Eaton GHG 521 Mode d'emploi

Taper
Mode d'emploi
Steckvorrichtungen für Industrieanwendungen
16 A, 3-polig, 4-polig, 5-polig, GHG 521
Plug and socket system for industrial use
16 A, 3-pole, 4-pole, 5-pole, GHG 521
Fiches et prises de 16 A, à 3 pôles, 4 pôles, 5 pôles,
pour utilisation industrielle, GHG 521
Betriebsanleitung
Operating instructions
Mode d’emploi
CROUSE-HINDS
SERIES
GHG 510 7001 P0003 D/GB/F (i)
2
Steckvorrichtungen für
Industrieanwendungen 16 A,
3-polig, 4-polig, 5-polig, GHG 521
Plug and socket system for
industrial use 16 A,
3-pole, 4-pole, 5-pole, GHG 521
Fiches et prises de 16 A,
à 3 pôles, 4 pôles, 5 pôles, pour
utilisation industrielle, GHG 521
Inhalt:
Inhalt ....................................................... 2
Maßbilder ...............................................15
1 Technische Angaben ............................... 3
1.1 Steckvorrichtung GHG 521. ..................... 3
2 Sicherheitshinweise ................................ 4
3 Normenkonformität............. .................... 4
4 Verwendungsbereich .............................. 4
5 Verwendung/ Eigenschaften ................... 4
6 Installation.......................... ..................... 5
6.1 Montage............................. ..................... 5
6.2 Öffnen des Gerätes/
Elektrischer Anschluss ............................ 5
6.3 Kabel- und Leitungseinführung;
Verschlussstopfen............................... .... 6
6.4 Schließen des Gerätes........ .................... 6
6.5 Inbetriebnahme.................. ..................... 6
7 Instandhaltung / Wartung ........................ 6
8 Reparatur / Instandsetzung /
Änderungen ............................................ 6
9 Entsorgung / Wiederverwertung ............. 6
Konformitätserklärung separat beigelegt.
Contents:
Contents ................................................. 2
Dimensional drawings ............................15
1 Technical data .......................................... 7
1.1 Plug and socket GHG 521 ....................... 7
2 Safety instructions .................................. 8
3 Conformity with standards ...................... 8
4 Field of application .................................. 8
5 Application/Properties ............................. 8
6 Installation ............................................... 9
6.1 Mounting ................................................. 9
6.2 Opening the device /
Electrical connection ............................... 9
6.3 Cable entry (KLE); blanking plug ............10
6.4 Closing the device ..................................10
6.5 Taking into operation ..............................10
7 Maintenance/Servicing...........................10
8 Repairs/Modifications ............................10
9 Disposal / Recycling ...............................10
Declaration of conformity, enclosed separately.
Contenu:
Contenu .................................................. 2
Plans cotés .............................................15
1 Caractéristiques techniques ..................11
1.1 Fiche et prise GHG 521 ..........................11
2 Consignes de sécurité ...........................12
3 Conformité avec les normes ..................12
4 Domaine d’utilisation .............................12
5 Utilisation/Propriétés ..............................12
6 Installation ..............................................13
6.1 Montage .................................................13
6.2 Ouverture de l’appareil/
Raccordement électrique .......................13
6.3 Entrées de câble (KLE)
bouchons de fermeture .........................14
6.4 Fermeture de l’appareil/
Fermeture du couvercle .........................14
6.5 Mise en service ......................................14
7 Maintien/Entretien .................................14
8 Réparation / Remise en état /
Modifications .........................................14
9 Évacuation des déchets / Recyclage ......14
Déclaration de conformité, jointe séparément.
3
1 Technische Angaben
1.1 Steckvorrichtung GHG 521
Bemessungsspannung U
N
:
2-polig + PE bis 500 V, 50/60 Hz
3-polig + PE bis 690 V, 50/60 Hz
3-polig + N + PE bis 690 V, 50/60 Hz
Max. Bemessungsstrom: 16 A
Max. Vorsicherung:
ohne therm. Schutz 16 A
mit therm. Schutz 35 A gG
Schaltvermögen: AC 3
Wandsteckdose 2-polig + PE schaltbar mit Stecker: 250 V/16 A
Schaltvermögen: AC 23 AC 22
Wandsteckdose 3-polig + PE mit Stecker: 500 V / 20 A 500 V / 25 A
690 V / 11 A 690 V / 25 A
Zulässige Umgebungstemperatur: -20° C bis +40° C (Listenausführung)
(Abweichende Temperaturen sind bei Sonderversionen möglich)
Zul. Lagertemperatur in Originalverpackung: -20° C bis +40° C
Schutzart bei geschlossenem und gesichertem
Klappdeckel sowie ordnungsgemäß gesteckten
Exponaten nach EN/IEC 60529
IP 66 (Listenausführung)
Schutzklasse nach EN/IEC 61140 I - wird von den Geräten erfüllt
Leitungseinführung: (Listenausführung)
Wandsteckdose mit Schalter 1 x M25 + 1 x Verschlussstopfen
Wandsteckdose mit Schalter 4 x Bohrung M25 (2 x oben, 2 x unten)
Geeignete Leitungen und Prüfdrehmomente
der Druckschraube
Ø (mm) Nm
Dichtung 1+2+3
1 2
3
min.
max.
(1)
8,0
10,0
1,5
2,0
Dichtung 1+2
1 2
3
min.
max.
(1)
10,0
13,0
2,3
2,6
Dichtung 1
1 2
3
min.
max.
(1)
13,5
1 7, 5
1,3
2,3
Prüfdrehmomente Einschraubgewinde 3,0 Nm
(1)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann
der Klemmbereich variieren. Bitte verwenden Sie im Zwischenbereich eine geeignete Kombination aus
Dichtungen, so dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
Stecker / Kupplung 2-polig+PE Ø 8 - 18 mm
Stecker / Kupplung 3-polig+PE Ø 8 - 21 mm
Stecker / Kupplung 3-polig+N+PE Ø 12 - 21 mm
Anschlussklemme Querschnitt Abisolierlänge
der Adern
Wandsteckdose mit Schalter 2 x 0,75 - 6 mm² 6 mm
Wandsteckdose ohne Schalter 2 x 1,50 - 6 mm² 10 mm
Flanschsteckdose 2 x 1,50 - 6 mm² 10 mm
Kupplung 2 x 1,50 - 6 mm² 10 mm
Steckeranschluss 2 x 1,50 - 6 mm² 10 mm
Prüfdrehmomente:
Deckelschrauben 2,5 Nm
Anschlussklemmen Wandsteckdose
Flanschsteckdose
Gerätestecker
Kupplung
2,5 Nm
2,5 Nm
2,5 Nm
2,5 Nm
Anschlussklemmen Stecker 1,5 Nm
Selbstschneidende Schrauben Größe 4 2,0 Nm
Selbstschneidende Schrauben Größe 5 3,0 Nm
Anschlussschrauben des Schalters 0,8 Nm
Gewicht: (Listenausführung)
Wandsteckdose ohne Schalter 2-polig+PE GHG 521 23 ca. 0,80 kg
Wandsteckdose schaltbar 2-polig+PE GHG 521 43 ca. 1,10 kg
Stecker 2-polig+PE GHG 521 73 ca. 0,32 kg
Flanschsteckdose 2-polig+PE GHG 521 83 ca. 0,37 kg
Gerätestecker 2-polig+PE GHG 521 93 ca. 0,26 kg
Kupplung 2-polig+PE GHG 521 33 ca. 0,48 kg
Wandsteckdose ohne Schalter 3-polig+PE GHG 521 24 ca. 0,85 kg
Wandsteckdose mit Schalter 3-polig+PE GHG 521 44 ca. 1,60 kg
Stecker 3-polig+PE GHG 521 74 ca. 0,39 kg
Flanschsteckdose 3-polig+PE GHG 521 84 ca. 0,42 kg
Gerätestecker 3-polig+PE GHG 521 94 ca. 0,31 kg
Kupplung 3-polig+PE GHG 521 34 ca. 0,54 kg
Wandsteckdose ohne Schalter 3-polig+N+PE GHG 521 25 ca. 0,90 kg
Stecker 3-polig+N+PE GHG 521 75 ca. 0,42 kg
Flanschsteckdose 3-polig+N+PE GHG 521 85 ca. 0,47 kg
Kupplung 3-polig+N+PE GHG 521 35 ca. 0,55 kg
Steckvorrichtungen für Industrieanwendungen 16 A,
3-polig, 4-polig, 5-polig, GHG 521
D
4
2 Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und geeignet
qualifizierte, unterwiesene Personen
gemäß den nationalen Rechtsvorschriften,
einschließlich der einschlägigen Normen für
elektrische Geräte.
