Eaton EXIT N Series Operating Instructions Manual

Taper
Operating Instructions Manual
Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
Explosion protected LED-exit luminaire
Series: EXIT N
Panneau de signalisation de sortie de secours lumineux
antidéflagrant à diodes électroluminescentes
Série: EXIT N
300 8000 2035 D/E/F (f)
Betriebsanleitung
Operating instructions
Mode d’emploi
CEAG
P
roducts
2
Maßbilder/Dimensional drawings/Dimensions
Bild 1/
fig. 1/
Fig.1
Befestigungsschrauben/
Fixing screws/
vis de fixation
Ø 5 mm
Bild 2 Netzanschluss/
fig. 2 Mains connection/
Fig. 2 schéma des connexions
PE
N
L
Batterie/
Battery/
Batterie
1
3
Bild 4 /
fig.4 /
Fig.4
Dauerlicht => ON
Permanent lighting
lumière permanente
Bereitschaftsleuchte => OFF
Emergency lights
luminaire d´urgence
Bild 3 Ladezustandsanzeige/
fig. 3 charging condition disply/
Fig.3 Affichage de l'état de
charge et de capacité
Kapazität/Capacity/Capacité
> 40 % < 60 %
Ladebetrieb/ Notlichtbetrieb/
Charging operation/ Emergency op./
Batterie charge Fonctionnement
d’éclairage de secours
 aus/off/
 an/on/allumée
 blinkend/flashing/clignotant
100 %
80 %
60 %
40 %
20 %
Batterie/
Battery/
Batterie
1. rote/red/rouge
LED
2.- 6. grüne/green/
verte LEDs
7. gelbe/yellow/
jaune LED
Anzeigedisplay/
indicator display/
rangée de LED’s
}
1
2
2
ON
OFF
Bild 5 Batteriewechsel/
fig.5 battery change/
Fig.5 changement de batterie
1 Nm
1 Nm
4
D
Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
ATEX EG-Baumusterprüfbescheinigung: BVS 09 ATEX E 029
Gerätekennzeichnung nach 94/9EG / und Norm:
EN 60079-0 ta max + 40 °C:
D II 2 G
Ex e ib mb IIC T5 Gb
ta max + 50 °C:
D II 2 G
Ex e ib mb IIC T4 Gb
D II 2 D
Ex tb IIIC T80°C Db
IECEx Konformitätsbescheinigung: IECEx BVS 13.0017
Gerätekenzeichnung nach
IEC 60079-0 ta max + 40 °C: Ex e ib mb IIC T5 Gb
ta max + 50 °C: Ex e ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Bemessungsspannung AC: 110 - 277 V *
DC: 110 - 250 V *
Bemessungsfrequenz: 50 - 60 Hz
Bemessungsstrom 110 V AC/DC: ca. 0,06 A
220 V AC/DC: ca. 0,035 A
Batterie: Akku 2x 6 V/ 0,8 Ah
Ladezeit (Kap. > 90 %): 28 h
Nennbetriebsdauer Notlichtbetrieb: 3 h **
Schutzklasse nach EN/IEC 61140: I
Schutzart nach EN/IEC 60529: IP 66
Zulässige Umgebungstemperatur: -20°C bis +40°C/+50°C
datenhaltig: -5°C bis +35°C
Lagertemperatur in Originalverpackung: -20°C bis +50°C
Gewicht mit Batterie ca. 2,5 kg
Klemmvermögen Anschlussklemme
2x je Klemme: 3 x 2,5 mm²
Ex e-Kabel- und Leitungseinführung M20x1,5
geeignete Leitungen und Prüfdrehmomente
der Druckschraube
Ø Nm
Dichtung 1 + 2:
1 2
min. 7, 0 1,5
max.
(1)(2)
9,0 1,4
Dichtung 2:
1
2
min. 9,5 1,0
max.
(2)
13,0 1,7
Metall: M20x1,5 Gewinde
Prüfdrehmoment Einschraubgewinde für
Ex e Kabel- und Leitungseinführung M20x1,5:
2,7 Nm
Prüfdrehmoment für Befestigungsschrauben
Haube:
2,4 Nm
* die Angaben berücksichtigen eine zusätzliche Spannungstoleranz von ± 10%
**
Hinweis: Bei neuen Batterien wird die gesamte nutzbare Batteriekapazität erst nach ca. 3 Lade/Entladezyclen
erreicht!
(1)
Der max. Klemmbereiche für Leitungen mit der Kombination aus Dichtung 1+2 kann je nach verwendetem
Leitungstyps und Anwendung variieren.
(2)
Bei der Wahl der Dichtungsgummis darauf achten, dass bei zukünftigen Wartungsarbeiten an der KLE, die
Druckschraube nachgezogen werden kann.
3. Normenkonformität
Diese Leuchte ist zum Einsatz in explosionsge-
fährdeten Be rei chen der Zone 1, 2, und 21, 22
gemäß EN/IEC 60079-10-1 und
EN/IEC 60079-10-2 geeignet.
Sie wurde entsprechend dem Stand der Technik
und gemäß DIN EN ISO 9001:2008 und
IEC 80079-34:2011 entwickelt, gefertigt und
geprüft.
Weitere Anforderungen wie die Richtlinie
"Elektromagnetische Verträglichkeit
(2004/108/EG) werden von der Leuchte
erfüllt.
Diese Leuchte entspricht den aufgeführten
Normen, in der separat beigelegten Konformi
-
tätserklärung.
4. Installation EXIT N
Die für das Errichten und Betreiben von
explosionsgeschützten elektrischen Betriebs -
mitteln geltenden Sicherheitsvorschriften
gemäß des Geräte- und Produktsicherheits-
gesetzes sowie die allgemein anerkannten
Regeln der Technik sind einzuhalten
(EN/IEC 60079-14)!
Transport und Lagerung der Leuchte ist nur in
Originalverpackung und der angegebenen
Lage gestattet!
4.1 Öffnen und Schließen der Leuchte
Lösen sie die vier Deckelschrauben (Schlitz
SW4 mm).
