Victron energy MultiPlus-II Manuel utilisateur

Taper
Manuel utilisateur
MultiPlus-II 12 | 3000 | 120-32
MultiPlus-II 24 | 3000 | 70-32
MultiPlus-II 48 | 3000 | 35-32
MultiPlus-II 48 | 5000 | 70-50
MultiPlus-II 48 | 8000 | 110-100
MultiPlus-II 48 | 10000 | 140-100
Manual
EN
Handleiding
NL
Manuel
FR
Anleitung
DE
Käyttöohje
FI
Användarhandbok
SE
Appendix
1
EN NL FR DE FI SE Appendix
1. SAFETY INSTRUCTIONS
In general
Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using
the product.
This product is designed and tested in accordance with international standards. The equipment should be used for the designated
application only.
WARNING: DANGER OF ELECTRICAL SHOCK
The product is used in combination with a permanent energy source (battery). Even if the equipment is switched off, a dangerous
electrical voltage can occur at the input and/or output terminals. Always switch the AC power off and disconnect the battery before
performing maintenance.
The product contains no internal user-serviceable parts. Do not remove the front panel and do not put the product into operation unless
all panels are fitted. All maintenance should be performed by qualified personnel.
Never use the product at sites where gas or dust explosions could occur. Refer to the specifications provided by the manufacturer of the
battery to ensure that the battery is suitable for use with this product. The battery manufacturer's safety instructions should always be
observed.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person
responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
WARNING: do not lift heavy objects unassisted.
Installation
Read the installation instructions before commencing installation activities. For electrical work, follow the local national wiring standard,
regulation and this installation instructions.
This product is a safety class I device (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals
must be provided with uninterruptible grounding for safety purposes. An additional grounding point is located on the outside
of the product. The ground conductor should be at least 4mm². If it can be assumed that the grounding protection is damaged, the
product should be taken out of operation and prevented from accidentally being put into operation again; contact qualified maintenance
personnel.
Ensure that the connection cables are provided with fuses and circuit breakers. Never replace a protective device by a component of a
different type. Refer to the manual for the correct part.
Do not invert neutral and phase when connecting the AC.
Check before switching the device on whether the available voltage source conforms to the configuration settings of the product as
described in the manual.
Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet or dusty environment.
Ensure that there is always sufficient free space around the product for ventilation, and that ventilation openings are not blocked.
Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts, curtains or other textiles, etc.
in the immediate vicinity of the equipment.
This inverter is provided with an internal isolation transformer providing reinforced insulation.
Transport and storage
On storage or transport of the product, ensure that the mains supply and battery leads are disconnected.
No liability can be accepted for damage in transit if the equipment is not transported in its original packaging.
Store the product in a dry environment; the storage temperature should range from 20 °C to 60 °C.
Refer to the battery manufacturer's manual for information on transport, storage, charging, recharging and disposal of the battery.
2
2. DESCRIPTION
2.1 Boats, vehicles and other stand-alone applications
The basis of the MultiPlus-II is an extremely powerful sine inverter, battery charger and transfer switch in a compact casing.
Important features:
Automatic and uninterruptible switching
In the event of a supply failure or when the generating set is switched off, the MultiPlus-II will switch over to inverter operation and take
over the supply of the connected devices. This is done so quickly that operation of computers and other electronic devices is not
disturbed (Uninterruptible Power Supply or UPS functionality). This makes the MultiPlus-II highly suitable as an emergency power
system in industrial and telecommunication applications.
Two AC outputs
Besides the usual uninterruptable output (AC-out-1), an auxiliary output (AC-out-2) is available that disconnects its load in the event of
battery operation. Example: an electric boiler that is allowed to operate only if the genset is running or shore power is available. There
are several applications for AC-out-2.
Please enter “AC-out-2” in the search box on our website and find the latest information about other applications.
Three phase capability
Three units can be configured for three-phase output. Up to 6 sets of three units can be parallel connected to provide 45 kW / 54 kVA
inverter power and more than 600 A charging capacity.
PowerControl maximum use of limited AC power
The MultiPlus-II can supply a huge charging current. This implies heavy loading of the AC mains or generator. Therefore a maximum
current can be set. The MultiPlus-II then takes other power users into account, and only uses 'surplus' current for charging purposes.
PowerAssist Extended use of generator or shore current: the MultiPlus-II “co-supply” feature
This feature takes the principle of PowerControl to a further dimension allowing the MultiPlus-II to supplement the capacity of the
alternative source. Where peak power is often required only for a limited period, the MultiPlus-II will make sure that insufficient AC mains
or generator power is immediately compensated for by power from the battery. When the load reduces, the spare power is used to
recharge the battery.
Programmable relay
The MultiPlus is equipped with a programmable relay. The relay can be programmed for different applications, for example as a starter
relay for a generator.
External current transformer (optional)
External current transformer option to implement PowerControl and PowerAssist with external current sensing.
Programmable analog/digital input/output ports (Aux in 1 and Aux in 2, see appendix)
The MultiPlus is equipped with 2 analog/digital input/output ports.
These ports can be used for several purposes. One application is communication with the BMS of a lithium-ion battery.
2.2 On-grid and off-grid systems combined with PV
External current transformer (optional)
When used in a grid-parallel topology the internal current transformer cannot measure the current to or from the mains. In this case an
external current transformer has to be used. See appendix.