Die Steckvorrichtungen GHG 521 sind nicht
für explosionsgefährdete Bereiche geeignet.
Sie sind bestimmungsgemäß in unbeschä-
digtem und einwandfreiem Zustand zu
betreiben.
Vor Inbetriebnahme müssen die Steckvor-
richtungen entsprechend der im Abschnitt 6
genannten Anweisung geprüft werden. Die
Steckvorrichtungen nur mit unbeschädigten
Steckern betreiben.
Beachten Sie die nationalen Sicherheits- und
Unfallverhütungsvorschriften und die
nachfolgenden Sicherheitshinweise in dieser
Betriebsanleitung, die wie dieser Text in
Kursivschrift gefasst sind!
3 Normenkonformität
Das Betriebsmittel entspricht den aufgeführten
Normen, in der separat beigelegten Konformi-
tätserklärung.
Verweise auf Normen und Richtlinien in dieser
Betriebsanleitung beziehen sich immer auf die
aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4 Verwendungsbereich
Die Steckvorrichtungen GHG 521 sind zum
Einsatz in Industriebereichen gemäß
EN/IEC 60309 geeignet!
Die eingesetzten Gehäusematerialien ein-
schließlich der außenliegenden Metallteile
bestehen aus hochwertigen Werkstoffen,
die einen anwendungsgerechten Korrosions-
schutz und Chemikalienresistenz in "normaler
Industrieatmosphäre" gewährleisten:
- schlagfestes Polyamid
- glasfaserverstärktes Polyester
- Edelstahl AISI 316 L.
Bei einem Einsatz in extrem aggressiver
Atmosphäre, können Sie zusätzliche Informati-
onen er die Chemikalienbeständigkeit der ein-
gesetzten Kunststoffe, bei Ihrer zuständigen
Cooper Crouse-Hinds Niederlassung erfragen.
5 Verwendung/Eigenschaften
Die Steckvorrichtungen GHG 521 dienen zur
Stromversorgung von standortvariablen
Vor-Ort-Steuerungen, elektrischen Anlagen
sowie von beweglichen Maschinen und
Antrieben in industriellen Bereichen. Sie sind
nach IEC bis max. 16 A einsetzbar
(siehe technische Daten).
Die Steckvorrichtungen sind generell für den in
der EN/IEC 60309 festgelegten Spannungsbe-
reich einsetzbar (z.B. UN 400V das entspricht
dem Spannungsbereich 380 - 415V).
Das am Stecker angeschlossene Betriebs-
mittel muss für die anliegende Netzspan-
nung geeignet sein.
Inbetriebnahme der Wandsteckdosen,
außer "2 polig+PE geschaltet":
Bild 1: Zur Inbetriebnahme der Steckdose
muss zuerst der Bajonettring Pos. 2 von der
Steckdose Pos. 1 abgeschraubt und aufge-
klappt werden.
Bild 2: Nach dem Stecken des Steckers in
die Steckdose wird, um die Schutzart IP 66
herzustellen, der Bajonettring des Steckers
Pos. 2 auf die Steckdose bis zum Anschlag
aufgeschraubt.
Zum Betreiben der Wandsteckdose mit
Verriegelungsschalter ist wie folgt vorzugehen:
Bild 1 und Bild 2: Wie oben beschrieben.
Bild 3: Danach wird der Schalter Pos. 3,
eingeschaltet und somit der Stecker in der
Steckdose verriegelt.
Nach dem Einschalten der Steckdose wird, um
die Schutzart gem. Typenschild auch mit
gestecktem Stecker zu erreichen, der Bajonett-
ring Pos. 2, des Steckers bis zum Anschlag auf
die Steckdose Pos. 1, aufgeschraubt.
Inbetriebnahme der Wandsteckdose
„2polig+PE schaltbar“:
Zum Einschalten der Steckdose ist der Stecker
bis zum Anschlag einzustecken und danach um
ca. 45° nach rechts zu drehen. Dabei wird der
Stecker in der Steckdose verriegelt (Bild 3.1).
Gültig für alle Wandsteckdosen:
Zum Ausschalten und Ziehen des Steckers ist in
umgekehrter Reihenfolge vorzugehen. Nach
dem Trennen des Steckers von der Steckdose
ist die Steckdose mit dem Klappdeckel zu
schließen und mit dem Bajonettring zu sichern.
Nach dem Einschalten der Steckdose wird, um
die Schutzart gem. Typenschild auch mit
gestecktem Stecker zu erreichen, der Bajonett-
ring des Steckers (Bild 2, Pos. 2) bis zum
Anschlag auf die Steckdose gedreht.
Das Stecken und Trennen des Steckers von
der Wandsteckdose mit Schalter ist nur im
ausgeschalteten Zustand möglich.
Steckvorrichtungen für Industrieanwendungen 16 A,
3-polig, 4-polig, 5-polig, GHG 521
D
Pos. 3
Bild 3
Bild 3.1
Pos. 1
Pos. 2
Bild 1 Bild 2
Pos. 2
Pos. 1
5
Die Verantwortung hinsichtlich bestim-
mungsgemäßer Verwendung dieser Steck-
vorrichtung liegt allein beim Betreiber.
Nach einem Kurzschluss im Stromkreis
ist die Funktionsfähigkeit zu überprüfen.
Angaben aus Punkt 3 und 4 sind bei der
Verwendung zu berücksichtigen.
Andere als die beschriebenen Anwendun-
gen sind ohne schriftliche Erklärung der
Fa. CCH / CEAG nicht zulässig.
Beim Betrieb sind die in der Betriebsanlei-
tung unter Punkt 7 genannten Anweisun-
gen zu beachten.
Die Stecker sind im Freien vorzugsweise mit
der Steckeröffnung (Stiftseite) nach unten
aufzubewahren bzw. mit optional erhältlichen
Steckerschutzkappen zu verschließen.
6 Installation
Für das Errichten / Betreiben sind die
relevanten nationalen Vorschriften sowie die
allgemein anerkannten Regeln der Technik
maßgebend.
6.1 Montage
Die Montage der Wandsteckdosen kann ohne
Öffnen des Gehäuses erfolgen.
