Eurotherm P304 Guide d'installation

Taper
Guide d'installation
When switched on the instrument
enters Level 1.
Press to scroll through a list
of parameters
available in this level.
The parameter values are adjusted
using the and keys,
provided that the parameter is not
read only or has been locked in
other levels.
Mnemonic Name Availability Explanation
SP
SETPOINT Always
Range SP.LO to SP.Hi.
AL.NAS
ALARMS MASK RESET Only if one or more alarms are
configured with mask at start
up
Use or to switch the upper display from OFF to rESEt,
then press to restore the alarm mask.
A-N
AUTO/MANUAL
SELECTION
Only if the external keyboard is
fitted
This may be selected by the Digital inputs on terminals 62 and 63
or select LoCAL for front button operation or CnCt for external
control. Default = LoCaL
AL1
ALARM 1 THRESHOLD Only if P61 ≠ OFF Used to set the point at which the alarm operates.
Range from 0 to pressure input full scale value for process and
band alarm.
From - pressure input to + pressure input full scale values for
deviation alarm.
The high limit may be expanded to 110% of span.
Default AL1 5%, AL2 60%, AL3 80% of range.
AL2
ALARM 2 THRESHOLD Only if P65 ≠ OFF
AL3
ALARM 3 THRESHOLD Only if P69 ≠ OFF
Pi.vAL
PRIMARY PRESSURE
INPUT VALUE
Only if P11 ≠ OFF
and
P12 = diff.P
This is read only and indicates the pressure measured if the
transducer is connected to the primary input terminals.
Si.vAL
SECONDARY
PRESSURE INPUT
VALUE
This is read only and indicates the pressure measured if the
transducer is connected to the secondary input terminals.
Levels of Operation
There are three levels of operation.
Level 1. This is designed for day to day operation and has no
passcode.
Level 2. Parameters available in level 1 are also available in level 2.
Level 2 contains additional parameters for commissioning purposes
and more detailed operation.
Configuration mode Configuration level sets all features of the
instrument and is carried out using a list of ‘P’ codes. Each P code is
associated with a particular feature of the instrument such as Input
Type, Ranging, Outputs, Alarms, Digital Communications, etc.
When Configuration level has been entered, a further level may be
selected:
Instrument calibration (ICAL)
These are described in the User Manual HA031861.
Level 1 Operation
Level 1 Parameters
6
The power supply input is not fuse protected.
Fuses should be provided externally
Recommended external fuse ratings are as
follows:-
For 24 V ac/dc, fuse type: T rated 2A 250V
For 100-230Vac, fuse type: T rated 2A 250V
Low voltage supply,
option
24V
ac (14 to 30Vac) 50/60Hz
24Vdc (14 to 32Vdc) 5% max
ripple
18VA at 24Vac; 12W a
t 24Vdc.
Polarity is not important.
Power Supply
Use copper conductors only.
A switch or circuit breaker must be included in the
building installation
It shall be in close proximity to the equipment and
within easy reach of the operator
It shall be marked as the disconnecting device for
the equipment.
Notes: A single switch or circuit breaker can drive
more than one instrument.
An earth (ground) connection is not required.
High voltage supply
100 to 230Vac
+15%, 50/60Hz,
22VA at 50Hz; 27VA at 60Hz
Ensure that the supply is correct for your instrument and connected to the correct terminals
3
Rear Terminal Connections
Alarm Outputs - AL1 AL2 and AL3
AL1 and AL2 Changeover relay: 264Vac, 2A
max (resistive load), 12Vdc, 100mA min
AL3 Normally open relay: 264Vac, 2A max
(resistive load), 12Vdc, 100mA min
Keyboard selectable: - Process variable /
deviation / Band / High / Low / Low masked on
start up, - Auto/manual reset
By default relays are de-energised in alarm state
Main and Secondary Inputs
m/A; 0-20mA, 4 – 20mA
VOLT; 0-5Vdc, 0-10Vdc
Strain Gauge; from 340 to 5000, 1-4mV/V,
EXC excitation 10V +7%
Precautions
Do not run input wires with power cables
Ground shielded cable at one point only
Sensor input not isolated from the Reset
Input
Outputs
Analogue: 0/10V, -10/+10V, 0/5V load 5K;
0/20mA, 4-20mA max load 500, all dc
OUT1 control: OUT2 Retransmission
Digital Communications
EIA485 Modbus/Jbus (RTU mode)
Address: 1 to 255
Baud: 600 to 19200
Format: 1 start bit, 8 bit with/without parity, 1
stop bit
Parity: Even/Odd
A CPI configuration port is also available
Transmitter Power Supply (TPSU) (Optional)
24Vdc +10% <28mA
Digital Inputs (contact closure)
DIG1 - Open = Auto; closed = Manual
DIG2 - Increase output value
DIG3 - Decrease output value
DIG4 - Set the control output to 0. The front
panel Auto/Man keys are disabled.