Frequency shift
When solar inverters are connected to the output of a MultiPlus-II, excess solar energy is used to recharge the batteries. Once the
absorption voltage is reached, charge current will reduce and excess energy will be fed back into the mains. If the mains is not
available, the MultiPlus-II will slightly increase the AC frequency to reduce the output of the solar inverter.
Built-in Battery Monitor
The ideal solution when the MultiPlus-II is part of a hybrid system (diesel generator, inverter/chargers, storage battery, and alternative
energy). The built-in battery monitor can be set to start and stop the generator:
- Start at a preset % discharge level, and/or
- start (with a preset delay) at a preset battery voltage, and/or
- start (with a preset delay) at a preset load level.
- Stop at a preset battery voltage, or
- stop (with a preset delay) after the bulk charge phase has been completed, and/or
- stop (with a preset delay) at a preset load level.
Autonomous operation when the grid fails
Houses or buildings with solar panels or a combined micro-scale heating and power plant or other sustainable energy sources have a
potential autonomous energy supply which can be used for powering essential equipment (central heating pumps, refrigerators, deep
freeze units, Internet connections, etc.) during a power failure. A problem is however that grid connected sustainable energy sources
drop out as soon as the grid fails. With a MultiPlus-II and batteries, this problem can be solved: the MultiPlus-II can replace the grid
during a power failure. When the sustainable energy sources produce more power than needed, the MultiPlus-II will use the surplus to
charge the batteries; in the event of a shortfall, the MultiPlus-II will supply additional power from the battery.
Programmable
All settings can be changed with a PC and free of charge software, downloadable from our website www.victronenergy.com
3
EN NL FR DE FI SE Appendix
2.3 Battery charger
2.3.1 Lead-acid batteries
Adaptive 4-stage charge algorithm: bulk absorption float storage
The microprocessor-driven adaptive battery management system can be adjusted for various types of batteries. The adaptive function
automatically adapts the charging process to battery use.
The right amount of charge: variable absorption time
In the event of slight battery discharge, absorption is kept short to prevent overcharging and excessive gas formation. After deep
discharging, the absorption time is automatically extended in order to fully charge the battery.
Preventing damage due to excessive gassing: the BatterySafe mode
If, in order to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, damage
due to excessive gassing will be prevented by automatically limiting the rate of voltage increase once the gassing voltage has been
reached.
Less maintenance and aging when the battery is not in use: the Storage mode
The Storage mode kicks in whenever the battery has not been subjected to discharge during 24 hours. In the Storage mode float
voltage is reduced to 2,2 V/cell (13,2 V for 12 V battery) to minimise gassing and corrosion of the positive plates. Once a week the
voltage is raised back to the absorption level to ‘equalize’ the battery. This feature prevents stratification of the electrolyte and
sulphation, a major cause of early battery failure.
Battery voltage sense: the correct charge voltage
Voltage loss due to cable resistance can be compensated by using the voltage sense facility to measure voltage directly on the DC bus
or on the battery terminals.
Battery voltage and temperature compensation
The temperature sensor (supplied with the product) serves to reduce charging voltage when battery temperature rises. This is
particularly important for maintenance-free batteries, which could otherwise dry out by overcharging.
Two DC outputs for charging two batteries
The main DC terminal can supply the full output current. The second output, intended for charging a starter battery, is limited to 4 A and
has a slightly lower output voltage (12 V and 24 V models only).
2.3.2 Li-ion batteries
Victron LiFePO4 Smart batteries
Use the VE.Bus BMS
2.3.3 Other Li-ion batteries
Please see https://www.victronenergy.com/live/battery_compatibility:start
2.3.4 More on batteries and battery charging
Our book ‘Energy Unlimited’ offers further information on batteries and battery charging, and is available free of charge on our website
(see www.victronenergy.com Support & Downloads General Technical Information). For more information on adaptive charging,
please also refer to the General Technical Information on our website.
2.4 ESS Energy Storage Systems: feeding energy back into the grid (not applicable to the
MultiPlus-II 12/3000/120-32)
When the MultiPlus-II is used in a configuration in which it will feed back energy into the grid it is required to enable grid code
compliance by selecting the appropriate grid code country setting with the VEConfigure tool.
Once set, a password will be required to disable grid code compliance or change grid code related parameters.
Depending on the grid code there are several reactive Power control modes:
Fixed cos φ
Cos φ as function of P
Fixed Q
Q as function of input voltage
Reactive Power capability
4
If the local grid code is not supported by the MultiPlus-II an external certified interface device should be used to connect the MultiPlus-II
to the grid.
The MultiPlus-II can also be used as a bidirectional inverter operating parallel to the grid, integrated into a customer designed system
(PLC or other) that takes care of the control-loop and grid measurement,
Special note regarding NRS-097 (South Africa)
1. The maximum allowed impedance of the network is 0.28 + j0.18
2. The inverter is fulfilling the unbalance requirement in case of multiple single phase units only when the Color Control GX is
part of the installation.
Special notes regarding AS 4777.2 (Australia/New Zealand)
1. IEC62109.1 certification and CEC approval for off-grid use does NOT imply approval for grid-interactive installations.
Additional certification to IEC 62109.2 and AS 4777.2.2015 are required before grid-interactive systems can be implemented.
Please check the Clean Energy Council website for current approvals.
2. DRM Demand Response Mode
When the AS4777.2 grid code has been selected in VEconfigure, DRM 0 functionality is available on port AUX1 (see
appendix A.