Die Wandsteckdosen dürfen bei der Direktmon-
tage an der Wand nur an den vorgesehenen
Befestigungspunkten eben aufliegen. Die
gewählte Schraube muss der Befestigungs-
öffnung angepasst sein (siehe Maßbild) und
sie darf die Öffnung nicht beschädigen
(z.B. Verwendung einer Unterlegscheibe).
Das Gerät ist mit mindestens 2 Schrauben
diagonal zu befestigen.
Die Wandsteckdosen und Flanschsteck-
dosen sind so zu montieren, dass die
Stecköffnung nicht nach oben zeigt.
Die Wandsteckdose mit Schalter ist zur
Schnappbefestigung auf dem CCH / CEAG
Gerätehalter Größe 4 durch seitliches
Einschieben in die Führungsnut von der linken
Seite des Gerätehalters, geeignet.
Die betreffende Montageanleitung ist zu
beachten.
6.2 Öffnen des Gerätes /
Elektrischer Anschluss
Der elektrische Anschluss des Betriebsmittels
darf nur durch Elektrofachpersonal erfolgen.
Die Isolation der Anschlussleitungen muss
bis an die Klemme heranreichen. Der Leiter
selbst darf nicht beschädigt sein.
Die ordnungsgemäß abisolierten Anschlusslei-
tungen der Kabel sind unter Berücksichtigung
einschlägiger Vorschriften anzuschließen.
Der elektrische Anschluss der Stecker erfolgt
wie in Bild 4 und 5 dargestellt: Der Steckerein-
satz (Pos. 2, Bild 5) ist durch Lösen der
Befestigungsschrauben (Pos. 3, Bild 4) aus der
Steckerhülse (Pos. 1, Bild 5) herauszunehmen.
Danach kann der Steckereinsatz an den
Anschlüssen der Steckerstifte angeschlossen
werden (siehe Ansicht 1, Bild 5).
Achtung: Bei Verlust der Befestigungs-
schrauben (Pos. 3, Bild 4), sind diese durch
gleichartige Schrauben zu ersetzen oder
direkt vom Hersteller anzufordern.
Der Zusammenbau erfolgt nach dem Kabelan-
schluss in umgekehrter Reihenfolge.
Der elektrische Anschluss der Gerätestecker
erfolgt, wie in Bild 6 bis 8 dargestellt.
Bild 6: Der Steckereinsatz Pos. 2, wird durch
Lösen der zwei Schrauben Pos. 3, aus dem
Geräteflansch Pos. 2, entnommen.
Bild 7: Jetzt können die Anschlussleitungen
Pos. 4, an den Anschlussklemmen des
Steckereinsatzes Pos. 2, wie unter Punkt 6.2
beschrieben, angeschlossen werden.
Bild 8: Zum Schluss wird der Steckereinsatz
Pos. 2, mit den Formschrauben Pos. 3, in den
Geräteflansch Pos. 1, lagerichtig eingeschraubt.
Die minimal und maximal anschließbaren
Leiterquerschnitte sind zu beachten
(siehe technische Daten).
Alle Schrauben und/oder Muttern der
Anschluss klemmen, auch die der nicht
benutzten, sind fest anzuziehen.
Die Anschlussklemmen sind für den Anschluss
von Kupferleitern ausgelegt. Bei der Verwen-
dung von mehr - oder feindrähtigen Anschluss-
kabel/-leitungen sind die Aderenden entspre-
chend den geltenden nationalen Vorschriften
zu behandeln (z.B. Verwendung von Aderend-
hülsen).
Befestigungspunkt B
Steckdose 16 A 4-pol.
Steckvorrichtungen für Industrieanwendungen 16 A,
3-polig, 4-polig, 5-polig, GHG 521
D
Pos. 3
L1
N
PE
Pos. 2 Pos. 1
Pos. 3
Pos. 2
Ansicht 1 Ansicht 2
Pos. 2 Pos. 3 Pos. 1
Pos. 2 Pos. 1
Pos. 4
Pos. 2 Pos. 1
Bild 4
Bild 5
Bild 6
Bild 7
Bild 8
B B
B B
6
6.3 Kabel- und Leitungseinführungen
(KLE); Verschlussstopfen
6.3.1 Steckvorrichtung
Für bewegliche Leitungen sind Trompeten-
verschraubungen oder andere geeignete
Einführungen mit zusätzlicher Zugent-
lastung zu verwenden.
Beim Einsatz von KLE mit einer niedrigeren
als der für das Gerät zutreffenden IP-Schutzart
(siehe Seite 3, technische Daten) wird die
IP-Schutzart des gesamten Gerätes reduziert.
Die für die eingesetzten KLE maßgebenden
Montagerichtlinien sind zu beachten.
Nicht benutzte Einführungsöffnungen sind mit
einem Verschlussstopfen zu verschließen, um
die Schutzart sicherzustellen.
Es ist darauf zu achten, dass bei der Installation
der KLE die für den Leitungsdurchmesser
geeigneten Dichtungseinsätze verwendet
werden. Bei ausschneidbaren Dichtungsein-
sätzen ist sicherzustellen,dass der Einsatz
ordnungsgemäß dem Leitungsdurchmesser
angepasst wird.
Zur Sicherstellung der Schutzart sind die
KLE fest anzuziehen.
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
Alle nicht benutzten metrischen CCH / CEAG
KLE können mit dem Verschluss für metrische
KLE verschlossen werden.
6.3.2 Stecker
Bild 9: Es dürfen generell nur die im Stecker
vorhandenen Dichteinsätze verwendet werden.
Bei der Installation der Leitung ist darauf zu
achten, dass die für den Leitungsdurchmesser
geeigneten Dichtungseinsätze verwendet
werden. Nach dem Anschluss der Leitung ist
die Überwurfmutter, Pos. 2, handfest bis zur
Erzielung der Dichtwirkung anzuziehen. Danach
sind die Schrauben, Pos. 4, der Zugentlastung,
Pos. 3, fest anzuziehen.
Achtung! Übermäßiges Anziehen kann
die Zugentlastungswirkung negativ
beeinträchtigen.
6.4 Schließen des Gerätes
Zur Sicherstellung der Schutzart sind die
Deckelschrauben, die Schrauben der Stecker
und der Kupplung fest anzuziehen.
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
Alle Fremdkörper sind aus dem Gerät
zu entfernen.
6.5 Inbetriebnahme
Vor Inbetriebnahme des Betriebsmittels sind
die in den einzelnen nationalen Bestimmungen
genannten Prüfungen durchzuführen. Außer-
dem ist vor der Inbetriebnahme die korrekte
Funktion und Installation des Betriebsmittels in
Übereinstimmung mit dieser Betriebsanleitung
und anderen anwendbaren Bestimmungen zu
überprüfen.
Vor jedem Stecken des Steckers in die
Steckdose ist dieser auf Beschädigungen zu
überprüfen.
Der Betreiber muss dafür sorgen, dass beim
Betrieb der Steckvorrichtung überall ein
gleiches Erdpotential anliegt.
Unsachgemäße Installation und Betrieb
der Steckvorrichtungen kann zum Verlust
der Garantie führen.
7 Instandhaltung / Wartung
Vor Öffnen des Gehäuses Spannungsfrei-
heit sicherstellen oder geeignete Schutz-
maßnahmen ergreifen.
Die erforderlichen Wartungsintervalle sind
anwendungsspezifisch und daher in Abhän-
gigkeit von den Einsatzbedingungen vom
Betreiber festzulegen.