RESET programmable for alarm, peak, zero
calibration or reset all.
NO
C
NC
NO
C
NC
SIG+
SIG-
CAL2
3 -
4 +
5 +
6 +
7 -
8
10 +
11 -
EXC+
SIG+
SIG-
CAL2
56 +
57 -
58 +
59 -
60
61
45
46
47
48
49
50
12 +
13 -
14
16 +
17 -
18 +
19 +
21 +
22 -
mA
VOLT
EXC+
EXC-
CAL1
RESET
OUT1
mA/V
ALARM2
C
NO
L/24V
N/24V
OUT2
mA/V
A/A’
B/B’
Com
EIA485
mA
VOLT
23
24
Secondary
Input
Primary
Input
ALARM3
EXC-
CAL1
51
52
53
54
ALARM1
DIG1
DIG3
DIG4
62
63
64
65
66
DIG2
POWER
SUPPLY
TPSU
Reinforced
insulation
boundaries
Insulation
boundaries
Block Diagram and Isolation Boundaries
Alarm 1
O/P
Alarm 3
O/P
Alarm 2
O/P
Secondary
An O/P
TPSU
Main An
I/P
Secondary
An I/P
Logic Input
CPI
interface
Modbus
comms
EIA485
Main An
O/P
4 x Logic
Input
Display
Keyboard
CPU
Power
Supply
1. Select a location which is subject to minimum vibration, the ambient
temperature is within 0 and 50
O
C (32 – 122
O
F) and operating
humidity of 0 to 85% RH non condensing.
2. Prepare a cut-out in the mounting panel to the size shown.
4. Detach the panel mounting clips
(3) and slide the sealing gasket (1)
over the case.
5. Slide the instrument case (2) into
the cut-out.
6. Attach the panel mounting clips.
Using a screwdriver, tighten the
threaded rod to a torque between
0.3 and 0.4 Nm.
7. To remove the controller from its
sleeve, ease the latching ears (4)
outwards and pull the controller
forward out of the sleeve. When
refitting ensure that the latching
ears click back into place to
maintain the panel sealing.
3. If more instruments are
mounted in the same panel
the minimum distance
between them should be
observed as shown.
3.62 x 3.62in
(92 x 92mm)
Not to scale
4.92in
(125mm)
4.92in
(125mm)
2
Order Code
Installation
1. Function
CC Pressure controller
Model Number
P304c
2.
Power Supply
VH 100 - 230Vac 50 / 60Hz
VL 24Vac / Vdc
3. Second Input
XXX None
RSP Analogue set point or second
PV input (differential pressure)
4. Options
SDXX
24Vdc TPSU + analogue DC
retransmission
SD4L
24Vdc TPSU + analogue DC
retransmission + RS 485 + 4
dig in
5. Custom Label
XXXXX None
6. Specials
XXXXX None
(2)
(3)
(3)
(4)
(4)
(1)
The keyboard consists of five push-buttons, labelled as follows:
Auto/Man
Press for more than 1 second to switch between Automatic and Manual mode. Automatic mode means normal closed
loop control; Manual means the output can be raised or lowered manually using the or keys.
PAGE
Press for more than 4 seconds to select the level of operation (see section 7). During parameter modification it is used
to scroll back to the previous parameter without storing the parameter changes.
SCROLL
During parameter modification it is used to scroll forward to the next parameter and to store the parameter changes.
Decrement or modify a parameter value. In manual mode it is used to decrement the output value. When pressed for
more than 3 seconds in automatic mode it is used to access and to decrease the set point parameter.
Increment or modify a parameter value.
In manual mode it is used to increment the output value. When pressed for more than 3 seconds in automatic mode it
is used to access and to increase the set point parameter.
In automatic mode, when pressed for less than 3 seconds, it is used to switch the lower display between set point value
SP, deviation valueDev’, output value OP%’, output value ‘RPMand peak value Peak’ (if this function is enabled).
At power-on the lower display shows the set point value if the automatic mode is selected or the output value in manual
mode.