Die Haube kann an den angespritzten
Scharnieren aufgeklappt werden. Zur
leichteren Montage kann die Haube aus den
Scharnieren ausgehängt werden. Beim
Ablegen der Haube auf glatte und saubere
Unterlage achten, damit der Siebdruck auf
der Haube nicht verkratzt wird
4.2 Montage der Leuchte
Warnung - Gefahr durch elektrostatische
Entladung!
Die Leuchte darf nicht in der Nähe von
ladungserzeugenden Prozessen installiert
werden.
Die Leuchte ist an den vier Befestigungspunkte
mit geeigneten Befestigungsschrauben
(Schraube Ø max. 5 mm, Bild 2) sicher auf
tragfähigem Untergrund anzuschrauben.
4.3 Netzanschluss
Haube wie beschrieben öffnen.
Führen Sie die Netzzuleitung durch die beschei
-
nigte Leitungseinführung M20x1,5 ein.
Verwenden Sie für Leitungen von 7 bis 9 mm
beide Dichtungseinsätze, von 9,5 bis 13 mm nur
den äußeren Dichtungseinsatz.
Achten Sie auf korrekten Sitz des verbleibenden
Dichtungseinsatzes in der Verschraubung.
1 Legende
Warnung
Dieses Symbol warnt von einer ernsten
Gefahr. Diese Warnung nicht zu beobach-
ten kann Tod oder die Zerstörung von
Einrichtungen zur Folge haben.
Achtung
Dieses Symbol warnt von einem mögli-
chen Ausfall. Wird diese Warnung nicht
beobachtet kann den Gesamtausfall der
Vorrichtung oder des Systems oder des
Betriebes erfolgen, an die es angeschlos-
sen wird.
1.1 Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und unterwiesene
Personen (EN/IEC 60079-14).
Die Leuchte darf nicht in der Zone 0 oder
20 eingesetzt werden!
Die auf der Leuchte angegebenen
technischen Daten sind zu beachten!
Die Anforderungen der EN/IEC 60079-31
u.a. in Bezug auf übermäßige Staub-
ablagerungen und Temperatur, sind vom
Anwender zu beachten
Umbauten oder Veränderungen an der
Leuchte sind nicht zulässig!
Die Leuchte ist bestimmungsgemäß in
unbe schädigtem und einwandfreiem
Zustand zu betreiben!
Als Ersatz dürfen nur Originalteile von
CEAG/Cooper Crouse-Hinds GmbH (CCH)
verwendet werden!
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von CEAG/CCH oder
einer qualifizierten „Elektrofachkraft“
durchgeführt werden!
Diese Betriebsanleitung während des
Betriebes nicht in der Leuchte lassen!
Die nationalen Unfallverhütungs- und
Sicherheitsvorschriften und die nachfolgen-
den Sicherheitshinweise, die in dieser
Betriebsanleitung mit einem ( ) gekenn-
zeichnet sind, beachten!
2. Technische Daten
5
D
Explosionsgeschützte LED-Rettungszeichenleuchte
Serie: EXIT N
Bei nicht benutzten Kabel-und Leitungs-
einführungen ist die Schutzscheibe zu
entfernen und durch einen bescheinigten
Verschlussstopfen (Drehmoment 1,7 Nm) zu
verschließen.
Beim Verschließen mit einem bescheinigten
Verschlussstopfen stets beide Dichtungsein
-
sätze verwenden!
Bei Metall-Kabeleinführungen sind die
Schutzkappen der nicht benutzten Einführun
-
gen zu entfernen und durch bescheinigte
Ex-Verschlussstopfen (min. IP66) zu verschlie-
ßen!
Achtung!
Nur festverlegte Leitungen zulässig! Bei
Verwendung anderer Leitungseinführungen
sind die Angaben des Herstellers hinsichtlich
Klemmvermögen und Zugentlastung zu
beachten!
Klemmen Sie die Leitungen L, N und PE am
Klemmstein sicher an (Bild 2).
Achten Sie auf sichere Lage der Leitungen.
Quetschen Sie keine Leitungen!
Die Schaltungsart kann über einen kleinen
Schalter auf der Platine eingestellt werden. Siehe
hierzu "Schaltungsart".
Montieren Sie die Haube mit den vier Schrau
-
ben. Ziehen Sie die Schrauben nur handfest an.
5. Funktion
5.1 Anzeigedisplay
Die in der Leuchte eingebaute Notlichtversor
-
gungseinheit ist mit einem Mikrocomputer zur
Ladung und Überwachung sowie mit einer aus
7Leuchtdioden bestehendem Anzeigedisplay
ausgestattet. Die fünf grünen LEDs zeigen den
Lade- und Kapazitätszustand der Batterie an. Die
rote LED signalisiert mögliche Störquellen, die
gelbe LED signalisiert den Notlichtbetrieb. (Bild 4)
Siehe hierzu auch S. 8: LED-Anzeigezustände
5.2 Schaltungsart
Bedingt durch die Lichtleistung der LED-Licht
-
quellen werden damit ausgerüstete Leuchten
fast ausschließlich als Rettungszeichenleuchten
eingesetzt.
Nachdem die Haube abgenommen wurde,
können über einen kleinen Schalter auf der
Platine"Bild 4" zwei Betriebszustände ausgewählt
werden:
Schaltungsart "Dauerlicht"
Schalterstellung "ON", Auslieferungszustand.
Die Leuchte leuchtet im Normal- und im
Notlichtbetrieb.
Schaltungsart "Bereitschaftsleuchte"
Schalterstellung "OFF"
Die weißen LEDs sind im Normalbetrieb aus.
Ladezustand und mögliche Störquellen werden
angezeigt.
Bei einem Netzausfall werden die weißen LEDs
eingeschaltet. Die gelbe LED zeigt den Notlichtbe
-
trieb an.
Der wöchentliche Funktionstest und der
Teilbetriebsdauertest alle 3 Monate, werden
in der Stellung "OFF" unterdrückt.