Sollte bei einer Wartung festgestellt werden,
dass Instandsetzungsarbeiten erforderlich
sind, ist Abschnitt 8 dieser Betriebsanleitung
zu beachten.
8 Reparatur / Instandsetzung /
Änderungen
Instandsetzungsarbeiten / Reparaturen dürfen
nur mit CCH / CEAG Originalersatzteilen
vorgenommen werden.
Reparaturen dürfen nur von Cooper
Crouse-Hinds oder einer qualifizierten
Elektrofachkraft in Übereinstimmung mit
national geltenden Regeln durchgeführt
werden
Umbauten oder Änderungen am Betriebs-
mittel sind nicht gestattet.
9 Entsorgung /
Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind
die jeweils geltenden nationalen Abfallbeseiti-
gungsvorschriften zu beachten. Zur Erleichte-
rung der Wiederverwertbarkeit von Einzeltei-
len sind Kunststoffteile mit dem Kennzeichen
des verwendeten Kunststoffes versehen.
Programmänderungen und -ergänzungen sind
vorbehalten.
Steckvorrichtungen für Industrieanwendungen 16 A,
3-polig, 4-polig, 5-polig, GHG 521
D
Codierung der Spannung und Polzahl
nach IEC
Spannung Farbe h (PE)
2-polig + PE
110 - 130V 50/60Hz gelb 4 Uhr
200 - 250V 50/60Hz blau 6 Uhr
3-polig + PE
200 - 250V 50/60Hz blau 9 Uhr
480 - 500V 50/60Hz schwarz 7 Uhr
380 - 415V 50/60Hz rot 6 Uhr
600 - 690V 50/60Hz schwarz 5 Uhr
3-polig + N + PE
480 - 500V 50/60Hz schwarz 7 Uhr
380 - 415V 50/60Hz rot 6 Uhr
600 - 690V 50/60Hz schwarz 5 Uhr
Pos. 2
Pos. 1 Pos. 3 Pos. 4
Bohrbild für Flanschsteckdose 3- + 4-polig
und Gerätestecker
Bohrbild für Flanschsteckdose 5-polig
Bild 9
7
1 Technical data
1.1 Plug and socket GHG 521
Rated voltage U
N
:
2-pole + PE up to 500 V, 50/60 Hz
3-pole + PE up to 690 V, 50/60 Hz
3-pole + N + PE up to 690 V, 50/60 Hz
Rated current: 16 A
Back-up fuse:
without thermal protection 16 A
with thermal protection 35 A gG
Switching capacity: AC 3
Wall socket 2-pole + PE switchable by switch: 250 V/16 A
Switching capacity: AC 23 AC 22
Wall socket 3-pole + PE, with switch: 500 V / 20 A 500 V / 25 A
690 V / 11 A 690 V / 25 A
Perm. ambient temperature: -20° C up to +40° C (catalogue version)
(Special versions permit deviating temperatures)
Perm. storage temperature in original packing: -20° C up to +40° C
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover:
IP 66 (catalogue version)
Insulation class acc. to EN/IEC 61140: I - is complied with by the devices
Cable entries: (catalogue version)
Wall socket with switch 1 x M25 + 1 x blanking plug
Wall socket without switch 4 x drilling M25 (2 x top, 2 x bottom)
Suitable cables and test torques of the
pressure screw
Ø cable (mm) Nm
Seal 1+2+3
1 2
3
min.
max.
(1)
8.0
10.0
1. 5
2.0
Seal 1+2
1 2
3
min.
max.
(1)
10.0
13.0
2.3
2.6
Seal 1
1 2
3
min.
max.
(1)
13.5
1 7. 5
1. 3
2.3
Test torque for screw in thread cable entry 3.0 Nm
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
Plug / Coupler 2-pole+PE Ø 8 - 18 mm
Plug / Coupler 3-pole+PE Ø 8 - 21 mm
Plug / Coupler 3-pole+N+PE Ø 12 - 21 mm
Supply terminal Cross section Stripped wire length
Wall socket with switch 2 x 0.75 - 6 mm² 6 mm
Wall socket without switch 2 x 1.50 - 6 mm² 10 mm
Flange socket 2 x 1.50 - 6 mm² 10 mm
Coupler 2 x 1.50 - 6 mm² 10 mm
Plug 2 x 1.50 - 6 mm² 10 mm
Test torques:
Cover screws 2.5 Nm
Terminals Wall socket
Flange socket
Inlet
Coupler
2.5 Nm
2.5 Nm
2.5 Nm
2.5 Nm
Terminals Plug 1.5 Nm
Self-cutting screws size 4 2.0 Nm
Self-cutting screws size 5 3.0 Nm
Switch connection screw 0.8 Nm
Weight: (catalogue version)
Wall socket without switch 2-pole+PE GHG 521 23 approx. 0.80 kg
Wall socket switchable 2-pole+PE GHG 521 43 approx. 1.10 kg
Plug 2-pole+PE GHG 521 73 approx. 0.32 kg
Flange socket 2-pole+PE GHG 521 83 approx. 0.37 kg
Inlet 2-pole+PE GHG 521 93 approx. 0.26 kg
Coupler 2-pole+PE GHG 521 33 approx. 0.48 kg
Wall socket without switch 3-pole+PE GHG 521 24 approx. 0.85 kg
Wall socket switchable 3-pole+PE GHG 521 44 approx. 1.60 kg
Plug 3-pole+PE GHG 521 74 approx. 0.39 kg
Flange socket 3-pole+PE GHG 521 84 approx. 0.42 kg
Inlet 3-pole+PE GHG 521 94 approx. 0.31 kg
Coupler 3-pole+PE GHG 521 34 approx. 0.54 kg
Wall socket without switch 3-pole+N+PE GHG 521 25 approx. 0.90 kg
Plug 3-pole+N+PE GHG 521 75 approx. 0.42 kg
Flange socket 3-pole+N+PE GHG 521 85 approx. 0.47 kg
Coupler 3-pole+N+PE GHG 521 35 approx. 0.55 kg
Plug and socket system for industrial use 16 A,
3-pole, 4-pole, 5-pole, GHG 521
GB
8
2 Safety instructions
Target group:
For skilled electricians and suitable
qualified, instructed personnel in
accordance with national legislation,
including the relevant standards.
The GHG 521 plugs and sockets are not
suitable for explosion hazardous areas.
They shall be used for their intended
purpose and in perfect and clean condition.
Prior to taking the plugs and sockets into
operation, they will have to be checked in
accordance with the instruction as per
section 6. The sockets may only be used in
undamaged condition.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
3 Conformity with standards
The apparatus are conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4 Field of application
The plugs and sockets GHG 521are suitable
for use in heavy industrial areas acc. to
IEC/EN 60309!
The enclosure materials employed, includ-
ing the exterior metal parts, are made of
high-quality materials which ensure a corro-
sion protection and resistance to chemical
substances corresponding to the require-
ments in a “normal industrial atmosphere”:
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L.
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
5 Use/Properties
The GHG 521 plugs and sockets are used for
the power supply of local controls with varying
locations, as well as of electrical installations,
mobile machinery and driving gear in industrial
areas. Acc. to IEC they are used up to max. 16A
(see page 7, technical data).
The plugs and sockets can generally be
used for the voltage range laid down in
IEC/EN 60309 (e.g. UN 400V that corresponds
to the voltage range 380-415V).
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
Taking into operation of the wall sockets,
except "2 pole + PE switched":
Fig. 1: In order to activate the socket, first
the bayonet ring item 2 is to be screwed off
the socket item 1 and to be folded open.
