Eaton Crouse-Hinds eLLB 20436 Mode d'emploi

Taper
Mode d'emploi
Explosionsgeschützte Deckeneinbauleuchten
eLLB 20.. /eLLB 20.. V-CG-S
Explosion Protected Recessed Ceiling light fittings
eLLB 20.. /eLLB 20.. V-CG-S
Luminaires dans le plafond pour atmosphères explosives
eLLB 20.. /eLLB 20.. V-CG-S
Betriebsanleitung
Operating instructions
Mode d’emploi
300 8000 1447 D/GB/F (m)
CROUSE-HINDS
SERIES
I
E
C
6
0
0
7
9
-
7
:
2
0
1
4
2
Schaltplan Serie / Wiring diagram series / Schéma des connexions, série
Elektrische Daten / Electrical data / Caractéristiques électriques:
Ausführung / Version / Modèle
2 x 18 W
(4 x 18 W)
2 x 36 W
(4 x 36 W)
2 x 58 W 2 x 18 W
V-CG-S
(4 x 18 W
V-CG-S)
2 x 36 W
V-CG-S
(4 x 36W
V-CG-S)
2 x 58 W
V-CG-S
Spannungsbereich AC / voltage
range AC / Gamme des tensions CA
110- 254 V 110 - 254 V 220 - 254 V 220 - 254 V 220 - 254 V 220 - 254 V
Frequenzbereich / Frequency range /
Gamme des fréquences
50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60Hz 50 - 60 Hz 50 - 60 Hz
Spannungsbereich DC / Voltage range DC
/ Gamme des tensions CC
110 - 250 V 110 - 250 V 195 - 250 V 195 - 250 V 195 - 250 V 195 - 250 V
kurzzeitige Überspannung AC/DC /
Transient excess voltage AC/DC /
Surtension transitoire CA/CC
<350 V
B
emessungsstrom in A / Rated current A
Courant nom. en A avec:
230 V AC
220 V DC
0,1
8(0,36)
0,19 (0,37)
0,34(0,68)
0,35 (0,69)
0,53 (1,06)
0,54 (1,07)
0,19 (0,37)
0,11 (0,12)
0,35 (0,69)
0,19 (0,20)
0,54
0,27
eLLB 20018/18; eLLB 20036/36; eLLB 20058/58
eLLB 20018/18 V-CG-S eLLB 20036/36 V-CG-S; eLLB 20058/58 V-CG-S
Durchgangsverdrahtung optional
through wiring optional
Durchgangsverdrahtung optional
through wiring optional
Lampe wird im DC Betrieb augeschalten/
Lamp would be shut off at DC mode
V-CG-S
Modul
Lampe 1 / lamp 1
Lampe 2 / lamp 2
Lampe 1 / lamp 1 Netzlampe
Lampe 2 / lamp 2 Notlampe
3
Schaltplan Serie / Wiring diagram series / Schéma des connexions, série
eLLB 20 4x18; 4 eLLB 20 4x36
eLLB 20 4x18 V-CG-S; 4 eLLB 20 4x36 V-CG-S
Durchgangsverdrahtung optional
through wiring optional
Durchgangsverdrahtung optional
through wiring optional
Lampe wird im DC Betrieb augeschalten/
Lamp would be shut off at DC mode
Lampe wird im DC Betrieb augeschalten/
Lamp would be shut off at DC mode
V-CG-S
Modul
Lampe 1 / lamp 1 Netzlampe
Lampe 2 / lamp 2 Notlampe
Lampe 3 / lamp 3 Netzlampe
Lampe 4 / lamp 4 Notlampe
Lampe 1 / lamp 1
Lampe 2 / lamp 2
Lampe 3 / lamp 3
Lampe 4 / lamp 4
4
Montagebilder/Maßzeichnung /
Illustrations for mounting/Dimensional drawing /
Illustrations du montage
1
5
9
2
6
3
7
4
8
18 W - 352/ 36 W u. 58 W 750
5
D
Explosionsgeschützte Deckeneinbauleuchten
eLLB 20.. /eLLB 20.. V-CG-S
2. Technische Daten
EU-Baumusterprüfbescheinigung: DMT 02 ATEX E 069
Gerätekennzeichnung nach 2014/34/EU und Norm
EN 60079-0
II 2 G Ex d e IIC T4 Gb
(V-CG-S Version)
II 2 G Ex d e mb ib IIC T4 Gb
II 2 D Ex tb IIIC T80°C Db
IECEx Konformitätsbescheinigung: IECEx BVS 14.0091
Gerätekennzeichnung nach IEC 60079-0: Ex d e IIC T4 Gb
(V-CG-S Version) Ex d e mb ib IIC T4 Gb
Ex tb IIIC T80°C Db
Schutzklasse nach EN/IEC 61140 I
Schutzart nach EN/IEC 60529 IP66
zulässige Umgebungstemperatur
(1)
eLLB 20 ... -25 °C bis +50 °C
eLLB 20058/58; -25 °C bis +40 °C
Lagertemperatur in der Originalverpackung -25 °C bis +50 °C
Lampenbestückung:
Leuchtstofflampen mit
Zweistiftlampenfassung G13 nach
eLLB 20 .18...
eLLB 20 .36...
eLLB 20058...