5.3 Ladetechnik
Mit der durch einen Mikrocomputer gesteuerten
Ladetechnik wird der Lade- und Entladestrom
erfasst, auf bereitet und einem Kapazitätszähler
zugeführt. Fünf grüne Leuchtdioden zeigen in
20%-Schritten den jeweiligen Ladezustand der
Batterie an, siehe Bild 3.
Bei Temperaturen unter -5°C und über +35°C ist
aus elektrochemischen Gründen nicht sicherge
-
stellt, dass die Batterie voll aufgeladen wird.
Beim Ladevorgang zeigt die führende, blinkende
LED die bis zu diesem Zeitpunkt eingeladene
Kapazität an. Die LEDs der bereits eingeladenen
Kapazität zeigen Dauer licht an (Bild 3). Der
Ladevorgang ist beendet, wenn alle 5 grünen
LEDs leuchten und keine mehr blinkt.
Die LED-Anzeige berücksichtigt den Kapazi-
täts-Rückgang der Batterie: d.h., geht z.B. die
Anzeige über die 3. grüne LED auch nach
längerer Ladezeit nicht hinaus, so liegt die
verfügbare Kapazität zwischen 40 und 60%.
Diese Anzeige wird bei jedem Notlichtbetrieb bis
zur Abschaltung durch den Tiefentladeschutz der
Batterie wieder aktualisiert.
5.4 Automatische Testfunktion
5.4.1 Funktionstest (FT)
Wöchentlich wird automatisch ein
Funktionstest (FT) durchgeführt.
5.4.2 Teil-Betriebsdauertest (TBT)
Alle 3 Monate wird automatisch ein
Teilbetriebsdauertest durchgeführt.
Falls innerhalb der letzten 3 Monate kein
Notlichtbetrieb >30 min. stattgefunden hat.
Hierbei erfolgt für ca 35 min. Notlichtbetrieb.
Die sich durch Selbstentladung im Normalbetrieb
reduzierende Batteriekapazität wird, durch den
Mikroprozessor gesteuert, nachgeladen.
5.5 Notlichtbetrieb
Notlichtbetrieb wird automatisch durch den
FT+TBT, durch Netzausfall oder manuell durch
Abschalten der Netzspannung eingeleitet.
Hierbei wird die gelbe LED im Anzeigedisplay
aktiviert.
Die zur Verfügung stehende Restkapazität wird
durch die 5 grünen Leuchtdioden angezeigt,
siehe Bild 3.
6. Inbetriebnahme
Vor der Inbetriebnahme die korrekte
Funktion und Installation der Leuchte in
Übereinstimmung mit dieser Betriebs anlei-
tung und anderen zutreffenden Bestimmun-
gen überprüfen!
Isolationsmessungen nur zwischen PE und
Außenleiter L sowie zwischen PE und N
durchführen!
– Messspannung: max. 1kV AC/DC
– Messstrom: max. 10 mA
Achtung: Eine Isolationsmessung
zwischen L und N darf nicht durchgeführt
werden, da sonst die Elektronik oder die
Netzein gangs sicherung im Gerät) zerstört
wird.
7. Instandhaltung
Die für die Instandhaltung, Wartung und Prüfung
von explosionsgeschützten Betriebs mitteln
geltenden Bestimmungen
(z.B. EN/IEC 60079-17) sind einzuhalten!
7.1 Batteriewechsel
Siehe Bild 5.
Sollte die Batteriekapazität durch Alterung der
Batterie nicht mehr ausreichend sein, muss die
Batterie ersetzt werden.
Nur zugelassene CEAG/CCH Originaler-
satzteile verwenden (siehe CEAG/CCH
Ersatzteilliste).
Leuchte spannungsfrei schalten!
Leuchte öffnen.
Steckverbindung zwischen Batterie und
Platine trennen.
Befestigungsschrauben der Batterie lösen und
entfernen.
Einbau der neuen Batterie in umgekehrter
Reihenfolge.
8. Wartung
Im Rahmen der Wartung sind vor allem die Teile,
von denen die Zündschutzart abhängt, zu prüfen
z. B.:
Gehäuse und Schutzwannen auf Risse und
Beschädigungen.
Dichtungen auf Beschädigungen.
Klemmen und Verschluss-Stopfen auf festen
Sitz.
Wegen der Gefahr elektrostatischer
Aufladung darf die Leuchte nur mit einem
feuchten, nicht fasernden Tuch oder
Schwamm gereinigt werden! Dazu nur
übliche Haushaltsspülmittel in vorgeschrie
-
bener Verdünnung mit Wasser benutzen! Die
Wassertemperatur darf maximal 50°C
betragen. Anschließend mit klarem Wasser
nachspülen, da sonst Spannungsrisse in der
Schutzwanne entstehen können!
9. Instandsetzung/ Reparaturen
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von COOPER CROUSE-
HINDS oder einer qualifizierten Elektrofach-
kraft in Übereinstimmung mit national
geltenden Regeln durchgeführt werden
(EN/IEC 60079-19).
Vor dem Austausch oder der Demontage von
Einzelteilen ist folgendes zu beachten:
Das Betriebsmittel vor dem Öffnen oder
vor Instandhaltungsarbeiten erst spannungs-
frei schalten!
Nur zugelassene CEAG/CCH Originalersatz-
teile verwenden (siehe CEAG/CCH Ersatzteil-
liste).
Programmänderungen und -ergänzungen sind
vorbehalten.
Bei der Entsorgung nationale Abfallbeseitigungs-
vorschriften beachten!
6
GB
Explosion protected LED-exit luminaire
Series: EXIT N
3. Conformity with standards
The luminaire is suitable for use in zone 1, 2
and 21, 22 hazardous areas acc. to
EN/IEC 60079-10-1 and EN/IEC 60079-10-2.
The luminaire is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
It has been designed, manufactured and tested
according to the state of the art and to
DIN EN ISO 9001:2008 and
IEC 80079-34:2011.
The luminaire fulfil further requirements, such
as the EC directive on electromagnetic
compatibility (2004/108/EC).
4. Installation EXIT
The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosion protected apparatus will have to be
observed (IEC/EN 60079-14)!
Transport and storage of the luminaire is
permitted in original packing and specified
position only!