Fig. 2: After pushing the plug into the socket,
the bayonet ring of the plug item 2 is screwed
to its stop onto the socket in order to establish
IP 66 protection category.
For operating the 4-pole wall socket (with
interlocking switch) proceed as follows:
Fig. 1 and fig. 2, as described above.
Fig. 3: The switch item 3 is switched on,
thereby locking the plug in the socket.
After switching on the socket, the bayonet ring
item 2 of the plug is screwed to its stop onto
the socket item 1 in order to maintain the
protection category acc. to the type label also
whilst the plug is inserted.
For operating the 2-pole with PE wall
socket (switched by plug) proceed as
follows:
In order to switch on the socket, the plug is
inserted, pushed fully home and then turned
through approx. 45° to the right. Thereby the
plug is locked in the socket (see fig. 3.1).
Valid for all wall sockets
Proceed in inverse order to switch off and pull
the plug from the wall socket with switch. After
having removed the plug from the socket, close
the latter with the folding cover and secure it
with the bayonet ring in order to establish IP 66
type of protection.
In order to ensure the socket's type of
protection acc. to the type label also with the
plug being inserted, the bayonet ring of the plug
(fig. 2, item 2) is turned to its stop onto the
socket.
The plug can be pushed into the socket
and pulled out of it only whilst the wall
socket with switch is switched off.
Item 3
Item 1
Item 2
Fig. 3
Fig. 3.1
Plug and socket system for industrial use 16 A,
3-pole, 4-pole, 5-pole, GHG 521
GB
Item 1
Item 2
Fig. 1 Fig. 2
9
The user alone is responsible for the appro-
priate use of this plug and socket system.
After a short in the circuit, the operative-
ness has to be checked.
The data as per point 3 and 4 will have to
be taken into account with the use.
Applications other than described are not
permitted without CCH / CEAG’s prior
written consent.
For the operation, the instructions stated in
section 7 of the operating instructions will
have to be observed.
In the open air, the plugs must be kept with the
plug opening (pin side) pointing downwards or
be closed with protective plug caps available as
an optional extra (see general catalogue).
6 Installation
For the mounting and operation, the
respective national regulations as well
as the general rules of engineering will have
to be observed.
6.1 Mounting
The wall sockets can be mounted without
opening their enclosure.
In case the wall sockets are mounted directly
onto the wall, they may rest evenly only at the
respective fastening points. The chosen screw
shall match the fastening hole (see dimensional
drawing) and it must not damage the hole
(e. g. use of a washer).
The device shall be fastened diagonally with at
least 2 screws.
The wall sockets and flange sockets shall
be mounted so that the plug hole does not
point upwards.
The wall sockets can be clipped onto the CCH /
CEAG mounting plate size 4. They are laterally
pushed into the guiding groove on the left-hand
side of the mounting plate.
The respective mounting instructions will have
to be observed.
6.2 Opening the device/
Electrical connection
The electrical connection of the device may
only be carried out by skilled staff.
The insulation of the conductors shall
reach up to the terminal. The conductor
itself shall not be damaged.
Taking into account the respective regulations,
the properly bared conductors of the cables
shall be connected.
The electrical connection of the plugs is
established as shown in fig. 4 and 5:
The plug insert (item 2, fig. 5) is removed from
the pin bushing (item 1, fig. 5), after the
fastening screws (item 3, fig. 4) have been
unscrewed. Thereafter, the plug insert can be
connected to the connections of the plug pins
(see view 1, fig. 5).
Attention: When the fastening screws
(item 3, fig. 4) get lost, they will have to be
replaced by similar screws or to be ordered
directly from the manufacturer.
Assembly is made in inverse order, after the
cable has been connected.
The inlets are electrically connected as shown
in fig. 6 to 8.
Fig. 6: After unscrewing the two screws item 3,
the plug insert item 2 is removed from the
flange item 2.
Fig. 7: Now the connecting leads item 4 can be
connected to the terminals of the plug insert
item 2 as described in point 6.2.
Fig. 8: Finally, using the self-cutting screws
item 3, the plug insert item 2 is screwed into
the flange, observing its proper position.
The connectible min. and max. conductor
cross-sections shall be observed
(see technical data).
All screws and/or nuts of the supply terminals,
also of those remaining vacant, shall be
tightened down.
The supply terminals are designed for the
connection of copper conductors. If multi- or
fine-wire connecting cables are used, the wire
ends will have to be handled in acc. with the
applicable national and international rules
(e.g. use of sleeves for strands).
Befestigungspunkt B
Steckdose 16 A 4-pol.
Item 3
Item 3
L1
N
PE
Item 2 Item1
Item 3
Item 2
View 1 View 2
Item 2 Item 3 Item 1
Item 2 Item 1
Item 4
Item 2 Item 1
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
B B
B B
Plug and socket system for industrial use 16 A,
3-pole, 4-pole, 5-pole, GHG 521
GB
10
6.3 Cable entries (KLE); blanking plugs
6.3.1 Plug and socket
Flexible cables shall be used with trum-
pet-shaped cable glands or other suitable
entries with additional pull-relief.
When using cable entries with a lower IP
protection than that which applies to the device
(see page 7, technical data), the IP protection of
the whole device will be reduced.
The mounting directives applicable to the cable
entries used shall be observed.
Unused holes shall be closed with a blanking
plug in order to establish the minimum
protection category.
In case of sealing inserts that are cut out, it
shall be ensured that the insert is properly
adapted to the cable diameter. Care has to be
taken that when fitting the cable entries,
sealing inserts appropriate to the cable
diameter are used.
In order to ensure the required minimum
protection category, the cable glands are to
be tightened down.
Overtightening might impair the protection
category.
All vacant metric CCH / CEAG cable entries
shall be closed with the certified blanking plug
for metric cable entries.
6.3.2 Plug
Fig. 9: In general, only the sealing inserts fitted
in the plug may be used. When mounting the
cable, attention has to be paid that sealing
inserts matching the cable diameter be used.
After having connected the cable, the coupling
ring item 2 is to be screwed fingertight until the
sealing effect is obtained. Then the screws item
4, of the pull-relief item 3, are to be tightened
down.
Mind! Overtightening might impair the
pull-relief effect!
6.4 Closing the device
In order to ensure the required minimum
protection category, the cover screws, the
screws of the plug and the coupler shall be
tightened down.
Overtightening might impair the protection
category.
Any foreign matter shall be removed from
the device.
6.5 Taking into operation
Prior to taking the apparatus into operation, the
tests specified in the relevant national
regulations shall be carried out. Apart from that,
the correct functioning and installation of the
apparatus in accordance with these operating
instructions and other applicable regulations will
have to be checked.
Check the plug for any damages before putting
it in the socket.
The user must ensure that a uniform equipoten-
tial earth applies throughout when the plug and
socket system is operated.
The inappropriate installation and opera-
tion of the plugs and sockets can entail the
loss of warranty.
7 Maintenance/Servicing
Before opening the enclosure, make sure
that the device is disconnected from the
voltage, or take appropriate protective
measures.
The required maintenance intervals depend
on the specific application and will therefore
have to be determined by the user dependent
on the conditions of use.
If during servicing, repairs prove to be
necessary, section 8 of these operating
instructions will have to be observed.
8 Repair / Overhaul /
Modifications
Repairs and overhaul may only be carried out
with genuine CCH / CEAG spare parts.
For replacement and repair only genuine
CCH / CEAG spare parts shall be used.