EN/IEC 60081-22/20
EN/IEC 60081-24/20
EN/IEC 60081-21/22
Klemmv
ermögen Anschlussklemme
2x je Klemme
einadrig
mehradrig
min. 1,5 mm
2
1,5 mm
2
max. 6,0 mm
2
6,0 mm
2
Leiterquerschnitt bei Durchgangsverdrahtung 2,5 mm
2
für max. 16 A
Ex-e-Kabel- und Leitungseinführung
Standardausführung M25 x 1,5
geeignete Leitungen und Prüfdrehmomente
der Druckschraube
Ø Nm
Dicht
ung 1+2+3
1 2
3
min. 8,0 1,5
max.
(2)
10,0 2,0
Dichtung 1+2
1 2
3
min. 10,0 2,3
max.
(2)
13,0 2,6
Dichtung 1
1 2
3
min. 13,5 1,3
max.
(2)
1 7, 5 2,3
Prüfdrehmomente Einschraubgewinde 3,0 Nm
Metall M20 x 1,5 Innengewinde
Prüfdrehmoment für Schlitzschraube der Scheibe 1,5 Nm
Gewicht
18 / 36 / 58 W (2-lampig.) ca. 15 / 22 / 26 kg
18 / 36 W (4-lampig) ca. 25 / 34 kg
(1)
Intensive Sonneneinstrahlung in Regionen mit hohen Umgebungstemperaturen kann im Leuchten inneren zu
unzulässig hohen Erwärmungen führen. Eine Reduzierung der Lebensdauer des EVGs kann eine Folge
hiervon sein. Zur Vermeidung sollten in diesen Regionen tagsüber die Leuchten über einen Lichtsensor
geschaltet werden.
(2)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann
der Klemmbereich variieren. Bitte verwenden Sie im Zwischenbereich eine geeignete Kombination aus
Dichtungen, so dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
1. Sicherheitshinweise:
Zielgruppe:
Elektrofachkräfte und geeignet
qualifizierte, unterwiesene
Personen gemäß den nationalen Rechts-
vorschriften, einschließlich der einschlägi-
gen Normen für elektrische Geräte in
explosionsgefährdeten Bereichen
(EN/IEC 60079-14).
Die Leuchte darf nicht in den Zonen 0 und
20 eingesetzt werden!
Die Anforderungen der EN/IEC 60079-31
u.a. in Bezug auf übermäßige Staubablage-
rungen und Temperatur, sind vom
Anwender zu beachten.
Die auf der Leuchte angegebenen
technischen Daten sind zu beachten!
Umbauten oder Veränderungen an der
Leuchte sind nicht zulässig!
Die Leuchte ist bestimmungsgemäß in
unbeschä digtem und einwandfreiem
Zustand zu betreiben!
Als Ersatz dürfen nur Originalteile von
Cooper Crouse-Hinds (CCH) / EATON
verwendet werden!
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von CCH / EATON
oder einer qualifizierten „Elektrofachkraft“
durchgeführt werden!
Lassen Sie diese Betriebsanleitung
während des Betriebes nicht in der
Leuchte!
Beachten Sie die nationalen Unfall-
verhütungs- und Sicherheitsvorschriften
und die nachfolgenden Sicherheitshinwei-
se, die in dieser Betriebsanleitung mit
einem ( ) gekennzeichnet sind!
6
D
Explosionsgeschützte Deckeneinbauleuchten
eLLB 20.. /eLLB 20.. V-CG-S
Klemmen Sie die Leitungen an den
Anschluss klemmen PE, N, L1, (L, L2, L3)
gemäß Klemmenbezeichnung an. (siehe
Schaltplan, Seite 2+3) Bei Einfachbelegung
der Klemmen kein Umbiegen (Schlaufe) der
Adern notwendig!
Ziehen Sie auch nicht benutzte Klemmen an!
Nur festverlegte Leitungen zulässig! Bei
Verwendung anderer Leitungseinführungen
sind die Angaben des Herstellers hinsichtlich
Klemmvermögen und Zugentlastung zu
beachten!
Bei nicht benutzten Kabel-und Leitungseinfüh-
rungen ist die Schutzscheibe zu entfernen und
durch einen Verschlussstopfen (Prüfdrehmo-
ment siehe Techn. Daten) zu verschließen.
Beim Verschließen mit einem Verschlussstopfen
die Dichtungseinsätze 1 und 2 verwenden!
Bei Metall-Kabeleinführungen sind die
Schutzkappen der nicht benutzten Einführungen
zu entfernen und durch bescheinigte Ex-Ver-
schlussstopfen (min. IP 66) zu verschließen!
Einsetz
en der Lampe:
Verwenden Sie nur solche Lampen,
die für diese Leuchten zugelassen sind,
siehe Technische Daten und Typenschild!