4.1 Opening and closing the light fitting
Unscrew the four screws of the cover.
The cover can be opened to the molded
hinges. For ease of installation, the cover can
be removed out of the hinges.
If putting down take care to prevent
scratches on the silk screen cover.
4.2 Installation of the fitting
Warning. Hazard due to electrostatic
charges!
Luminaire must not be installed in the
vicinity of charge-generating processes!
The luminaire shall be fitted by using the four
mounting clips with suitable fixing screws
(Ø: 5 mm, fig. 2) onto a suitable surface.
4.3 Mains connection
Open the cover as described.
Pass the cable through the certified Ex cable
entry M 20 x 1,5. Use both sealing inserts for
cables from 7,0 to 9,0 mm, and the outer sealing
insert only for cables from
9,5 to 13 mm.
1 Legende
Warning
This symbol warns of a serious hazard.
Failure to observe this warning may result
in death or the destruction of property.
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result
in the total failure of the device or the
system or plant to which it is connected.
1.1 Safety instructions
For skilled electricians and
instructed personnel in accordance
with national legislation, including the
relevant standards and, where applicable, in
acc. with
IEC/EN 60079-14 on electrical apparatus for
explosive atmospheres.
The light fitting must not be operated in
zone 0 or 20 hazardous areas!
The technical data indicated on the light
fitting are to be observed!
The requirements of the
EN/IEC 60079-31 regarding excessive dust
deposits and temperature to be considered
from the user.
Changes of the design and modifications
to the light fitting are not permitted!
The light fitting shall be operated as
intended and only in undamaged and perfect
condition!
Only genuine CEAG/Cooper Crouse-Hinds
GmbH (CCH) spare parts may be used for
replacement!
Repairs that affect the explosion protection
(see national standard), may only be
carried out by CEAG/CCH or a qualified
electrician”!
Do not keep these operating instructions
inside the light fitting during operation!
The national safety rules and regulations for
pre vention of accidents and the following
safety in structions which are marked with an (
) in these operating instruction, will have to
be observed!
2. Technical data
ATEX type examination certificate: BVS 09 ATEX E 029
Marking acc. to 94/9/EG and standard:
EN 60079-0 ta max + 40 °C:
D II 2 G
Ex e ib mb IIC T5 Gb
ta max + 50 °C:
D II 2 G
Ex e ib mb IIC T4 Gb
D II 2 D
Ex tb IIIC T80°C Db
IECEx type examination certificate: IECEx BVS 13.0017
Category of application:
IEC 60079-0 ta max + 40 °C: Ex e ib mb IIC T5 Gb
ta max + 50 °C: Ex e ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Rated voltage: AC: 110 - 277 V *
DC: 110 - 250 V *
Rated frequency: 50 - 60 Hz
Rated current: 110 V AC/DC: approx. 0,06 A
220 V AC/DC: approx. 0,035 A
Battery: Accu 2x 6 V/ 0,8 Ah
Charging time: 28 h
Duration of emergency lighting: 3 h **
Insulation class to IEC/EN 61140: I
Degree of protection accd. IEC/EN 60529: IP 66
Operation temperature: -20°C to +40°C/+50°C
specified data: -5°C to +35°C
Storage temperature in original packing: -20°C to +50°C
Weight: approx. 2,5 kg
Supply terminal clamping capacity
2x per terminal: 3 x 2,5 mm²
Ex-e cable entry M20x1,5
suitable
c
ables and test torques of the pressure
screw
Ø Nm
seal 1 + 2:
1 2
min. 7, 0 1,5
max.
(1)(2)
9,0 1,4
seal 2:
1 2
min. 9,5 1,0
max.
(2)
13,0 1,7
metal: M20x1,5 thread
Test torque flange for Ex e cable entry M20x1,5: 2,7 Nm
Test torque for mounting screws cover: 2,4 Nm
* the data consider an additional voltage tolerance of ± 10 %
** Note: New batteries will reach their total useful capacity only after 3 charging/discharging cycles
(1)
The maximum clamping area for cables with the seal combination 1+2 can vary according to the type
of cable used.
(2)
When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future
maintenance work on the cable entry
7
GB
GB
Explosion protected LED-exit luminaire
Series: EXIT N
Pay attention to the proper fit of the
remaining sealing insert in the certified cable
gland.
In case of unused cable entries, remove their
protective cover and close the entries with a
blanking plug (torque of 1.7 Nm).
When closing the gland with a blanking plug,
always use both sealing inserts!
When metal cable entries are used, the
protective caps of the unused entries are to
be removed and the entries to be closed with
certified Ex blanking plugs (min. IP66)!
Attention!
Only fix laid cable may be used for connec
-
tion!
If cable glands from other manufacturer are
used the instructions regarding strain relief
and clamping capacity must be observed!
Connect the conductors to the terminals L, N
and PE in accordance with the terminal marking
(see fig. 2).
Take care not to pinch any conductors.
Install the protective cover with the four screws.
Tighten the screws only hand-tight!
5. Function
5.1 Display
Luminaires equipped with LED-lightsources are
used normally as exit-luminaires due to the light
output of the LEDs. Therefor these light fittings
have to be operated continuously (Independent
system mode).
The luminaire is fitted with a microcomputer for
charging and monitoring and with a display
composed of 7 light emitting diodes. The five
green LED’s indicate the battery’s charge state
and available capacity. The red LED signals
possible failures, the yellow LED signals the
emergency operation (fig. 4).
See also page 8: table of LED indication status.
5.2 Adjustment
Because of the light source energy of the LED
diodes, the luminaires are used almost
exclusively as luminaires for emergency exit
signs.
After removing the hood, it is possible to adjust
to two operating positions by means of the small
switch situated on the front of the plate with the
inscription "Drawing 6A".
"Permanent lighting" position
Position "ON", delivery position.
The light goes on in normal service and
emergency situations.
"Emergency lighting" position
Position "OFF", delivery position.
The white LED diodes are off in normal service
conditions.
Loading status and possible sources of
interference will be indicated.
In case of power failure, the white LEDs shine.