Repairs may only be carried out by
CCH / CEAG or a qualified electrician in
compliance with the respective national
regulations.
Modifications to the device or changes of
its design are not permitted.
9 Disposal / Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed. In order
to facilitate the recycling of individual com -
ponents, plastic parts are provided with the
identification mark of the plastic material
used.
Subject to modifications or supplement of
the product range.
Code for voltage and no. of poles
acc. to IEC
Voltage Colour h (PE)
2-pole + PE
110 - 130V 50/60Hz yellow 4 h
200 - 250V 50/60Hz blue 6 h
3-pole + PE
200 - 250V 50/60Hz blue 9 h
480 - 500V 50/60Hz black 7 h
380 - 415V 50/60Hz red 6 h
600 - 690V 50/60Hz black 5 h
3-pole + N + PE
480 - 500V 50/60Hz black 7 h
380 - 415V 50/60Hz red 6 h
600 - 690V 50/60Hz black 5 h
Item 2
Item 1 Item 3 Item 4
Drilling template for flange sockets
3- + 4-pole and inlets
Drilling template for flange sockets 5-pole
Fig. 9
Plug and socket system for industrial use 16 A,
3-pole, 4-pole, 5-pole, GHG 521
GB
11
Fiches et prises de 16 A, à 3 pôles, 4 pôles, 5 pôles,
pour utilisation industrielle, GHG 521
F
1 Caractéristiques techniques
1.1 Fiche et prise GHG 521
Tension nominale U
N
:
2 pôles + PE jusqu’à 500 V, 50/60 Hz
3 pôles + PE jusqu’à 690 V, 50/60 Hz
3 pôles + N + PE jusqu’à 690 V, 50/60 Hz
Courant nominal: 16 A
Fusible maximal placé en amont:
sans protection thermique 16 A
avec protection thermique 35 A gG
Puissance de coupure: AC 3
Prise murale 2 pôles + PE, avec interrupteur: 250 V/16 A
Puissance de coupure: AC 23 AC 22
Prise murale 3 pôles + PE, avec interrupteur: 500 V / 20 A 500 V / 25 A
690 V / 11 A 690 V / 25 A
Température ambiante admissible: -20° C à +40° C (modèle de liste)
(En cas de modèles spéciaux d’autres températures possibles)
Température de stockage dans l’emballage original: -20° C à +40° C
Indice de protection selon CEI/EN 60529 avec le couver
-
cle rabattant fermé et arrêté et
les dispositifs dûment enfichés
IP 66 (modèle de liste)
Classe d’isolation selon CEI/EN 61140 I - est remplie par les dispositifs
Entrée de câble: (modèle de liste)
Prise murale avec interrupteur 1 x M25 +
1 x bouchon de fermeture
Prise murale sans interrupteur 4 x alésage M25 (2 x dessus, 2 x dessous)
Dimensions des câbles et couples de serrage Ø câble (mm) Nm
Garniture 1+2+3
1 2
3
min.
max.
(1)
8,0
10,0
1,5
2,0
Garniture 1+2
1 2
3
min.
max.
(1)
10,0
13,0
2,3
2,6
Garniture 1
1 2
3
min.
max.
(1)
13,5
1 7, 5
1,3
2,3
Couple d' essai pour l’entrée de câble 3,0 Nm
(1)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la
possibilité de resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
Fiche / Prolongateur à 2 pôles+PE Ø 8 - 18 mm
Fiche / Prolongateur à 3 pôles+PE Ø 8 - 21 mm
Fiche / Prolongateur à 3 pôles+N+PE Ø 12 - 21 mm
Borne de connexion Section transv. Longueur dénudée
des fils
Prise murale avec interrupteur 2 x 0,75 - 6 mm² 6 mm
Prise murale sans interrupteur 2 x 1,50 - 6 mm² 10 mm
Prise à bride 2 x 1,50 - 6 mm² 10 mm
Prolongateur 2 x 1,50 - 6 mm² 10 mm
Connexion de la fiche 2 x 1,50 - 6 mm² 10 mm
Torques d’essai:
Vis de couvercle 2,5 Nm
Bornes de connexion Prise murale
Prise à bride
Connecteur
Prolongateur
2,5 Nm
2,5 Nm
2,5 Nm
2,5 Nm
Bornes de connexion Fiche 1,5 Nm
Vis auto-taraudeuse taille 4 2,0 Nm
Vis auto-taraudeuse taille 5 3,0 Nm
Vis de connexion de la interrupteur 0,8 Nm
Poids: (modèle de liste)
Prise murale sans interrupter 2-p+PE GHG 521 23 env. 0,80 kg
Prise murale possible interrupter
2-p+PE GHG 521 43 env. 1,10 kg
Fiche 2-p+PE GHG 521 73 env. 0,32 kg
Prise à bride 2-p+PE GHG 521 83 env. 0,37 kg
Connecteur 2-p+PE GHG 521 93 env. 0,26 kg
Prolongateur 2-p+PE GHG 521 33 env. 0,48 kg
Prise murale sans interrupter 3-p+PE GHG 521 24 env. 0,85 kg
Prise murale possible interrupter
3-p+PE GHG 521 44 env. 1,60 kg
Fiche 3-p+PE GHG 521 74 env. 0,39 kg
Prise à bride 3-p+PE GHG 521 84 env. 0,42 kg
Connecteur 3-p+PE GHG 521 94 env. 0,31 kg
Prolongateur 3-p+PE GHG 521 34 env. 0,54 kg
Prise murale sans interrupter 3-p+N+PE GHG 521 25 env. 0,90 kg
Fiche 3-p+N+PE GHG 521 75 env. 0,42 kg
Prise à bride 3-p+N+PE GHG 521 85 env. 0,47 kg
Prolongateur 3-p+N+PE GHG 521 35 env. 0,55 kg
12
2 Consignes de sécurité
Groupe cible:
Pour les électriciens qualifiés et les
personnels ayant reçu les formations
adéquates, conformément à la législation
nationale en vigueur.
Les fiches et prises du type GHG 521 ne
doivent pas être utilisées en atmosphère
explosive.
Elles ne doivent être employées que pour la
fonction qui leur est dévolue et qu’en parfait
état de propreté et de fonctionnement.
Avant leur mise en service, les fiches et
prises doivent être vérifiées selon l’instruc-
tion donnée dans la section 6.
Les prises ne doivent être utilisées qu’avec
les fiches y appartenants et en parfait état.
Respectez les prescriptions nationales de
sécurité et de prévoyance contre les
accidents ainsi que les consignes de sécurité
qui suivent dans ce mode d’emploi et qui
sont mises en italique comme ce texte!
3 Conformité avec les normes
Les Appareils sont conformes aux normes
reprises dans la déclaration de conformité.
Les références aux normes et directives dans
cette notice se réfèrent toujours à la dernière
version. Les suppléments éventuels doivent
également être respectés.
4 Domaine d’utilisation
Les fiches et prises du type GHG 521
conviennent à l’emploi en atmosphère indus-
trielle selon CEI/EN 60309!
Pour l’enveloppe, y compris les pièces métal-
liques extérieures, des matières de qualité su-
périeure ont été employées qui assurent une
protection appropriée contre la corrosion et
une résistance contre des agents chimiques
en “atmosphère industrielle normale”:
- polyamide résistant au choc
- polyester renforcé par fibre de verre
- acier spécial AISI 316 L.