To enable grid connection, a resistance of between 5kOhm and 16kOhm must be present between the terminals of port AUX1
(marked + and - ). The MultiPlus-II will disconnect from the grid in case of an open circuit or a short circuit between the
terminals of port AUX1. The maximum voltage that may be present between the terminals of port AUX1 is 5 V.
Alternatively, if DRM 0 is not required, this functionality can be disabled with VEConfigure.
5
EN NL FR DE FI SE Appendix
3.OPERATION
3.1 On/Off/Charger Only Switch
When switched to on, the product is fully functional. The inverter will come into operation and the LED inverter onwill light up.
An AC voltage connected to the AC interminal will be switched through to the AC outterminal, if within specifications. The inverter will
switch off, the mains onLED will light up and the charger commences charging. The bulk, absorptionor floatLEDs will light up,
depending on the charger mode.
If the voltage at the AC-interminal is rejected, the inverter will switch on.
When the switch is switched to charger only, only the battery charger of the Multi will operate (if mains voltage is present). In this mode
input voltage also is switched through to the AC outterminal.
NOTE: When only the charger function is required, ensure that the switch is switched to charger only. This prevents the inverter from
being switched on if the mains voltage is lost, thus preventing your batteries from running flat.
3.2 Remote control
Remote control is possible with either a switch or with a Multi Control panel.
The Multi Control panel has a simple rotary knob with which the maximum current of the AC input can be set: see PowerControl and
PowerAssist in Section 2.
3.3 Equalisation and forced absorption
3.3.1 Equalisation
Traction batteries require regular additional charging. In the equalisation mode, the MultiPlus-II will charge with increased voltage for
one hour (1 V above the absorption voltage for a 12 V battery, 2 V for a 24 V battery). The charging current is then limited to 1/4 of the
set value. The bulkand absorptionLEDs flash intermittently.
Equalisation mode supplies a higher charging voltage than most DC consuming
devices can cope with. These devices must be disconnected before additional
charging takes place.
3.3.2 Forced absorption
Under certain circumstances, it can be desirable to charge the battery for a fixed time at absorption voltage level. In Forced Absorption
mode, the MultiPlus-II will charge at the normal absorption voltage level during the set maximum absorption time. The absorption
LED lights.
3.3.3 Activating equalisation or forced absorption
The MultiPlus-II can be put into both these states from the remote panel as well as with the front panel switch, provided that all switches
(front, remote and panel) are set to onand no switches are set to charger only’.
In order to put the MultiPlus-II in this state, the procedure below should be followed.
If the switch is not in the required position after following this procedure, it can be switched over quickly once. This will not change the
charging state.
NOTE: Switching from onto charger onlyand back, as described below, must be done quickly. The switch must be toggled such that
the intermediate position is 'skipped', as it were. If the switch remains in the offposition even for a short time, the device may be turned
off. In that case, the procedure must be restarted at step 1. A certain degree of familiarisation is required when using the front switch on
the Compact in particular. When using the remote panel, this is less critical.
Procedure:
1. Check whether all switches (i.e. front switch, remote switch or remote panel switch if present) are in the onposition.
2. Activating equalisation or forced absorption is only meaningful if the normal charging cycle is completed (charger is in 'Float').
3. To activate:
a. Switch rapidly from onto charger onlyand leave the switch in this position for ½ to 2 seconds.
b. Switch rapidly back from charger onlyto onand leave the switch in this position for ½ to 2 seconds.
c. Switch once more rapidly from onto ‘charger onlyand leave the switch in this position.
4. On the MultiPlus-II (and, if connected, on the MultiControl panel) the three LEDs Bulk, Absorptionand Floatwill now flash 5 times.
5. Subsequently, the LEDs Bulk, Absorptionand Float will each light during 2 seconds.
a. If the switch is set to onwhile the BulkLED lights, the charger will switch to equalisation.
b. If the switch is set to onwhile the AbsorptionLED lights, the charger will switch to forced absorption.
c. If the switch is set to onafter the three LED sequence has finished, the charger will switch to Float’.
d. If the switch is has not been moved, the MultiPlus-II will remain in ‘charger only’ mode and switch to Float’.
6
3.4 LED Indications
LED off
LED flashes
LED illuminated
Inverter
Inverter
The inverter is on and supplies
power to the load.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The nominal output of the inverter is
exceeded. The overloadLED
flashes
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Inverter
The inverter is switched off due to
overload or short circuit.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The battery is almost fully
exhausted.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Inverter
The inverter has switched off due to
low battery voltage.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The internal temperature is reaching
a critical level.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
7
EN NL FR DE FI SE Appendix
Charger
Inverter
The inverter has switched off due to
the electronics temperature being
too high.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
-If the LEDs are flashing alternately,
the battery is nearly exhausted and
the nominal output is exceeded.
-If overloadand low batteryflash
simultaneously, the ripple voltage
on the battery terminals is too high.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The inverter switched off due to
excess ripple voltage on the battery
terminals.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Battery Charger
Charger
Inverter
The AC input voltage is switched
through and the charger operates in
bulk mode.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The mains voltage is switched
through and the charger is on.
The set absorption voltage,
however, has not yet been reached.