The yellow LEDs function in emergency
situations.
The weekly function test and the partial
operating time test, performed every 3
months, will be set in the position ´OFF´.
5.3 Charging
The microcomputer controlled charging system
measures the charging and discharging current
and transmits it to a capacity meter. Five green
light emitting diodes indicate in 20%-steps the
actual charge state of the battery, see fig. 3.
Overcharging is prevented by means of this
charging control dependent on the capacity. Only
the energy drawn is recharged. The so-called
memory effect is thus also prevented.
At temperatures below -5°C and above +35°C
the battery will not be fully charged for
electrochemical reasons.
During the charging process the leading flashing
LED indicates the amount of capacity charged so
far. The LED’s for the capacity already charged
indicate continuously (fig. 3). The charging
process is complete when all five green LED’s
are illuminated and none is flashing.
The LED display takes into account the decline in
the capacity of the battery: i.e., if the indication
does not go beyond the 3rd green LED even
after an extended charging period, the available
capacity is between 40 and 60%.
This indication is updated again on each
emergency lighting operation until the battery is
shut down by the deep discharge protection for
the battery.
The reduction in the battery capacity due to
self-discharge in normal operation is automatical
-
ly recharged controlled by the microprocessor.
5.4 Automatic function test
5.4.1 Function test (FT)
A function test (FT) is performed automatically.
5.4.2 Partial operating time test (TBT)
Every 3 months a partial operating time test is
performed. If no emergency lighting operation >
30 min. has occurred during the last 3 months.
During this test emergency lighting operation is
performed for approx. 35 min.
5.5. Emergency lighting operation
Emergency lighting operation is automatically
initiated by the FT+TBT, by mains failure, or
manually by shutting down the mains supply.
During this process the emergency luminaire
marked in red is switched to battery operation.
The residual capacity available is indicated by the
5 green light emitting diodes, see figure 3.
6. Taking into operation
Prior to operation, check the light fitting
for its proper functioning and installation in
compliance with these operating instructions
and other applicable regulations!
Only carry out insulation measurements
between PE and the external conductor L as
well as between PE and N.
– measuring voltage: max. 1 kV AC/DC
– measuring current: max. 10 mA
Mind: There must no insulation measure-
ment be carried out between L and N, since
that would destroy the electronics (mains
input fuse in the unit).
7. Maintenance
Observe the national regulations
applicable to the maintenance, servicing and
test of apparatus for explosive atmospheres
e.g IEC/EN 60079-17 as well as the general
rules of engineering!
7.1 Battery replacement
See fig. 5
When the battery shows low capacity because
of ageing the battery has to be changed.
Only use certified genuine CEAG/CCH spare
parts! (See CEAG/CCH spare parts list).
Cut the apparatus off the voltage before
opening it!
Open the luminaire.
Unplug the connection between batterie
printed board.
Unscrew and remove the screws of the
battery housing.
Assemble the new battery in reverse order.
8. Servicing
When servicing, in particular those components
that affect the explosion protection, will have to
be checked, e. g.:
Housing and protective bowl for any cracks
or damages.
Gaskets for their perfect condition.
Terminals and blanking plugs for their firm
fit.
Because of the risk of an electrostatic
charge, the light fitting shall only be cleaned
with a damp, non-fibrous cloth or sponge!
Only use customary household washing-up
liquid diluted in water as specified! The
water temperature may be max. 50°C.
After that, rinse with clear water to prevent
the risk of tension cracks in the protective
bowl!
9. Repair/Overhaul
Repairs that affect the explosion protec-
tion, may only be carried out by COOPER
CROUSE-HINDS or a qualified electrician in
compliance with the applicable national rules
(IEC/EN 60079-19).
Prior to replacing or removing any components,
observe the following:
Cut the apparatus off the voltage before
opening it or carrying out repairs! Only use
certified genuine CEAG/CCH spare parts!
(See CEAG/CCH spare parts list).
Subject to alteration or supplement of this
product series.
Regarding waste disposal, observe the relevant
national regulations! The plastic materials are
marked with material identifications.
8
ATEX Certificat de Conformité: BVS 09 ATEX E 029
Marquage selon 94/9/CE et directive:
EN 60079-0 ta max + 40 °C:
D II 2 G
Ex e ib mb IIC T5 Gb
ta max + 50 °C:
D II 2 G
Ex e ib mb IIC T4 Gb
D II 2 D
Ex tb IIIC T80°C Db
IECEx Certificat de Conformité: IECEx BVS 13.0017
Marquage selon:
IEC 60079-0 ta max + 40 °C: Ex e ib mb IIC T5 Gb
ta max + 50 °C: Ex e ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Gamme des tensions CA: 110 - 277 V *
CC: 110 - 250 V *
Gamme des fréquences: 50 - 60 Hz
Courant nom. 110 V CA/CC: env. 0,06 A
220 V CA/CC: env. 0,035 A
Batterie: Cellules 2x 6 V/ 0,8 Ah
Durée de charge: 28 h
Durée de service d’éclairage de secours: 3 h **
Classe d’isolation selon CEI/EN 61140: I
Indice de protection selon CEI/EN 60529: IP 66
Température ambiante: -20°C à +40°C/+50°C
conseillée: -5°C à +35°C
Température de stockage dans l’emballage original: -20°C à +50°C
Poids: env. 2,5 kg
Capacité de serrage des bornes
2x par borne: 3 x 2,5 mm²
Entrée de câble Ex-e M20x1,5
câbles appropriés et couples d'essai de la vis de
pression
Ø Nm
phoque 1+2:
1 2
min. 7, 0 1,5
max.
(1)(2)
9,0 1,4
phoque 2:
1
2
min. 9,5 1,0
max.
(2)
13,0 1,7
Fils de métal: M20x1,5 fil
Couple de test pour filetage pour
Entrée de câble Ex-e M20x1,5:
2,7 Nm
Couple de test pour les vis de montage capot: 2,4 Nm
* les indications prennent en considération une tolérance de tension supplémentaire
** Note: Une batterie neuve n’atteint sa capacité utile totale qu’après 3 cycles de charge et de décharge
(1)
Lorsque les bagues 1+2 sont utilisées, la capacité de serrage maximale peut varier légèrement selon le type de
câble utilisé.