En cas d‘utilisation en atmosphère extrème-
ment corrosive, vous pouvez obtenir des
informations complémentaires sur la résis-
tance chimique des plastiques utilisés chez
la succursale Cooper Crouse-Hinds de votre
région.
5 Utilisation/Propriétés
Les fiches et prises GHG 521 servent à
l’alimentation en courant de réglages auto-
matiques en place à emplacement variable
et d’installations électriques ainsi que de
machines et de mécanismes de commande
mobiles en atmosphère industrielle.
Elles peuvent être exploitées jusqu’à 16A
au maxi selon CEI (voir caractéristiques
techniques).
Les prises et fiches sont utilisables dans les
fourchettes de tension comprises dans la
norme CEI/EN 60309 (par exemple, UN 400V
appartient à la fourchette 380 - 415V).
L’ appareil connecté à la fiche doit être
adapté à la tension du réseau correspon-
dant.
Mise en service des prises murales, sauf
"2 pôles + PE activé":
Fig. 1: Pour la mise en circuit de la prise,
il faut d’abord dévisser l’anneau à baïonnette,
pos. 2 de la prise, pos. 1, et le déplier.
Fig. 2: Après avoir enfiché la fiche dans la prise,
l’anneau à baïonnette de la fiche, pos. 2, est
vissé jusqu’à sa butée sur la prise afin d’établir
l’indice de protection IP 66.
Pour la mise en circuit de la prise murale
avec interrupteur de verouillage procédez
comme suit:
Fig. 1 et Fig. 2, comme décrit ci-dessus.
Fig. 3: Puis, l’interrupteur pos. 3 est enclenché
et, par conséquent, la fiche est bloquée dans la
prise.
Afin d’assurer le mode de protection selon la
plaque signalétique après la mise en circuit de
la prise avec la fiche mise en place, l’anneau à
baïonnette de la fiche, pos. 2, est vissé jusqu’à
sa butée sur la prise pos. 1.
Pour la mise en circuit "2 pôle+PE":
Pour la mise en circuit de la prise, la fiche doit
être enfichée jusqu’à sa butée dans celle-ci et
ensuite être tournée de 45° à droite. De cette
manière, la fiche est bloquée dans la prise
(voir Fig. 3.1).
Valable pour toutes les prises murales:
Pour la mise hors circuit et pour retirer la fiche
de la prise murale à 4 pôles, procédez dans
l’ordre inverse.
Après avoir séparé la fiche de
la prise, celle-ci doit être fermée avec le
couvercle à charnière et bloquée avec l’anneau
à baïonnette, afin d’établir l’indice de protection
IP 66 (voir Fig. 2, pos. 2).
La fiche ne peut être enfichée dans la prise
ou retirée de celle-ci que lorsque la prise
est mise hors circuit.
Pos. 3
Pos. 2
Pos. 1
Pos 2
Pos. 1
Pos. 2
Fig. 3
Fig. 1 Fig. 2
Fig. 3.1
Fiches et prises de 16 A, à 3 pôles, 4 pôles, 5 pôles,
pour utilisation industrielle, GHG 521
F
13
Seul l’utilisateur est responsable de l’em-
ploi comme prévu de cette fiche et prise.
Après un court-circuit dans le circuit, la
capabilité de fonctionner doit être vérifiée.
Pour l’emploi, les consignes des sections 3
et 4 devront être respectées.
Des emplois autres que ceux décrits ne
sont admis qu’avec le consentement par
écrit de la part de CCH / CEAG.
Lors de l’exploitation, les instructions selon
point 7 de ce mode d’emploi doivent être
respectées.
En plein air, les fiches doivent être gardées avec
leur ouverture (côté des broches) vers le bas.
A l’option, elles peuvent être fermées avec les
capuchons protecteurs pour la fiche qui sont
disponibles sur demande (voir catalogue général).
6 Installation
Pour l’installation la règlementation nationale
en vigueur ainsi que les règles de la tech-
nique généralement reconnues devront être
respectées.
6.1 Montage
Le montage des prises murales peut se faire
sans ouvrir l’enveloppe.
En cas de montage directement au mur, les
prises murales ne doivent reposer au niveau
du mur qu’en les points de fixation prévus. La
vis choisie doit correspondre au trou de fixation
(voir plan coté) et elle ne doit pas avarier
l’ouverture (par ex. emploi d’une rondelle).
Le dispositif doit être fixé en diagonale avec
au moins deux vis.
Le montage de la prise murale et de la
prise à bride doit se faire de sorte que l’ou-
verture d’enfichage soit dirigée vers le bas.
Les prises murales avec interrupteur peuvent
être verrouillées par ressort sur le porte-appareil
CCH / CEAG, taille 4, en les poussant latérale-
ment dans la rainure de guidage du côté
gauche du porte-appareil.
Les instructions respectives pour le montage
devront être respectées.
6.2 Ouverture du dispositif/
Raccordement électrique
Le raccordement électrique du dispositif ne doit
se faire que par du personnel qualifié.
L’isolation doit couvrir le conducteur
jusqu’à la borne. Le conducteur lui-même
ne doit pas être endommagé.
En tenant compte des règlements respectifs,
les conducteurs dûment dénudés des câbles
sont raccordés.
Le raccordement électrique des fiches se fait
comme montré dans les figures 4 et 5:
Les vis de fixation (pos. 3, Fig. 4) de l’insert de
la fiche (pos. 2, Fig. 5) sont desserrées pour le
sortir de l’alvéole. Puis, l’insert peut être
raccordé aux connexions des contacts mâles
(voir vue 1, Fig. 5).
Attention: En cas de perte des vis de
fixation (pos. 3, Fig. 4) celles-ci doivent être
remplacées par des vis similaires ou être
demandées au fabricant.
Après le raccordement du câble, le montage se
fait dans l’ordre inverse.
Le raccordement électrique des connecteurs se
fait comme montré dans les figures 6 à 8.
Fig. 6: Après avoir dévissé les deux vis pos. 3,
l’insert de commutation pos. 2 est sorti de la
bride pos. 2.
Fig. 7: Puis, les fils d’alimentation pos. 4
peuvent être raccordés aux bornes de l’insert
de commutation pos. 2, comme décrit sous
point 6.2.
Fig. 8: Enfin, l’insert de commutation pos. 2 est
vissé dans la bride pos. 1 au moyen des vis
auto-taraudeuses pos. 3 tout en respectant sa
position correcte.
Les sections minimales et maximales
admissibles des conducteurs doivent être
respectées (voir caractéristiques techniques).
Toutes les vis et/ou écrous des bornes de
connexion, aussi celles des bornes non
utilisées, doivent être serrées à fond.
Les bornes sont prévues pour le raccordement
de conducteurs en cuivre. En cas d’utiliser des
câbles de connexion multifilaires ou à fils de
faible diamètre, les bouts de fil doivent être
traités selon la règlementation nationale et
internationale y applicable (par ex. emploi des
embouts).
Point de fixation B
Prise de 16 A 4 pôles
Pos. 3
Pos. 1
L1
N
PE
Pos. 2 Pos. 1
Pos. 3
Pos. 2
Vue 1 Vue 2
Pos. 2 Pos. 3 Pos.1
Pos. 2 Pos. 1
Pos. 4
Pos. 2 Pos. 1
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
B B
B B
Fiches et prises de 16 A, à 3 pôles, 4 pôles, 5 pôles,
pour utilisation industrielle, GHG 521
F
14
6.3 Entrées de câble (KLE);
bouchons de fermeture
6.3.1 Fiche et prise
Pour des câbles flexibles il faudra utili-
ser des presses-étoupes à trompette ou
d’autres entrées convenables avec dé-
charge de traction supplémentaire.