(BatterySafe mode)
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The mains voltage is switched
through and the charger operates in
absorption mode.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
8
Charger
Inverter
The mains voltage is switched
through and the charger operates in
float mode.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Charger
Inverter
The mains voltage is switched
through and the charger operates in
equalize mode.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Special Indications
PowerControl
Charger
Inverter
The AC input is switched through.
The AC output current is equal to
the preset maximum input current.
The charge current is reduced to 0.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
Power Assist
Charger
Inverter
The AC input is switched through
but the load requires more current
than the preset maximum input
current. The inverter is switched on
to supply the required additional
current.
Mains on
on
Inverter on
Bulk
Overload
off
Absorption
Low battery
charger
only
Float
Temperature
For more error codes see section 7.3
For the latest and most up to date information about the blink codes,
please refer to the Victron Toolkit app.
Click on or scan the QR code to get to the Victron Support and
Downloads/Software page.
9
EN NL FR DE FI SE Appendix
4. INSTALLATION
This product may only be installed by a qualified electrical engineer.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at
least 10 cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
Never position the appliance directly above the batteries.
The MultiPlus-II is suitable for wall mounting. A solid surface, suitable for the weight and dimensions of the product must be available
(e.g., concrete, or masonry). For mounting purposes, a hook and two holes are provided at the back of the casing (see appendix G).
The device can be fitted either horizontally or vertically. For optimal cooling, vertical fitting is preferred.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should
be used. See table.
12/3000/120
24/3000/70
48/3000/35
48/5000/70
48/8000/110
48/10000/140
Recommended battery capacity (Ah)
4001200
200-700
100400
200-800
200800
250 - 1000
Recommended DC fuse
400 A
300 A
125 A
200 A
300 A
400 A
Recommended cross section (mm2)
per + and - connection terminal *, **
0 5 m***
2x 50 mm
2
50 mm
2
35 mm
2
70 mm
2
2x 50 mm
2
2x 50 mm
2
5 10 m***
2x 70 mm2
95 mm2
70 mm2
2x70mm2
2x 70 mm2
2x 70 mm2
* Follow local installation rules.
** Do not locate battery cables in a closed conduit.
*** “2x” means two positive and two negative cables.
Remark: Internal resistance is the important factor when working with low capacity batteries. Please consult your supplier or the relevant
sections of our book Energy Unlimited, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use a torque wrench with insulated box spanner in order to avoid shorting the
battery.
Recommended torque: 12 Nm (M8 nut)
Avoid shorting the battery cables.
Undo the two screws at the bottom of the enclosure and remove the service panel.
Connect the battery cables: see Appendix A.
Tighten the nuts well for minimal contact resistance.
10
4.3 Connection of the AC cabling
The MultiPlus-II is a safety class I product (supplied with a ground terminal
for safety purposes). Its AC input and/or output terminals and/or
grounding point on the outside of the product must be provided with
an uninterruptible grounding point for safety purposes.
The MultiPlus-II is provided with a ground relay (relay H, see appendix B)
that automatically connects the Neutral output to the chassis if no
external AC supply is available. If an external AC supply is provided, the
ground relay H will open before the input safety relay closes. This ensures
the correct operation of an earth leakage circuit breaker that is connected
to the output.
In a fixed installation, an uninterruptable grounding can be secured by
means of the grounding wire of the AC input. Otherwise the casing
must be grounded.
In a mobile installation (for example, with a shore current plug),
interrupting the shore connection will simultaneously disconnect the
grounding connection. In that case, the casing must be connected to
the chassis (of the vehicle) or to the hull or grounding plate (of the
boat).
In case of a boat, direct connection to the shore ground is not
recommended because of potential galvanic corrosion. The solution to this
is using an isolation transformer.
Recommended torque: 1.6 Nm
The terminal blocks can be found on the printed circuit board, see Appendix A.
Do not invert neutral and phase when connecting the AC.
The inverter does incorporate a mains frequency isolating transformer. This precludes the possibility of DC current at any AC port.
Therefore type A RCD’s can be used.
AC-in
The AC input cable can be connected to the terminal block ACin.
From left to right: “N” (neutral), “PE” (earth) and “L” (phase)
The AC input must be protected by a fuse or magnetic circuit breaker rated at 32 A( for 3 kVA model), 50 A( for 5 kVA
model) and 100 A( for 8 kVA and 10 kVA model) or less, and cable cross-section must be sized accordingly. If the input AC
supply is rated at a lower value, the fuse or magnetic circuit breaker should be down sized accordingly.
AC-out-1
The AC output cable can be connected directly to the terminal block AC-out’.
From left to right: “N” (neutral), “PE” (earth) and “L” (phase)
With its PowerAssist feature the Multi can add up to 3 kVA (that is 3000 / 230 = 13 A) to the output during periods of peak power
requirement. Together with a maximum input current of 32 A this means that the output can supply up to 32 + 13 = 45 A.
An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be included in series with the
output, and cable cross-section must be sized accordingly.
AC-out-2
A second output is available that disconnects its load in the event of battery operation. On these terminals, equipment is connected
that may only operate if AC voltage is available on AC-in-1, e.g. an electric boiler or an air conditioner. The load on AC-out-2 is
disconnected immediately when the Quattro switches to battery operation. After AC power becomes available on AC-in-1, the load
on AC-out-2 will be reconnected with a delay of approximately 2 minutes. This to allow a genset to stabilise.
4.4 Optional Connections
A number of optional connections are possible:
4.4.1 Remote Control
The product can be remotely controlled in two ways.