(2)
Lors de la sélection des bagues d’étanchéité au moment de l’installation, il faut s’assurer qu’il reste une marge
de serrage suffisante au niveau du chapeau du presse étoupe. Cela permettra de pouvoir resserrer le presse
étoupe lors d’une future maintenance.
3. Conformité avec les normes
Ce luminaire convient à l’utilisation dans les
zones 1, 2 et 21, 22 d’une atmosphère explosive
selon CEI/EN 60079-10-1 et CEI/EN 60079-10-2.
Ce luminaire sont conformes aux normes
reprises dans la déclaration de conformité, jointe
séparément.
«Compatibilité ectromagnétique»
(2004/108/CEE).
Il a été conçu, construit et testé selon l’état
actuel de la technique et selon EN ISO 9001:
2008 et IEC 80079-34:2011.
4. Installation EXIT N
Lors de l’installation et de l’exploitation
des appareils électriques pour atmosphère
explosive, les règlements nationaux ainsi que
les règles de la technique généralement
reconnues doivent être respectés
(CEI/EN 60079-14)!
Le transport et le stockage ne sont permis
que dans l’emballage original et dans la
position spécifiée!
4.1 Ouverture et fermeture du panneau
Desserrez les quatre vis du couvercle
(Tournevis 4 mm).
Enlevez le couvercle. Posez le couvercle sur
une surface propre et lisse afin de ne pas
rayer la sérigraphie du couvercle!
4.2 Montage du panneau
Warning. Hazard due to electrostatic
charges!
Luminaire must not be installed in the
vicinity of charge-generating processes!
Le panneau doit être correctement fixé à l’aide
des quatre pattes de fixation avec des vis
appropriées (vis Ø maximum 5 mm, fig.2) sur un
support solide.
4.3 Raccordement au secteur
Ouvrez le capot comme décrit.
Faites passer le câble d’alimentation secteur
dans le passe-câble marqué M 20x1,5. Utilisez
pour les câbles de 7,0 à 9,0 mm les deux inserts
d’étanchéité, pour les câbles de 9,5 à 13,0 mm
seulement l’insert d’étanchéité extérieur.
Veillez à l’assise correcte des inserts
d’étanchéité restants dans l’assemblage
vissé. En cas de non utilisation de câbles ou
de passe-câbles, la rondelle de protection doit
être retirée et remplacée par un bouchon de
fermeture homologué.
(couple de serrage 1,7 Nm).
1 Légende
Avertissement
Ce symbole avertit d’un danger grave. Le
non-respect de cet avertissement peut
entrainer la mort ou la destruction de
biens.
Attention
Ce symbole met en garde contre un
éventuel défaut. Le non-respect de cette
consigne peut entrainer une panne totale
de l’appareil ou du système ou de
l’installation à laquelle il est connecté.
1.1 Consignes de sécurité
Pour le personnel électricien
qualifié et le personnel instruit
suivant la règle mentation légale, y
compris les normes respectives
ainsi que, le cas échéant, CEI/EN 60079-14
pour apppareils électriques utilisables en
atmosphère explosive.
Il n’est pas permis d’utiliser le luminaire
dans la zone 0, et 20.
Les caractéristiques techniques indiquées
sur le luminaire doivent être respectées!
Les exigences des CEI/EN 60079-31 en ce
qui concerne des dépôts de poussière
démesurés et une température doivent
être considérées par I’utilisateur.
Il n’est pas permis de transformer ou de
modifier le luminaire!
Le luminaire ne doit être exploité que pour
la fonction qui lui est dévolue et qu’en état
intact et parfait!
Seules des pièces de rechange d’origine
CEAG/Cooper Crouse-Hinds GmbH (CCH)
doivent être employées pour le remplace-
ment!
Des réparations qui portent sur la
protection contre l’explosion, ne doivent
être exécutées que par CEAG(CCH) ou par
un «électricien» qualifié!
Ce mode d’emploi ne doit pas être laissé
dans le luminaire pendant son exploitation!
Veuillez respecter les prescriptions nationales
de sécurité et de prévoyance contre les
accidents ainsi que les consignes de sécurité
qui sont marquées d’un
( ) dans ce mode d’emploi!
ATEX Certificat de Conformité: BVS 09 ATEX E 029
Marquage selon 94/9/CE et directive:
EN 60079-0 ta max + 40 °C:
D II 2 G
Ex e ib mb IIC T5 Gb
ta max + 50 °C:
D II 2 G
Ex e ib mb IIC T4 Gb
D II 2 D
Ex tb IIIC T80°C Db
IECEx Certificat de Conformité: IECEx BVS 13.0017
Marquage selon:
IEC 60079-0 ta max + 40 °C: Ex e ib mb IIC T5 Gb
ta max + 50 °C: Ex e ib mb IIC T4 Gb
Ex tb IIIC T80°C Db
Gamme des tensions CA: 110 - 277 V *
CC: 110 - 250 V *
Gamme des fréquences: 50 - 60 Hz
Courant nom. 110 V CA/CC: env. 0,06 A
220 V CA/CC: env. 0,035 A
Batterie: Cellules 12 V/ 800 Ah
Durée de charge: 28 h
Durée de service d’éclairage de secours 3 h **
Classe d’isolation selon I
Indice de protection selon IP 66
Température ambiante: -20°C à +40°C/+50°C
conseillée: -5°C à +35°C
Température de stockage dans l’emballage original: -40°C à +60°C
Poids: env. 2,5 kg
Capacité de serrage des bornes,
2 x par borne: 3 x 2,5 mm²
Entrée de câble Ex-e:
modèle standard M20x1,5 pour câbles Ø 5,5 à 13 mm
Fils de métal: M20x1,5
Couple d' essai pour l’entrée de câble
Ex-e M20x1,5: : 3,75 Nm
Couple d' essai pour la vis de pression: 2,5 Nm
(pour étancher le câble ou le bouchon de fermeture)
*
les indications prennent en considération une tolérance de tension supplémentaire
**
Note: Une batterie neuve n’atteint sa capacité utile totale qu’après 3 cycles de charge et de
décharge.