Achtung: Sicherheitstechnische Hinweise
des Lampenherstellers beachten
Zweistiftsockellampe (G13)
Lampe in beide Fassungen bis zum Anschlag
einstecken, siehe Bild 7 so dass an jeder Seite
der Lampe beide Stifte im Eingriff der Fassung
sind.
Danach die Lampe um 90° in Raststellung
drehen, siehe Bild 8, wobei die grüne Fläche in
der Fassung sichtbar wird. Die Lampe ist nun
gegen Herausfallen gesichert.
Installation der Leuchte mit V-CG-S - Modul:
siehe Seite 11.
5. Inbetriebnahme
Überprüfen Sie vor der Inbetriebnahme die
korrekte Funktion und Installation der Leuchte
in Übereinstimmung mit dieser Betriebsanlei-
tung und anderen zutreffenden Bestimmun-
gen!
Führen Sie Isolationsmessungen nur
zwischen PE und Außenleiter L1 (L,L2,L3)
sowie zwischen PE und N durch!
– Messspannung: max. 1 kV AC/DC
– Messstrom: max. 10 mA
3. Normenkonformität
Diese Leuchte ist zum Einsatz in explosionsge-
fährdeten Bereichen der Zone 1,2, 21 und 22
gemäß EN/IEC 60079-10-1 und
EN/IEC 60079-10-2 geeignet.
Sie entspricht den aufgeführten Normen, in der
separat beigelegten Konformitätserklärung.
Verweise auf Normen und Richtlinien in dieser
Betriebsanleitung beziehen sich immer auf die
aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4. Installation
Halten Sie die für das Errichten und
Betreiben von explosionsgeschützten
elektrischen Betriebsmitteln geltenden
Sicherheitsvorschriften gemäß des Geräte-
sicherheitsgesetzes sowie die allgemein
anerkannten Regeln der Technik ein
(EN/IEC 60079-14)!
Transport und Lagerung der Leuchte ist nur in
Originalverpackung und angegebener Lage
gestattet!
Öffnen und Schließen der Leuchte
Die Schlitzschrauben mit geeignetem
Schraubendreher lösen und Schutzscheibe
abklappen, siehe Bild 1 und 2.
Zum Schließen der Schutzscheibe Schrauben
nur handfest anziehen.(Prüfdrehmoment:
1,5 Nm)
Montag
eabmessungen: siehe Bild 9
Deckeneinbau
Zum Deckeneinbau in ausreichend tragfähige
Deckenkonstruktionen sind die seitlichen
Befestigungslaschen (4 x bei 18 W/ 6 x bei
36/8 x bei 58 W) mit einem Sechskantschrau-
bendreher SW4 durch die Löcher in der
R
ahmenblende fest anzuziehen. Die Löcher
sind danach mit beigefügtem Verschlussstopfen
zu verschließen.
Beachten Sie die Maße für
den Deckenausschnitt!
Zusätzlich bieten die beiden Gewindebohrun-
gen M8 x 18 mm tief eine ausreichende
B
efestigungsmöglichkeit.
Verwenden Sie keine zu langen Schrauben!
Montagezubehör:
s. CCH / EATON Katalog.
Netzanschluss
Zum Öffnen des Anschlussraumes grünen
Drehgriff in Pfeilrichtung bis zum Anschlag
drehen, dann ziehen und die Klappe abklappen,
siehe Bild 5 und 6.
- Die Leitung durch die Ex-Kabel- und
Leitungseinführung einführen (Bild 5).
Für Leitungen von Ø 8 bis 10 mm
Dichtungsein sätze 1,2 und 3, von Ø 10 bis 13
mm Dichtungsein sätze 1 und 2 und von
Ø 13,5 bis 17,5 mm Dichtungsein satz 1
verwenden.
6. Instandhaltung
Halten Sie die für die Instandhaltung,
Wartung und Prüfung von explo sions-
geschützten Betriebsmitteln geltenden
Bestimmungen z.B. EN/IEC 60079-17 ein!
Wartung:
Im Rahmen der Wartung sind vor allem die Teile,
von denen die Zündschutzart abhängt, zu
prüfen z.B.:
Gehäuse und Schutzglas auf Risse und
Beschädigungen.
Dichtungen auf Beschädigungen.
Klemmen und Verschlussstopfen auf festen Sitz.
Lampenwechsel:
Beachten Sie für den Lampenwechsel die
Wechselintervalle gemäß Vorgabe der
Lampenhersteller!
Ein Lampenwechsel kann ohne Freischalten
vom Netz durchgeführt werden, da die
Fassungen beim Öffnen der Schutzwanne
durch einen allpoligen Trennschalter span
-
nungsfrei geschaltet werden.
Beachten sie jedoch, dass nationale
V
orschriften oder lokale Anwendungsricht-
linien hiervon abweichend sein können!
7. Instandsetzung
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von CCH / EATON oder
einer qualifizierten Elektrofachkraft in
Übereinstimmung mit national geltenden
Regeln durchgeführt werden.