Lorsque des entrées de câble avec un indice de
protection IP inférieur à celui du dispositif sont
employées (voir page 11, caractéristiques
techniques), l’indice de protection IP de
l’ensemble sera réduit.
Les directives pour le montage applicables aux
entrées de câble montées doivent être
respectées.
Des ouvertures d’entrée non utilisées doivent
être fermées avec un bouchon de fermeture
pour établir l’indice de protection.
Lors du montage des entrées de câble il faudra
veiller à ce que des garnitures d’étanchéité
correspondant au diamètre du câble soient
utilisées. En cas de garnitures qui doivent être
coupées sur mesure, il faudra faire attention à
ce que la garniture soit adaptée au diamètre du
câble.
Les entrées de câble doivent être serrées à
fond pour maintenir l’indice de protection.
Au cas où elles seraient forcées, cela pour-
rait être nuisible à l’indice de protection.
Toutes les entrées de câble métriques CCH /
CEAG non utilisées doivent être fermées avec
un bouchon de fermeture pour des entrées de
câble métriques.
6.3.2 Fiche
Fig. 9: Généralement, les garnitures pourvues
dans la fiche doivent être utilisées. Lors du
montage du câble, il faut faire attention à ce
que des garnitures convenables pour le
diamètre du câble soient employées. Après
avoir connecté le câble, la collerette de fixation
pos. 2, doit être vissée à la main jusqu’à ce que
l’étanchéité soit assurée. Puis, les vis pos. 4, de
la pince de décharge de traction pos 3, doivent
être serrées à fond.
Attention! Un serrage excessif peut nuir
à l’effet de décharge de traction.
6.4 Fermeture du dispositif
Les vis du couvercle, de la fiche et du
prolongateur doivent être serrées à fond afin
d’assurer l’indice de protection minimum
requis.
Au cas où elles seraient forcées, cela pour-
rait être nuisible à l’indice de protection.
Tout corps étranger doit être ôte du
dispositif.
6.5 Mise en service
Avant la mise en service du matériel, les
vérifications spécifiées dans les règlements
nationaux individuels devront être exécutées.
De plus, il faudra vérifier son fonctionnement et
installation corrects en conformité avec ce
mode d’emploi et avec d’autres règlements y
applicables.
Chaque fois que la fiche est enfichée dans la
prise, elle devra d’abord être vérifiée pour des
avaries.
L’utilisateur doit veiller à ce que le même
potentiel terrestre soit appliqué en tout lieu.
L’installation et l’exploitation inadéquates
des fiches et prises peut entraîner la perte
de la garantie.
7 Maintien / Entretien
Avant d’ouvrir l’enveloppe, débrancher
le dispositif de la tension ou prendre des
mesures préventives appropriées.
Les intervalles de service requis dépendent
de l’emploi spécifique et devront donc être
fixés par l’utilisateur en tenant compte des
conditions d'utilisation.
Si, lors d’un entretien, on constate que des
travaux d’entretien sont nécessaires, il faudra
suivre le point 8 de ce mode d’emploi.
8 Réparation / Remise en état
Des réparations ne doivent être exécutées
qu’à l’aide de pièces de rechange d’origine
CCH / CEAG.
Des réparations ne devront être exécutées
que par CCH / CEAG ou par un électricien
qualifié en conformité avec la règlementa-
tion nationale en vigueur.
Il n’est pas permis de transformer ou de
modifier ce matériel.
9 Évacuation des déchets /
Recyclage
Lors de l’évacuation de ce matériel électrique,
la règlementation nationale respective en
vigueur devra être respectée. Pour faciliter la
réutilisation des composants individuels, des
pièces en matière plastique sont repérées de
la marque distinctive de la matière plastique
employée.
Sous réserve de modification ou de supplé-
ment de cette série de produits.
Codage de la tension et du nombre de pôles
selon CEI
Tension Couleur h (PE)
2 pôles + PE
110 - 130V 50/60Hz jaune 4 h
200 - 250V 50/60Hz bleu 6 h
3 pôles + PE
200 - 250V 50/60Hz bleu 9 h
480 - 500V 50/60Hz noir 7 h
380 - 415V 50/60Hz rouge 6 h
600 - 690V 50/60Hz noir 5 h
3 pôles + N + PE
480 - 500V 50/60Hz noir 7 h
380 - 415V 50/60Hz rouge 6 h
600 - 690V 50/60Hz noir 5 h
Pos. 2
Pos. 1 Pos. 3 Pos. 4
Gabarit de perçage pour prise à bride
3 et 4 pôles et connecteur
Gabarit de perçage pour prise à bride
5 pôles
Fig. 9
Fiches et prises de 16 A, à 3 pôles, 4 pôles, 5 pôles,
pour utilisation industrielle, GHG 521
F
15
Maßbilder in mm / Dimensions in mm / Dimensions en mm
X = Befestigungsmaße / X = fixing dimensions / X = dimensions de fixation
Wandsteckdose schaltbar mit Stecker
2-polig+PE /
Wall socket switchable by plug 2-pole+PE /
Prise murale sans interrupteur à 2 pôl. +PE
Wandsteckdose mit Schalter 4-polig /
Wall socket with switch 4-pole /
Prise murale avec interrupteur à 4 pôles
Stecker 3-polig / Plug 3-pole /
Fiche à 3 pôles
Stecker 4-polig / Plug 4-pole /
Fiche à 4 pôles
Stecker 5-polig / Plug 5-pole /
Fiche à 5 pôles
Gerätestecker 3-polig / Inlet 3-pole /
Connecteur à 3 pôles
Gerätestecker 4-polig / Inlet 4-pole /
Connecteur à 4 pôles
90
X80
121
11
X115
155
223
7
Kupplung 3-polig / Coupler 3-pole /
Prolongateur à 3 pôles
Kupplung 4-polig / Coupler 4-pole /
Prolongateur à 4 pôles
Kupplung 5-polig / Coupler 5-pole /
Prolongateur à 5 pôles
Maß / Dimensions / Dim. / A
Wandsteckdose ohne Schalter 3-polig /
Wall socket w/o switch 3-pole /
Prise murale sans interrupteur à 3 pôl.
163
Wandsteckdose ohne Schalter 4-polig /
Wall socket w/o switch 4-pole /
Prise murale sans interrupteur à 4 pôl.
160
Wandsteckdose ohne Schalter 5-polig /
Wall socket w/o switch 5-pole /
Prise murale sans interrupteur à 5 pôl.
159
Maß / Dimensions / Dim. / A B C
Flanschsteckdose 3-polig /
Flange socket 3-pole /
Prise à bride à 3 pôles
109
75 72
Flanschsteckdose 4-polig /
Flange socket 4-pole /
Prise à bride à 4 pôles
111
72 76,5
Flanschsteckdose 5-polig /
Flange socket 5-pole /
Prise à bride à 5 pôles
111
75 84
110
X100
147
11
X135
175
236
7
Wandsteckdose mit Schalter 5-polig /
Wall socket with switch 5-pole /
Prise murale avec interrupteur à 5 pôles
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2018 Eaton
All Rights Reserved
Printed in Germany
dd
Publication No.
GHG 510 7001 P0003 D/GB/F (i)
Auflage / 31.2018 / MS
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Eaton GHG 521 Mode d'emploi

Taper
Mode d'emploi