+
To reset the stored peak value and to reset the alarms. This function is disabled when the device is controlled by serial
link.
+ or
+
Jump to max or min parameters value when instrument is in Manual mode.
+ or
+
Used only at power-up when the instrument detects a parameter error; see the “ERROR CODES” section in the User
Manual for further information.
Note: Actions which require two or more pushbuttons to be pressed must follow exactly the pushbutton sequence shown.
Keyboard
Tuning Algorithm
flashing = first step activated
lit = second step activated
Switch On
A brief self test start up seque
n
ce lights all segments of the
display followed briefly by the firmware version number
and the instrument type (P304c).
The display then opens in Operator level 1 and a typical
view is shown below.
Measured Value (PV)
Selected parameter
In automatic mode, press to select between:
SP (setpoint); Dev (deviation SP -
PV);
OP%
(output power);
RPM (Output value scaled to Revolutions Per Minute);
Peak
(peak value)
Bar
Graph - measured
variable.
Alarm setpoint values are
d
isplayed.
First segment blinks for
pressure lower than zero.
Last segment blinks for
pressure greater than full scale
value.
Units
kg/cm
2
, psi, bar, MPa
Status
indication
5
Any alarm
active (red)
Alarm 1, 2 or
3 active
Manual
mode
selected
Device
controlled by
serial link
Remote
setpoint
selected
Man Tune Rem RSP
ALM
1 2 3
This guide is intended to describe installation and general
operation.
Further information and a full specification is available in
the User Manual Part Number HA031861. which may be
downloaded from www.eurotherm.co.uk.
P304
c
Process Controller Quick Start Guide
P304c is a microprocessor based pressure and process
controller based on the Piccolo range of instruments. It is
suitable for use on a wide range of processes including
the control and indication of extruder melt pressure.
Two process inputs are available which are user
configurable for 350 strain gauges, voltage or current.
A 24Vdc power supply provides the voltage for two or
four wire transducers.
Two voltage or mA outputs may be configured for control
purposes or for retransmission of process measurements.
Three alarms may be attached to the measured variable
to provide indication and interlocks of any out of
tolerance condition.
EIA485 3-wire digital communications uses Modbus/Jbus
communications.
Configuration and commissioning parameters may be set
through the front panel keys (protected by different levels
of access).
Description
Unpacking
The package contains:
P304c controller mounted in its sleeve
2 X Panel securing clips
Installation sheets in English, French, German and
Italian
Sealing gasket
GB
Part Number HA031859EF/2 (CN31907) 7/14
*HA031859EF*
1
Dimensions
96mm
(3.78in)
15mm
(0.59 in)
128mm (5.04 in) 96mm (3.78 in)
These inputs may be used to measure differential pressure. A typical example
measures the pre and post screen pressures in screen changer applications.
Transmitter Power
Supply TPSU
mA-
-
+
2 Wire
4-20mA
mA+
+
-
2 Wire Transmitter
3/17
4/18
58
59
mA-
-
+
4 Wire
4-20mA or
0-20mA
mA+
-
+
4 Wire Transmitter
Input power
for transmitter
Transmitter Power
Supply TPSU
+
-
3/17
4/18
58
59
Wiring
This section shows typical wiring
diagrams for input sensors
Strain Gauge
The calibration resistor may be internally or externally mounted in some transducers
Wire Sizes
The screw terminals accept
wire sizes from 0.5 to 1.5 mm
(16 to 22AWG). Hinged covers
prevent hands or metal making
accidental contact with live
wires.
The rear terminal screws
should be tightened to a
torque of between 0.3 and 0.4
Nm.
4
The diagram shows a pressure
transducer with internal calibration
resistor.
For transducers without an internal
resistor connect an external resistor
between terminals 13 and 14 (primary
input) or 7 and 8 (secondary input).
The resistor is only switched in when
calibrating the transducer. See the User
Manual.
For transducer terminal numbers, refer
to the manufacturers data.
CAL2
SIG-
EXC+
Rcal
CAL1
SIG+
10/16
11/17
8/14
7/13
6/12
EXC-
Code Description Disponibilité
Plage. Utiliser ou pour modifier la valeur.