(EN/IEC 60079-19)
Vor dem Austausch oder der Demontage
von Einzelteilen ist folgendes zu beachten:
Schalten Sie das Betriebsmittel vor dem
Öffnen oder vor Instandhaltungsarbeiten
erst spannungsfr
ei! Benutzen Sie nur von
CCH / EATON freigegebene Ersatzteile!
Siehe Ersatzteilkatalog CCH / EATON.
8. Entsorgung / Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind die
jeweils geltenden nationalen Abfallbeseitigungs-
vorschriften zu beachten.
Zusätzliche Informationen zur Entsorgung des
Produktes können Sie bei Ihrer zuständigen
Cooper Crouse-Hinds / EATON Niederlassung
erfragen.
Programmänderungen und -ergänzungen sind
vorbehalten.
7
GB
Explosion Protected Recessed Ceiling light fittings
eLLB 20.. /eLLB 20.. V-CG-S
1. Safety instructions:
Target group:
For skilled electricians and
suitable qualified, instructed
personnel in accordance with national
legislation, including the relevant
standards and, where applicable, in acc.
with IEC/EN 60079-14 on electrical
apparatus for explosive atmospheres.
The light fitting must not be operated in
zone 0 and 20 hazardous areas!
The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the
user.
The technical data indicated on the light
fitting are to be observed!
Changes of the design and modifications
to the light fitting are not permitted!
The light fitting shall be operated as
intended and only in undamaged and
perfect condition!
Only genuine Cooper Crouse-Hinds (CCH) /
EATON spare parts may be used for
replacement!
Repairs that affect the explosion protection
(see national standard), may only be carried
out by CCH / EATON or a qualified
electrician”!
Do not keep these operating instructions
inside the light fitting during operation!
The national safety rules and regulations
for pre vention of accidents and the
following safety in structions which are
marked with an ( ) in these operating
instruction, will have to be observed!
2. Technical data
EU-Type Examination Certificate: DMT 02 ATEX E 069
Marking acc. to 2014/34/EU and standard:
EN 60079-0
II 2 G Ex d e IIC T4 Gb
(V-CG-S version)
II 2 G Ex d e mb ib IIC T4 Gb
II 2 D Ex tb IIIC T80°C Db
IECEx Certificate of Conformity: IECEx BVS 14.0091
Category of application: IEC60079-0 Ex d e IIC T4 Gb
(V-CG-S version) Ex d e mb ib IIC T4 Gb
Ex tb IIIC T80°C Db
Insulation class to IEC/EN 61140 I
Degree of protection accd. to IEC/EN 60529 IP66
Permissable ambient temperatures
(1)
eLLB 20 ... -25 °C to +50 °C
eLLB 20058/58; -25 °C to +40 °C
Storage temperature in original packing -25 °C to +50 °C
Fluorescent lamps
Bi-pin lamps
eLLB 20 .18...
eLLB 20 .36...
eLLB 20058...
IEC/EN 60081-22/20
IEC/EN 60081-24/20
IEC/EN 60081-21/22
Supply terminal clamping capacity
2 x per terminal
single-wire
multi-wire
min. 1
.5 mm
2
1.5 mm
2
max. 6.0 mm
2
6.0 mm
2
Conductor cross-section with through-wiring 2.5 mm
2
for max. 16 A
Ex-e cable entry
Standard version M25 x 1.5
suitable
c
ables and test torques of the
pressure screw
Ø Nm
Seal 1+2+3
1 2
3
min. 8.0 1. 5
max.
(2)
10.0 2.0
Seal 1+2
1 2
3
min. 10.0 2.3
max.
(2)
13.0 2.6
Seal 1
1 2
3
min. 13.5 1. 3
max.
(2)
1 7. 5 2.3
Test torque for screw in thread cable entry 3.0 Nm
Metal thread M20 x 1.5
Test torque for cover glass pane screw 1.5 Nm
Weight
18 / 36 / 58 W (2-lamps) approx. 15 / 22 / 26 kg
18 / 36 W (4-lamps) approx. 25 / 34 kg
(1)
Intensive sun radiation in areas of high ambient temperatures may cause inadmissible temperature rise inside
of the luminaire. This may result a decrease in lifetime of the electronic ballast (EVG). Therefore those
luminaires should be switched off during daytime by a photocell control
.
(2)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
8
Connect the conductors to the terminals
PE, N, L1, (L, L2, L3) in accordance with
the terminal marking (see wiring diagram,
page 2+3). With single connection of the
terminal no bending (loop) of the conductor
required! Also tighten vacant terminals!
Use only fixed installed cables! If cable
glands of other manufacturer are used the
specifications regarding clamping and strain
relief have to be observed.
In case of unused cable entries, remove their
protective cover and close the entries with a
blanking plug (test torque see technical data).
When closing the gland with a blanking plug,
always use sealing inserts 1+2!
When metal cable entries are used, the
protective caps of the unused entries are to be
removed and the entries to be closed with
certified Ex blanking plugs! (min. IP 66)
Fitting the lamps:
Only use such lamps that have been
certified for these light fittings, see Technical
data and type label! Note! Observe the
safety instructions of the lamp manufacturer!