With an external switch (connection terminal M, see appendix A). Operates only if the switch on the MultiPlus-II is set to “on”.
With a Multi Control panel (connected to one of the two RJ45 sockets L, see appendix A). Operates only if the switch on the
MultiPlus-II is set to “on”.
4.4.2. Programmable relay
The product is equipped with a programmable relay.
The relay can be programmed for all kinds of other applications however, for example as a starter relay for a generator.
4.4.3 Programmable analog/digital input/output ports
The product is equipped with 2 analog/digital input/output ports.
These ports can be used for several purposes. One application is communication with the BMS of a lithium-ion battery.
4.4.4 Starter battery (connection terminal E, see appendix A)
The Multiplus-II has a connection for charging a starter battery. Output current is limited to 4 A.
11
EN NL FR DE FI SE Appendix
4.4.5 Voltage sense (connection terminal J, see appendix A)
For compensating possible cable losses during charging, two sense wires can be connected with which the voltage directly on the
battery or on the positive and negative distribution points can be measured. Use wire with a cross-section of 0,75 mm².
During battery charging, the Quattro will compensate the voltage drop over the DC cables up to a maximum of 1 Volt (i.e. 1 V over the
positive connection and 1 V over the negative connection). If the voltage drop threatens to become larger than 1 V, the charging current
is limited in such a way that the voltage drop remains limited to 1 V.
4.4.6 Temperature sensor (connection terminal J, see appendix A)
For temperature-compensated charging, the temperature sensor (supplied with the Quattro) can be connected. The sensor is isolated
and must be fitted to the negative terminal of the battery.
4.4.7 Parallel Connection
Up to six identical units can be connected in parallel. When connecting MultiPlus-II units in parallel, the following requirements must be
met:
All units must be connected to the same battery
A maximum of six units connected in parallel.
Only identical devices may be connected in parallel.
The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the connection between the batteries and the DC
distribution point must at least equal the sum of the required cross-sections of the connections between the distribution point and
the MultiPlus-II units.
Place the MultiPlus-II units close to each other, but allow at least 10cm for ventilation purposes under, above and beside the units.
It is essential the negative battery terminal between the units is always connected. A fuse or circuit breaker is not allowed.
UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection or splitter boxes are not
permitted.
Always interconnect the negative battery cables before placing the UTP cables.
Only one remote control means (panel or switch) can be connected to the system.
4.4.8 Three-phase operation
The MultiPlus-II can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made by means of
standard RJ45 UTP cables (the same as for parallel operation). The system (MultiPlus-II plus an optional control panel) will require
subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.5.
1. Note: the MultiPlus-II is not suitable for 3-phase delta (Δ) configuration.
2. When the AS4777.2 grid code has been selected in VEConfigure, only 2 units in parallel per phase are allowed in a three
phase system.
12
5. CONFIGURATION
This section is intended mainly for stand-alone applications
For grid connected Energy Storage Systems (ESS) please see https://www.victronenergy.com/live/ess:start
Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.
5.1 Standard settings: ready for use
On delivery, the MultiPlus-II is set to standard factory values. In general, these settings are suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard MultiPlus-II factory settings
Inverter frequency 50 Hz
Input frequency range 45 65 Hz
Input voltage range 180 265 VAC
Inverter voltage 230 VAC
Stand-alone / parallel / 3-phase stand-alone
AES (Automatic Economy Switch) off
Ground relay on
Charger on/ off on
Battery charge curve four-stage adaptive with BatterySafe mode
Charging current 100% of the maximum charging current
Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 28.8 V / 57.6 V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 27.6 V / 55.2 V
Storage voltage 26.4 V / 52.8 V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection on
AC input current limit 32 A for 3kVA and 50 A for 8kVA and 10kVA (= adjustable current limit for
PowerControl and PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Programmable relay alarm function
PowerAssist on
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software
configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50 Hz; 60 Hz
Input frequency range
Input frequency range accepted by the MultiPlus-II. The MultiPlus-II synchronises within this range with the AC input frequency. The
output frequency is then equal to the input frequency.
Adjustability: 45 65 Hz; 45 55 Hz; 55 65 Hz
Input voltage range
Voltage range accepted by the MultiPlus-II. The MultiPlus-II synchronises within this range with the AC input. The output voltage is then
equal to the input voltage.
Adjustability: Lower limit: 180 230 V
Upper limit: 230 270 V
Note: the standard lower limit setting of 180 V is intended for connection to a weak mains supply, or to a generator with unstable AC
output. This setting may result in a system shut down when connected to a ‘brushless, self excited, externally voltage regulated,
synchronous AC generator’ (synchronous AVR generator). Most generators rated at 10 kVA or more are synchronous AVR generators.
The shut down is initiated when the generator is stopped and revs down while the AVR simultaneously ‘tries’ to keep the output voltage
of the generator at 230 V.
The solution is to increase the lower limit setting to 210 VAC (the output of AVR generators is generally very stable), or to disconnect
the MultiPlus-II from the generator when a generator stop signal is given (with help of an AC contactor installed in series with the
generator).
13
EN NL FR DE FI SE Appendix
Inverter voltage
Output voltage of the MultiPlus-II in battery operation.
Adjustability: 210 245 V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
increase total inverter power (several devices in parallel)
create a split-phase system with a separate autotransformer: see VE autotransformer datasheet and manual
create a 3-phase system.