P1 SÉLECTION DE L'ENTRÉE PRESSION Toujours
Str Jauge de contrainte (défaut),
0-20 mA, 4-20 mA, 0-5V, 0-10V
P2 UNITÉ TECHNIQUE D'ENTRÉE PRESSION Toujours
OFF - toutes les voyants sont désactivées
hGcN2 - voyant (kg/cm
2
) éclairée
PSI - voyant (PSI) éclairée (défaut)
bAr - voyant (bar) éclairée
NPa - voyant (MPa) éclairée
P3 VALEUR PLEINE ÉCHELLE D'ENTRÉE DE
PRESSION
Toujours De 10 à 99950. (défaut = 10000)
P4
VALEUR BASSE ÉCHELLE D'ENTRÉE DE
PRESSION
Toujours
De -/+ 25 % de la valeur pleine échelle. (défaut = 0)
P5 POSITION DU POINT DÉCIMAL DE L'ENTRÉE
DE PRESSION
Toujours nnnnn (défaut), nnnn.n, nnn.nn, nn.nnn, n.nnnn.
P6 VALEUR DE REPLI DE L’ENTRÉE PRESSION Toujours Configure l'état d'alarme en cas de capteur ouvert.
Hi
Haut (défaut)
LO
Bas
P7 CALIBRATION SHUNT Toujours
Off désactivée
On activée (défaut)
P8
VALEUR SHUNT
Si P7 = activé
De 40,0 à 100,0 %.
(défaut 80,0 %)
P9 DÉLAI D'ACTUALISATION DE L'AFFICHAGE
ENTRÉE PRESSION
Toujours 0,050, 0,100, 0,250, 0,400 sec.
(défaut = 0,400)
P11 SÉLECTION DE L'ENTRÉE SECONDAIRE Si l'entrée secondaire
est installée
Désactivé, 0-20 mA, 4-20 mA, 0-5 V, 0-10 V, Str jauge de
contrainte
(défaut = 4-20)
P12 FONCTION DE L’ENTRÉE SECONDAIRE Si P11 ≠ OFF
Modifiable si P11 ≠
Str ; sinon forcé sur
rSP
rsp (l'entrée fonctionne comme une consigne déportée)
DiffP (l'entrée joue le rôle de second capteur pour la mesure de
la pression différentielle).
(défaut = rsp)
P19
VALEUR HAUTE ÉCHELLE DE L'ENTRÉE
SECONDAIRE
Si P11 ≠ OFF &
P12 = diff.P
De 0 à la valeur pleine échelle (4000, 8000, 20000, 40000, 80000 ou
99950, selon la valeur pleine échelle de l'entrée de pression).
(défaut = 10000)
P20 VALEUR BASSE ÉCHELLE DE L'ENTRÉE
SECONDAIRE
De -/+ 25 % du paramètre 'Valeur pleine échelle entrée secondaire'
(SI.FSV) (défaut 0)
P21 REPLI DE L'ENTRÉE SECONDAIRE
Si P11 ≠ OFF &
P12 = rSP
Hi Haut LO Bas (défaut)
P22 PLAGE BASSE DE L’ENTRÉE CONSIGNE
DÉPORTÉE
De 0 (défaut) à P3.
P23 PLAGE HAUTE DE L’ENTRÉE CONSIGNE
DÉPORTÉE
De 0 à P3 (défaut)
P24 DÉLAI D'ÉCHANTILLONNAGE DE L’ENTRÉE
SECONDAIRE
P12 = rSP
0,100, 0,200, 0,500 (défaut), 1,000 seconde
P35 SÉLECTION DE LA SORTIE RÉGULATION Toujours 0-20 mA, 4-20 mA, 0-10 V (défaut), -10,10 V, 0-5 V
P36 PLAGE BASSE DE LA SORTIE RÉGULATION Toujours De -10000 à P37 (défaut = 0)
P37 PLAGE HAUTE DE LA SORTIE RÉGULATION Toujours De P36 à 10000 (défaut =100,0)
P38 POSITION DÉCIMALE SUR LA SORTIE
RÉGULATION
Toujours
Utilisez les touches
ou pour sélectionner la position de la
décimale
P39 INDICATION DU MODE MANUEL DE LA
SORTIE RÉGULATION
Toujours 100,0 % (défaut) ou
rPN - mis à l'échelle avec les paramètres P36 et P37 (indication
RPM)
P40
SÉLECTION DIRECT/INVERSE POUR SORTIE
RÉGULATION
Toujours
r d, r r, d d, d r. (défaut = r d)
Voir le manuel pour avoir plus de détails.