Bi-pin lamp (G13)
The lamp is to be inserted to its stop into both
holders, see fig. 7, so that both pins on either
side of the lamp engage in the holder.
Then turn the lamp through 90° to its lock-in
position, see fig. 8, the green surface in the
holder getting visible. Now the lamp is secured
against falling out.
Installation of luminaires with
V-CG-S -module:
see page 11
5. Taking into operation
Prior to operation, check the light fitting
for its proper functioning and installation in
compliance with these operating instruc-
tions and other applicable regulations!
Only carry out insulation measurements
between PE and the external conductor L1
(L, L2, L3) as well as between PE and N.
– measuring voltage: max. 1 kV AC/DC
– measuring current: max. 10 mA
3. Conformity with standards
The light fitting is suitable for use in zone 1, 21,
2 and 22 hazardous areas acc. to
IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
The light fitting is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4. Installation
The respective national regulations as
well as the general rules of engineering
which apply to the installation and opera-
tion of explosion protected apparatus will
have to be observed (IEC/EN 60079-14)!
Transport and storage of the luminaire is
permitted in original packing and specified
position only!
Opening and closing the light fitting
Unscrew the slotted screws on the cover
pane and open the pane (see fig. 1 and 2)
To close the glass pane, press tightly onto the
luminaire housing and hand-screw
(Test torque 1.5 Nm)
Mount
ing dimensions: see fig. 9
Recessed ceiling installation
For recessed ceiling installation into sufficient
capable ceilings the mounting lugs (4 x 18 W/
6 x 36 W / 8 x 58 W) have to be screwed with
an Allen key 4 mm through the aperture in the
mount
ing frame. The apertures have to be
sealed with blanking plugs after be used.
Observe the correct ceiling cutout!
When fixing the mounting accessories onto the
light fitting (M8 x 18), observe the max. depth
of thread!
Do not use too long screws!
Accessories for mounting:
See CCH / EATON catalogue.
Mains connection
To open the connection box, turn the green han
-
dle to its stop in the direction of arrow, then pull
it and f
old down the flap, see fig. 5 and 6.
Use sealing inserts 1, 2 and 3 for cables from
8 to 10 mm Ø, sealing inserts 1 and 2 for
cables from 10 to 13 mm Ø and sealing
insert 1 for cables from 13.5 to 17.5 mm Ø.
6. Maintenance
Observe the national regulations
appli cable to the maintenance, servicing and
test of apparatus for explosive atmospheres
e.g IEC/EN 60079-17 as well as the general
rules of engineering!
Servicing:
When servicing, in particular those components
that affect the explosion protection, will have to
be checked, e.g.:
Housing and cover pane for any cracks or
damages.
– Gaskets for their perfect condition.
Terminals and blanking plugs for their firm fit.
Lamp replacement:
Lamp replacement: Keep replacement intervals
as specified by the lamp manufacturer!
Lamp replacement can be done without cut
off the luminaire from mains supply, because
an all pole switch will isolate the lampholders
while opening the protective bowl.
Notice: Observe national standards or directions
f
or use which can be divergent to this!
7. Repair
Repairs that affect the explosion
protection, may only be carried out by CCH /
EATON or a qualified electrician (Competent
person) in compliance with the applicable
national rules (IEC/EN 60079-19).
Prior to replacing or removing any
components, observe the following:
Cut the apparatus off the voltage before
opening it or carrying out repairs! Only use
certified genuine CCH / EATON spare parts
(see CCH / EATON spare parts list)!
8. Disposal/Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed.
In case of disposal you can obtain additional
information from your Cooper Crouse-Hinds /
EATON branch.
Subject to mod
ifications or supplement of the
product range.
GB
Explosion Protected Recessed Ceiling light fittings
eLLB 20.. /eLLB 20.. V-CG-S
9
F
Luminaires dans le plafond pour atmosphères explosives
eLLB 20.. /eLLB 20.. V-CG-S
1. Consignes de sécuritée:
Groupe cible:
Pour les électriciens qualifiés et
les personnels ayant reçu les
formations adéquates, conformément à la
législation nationale en vigueur et, si
applicable, à la norme CEI/EN 60079-14
sur les installations électriques pour les
atmosphères explosives.
Il n’est pas permis d’utiliser le luminaire
dans la zone 0 et 20.
Les exigences des CEI/EN 60079-31 en ce
qui concerne des dépôts de poussière
démesurés et une température doivent
être considérées par I’utilisateur.
Les caractéristiques techniques indiquées
sur le luminaire doivent être respectées!
Il n’est pas permis de transformer ou de
modifier le luminaire!
Le luminaire ne doit être exploité que pour
la fonction qui lui est dévolue et qu’en état
intact et parfait!
Seules des pièces de rechange d’origine
Cooper Crouse-Hinds(CCH) / EATON
doivent être employées pour le remplace-
ment!
Des réparations qui portent sur la
protection contre l’explosion, ne doivent
être exécutées que par CCH / EATON ou
par un «électricien» qualifié!
Ce mode d’emploi ne doit pas être laissé
dans le luminaire pendant son exploitation!