2. Caractéristiques techniques
F
Panneau de signalisation de sortie de secours lumineux antidéflagrant à
diodes électroluminescentes Série: EXIT N
9
Utilisez toujours les deux inserts d’étanchéité
lors de la fermeture avec le bouchon
homologué !
En cas de passe-câble en métal, les capu
-
chons de protection des passe-câbles non
utilisés doivent être enlevés et remplacés par
des bouchons de fermeture antidéflagrants
homologués (minimum IP66) !
Attention Seul un câblage fixe est
autorisé ! Dans le cas d’utilisation d’autres
passe-câbles, respectez les instructions du
fabricant en ce qui concerne le serrage des
bles et l’absence de tension mécanique sur
ceux-ci !
Raccordez sûrement les câbles L, N et PE au
bornier (fig. 2).
Montez la carte à LED. Veillez à une pose
correcte et sûre des câbles. Evitez tout
pincement des câbles !
Monter le couvercle avec les quatre vis. Les vis
ne doivent être serrées qu’à la main.
5. Fonction
5.1 Afficheur
Du fait de la puissance lumineuse des sources
lumineuses à DEL, les lampes qui en sont
équipées sont utilisées quasi exclusivement en
tant que lampes de signalisation de secours.
Pour cette raison, ces lampes doivent unique
-
ment être en circuit en permanence.
Le bloc d’alimentation en lumière de secours
intégré dans la lampe est équipé d’un microcal
-
culateur destiné au chargement et à la surveil-
lance ainsi que d’un afficheur composé de 7
diodes lumineuses.
Les 5 DEL vertes indiquent l’état de charge et de
capacité de la pile. La DEL rouge signale
d’éventuelles sources de perturbation, la DEL
jaune signale le mode éclairage de secours
(figure 4).
Voir à ce sujet également page 8 : Etats
d’affichage par DEL
5.2 Type de réglage
En raison de la puissance des sources de
lumière LED, les luminaires qui en sont équipés
seront utilisés presque exclusivement comme
luminaires pour panneaux de sortie de secours.
Après retirement du couvercle, il est possible par
le biais d´un petit interrupteur situé sur le côté
avant de la plaque ´Dessin 6A´ de régler deux
positions de service.
Type de réglage ´lumière permanente´
Position ´ON´, livraison dans cette position.
Le luminaire s´allume en situations de service
normal et d´urgence.
Type de réglage ´luminaire d´urgence´
Position ´OFF´, livraison dans cette position.
Les diodes LED blanches sont éteintes en
situation de service normal.
L´état de chargement et les anomalies éven
-
tuelles seront indiqués.
En cas de panne, les diodes LED blanches
s´allument. La diode LED jaune fait état de mode
d´urgence.
Le test de fonction hebdomadaire et le
test partiel de durée de service, effectué tous
les 3 mois, seront enclenchés en position
´OFF´.
5.3 Technique de charge
La technique de charge pilotée par micro-ordina
-
teur détecte le courant de charge et de
décharge, le conditionne et le transmet à un
capacimètre. Cinq diodes luminescentes vertes
indiquent par pas de 20% l’état de charge
respectif de la batterie, voir fig. 3.
La commande de charge en fonction de la
capacité empêche la surcharge. Seule la quantité
d’énergie préalablement consommée sera
rechargée. L’effet de mémoire des batteries est
également éliminé.
En cas de températures au-dessous de -5°C et
au-dessus de +35°C, une pleine charge des
batteries n’est pas assurée pour des raisons
électrochimiques
Pendant le processus de charge, la LED clignotant
en tête indique la quantité de capacité absorbée
jusqu’à ce moment. Les diodes luminescentes se
rapportant à la capacité déjà absorbée sont
allumées en continu.
Les diodes luminescentes se rapportant à la
capacité encore manquante ne s’allument pas
(fig. 3). Le processus de charge est terminé
lorsque toutes les 5 diodes vertes s’allument et
qu’aucune diode ne clignote plus.
L’affichage des diodes luminescentes tient
compte de la diminution de capacité de la
batterie: à savoir, si l’affichage ne dépasse pas la
3e LED verte même après une période de
charge prolongée, la capacité disponible se situe
entre 40 et 60%.
Cette indication est réactualisée lors de chaque
fonctionnement d’éclairage de secours jusqu’à la
mise hors service par la protection contre la
décharge profonde de la batterie.
5.4 Fonction de test automatique
5.4.1 Fonction de test (FT)
Une fonction de test (FT) est exécutée automati
-
quement chaque semaine.
5.4.2 Test partiel de durée de service (TBT)
Tous les 3 mois, un test partiel de durée de
service est automatiquement effectué. Si aucun
fonctionnement de secours > 30 min n’a eu lieu
au cours des 3 derniers mois. Le fonctionnement
d’éclairage de secours est alors activé pendant
env. 35 min.
5.5 Fonctionnement d’éclairage de secours
Le fonctionnement d’éclairage de secours est
automatiquement enclenché par FT+TBT, en cas
de panne de secteur ou manuellement par
coupure de la tension du secteur.
Ce faisant, la lampe d’éclairage de secours
marquée en rouge est commutée sur le fonction
-
nement sur batterie.
La capacité résiduelle disponible est indiquée par
les 5 diodes lumineuses vertes, voir figure 5, la
DEL jaune signale le mode éclairage de secours
(figure 3),défectueuse sont reconnus.
6 Mise en service
Vérifiez que l’installation et le fonctionne-
ment corrects de l’afficheur soient conformes
aux instructions de cette notice d’utilisation et
à toutes les autres prescriptions en vigueur !
Les mesures d’isolation ne doivent être
effectuées qu’exclusivement entre PE et les
câbles extérieurs L ainsi qu’entre PE et N !