The standard product settings are for standalone operation. For parallel, three-phase or split phase operation see section 5.3.
AES (Automatic Economy Switch)
If this setting is turned ‘on’, the power consumption in no-load operation and with low loads is decreased by approx. 20 %, by slightly
'narrowing' the sinusoidal voltage. Applicable in stand-alone configuration only.
Search Mode
Instead of the AES mode, the search mode can also be chosen. If search mode is ‘on’, the power consumption in no-load operation is
decreased by approx. 70 %. In this mode the MultiPlus-II, when operating in inverter mode, is switched off in case of no load or very low
load, and switches on every two seconds for a short period. If the output current exceeds a set level, the inverter will continue to
operate. If not, the inverter will shut down again.
The Search Mode shut downand remain onload levels can be set with VEConfigure.
The standard settings are:
Shut down: 40 Watt (linear load)
Turn on: 100 Watt (linear load)
Ground relay (see appendix B)
With this relay, the neutral conductor of the AC output is grounded to the chassis when the back feed safety relays are open. This
ensures the correct operation of earth leakage circuit breakers in the output. If required an external ground relay can be connected (for a
split-phase system with a separate autotransformer). See appendix A.
Battery charge algorithm
The standard setting is ‘Four-stage adaptive with BatterySafe mode’. See Section 2 for a description.
This is the recommended charge algorithm for lead acid batteries. See the help files in the software configuration programs for other
features.
Battery type
The standard setting is the most suitable for Victron Gel Deep Discharge, Gel Exide A200, and tubular plate stationary batteries (OPzS).
This setting can also be used for many other batteries: e.g. Victron AGM Deep Discharge and other AGM batteries, and many types of
flat-plate flooded batteries.
With VEConfigure the charge algorithm can be adjusted to charge any battery type (Nickel Cadmium batteries, Lithium-ion batteries)
Absorption time
In case of the standard setting ‘Four-stage adaptive with BatterySafe mode’ the absortion time depends on the bulk time (adaptive
charge curve), so that the battery is optimally charged.
Automatic equalisation charging
This setting is intended for flooded tubular plate traction or OPzS batteries. During absorption the voltage limit increases to 2,83 V/cell
(34 V for a 24 V battery) once the charge current has tapered down to less than 10 % of the set maximum current.
Not adjustable with DIP switches.
See ’tubular plate traction battery charge curve’ in VEConfigure.
Storage voltage, Repeated Absorption Time, Absorption Repeat Interval
See Section 2.
Bulk Protection
When this setting is ‘on’, the bulk charging time is limited to 10 hours. A longer charging time could indicate a system error (e.g. a
battery cell short-circuit).
AC input current limit
These are the current limit settings for which PowerControl and PowerAssist come into operation:
12/3000/120-32
24/3000/70-32
48/3000/35-32
48/5000/70-50 48/8000/110 48/10000/140
PowerAssist setting range, grid in-line topology
4 A 32 A
6 A 50 A
11 A 100 A
11 A 100 A
PowerAssist setting range, grid parallel topology
with external current transformer
4 A 50 A 6 A 100 A 11 A 100 A 11 A 100 A
Factory setting: maximum grid in-line topology value.
14
UPS feature
If this setting is ‘on’ and AC on the input fails, the MultiPlus-II switches to inverter operation practically without interruption.
The output voltage of some small generator sets is too unstable and distorted for using this setting the MultiPlus-II would continually
switch to inverter operation. For this reason, the setting can be turned off. The MultiPlus-II will then respond less quickly to AC input
voltage deviations. The switchover time to inverter operation is consequently slightly longer, but most equipment (most computers,
clocks or household equipment) is not adversely impacted.
Recommendation: Turn the UPS feature off if the MultiPlus-II fails to synchronise, or continually switches back to inverter operation.
Dynamic current limiter
Intended for generators, the AC voltage being generated by means of a static inverter (so-called ‘inverter’ generators). In these
generators, engine rpm is reduced in case of low load: this reduces noise, fuel consumption and pollution. A disadvantage is that the
output voltage will drop severely or even completely fail in the event of a sudden load increase. More load can only be supplied after the
engine is up to speed.
If this setting is ‘on’, the MultiPlus-II will start supplying extra power at a low generator output level and gradually allow the generator to
supply more, until the set current limit is reached. This allows the generator engine to get up to speed.
This setting is also often used for ‘classical’ generators that respond slowly to sudden load variation.
Weak AC
Strong distortion of the input voltage can result in the charger hardly operating or not operating at all. If WeakAC is set, the charger will
also accept a strongly distorted voltage, at the cost of greater distortion of the input current.
Recommendation: Turn WeakAC on if the charger is hardly charging or not charging at all (which is quite rare!). Also turn on the
dynamic current limiter simultaneously, and reduce the maximum charging current to prevent overloading the generator if necessary.
Note: when WeakAC is on, the maximum charge current is reduced by approximately 20 %.
BoostFactor
Change this setting only after consulting with Victron Energy or with an engineer trained by Victron Energy!
Programmable relay
The relay can be programmed for all kinds of other applications, for example as a starter relay for a generator.
Auxiliary AC output (AC-out-2)
Intended for non-critical loads and directly connected to the AC input. With current measurement circuit to enable PowerAssist.