Veuillez respecter les prescriptions
nationales de sécurité et de prévoyance
contre les accidents ainsi que les
consignes de sécurité qui sont marquées
d’un ( ) dans ce mode d’emploi!
2. Caractéristiques techniques
UE-Certificat de Conformité: DMT 02 ATEX E 069
Marquage selon 2014/34/UE et directive:
EN 60079-0
II 2 G Ex d e IIC T4 Gb
(V-CG-S version)
II 2 G Ex d e mb ib IIC T4 Gb
II 2 D Ex tb IIIC T80°C Db
IECEx Certificat de Conformité: IECEx BVS 14.0091
Marquage selon: IEC60079-0 Ex d e IIC T4 Gb
(V-CG-S version) Ex d e mb ib IIC T4 Gb
Ex tb IIIC T80°C Db
Classe d’isolation selon CEI/EN 61140 I
Indice de protection selon CEI/EN 60529
IP66
Température ambiante
(1)
eLLB 20 ... -25 °C à +50 °C
eLLB 20058/58; -25 °C à +40 °C
Température de stockage dans l’emballage
original
-25 °C à +50 °C
Luminaires avec douille de lampe
lampe double broche G13
eLLB 20 .18...
eLLB 20 .36...
eLLB 20058...
CEI/EN
60081-22/20
CEI/EN
60081-24/20
CEI/EN
60081-21/22
Capacité de serrage des bornes,
2 x par borne
unifilaire
multifilaire
min. 1,5 mm
2
1,5 mm
2
max. 6,0 mm
2
6,0 mm
2
Section transversale du conducteur en cas
d’interconnexion
2,5 mm
2
pour 16 A au maxi
Entrée de câble Ex-e M25 x 1,5
pour câbles d’un modèle standard
câbles appropriés et couples d’essai de la vis
de pression
Ø Nm
Garnit
ure 1+2+3
1 2
3
min. 8,0 1,5
max.
(2)
10,0 2,0
Garniture 1+2
1 2
3
min. 10,0 2,3
max.
(2)
13,0 2,6
Garniture 1
1 2
3
min. 13,5 1,3
max.
(2)
1 7, 5 2,3
Couple d' essai pour l’entrée de câble 3,0 Nm
Métal: M20 x 1,5
Couple de contrôle pour fermer l’écran
protecteur
1,5 Nm
Poids des luminaires
18 / 36 / 58 W (2 lampes) env. 15 / 22 / 26 kg
18 / 36 W (4-lampes) env. 25 / 34 kg
(1)
Le rayonnement solaire intensive dans des régions à température ambiante élevée peut provoquer à l’intérieur
du luminaire un échauffement extensif. Ceci peut impliquer une réduction de durée de vie considérable. Pour
pallier à cela, il est préconiser d’utiliser un interrupteur photoélectrique.
(2)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la
possibilité de resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
10
F
Luminaires dans le plafond pour atmosphères explosives
eLLB 20.. /eLLB 20.. V-CG-S
Connecter les câbles aux bornes PE, N, L1,
(L, L2, L3) suivant le repérage des bornes
(voir schéma des con nexions sur page 2+3).
En cas d'occupation simple de la borne, il
n'est pas nécessaire de replier le conducteur
(boucle!) Serrer aussi les bornes non
utilisées!
Utilisez seulement les câbles installés
fixes ! Si des presse-étoupe de câble de
l'autre constructeur sont utilisés on doit
observer les caractéristiques concernant le
serrage et le passe-fils.
En cas d’entrées de câble non utilisées, leur
disque pro tecteur doit être enlevé, et l’entrée
doit être fermée avec un bouchon de fermeture
(voir les Caractéristiques techniques).
En fermant par un bouchon de fermeture,
toujours utiliser les 1+2 joints d’étanchéité
En cas d’entrées de câble métalliques, enlever
les obtura teurs protecteurs des entrées non
utilisées et les fermer avec des bouchons de
fermeture Ex certifiés (min. IP 66)!
Mise en place de la lampe :
Respectez les consignes de sécurité
par le fabricant de lampes!
N’utiliser que des lampes homologuées
pour ces luminaires, voir Caractéristiques
techniques et plaque signalétique!
Lampe double broche (G13)
Introduire la lampe jusqu’à sa butée dans les
deux douilles selon fig. 7, de manière que les
deux broches de chaque côté de la lampe
soient prises par la douille.
Puis tourner la lampe de 90° en position de
crantage selon fig. 8. Une surface verte dans la
douille deviendra alors visible. Maintenant la
lampe est protégée de tomber du luminaire.
Installation de la lampe avec le module
V-CG-S: Voir page 11
5. Mise en service
Avant la mise en service, contrôlez le bon
fonctionnement et vérifiez que l’installation
de la lampe respecte la présente instruction
ainsi que les autres dispositions applicables.
(CEI/EN 60079-14)
Les mesures d’isolement doivent être effec-
tuées uniquement entre PE et le conducteur
extérieur L1 (L,L2,L3) ainsi qu’entre PE et N!