- Tension de mesure :maximum 1kV AC/DC
- Courant de mesure : maximum 10 mA
Attention: ne pas effectuer de mesure
d’isolation entre L et N, sinon il y a destruc-
tion de l’électronique ou du fusible de
protection d’alimentation secteur de
l’appareil.
7. Entretien
Respectez la réglementation en vigueur
en ce qui concerne l’entretien, la maintenance
et le contrôle des moyens d’exploitation
antidéflagrants (par ex. CEI/EN 60079-17)!
7.1 Remplacement de la pile
Si un vieillissement affecte la capacité de la pile,
il faut remplacer cette dernière.
N’utilisez que des pièces détachées
agréées d’origine CEAG/CCH (voir liste des
pièces détachées CEAG/CCH).
Mettez la lampe hors tension!
Lampe ouvert.
Connecteur entre la batterie et le conseil
d'administration distinct..
Les vis de fixation et retirer le dégagement de
la batterie.
Montez la nouvelle pile en suivant l’ordre inverse.
8. Maintenance
Il faut avant tout vérifier les pièces desquelles
dépend le type de protection antidéflagrante, par
ex. :
Fissures et dommages au boîtier et au carter
de protection.
Dommages aux joints.
Positionnement correct des borniers et des
bouchons de fermeture.
En raison du risque de charge électrosta
-
tique, le panneau ne doit être nettoyé qu’à
l’aide d’un chiffon non pelucheux ou d’une
éponge humides ! N’utilisez pour cela que
des produits de rinçage ménagers dilués
dans de l’eau à la concentration prescrite !
La température de l’eau ne doit pas
dépasser 50° C. Rincez ensuite à l’eau claire,
sinon il y a risque de fissures de tension
dans le carter de protection !
9. Réparation/Remise en état
Des réparations qui portent sur la
protection contre l’explosion, ne devront être
exécutées que par COOPER CROUSE-HINDS
ou par un électricien qualifié en conformité
avec la règlementation nationale en vigueur
(CEI/EN 60079-17).
Respectez les instructions suivantes avant le
remplacement ou le démontage de pièces
détachées:
Mettre d’abord le panneau hors tension
avant toute ouverture ou travaux de répara-
tion !
N’utilisez que des pièces détachées agréées
d’origine CEAG/CCH (voir liste des pièces
détachées CEAG/CCH).
Des modifications ou extensions de programmes
font l’objet de réserves.
Respectez les prescriptions légales de traite
-
ment des déchets en cas d’élimination !
F
F
Panneau de signalisation de sortie de secours lumineux antidéflagrant à
diodes électroluminescentes Série: EXIT N
10
1)
Siehe auch 5. Funktion:
Bei reduzierter Batterie-Kapazität wird auch
nur die verfügbare Kapazität angezeigt.
Beispiel:
Wurde beim letzten Kapazitätstest
nur 65% Restkapazität ermittelt, so bleibt
die Anzeige bei 4 grünen LEDs in Dauerlicht
bestehen (verfügbare Kapazität 60-80%).
2)
beliebige Kombinationen der Anzeige
möglich gemäß Lade- / Entladezustand.
1)
See also chapter 5. Function:
In case of reduced battery capacity only the
available capacity is indicated.
Example:
If during the last capacity test only 65%
remaining capacity was found, then the
indication stops at 4 green LEDs continuous-
ly illuminated (available capacity 60-80%).
2)
Any combination of indications possible
depending on charge / discharge state.
1)
Voir également 5. Fonctionnement:
Si la capacité de la batterie est réduite, seule
la capacité disponible est indiquée.
Exemple:
Si une capacité résiduelle de seulement
65% a été déterminée lors du dernier test
de capacité, l’indication reste fixée à 4 LED
vertes allumées en permanence (capacité
disponible 60-80%).
2)
combinaisons quelconques de l’indication
possible suivant l’état de charge ou
décharge.
LED-Anzeigezustände/
LED
rot/
red/
rouge
LED
grün/
green/
vert
1)
LED gelb/
yellow/
jaune
Batterie Kapazität/
battery-/capacity/
Capacité de la batterie
Funktion/
Function/
Fonction
Maßnahmen/
Action/
Mesures
-
< 20 %
}
Batterie wird geladen/
battery on charge/
Batterie en charge
Batterie o.k.
Keine/
None/
Aucune
-
< 40 %
-
< 60 %
-
< 80 %
-
< 100 %
-
- 100 %
Batterie ist geladen
battery charge completed
Batterie charge
i. O./ok
Keine/
None/
Aucune
-
80 - 100 %
}
Notlichtbetrieb
emergency operation
Fonctionnementd’éclairage
de secours
Batterie wird entladen
Battery is being discharged
Batterie en cours de
décharge
Funktion i. O.
Keine/
None/
Aucune
-
60 - 80 %
-
40 - 60 %
-
20 - 40 %
-
0 - 20 %
- - - 0 %
Batterie entladen/
battery discharged
Batterie déchar-
gée
Netzspannung einschalten/
Switch on mains supply/
Vérifier l’appareil d’éclairage
de secours
(
²)
0 - 100 %
Störung im Notlichtstrom-
kreis/
Emergency circuit defec-
tive/
Appareil d’éclairage de
secours défectueux
Notlichtgerät prüfen/
Check emergencylighting
device/
Vérifier l’appareil d’éclairage
de secours
oder/or/
ou
Notlichtdauer < 30 min
Batterielade-/Entladezyklus
durchführen
Duration of emergency
lighting < 30 min
Perform battery charging/
discharging cycle
(see chap. 6. Fault indicator)
Durée d’éclairage de se-
cours < 30 min
charge/décharge de la bat-
terie
(voir chap. 6 Indication de
défaut)
LED blinkt
LED flashing
LED clignotant
LED leuchtet
LED illumi-
nated
LED illuminé
LED Affichage de l'état de charge et
de capacité
LED-indication status/
11
Notizen
Notes
Remarques
Publication No.
300 8000 2035 /(F) /
Auflage /03.15/CS
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2015 Eaton
All Rights Reserved
Printed in Germany
dd
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Eaton EXIT N Series Operating Instructions Manual

Taper
Operating Instructions Manual

dans d''autres langues