5.3 Configuring the MultiPlus-II
The following hardware is required:
A MK3-USB (VE.Bus to USB) interface.
Alternatively, the Interface MK2.2b (VE.Bus to RS232) can be used (RJ45 UTP cable needed).
5.3.1 VE.Bus Quick Configure Setup
VE.Bus Quick Configure Setup is a software program with which systems with a maximum of three Multis (parallel or three phase
operation) can be configured in a simple manner.
The software can be downloaded free of charge at www.victronenergy.com.
5.3.2 VE.Bus System Configurator
For configuring advanced applications and/or systems with four or more Multis, VE.Bus System Configurator software must be used.
The software can be downloaded free of charge at www.victronenergy.com .
15
EN NL FR DE FI SE Appendix
6. MAINTENANCE
The MultiPlus-II does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and
oil/soot/vapours, and keep the device clean.
7. ERROR INDICATIONS
With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your Victron Energy
supplier.
We recommend to use the toolkit app to link LED alarm codes to a description of the problem/alarm, see
https://www.victronenergy.com/support-and-downloads/software#victron-toolkit-app
7.1 General error indications
Problem
Cause
Solution
No output voltage on
AC-out-2.
MultiPlus-II in inverter mode
Multi will not switch over to
generator or mains
operation.
Circuit breaker or fuse in the
AC-in input is open as a result of
overload.
Remove overload or short
circuit on AC-out-1 or AC-out-
2, and reset fuse/breaker.
Inverter operation not
initiated when switched on.
The battery voltage is
excessively high or too low. No
voltage on DC connection.
Ensure that the battery voltage
is within the correct range.
Low batteryLED flashes.
The battery voltage is low.
Charge the battery or check
the battery connections.
Low batteryLED lights.
The converter switches off
because the battery voltage is
too low.
Charge the battery or check
the battery connections.
OverloadLED flashes.
The converter load is higher than
the nominal load.
Reduce the load.
OverloadLED lights.
The converter is switched off due
to excessively high load.
Reduce the load.
TemperatureLED flashes
or lights.
The environmental temperature
is high, or the load is too high.
Install the converter in cool
and well-ventilated
environment, or reduce the
load.
Low batteryand overload
LEDs flash intermittently.
Low battery voltage and
excessively high load.
Charge the batteries,
disconnect or reduce the load,
or install higher capacity
batteries. Fit shorter and/or
thicker battery cables.
Low batteryand overload
LEDs flash simultaneously.
Ripple voltage on the DC
connection exceeds 1,5 Vrms.
Check the battery cables and
battery connections. Check
whether battery capacity is
sufficiently high, and increase
this if necessary.
Low batteryand overload
LEDs light.
The inverter is switched off due
to an excessively high ripple
voltage on the input.
Install batteries with a larger
capacity. Fit shorter and/or
thicker battery cables, and
reset the inverter (switch off,
and then on again).
16
One alarm LED
lights and the
second flashes.
The inverter is switched off due to
alarm activation by the lighted LED.
The flashing LED indicates that the
inverter was about to switch off due
to the related alarm.
Check this table for appropriate
measures in regard to this alarm
state.
The charger does
not operate.
The AC input voltage or frequency is
not within the range set.
Ensure that the AC input is between
185 VAC and 265 VAC, and that the
frequency is within the range set
(default setting 45-65 Hz).
Circuit breaker or fuse in the
AC-in input is open as a result of
overload.
Remove overload or short circuit on
AC-out-1 or AC-out-2, and reset
fuse/breaker.
The battery fuse has blown.
Replace the battery fuse.
The distortion or the AC input voltage is
too large (generally generator supply).
Turn the settings WeakAC and
dynamic current limiter on.
The charger does
not operate.
BulkLED flashes
and
Mains onLED
illuminates.
MultiPlus-II is in Bulk protectionmode
thus, the maximum bulk charging time
of 10 hours is exceeded.
Such a long charging time could
indicate a system error (e.g. a battery
cell short-circuit).
Check your batteries.
NOTE:
You can reset the error mode by
switching off and back on the
MultiPlus-II.
The standard MultiPlus-II factory
setting of the Bulk protectionmode
is switched on. The Bulk protection
mode can be switched off with help of
VEConfigure only.
The battery is not
completely charged.
Charging current excessively high,
causing premature absorption phase.
Set the charging current to a level
between 0.1 and 0.2 times the battery
capacity.
Poor battery connection.
Check the battery connections.
The absorption voltage has been set to
an incorrect level (too low).
Set the absorption voltage to the
correct level.
The float voltage has been set to an
incorrect level (too low).
Set the float voltage to the correct
level.
The available charging time is too short
to fully charge the battery.
Select a longer charging time or
higher charging current.
The absorption time is too short. For
adaptive charging this can be caused
by an extremely high charging current
with respect to battery capacity, so that
bulk time is insufficient.
Reduce the charging current or select
the ‘fixed’ charging characteristics.
The battery is
overcharged.
The absorption voltage is set to an
incorrect level (too high).
Set the absorption voltage to the
correct level.
The float voltage is set to an incorrect
level (too high).
Set the float voltage to the correct
level.
Poor battery condition.
Replace the battery.
The battery temperature is too high
(due to poor ventilation, excessively
high environmental temperature, or
excessively high charging current).
Improve ventilation, install batteries
in a cooler environment, reduce the
charging current, and connect the
temperature sensor.