– Tension de mesure: max. 1kV AC/DC
Intensité de mesure: max. 10 mA
3. Conformité avec les normes
Ce luminaire convient à l’utilisation dans les
zones 1, 2, 21 et 22 d’une atmosphère
explosive selon CEI/EN 60079-10 -1et
CEI/EN 60079-10-2.
Ce luminairel sont conformes aux normes
reprises dans la déclaration de conformité,
jointe séparément.
Le produit est protégé par des brevets. Pour
plus d'informations, s'il vous plaît contacter
votre représentant Cooper Crouse-Hinds /
EATON local.
4. Installation
Lors de l’installation et de l’exploitation
des appareils électriques pour atmosphère
explosive, les règlements nationaux ainsi
que les règles de la technique généralement
reconnues doivent être respectés!
(CEI/EN 60079-14)
Le transport et le stockage ne sont permis que
dans l’emballage original et dans la position
spécifiée!
Ouverture et fermeture de l’appareil
d’éclairage
Avec un tournevis approprié, desserrez les vis
à tête fendue et rabattez l’écran protecteur,
voir figures 1 et 2.
Pour fermer l’écran protecteur, serrez les vis
uniquement à la main. (Couple de contrôle :
1,5 Nm)
Cot
es de montage : voir figure 9
Montage dans le plafond
Pour le montage dans des constructions de
plafond suffisamment porteuses, utilisez un
tournevis pour vis six pans, ouverture de clé 4,
pour visser les pattes de fixation latérales
(4 pattes pour 18 W / 6 pattes pour 36 W /
8 pattes pour 58 W) à travers les trous prévus
dans le cadre.
A l’aide des bouchons obtura-
teurs fournis, fermez ensuite les trous.
Respectez les cotes pour la découpe de
plafond.
Respecter lors de la fixation des accessoires
de montage au luminaire que les trous de
fixation doivent avoir une profondeur du pas
de M8 x18 mm au maxi!
Ne pas utiliser de vis trop longues!
Accessoires pour le montage :
voir le catalogue CCH / EATON
Branchement sur secteur
Afin d’ouvrir la boîte de connexion, tourner la
poignée verte jusqu’à sa butée, puis la tirer et
rabattre la trappe, voir fig. 5 et 6.
- Utiliser les garnitures d'étanchéité 1,2 et 3
pour les câbles de 8 à 10 mm Ø, 1 et 2 pour
les câbles 10-13 mm Ø et 1 pour câbles de
13,5 à 17,5 mm Ø. Veiller à ce que les
garnitures restent bien positionnées dans le
presse-étoupe.
6. Maintenance
En ce qui concerne l’entretien, le test et
la
para tion
des appareils électriques pour
atmo sphère explosive, les règlements
nationaux y applicables par exemple
CE/EN 60079-17 ainsi que les règles de la
technique généralement reconnues devront
être respectés!
Maintenance :
Dans le cadre de la maintenance, il faut surtout
contrôler les parties dont dépend la protection
„e, par exemple :
Recherche de fissures et d’endommagements
sur le boîtier et le verre de protection
Recherche d’endommagement des joints
d’étanchéité
Bonne assise des bornes et bouchons
obturateurs
Remplacement de lampe :
Considérez les changements de lampe pour
le changement de lampe : Considérez les
intervalles de vidange conformément à la
norme des fabricants de lampe !
Un changement de lampe peut être mis en
oeuvre sans déconnecter du réseau, puisque
les versions sont enclenchées sans tension
en l'ouverture du baquet de protection par un
sectionneur allpoligen.
Considérez toutefois que des dispositions
nationales ou des directives d'application
locales peuvent être divergentes !
7. Réparation
Pour les réparations en rapport avec la
protection contre les explosions, seul CCH /
EATON ou un électricien qualifié est autorisé
à intervenir conformément à la réglementa-
tion nationale en vigueur (CEI/EN 60079-19).
Avant de remplacer ou d’enlever des
compo sants, il faut observer le suivant:
Mettre l’appareil hors tension avant de
l’ouvrir ou de le réparer! N’utiliser que des
pièces de rechange approuvées d’origine
CCH / EATON! (Voir liste des pièces de
rechange CCH / EATON).
8. Évacuation des déchets /
Recyclage
Lors de l’évacuation de ce matériel électrique,
la règlementation nationale respective en
vigueur devra être respectée.
En cas d'élimination, vous pouvez obtenir des
informations supplémentaires auprès de votre
branche Cooper Crouse-Hinds / EATON.
Sous réserve de modification ou de supplément
de cette série de produits.
11
Installation der Leuchte mit V-CG-S-Modul
Das V-CG-S Modul überwacht und meldet an
das angeschlossene CEAG Notlichtversorgungs-
system die Funktion der Leuchtstofflampe.
Im DC-Betrieb wird eine Lampe abgeschaltet,
die zweite Lampe (grüne Markierung am
Fassungsträger) leuchtet weiter.