P55
SÉLECTION DE LA SORTIE RETRANSMISSION
Si la retrans. est
installée
OFF, 0-20 mA, 4-20 mA, 0-10 V (défaut), -10 à +10 V, 0-5 V
P56 PLAGE BASSE DE LA SORTIE
RETRANSMISSION
Si P55 ≠ OFF
0 à P3. (défaut = 0)
P57 PLAGE HAUTE DE LA SORTIE
RETRANSMISSION
Si P55 ≠ OFF 0 à P3. (défaut = P3)
P61 APLLICATION DE L’ALARME 1 SUR LA
VOIE D’ENTRÉE
Toujours
OFF désactivée
ProC alarme de process (défaut)
Band alarme de bande
dev alarme de déviation
P62 TYPE ALARME 1
Si P61 ≠ OFF HI Haute, LO basse, InhIb basse avec masque au
démarrage
(défaut)
P63 MODE DE RÉINITIALISATION DE L’ALARME 1
Si P61 ≠ OFF AUto réinitialisation automatique (défaut) Latch
réinitialisation manuelle
P64 REPLI DE L'ALARME1
Si P61 ≠ OFF FS mode repli (défaut),
nFS mode sans repli
P65
LIAISON VOIE ENTRÉE ALARME 2
Toujours
Comme P61
P66 TYPE ALARME 2
Si P65 ≠ OFF Comme P62 (défaut = HI)
P67 MODE DE RÉINITIALISATION DE L’ALARME 2
Si P65 ≠ OFF
Comme P63
P68 MODE DE REPLI DE L’ALARME 2
Si P65 ≠ OFF
Comme P64
P69
LIAISON VOIE ENTRÉE ALARME 3
Toujours
Comme P61
P70 TYPE ALARME 3
Si P69 ≠ OFF Comme P62 (défaut = HI)
P71 MODE DE RÉINITIALISATION DE L’ALARME 3
Si P69 ≠ OFF
Comme P63
P72 MODE DE REPLI DE L’ ALARME 3
Si P69 ≠ OFF
Comme P64
P81
CONFIGURATION DE L’ENTRÉE LOGIQUE
Ce paramètre configure l'entrée logique sur
les bornes 23 et 24
Toujours
OFF désactivée
AL initialisation alarme
P réinitialisation pic
AL-P initialisation alarme + pic (défaut)
CAL.0 calibration zéro
ALL calibration zéro, réinitialisation alarme et pic
P82 ÉTAT ENTRÉE DE L’ENTREE LOGIQUE
Si P81 ≠ OFF CLOSE active (défaut)
OPEn inactive
P83 DÉTECTION DU PIC Toujours
OFF désactivée
HI pic maximum (défaut)
LO pic minimum
P84 FRÉQUENCE DE L’ALIMENTATION Toujours
50 (Hz), 60 (Hz), Auto détection automatique (défaut)
P85 LECTURE DE LA FRÉQUENCE DE
L’ALIMENTATION
Quand P84 = Auto
50 (Hz), 60 (Hz), en dessous de 50 Hz détection automatique
non possible
P86 DÉMARRAGE MANUEL/AUTO Toujours
AUto automatique
Nan manuel (défaut)
P87 TRANSFERT MANUEL/AUTO Toujours
BUNpL sans à-coups (défaut)
SP mode de modification de la consigne
P91 ADRESSE DE COMMUNICATION SÉRIE Modbus seulement
OFF désactivée (défaut)
1 à 255
P92 TYPE DE PROTOCOLE
Si P91 ≠ OFF NodbS modbus (défaut)
JbUS Jbus
P93 TYPE DE COMMUNICATION
Si P91 ≠ OFF 8nonE (défaut), 8EvEn, 8 odd.
P94 VITESSE DE COMMUNICATION EN BAUD
Si P91 ≠ OFF
600, 1200, 2400, 4800, 9600, 19200 (défaut = 19200)
P98 MOT DE PASSE POUR LE NIVEAU 2 Toujours 0 à 9999 (0 = pas de mot de
passe)
(défaut = 2)
(défaut = 4)
P99 MOT DE PASSE POUR LA CONFIGURATION Toujours
rEc.L
POINT DE REPRISE (RAPPEL
CONFIGURATION)
Toujours
nonE (défaut),
fAct pour revenir aux paramètres d'usine
Consulter le manuel HA031861 pour obtenir une explication complète des codes P.
Pour accéder au niveau Configuration et le quitter, suivre la procédure
indiquée à la section 7.
Codes ‘P’ du niveau Configuration
L'affichage indique ConF. Appuyer sur pour sélectionner le code ‘P’ dans le tableau suivant (ou sur pour revenir en arrière).
