens should be regularly inspected for scratches and chips and, if damaged, must be replaced.
HIGH VIBRATION AREAS:
Periodic inspection of fastener tightness is required; recommended every six (6) months.
Technical information, advice and recommendations contained in these documents are based on information that Killark
believes to be reliable. All the information and advice contained in these documents is intended only for use by persons
having been trained and possessing the requisite skill and know-how and to be used by such persons only at their own
discretion and risk.
The nature of these instructions is informative only and do not cover all of the details, variations or combinations in which
this equipment may be used, its storage, delivery, installation, check out, safe operation, and maintenance. Since conditions
of use of the product are outside of the care, custody and control of Killark, the purchaser should determine the suitability
of the product for its intended use, and assumes all risk and liability whatsoever in connection therewith.
REMEMBER TO SAVE ONE OF THESE SHEETS FOR MAINTENANCE PERSONNEL
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

KILLARK WLAL Series LED Luminaries Guide d'installation

Taper
Guide d'installation