Mit dem V-CG-S-Überwachungsmodul mit
Codierschalter für max. 20 Adressen kann die
V-CG-S Leuchte als einzelüberwachte Notleuch-
te an CEAG Notlichtversorgungssystemen
betrieben w
erden. Hierbei kann der Betreiber
die Schaltungsart frei programmieren. So
können an einem Endstromkreis bis zu
20 Leuchten in unterschiedlichen Schaltungs-
arten betrieben werden.
Weitere Informationen zu den Schaltungsarten
entnehmen sie den technischen Unterlagen der
verwendeten Notlichtversorgungsgeräte.
Adressierung
Vor Inbetriebnahme der Leuchte muss die
individuelle Leuchtenadressierung eingestellt
werden. Hierzu ist mit einem geeigneten
Schraubendreher die gewünschte Adresse
(1 - 20) am Adressschalter einzustellen (Pfeil auf
Zahl, Bild
A
). Soll die Leuchte nicht überwacht
werden, ist immer die Stellung 0/0 einzustellen
(Siehe Tabelle
B
)
Zulässige Anschlussleistung nicht
überschreiten!
Installation of luminaires with V-CG-S
module
The V-CG-S module monitors and indicates to
the connected CEAG emergency supply system
the operation of the supply unit circuit and the
function of the luminaire.
In DC mode, one luminaire will be turned off
while the other continues to shine
(green markings on the luminaire holder).
T
he V-CG-S module allows single monitoring of
these luminaires in CEAG emergency lighting
systems. The switching mode (maintained/
non-maintained and switched emergency
luminaires) is freely programmable and mixed
operation up to 20 addresses in a single circuit
is possible.
For further information to the switching mode
please refer to the relevant instruction manual
of the emergency power supply unit.
Addressing
Before fitting the cover, the addressing of the
individual luminaires is to be carried out. The
desired address (1 - 20) is set on the address
switch by means of a suitable screw driver
(Arrowhead to No., fig.
A
). If the luminaire
should not be monitored the code 0/0 has to
be selected (see table
B
).
Do not exceed the permissible power
output!
Installation de la lampe avec le module
V-CG-S
Le module V-CG-S surveille et signale au
système d’alimentation de l’éclairage de
secours CEAG raccordé, le fonctionnement de
la lampe fluorescente compacte.
En mode DC, une des lampes est mise
hors-tension alors que l´autre continue à briller
(marquage vert sur le support de lampe).
A
vec le module de surveillance V-CG-S équipé
d’un commutateur de codage pour un
maximum de 20 adresses, la lampe exploitée
comme lampe de secours unique contrôlée,
reliée aux systèmes d’alimentation d’éclairage
de secours CEAG. L’exploitant peut dans ce
cas, programmer librement le mode de commu-
tation. Ainsi, jusqu’à 20 afficheurs peuvent être
e
xploités avec différents modes de commuta-
tion dans un circuit électrique terminal.
Pour de plus amples informations au mode de
commutation référez-vous s’il vous plaît au
manuel d’instruction approprié de l’unité
d’approvisionnement d’alimentation de secours.
Adressage
L’adressage individuel des afficheurs doit être
effectué avant le montage du couvercle du
panneau de l’afficheur. Pour cela, procédez au
réglage de l’adresse souhaitée (1 - 20) au
commutateur d’adresses à l’aide d’un tournevis
approprié. (flèche face aux nombres, fig.
A
).
Si l’afficheur ne doit pas être surveillé, régler
toujours la position sur 0/0 (
B
).
Ne dépassez pas la puissance de raccorde-
ment admissible de l’onduleur.
1 2
A
Adressierung / Addressing / Adressage
B
Adressierung / Addressing / Adressage
Adressschalter 1/
Address switch 1/
Position de l’interrupteur 1
Adressschalter 2 /
Address switch 2 /
Position de l’interrupteur 2
Leuchtenadresse /
Luminaire address /
Adresse de luminaire
0 0 Überw
achung aus / monitoring off /
aucune surveillance
0 1 1
0 2 2
... ... ...
1 0 10
1 1 11
... ... ...
... ... ...
2 0 20
2 1 nicht zulässig
/not permissable/
pas possible
... ... ...
9 9 nicht zulässig
/not permissable/
pas possible
Zulässige Leuchtenanzahl je Abgangsstromkreis / Max. no. of luminaires to each
output circuit / Nombre de lampes admissible par circuit de départ
Typ / type / Type eLLB 20018/18 eLLB 20036/36 eLLB 20058/58 eLLB 20418 eLLB 20436
Anschluss an / Connection to / Raccordement à: CEAG...
SKU 2x3 A V-CG-S 16 9 6 8 5
SKU 1x6 A V-CG-S 20 17 11 10 9
SKU 4x1 A CG 5 3 2 2 1
SKU 2x3 A CG 12 9 6 6 5
SKU 1x6 A CG 18 17 11 9 8
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2017 Eaton
All Rights Reserved
Printed in Germany
dd
Publication No.
300 8000 1447 D/GB/F (m)
Auflage / 23.2017 / CS
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Eaton Crouse-Hinds eLLB 20436 Mode d'emploi

Taper
Mode d'emploi