8
FR
Pour changer le mode de fonctionnement, suivre les étapes ci-
dessous :
1. Appuyer de manière continue sur jusqu'à ce que l'écran
affiche "GoTo" (environ 4 secondes)
2. Appuyer sur ou pour sélectionner le niveau de
fonctionnement souhaité sur l'affichage supérieur :
LEv1 Mode de fonctionnement normal, niveau 1
LEv2 Mode de fonctionnement normal, niveau 2
ConF Niveau Configuration
Mném. Paramètre Disponibilité
SP
CONSIGNE
voir 'Paramètres Niveau 1'
AL.NAS
RÉINITIALISATION DE L’INHIBITION DES ALARMES
A-N
SÉLECTION AUTO/MANUEL
Lr.SP
SÉLECTION CONSIGNE LOCALE/DÉPORTÉE
Si P12 = rSP
La dernière sélection est restaurée au démarrage. Défaut
= LoC
SP.Lo
LIMITE BASSE DU POINT DE CONSIGNE
Toujours
Plage 0 à SP.H.i (Défaut = 0)
SP.Hi
LIMITE HAUTE DU POINT DE CONSIGNE
Toujours
Plage SP.Lo à P3. (Défaut = P3)
SP.rr
VALEUR DE LA RAMPE SUR LA CONSIGNE Toujours
Pour limiter la vitesse de variation de la valeur de
consigne. (Défaut = OFF).
AL1
SEUIL ALARME 1 Si P61 ≠ OFF
voir 'Paramètres Niveau 1'
A1.HS
HYSTERESIS ALARME 1 Si P61 ≠ OFF
Plage 0,1 à 10,0 %. (Défaut = 1,0).
AL2
SEUIL ALARME 2
Si P65 ≠ OFF
voir 'Paramètres Niveau 1'
A2.HS
HYSTERESIS ALARME 2
Si P65 ≠ OFF
Plage 0,1 à 10,0 %. (Défaut = 1,0).
AL3
SEUIL ALARME 3 Si P69 ≠ OFF
voir 'Paramètres Niveau 1'
A3.HS
HYSTERESIS ALARME 3 Si P69 ≠ OFF
Plage 0,1 à 10,0 %. (Défaut = 1,0).
Pi.vAL
VALEUR D'ENTRÉE PRESSION PRINCIPALE
voir 'Paramètres Niveau 1'
Si.vAL
VALEUR D'ENTRÉE PRESSION SECONDAIRE
Lo.C
CALIBRATION DU ZÉRO Toujours
Utiliser ou pour faire passer l'affichage supérieur
de OFF à On.
Ensuite, appuyer sur pour lancer la calibration.
On peut aussi sélectionner CLEAr pour supprimer la
calibration de terrain et revenir à la calibration d'usine.
Défaut : Calibration zéro : 0
Calibration plage : Pleine échelle pour la saisie linéaire ;
33,3 mV pour la jauge de contrainte.
Lo.2.C
CALIBRATION DU ZÉRO POUR L'ENTRÉE
SECONDAIRE
Si P11 ≠ OFF
& P12 = diff.P
Hi.C
CALIBRATION PLAGE HAUTE Toujours
Hi.2.C
CALIBRATION PLAGE HAUTE POUR L'ENTRÉE
SECONDAIRE
Si P11 ≠ OFF &
P12 = diff.P
tUne
RÉGLAGE AUTOMATIQUE
Toujours
En mode manuel, démarre l'algorithme TUNE. En mode
auto, active la fonction ADAPTATIVE. (Défaut = OFF).
Pb
BANDE PROPORTIONNELLE Toujours
Plage 1 à 10000 %. (Défaut = 100).
Ti
TEMPS D’INTEGRALE Toujours
Plage 0,1 à 999 s. (Défaut = 5,0).
Td
TEMPS DE DÉRIVEE Toujours
Plage 0,0 à 999 s. (Défaut = 0,0).
IP
CENTRAGE D’INTÉGRALE Toujours
Plage 0,0 à 100%. (Défaut = 50,0).
oP.Hi
LIMITATION SORTIE DE RÉGULATION Toujours
Plage 10,0 à 100,0. (Défaut = 100,0).
Ctr.t
TYPE DE RÉGULATION Toujours
PI ou PID. (Défaut = PI)
Ctr.FL
FILTRE POUR AFFICHAGE ET RÉGULATEUR Toujours
Plage OFF, 0,5, 1, 2, 4, 8, 16 sec. (Défaut = 1 sec).