The charging
current drops to 0
as soon as the
absorption phase
initiates.
The battery is over-heated (>50 °C)
Install the battery in a cooler
environment
Reduce the charging current
Check whether one of the
battery cells has an internal
short circuit
Defective battery temperature sensor
Disconnect the temperature sensor
plug in the MultiPlus-II. If charging
functions correctly after
approximately 1 minute, the
temperature sensor should be
replaced.
17
EN NL FR DE FI SE Appendix
7.2 Special LED indications
(for the normal LED indications, see section 3.4)
Mains onflashes and there is no output voltage.
The device is in charger onlyoperation and mains supply is present. The
device rejects the mains supply or is still synchronising.
Bulk and absorption LEDs flash synchronously
(simultaneously).
Voltage sense error. The voltage measured at the voltage sense connection
deviates too much (more than 7 V) from the voltage on the positive and
negative connection of the device. There is probably a connection error.
The device will remain in normal operation.
NOTE: If the "inverter on" LED flashes in phase opposition, this is a VE.Bus
error code (see further on).
Absorption and float LEDs flash synchronously
(simultaneously).
The battery temperature as measured has an extremely unlikely value. The
sensor is probably defective or has been incorrectly connected. The device
will remain in normal operation.
NOTE: If the "inverter on" LED flashes in phase opposition, this a VE.Bus
error code (see further on).
7.3 VE.Bus LED indications
Equipment included in a VE.Bus system (a parallel or 3-phase arrangement) can provide so-called VE.Bus LED indications. These LED
indications can be subdivided into two groups: OK codes and error codes.
7.3.1 VE.Bus OK codes
If the internal status of a device is in order but the device cannot yet be started because one or more other devices in the system
indicate an error status, the devices that are in order will indicate an OK code. This facilitates error tracing in a VE.Bus system, since
devices not requiring attention are easily identified as such.
Important: OK codes will only be displayed if a device is not in inverter or charging operation!
A flashing bulkLED indicates that the device can perform inverter operation.
A flashing floatLED indicates that the device can perform charging operation.
NOTE: In principle, all other LEDs must be off. If this is not the case, the code is not an OK code.
However, the following exceptions apply:
The special LED indications above can occur together with the OK codes.
The low batteryLED can function together with the OK code that indicates that the device can charge.
7.3.2 VE.Bus error codes
A VE.Bus system can display various error codes. These codes are displayed with the inverter on, bulk, absorptionand floatLEDs.
To interpret a VE.Bus error code correctly, the following procedure should be followed:
1. The device should be in error (no AC output).
2. Is the inverter onLED flashing? If not, then there is no VE.Bus error code.
3. If one or more of the LEDs bulk, absorptionor floatflashes, then this flash must be in phase opposition to the inverter onLED,
i.e. the flashing LEDs are off if the inverter onLED is on, and vice versa. If this is not the case, then there is no VE.Bus error
code.
4. Check the bulkLED, and determine which of the three tables below should be used.
5. Select the correct column and row (depending on the absorptionand floatLEDs), and determine the error code.
6. Determine the meaning of the code in the tables below.
18
All of the conditions below must be met!:
1. The device is in error! (No AC output)
2. Inverter LED flashes (in opposition to any flashing of the Bulk, Absorption or Float LED)
3. At least one of the LEDs Bulk, Absorption and Float is on or flashing
Bulk LED off Bulk LED flashes Bulk LED on
Absorption LED Absorption LED Absorption LED
off
flashing
on
off
flashing
on
off
flashing
on
Float LED
off 0 3 6
Float LED
Off 9 12 15
Float LED
off 18 21 24
flashing 1 4 7 flashing 10 13 16 flashing 19 22 25
on 2 5 8 On 11 14 17 on 20 23 26
Bulk LED
Absorption LED
Float LED
Code Meaning: Cause/solution:
1
Device is switched off because one of
the other phases in the system has
switched off.
Check the failing phase.
3 Not all, or more than, the expected
devices were found in the system.
The system is not properly configured. Reconfigure the system.
Communication cable error. Check the cables and switch all equipment off,
and then on again.
4 No other device whatsoever detected. Check the communication cables.
5 Overvoltage on AC-out. Check the AC cables.
10 System time synchronisation problem
occurred.
Should not occur in correctly installed equipment. Check the communication
cables.
14 Device cannot transmit data. Check the communication cables (there may be a short circuit).
17
One of the devices has assumed
‘master’ status because the original
master failed.
Check the failing unit. Check the communication cables.
18 Overvoltage has occurred. Check AC cables.
22 This device cannot function as ‘slave’. This device is an obsolete and unsuitable model. It should be replaced.
24 Switch-over system protection initiated.
Should not occur in correctly installed equipment. Switch all equipment off,
and then on again. If the problem recurs, check the installation.
Possible solution: increase lower limit of AC input voltage to 210 VAC
(factory setting is 180 VAC)
25
Firmware incompatibility. The firmware
of one the connected devices is not
sufficiently up to date to operate in
conjunction with this device.
1) Switch all equipment off.
2) Switch the device returning this error message on.
3) Switch on all other devices one by one until the error message reoccurs.
4) Update the firmware in the last device that was switched on.
26 Internal error. Should not occur. Switch all equipment off, and then on again. Contact
Victron Energy if the problem persists.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138

Victron energy MultiPlus-II Manuel utilisateur

Taper
Manuel utilisateur