ASb
VEILLE AUTOMATIQUE
Toujours
Plage On ou OFF. (Défaut = OFF).
ASb.PL
LIMITE BASSE DE LA PRESSION AUTOMATIQUE
DE VEILLE
Si ASb = On
Plage 0 à 15 %. (Défaut 5 %)
ASb.rT
DÉLAI DE REPRISE AUTOMATIQUE DE VEILLE
Si ASb = On
Plage 0 à 60 puis
OFF (sortie bloquée).
A1.FL
FILTRE DE L’ALARME 1 Si P61 ≠ OFF
Plage OFF, 0,4, 1, 2, 3, 4, 5 sec. (Défaut = 0,4 sec).
A2.FL
FILTRE DE L’ALARME 2 Si P65 ≠ OFF
A3.FL
FILTRE DE L’ALARME 3
Si P69 ≠ OFF
ro.FL
FILTRE DE LA SORTIE RETRANSMISSION Si P55 ≠ OFF
At.t
TEMPS SUR LA FONCTION SMART
Ces paramètres s'appliquent lorsque la fonction TUnE
est activée.
Voir le manuel HA031861 pour avoir plus de détails
At.StP
ÉTAPE DANS LA FONCTION SMART
At.iP
SÉLECTION AUTOMATIQUE DE LA VALEUR DE PRÉ-CHARGE
INTÉGRALE
At.AFL
SÉLECTION AUTOMATIQUE DE LA CONSTANTE DE TEMPS DU FILTRE
At.t0
TEMPS DE RETARD DU PROCESS
At.Pt
CONSTANTE DE TEMPS DU PROCESS
At.PG
GAIN DU PROCESS
At.t1
TEMPS DE DÉMARRAGE DE LA FONCTION SMART
At.t2
TEMPS D'ARRÊT DE LA FONCTION SMART
At.AdS
ÉTAPE ADAPTATIVE
Paramètres Niveau 1 et 2
Pour sélectionner d'autres niveaux de fonctionnement
3. Confirmer le choix en appuyant sur .
4. Saisir le mot de passe (s'il est configuré) en utilisant ou
. LEv2 défaut 2. Conf défaut 4.
5. Appuyer sur pour ajuster cette valeur. Si les mots de passe
ne sont pas configurés, le niveau sélectionné sera saisi à 3 ci-
dessus.
Une fois le niveau choisi, appuyer sur pour faire défiler les
paramètres puis sur ou pour modifier leurs valeurs.
7
Calibration des transducteurs de pression connectés à l'entrée principale et dotés d'une résistance shunt interne.
Au niveau configuration régler les codes ‘P’ pertinents pour le transducteur étalonné, par exemple :
P1
= Str
P5 = la position de la décimale requise
P2 = unités de pression, par ex psi P6 = comme sélectionné - normalement haut
P3 = Echelle haute de la jauge de contrainte, par ex. 10000 psi P7 = Activé. Calibration shunt activée, si le transducteur de
pression est doté d'une résistance shunt interne.
P4 = Echelle basse de la jauge de contrainte, par ex. 0 psi P8 = le pourcentage correct (80 % pour un transducteur
typique).
Au niveau 2
1. Sélectionner Lo.C (calibration basse de l'entrée principale)
2. Utiliser ou pour faire passer l'affichage supérieur de OFF à On.
3. Ensuite, appuyer sur pour lancer la calibration.
4. L'instrument affiche la progression de l'étalonnage
5. Sélectionner Hi.C (calibration de plage de l'entrée principale. Noter qu'il s'agit de 80 % de la plage comme configuré par P8.)
6. Utiliser ou pour faire passer l'affichage supérieur de OFF à On.
7. Ensuite, appuyer sur pour lancer la calibration.
8. L'instrument affiche la progression de l'étalonnage
Calibration des transducteurs de pression avec une résistance de shunt externe
Relier la résistance shunt externe (valeur spécifiée par le fabricant du transducteur) entre les bornes 17 (Cal1) et 14 (Cal2).
S'assurer que les valeurs sur l’échelle haute et basse ont été réglées pour correspondre à la plage du transducteur, que la fonction Shunt
est activée et que P8 est configuré sur le pourcentage correct indiqué ci-dessus.
Au niveau 2, répéter les étapes 1 à 8 ci-dessus.
Calibration des transducteurs de pression amplifiés avec une résistance de shunt interne
Au niveau configuration, s'assurer que P7 est configuré sur OFF puis répéter les étapes 1 à 8 ci-dessus.
Calibration d'un transducteur de pression connecté à l'entrée secondaire
Comme ci-dessus, mais au niveau 2 utiliser les paramètres Lo.2.C (calibration du zéro) et Hi.2.C (calibration de la plage haute) au lieu de
Lo.C et Hi.C.
Calibration du transducteur de pression
Cette section décrit comment calibrer l'instrument selon le
transducteur de pression spécifique utilisé. L'instrument doit être
mis sous tension pendant au moins 15 minutes pour permettre au
transducteur d'atteindre les conditions d'exploitation.
9
Tous droits strictement réservés. La reproduction, la distribution ou le
stockage de ce document d'une manière quelconque est interdite sans
l'autorisation écrite préalable d'Eurotherm.
Les informations figurant dans le présent document sont susceptibles
d'évoluer sans préavis et sont fournies à titre informatif uniquement.
Eurotherm décline toute responsabilité quant aux pertes éventuelles
consécutives à des erreurs commises dans le présent document.
Cet instrument est conçu pour des applications industrielles de régulation des procédés et de la température et satisfait aux exigences des directives européennes en
matière de sécurité et de compatibilité électromagnétique.
Les informations contenues ici sont sujettes à modification sans préavis. Bien que tous les efforts aient été consentis pour assurer l'exactitude des informations, le
fournisseur décline toute responsabilité pour les erreurs susceptibles de s’y être glissées.
La sécurité et la protection CEM peuvent être gravement compromises si l'instrument n'est pas utilisé de la manière indiquée. Il incombe à l'installateur de veiller à la
sécurité et à la compatibilité électromagnétique de toute installation.
Cet instrument est conforme à la directive européenne sur les basses tensions 2006/95/CE, en vertu de l’application de la norme de sécurité EN 61010.
Déballage et stockage Si l'emballage ou l'appareil est endommagé à la livraison, ne pas l'installer et contacter le fournisseur. Si l'appareil doit être stocké avant
utilisation, le protéger de l'humidité et de la poussière à une température ambiante comprise entre -20
O
C et +70
O
C.
Précautions en matière de décharges électrostatiques. Toujours respecter les précautions électrostatiques avant de manipuler l'appareil.
Entretien et réparation. Cet instrument ne contient aucune pièce réparable par l'utilisateur. Contacter le fournisseur pour toute réparation.
Nettoyage. Utiliser de l'alcool isopropylique pour le nettoyage des étiquettes. Ne pas utiliser d'eau ni de produits à base d'eau. Utiliser une solution savonneuse douce
pour nettoyer les autres surfaces extérieures.
Compatibilité électromagnétique Cet instrument est conforme aux exigences de protection essentielles de la directive EMC 2004/108/CE, par l’application d’un fichier
de construction technique. Il satisfait aux exigences générales de l'environnement industriel défini dans EN 61326.
Attention : Condensateurs chargés. Avant de sortir un instrument de son boîtier, débrancher l'alimentation et attendre au moins deux minutes pour permettre aux
condensateurs de se décharger. Dans tous les cas, éviter de toucher aux composants électroniques de l'instrument lors du retrait de son boîtier.
Symboles. Si des symboles apparaissent sur cet instrument, ils ont les significations suivantes :
W Consulter le manuel. D Risque de choc électrique. O Prendre des précautions contre l'électricité statique. - Protection par DOUBLE ISOLATION
Catégorie d'installation et degré de pollution. Cet instrument a été conçu pour satisfaire aux exigences de la norme EN61010, catégorie d'installation II, degré de
pollution 2, telles qu'elles sont définies ci-dessous :
Catégorie d’installation II (CAT II). La tension de choc nominale pour un équipement ayant une alimentation 230 V nominale est de 2500 V.
Mesure Catégorie I (CAT 1). Les circuits supportent des pics de tension de 1500V.
Degré de pollution 2. Dans des conditions d'utilisation normales, seule une pollution non conductrice se produira. Cependant, une conductivité temporaire due à la
condensation se produira.
Personnel. L'installation ne doit être confiée qu’au personnel adéquatement qualifié.
Sécurité et informations CEM
Protection des parties sous tension. Afin d'éviter que les mains ou les outils en métal n'entrent au contact de composants sous tension, l'unité devra être installée dans
une armoire.
Câblage. Il est impératif de raccorder l'unité conformément aux informations figurant dans cette fiche d'instructions. Toujours utiliser des câbles en cuivre. Le câblage
doit respecter toute la réglementation locale en la matière, par exemple au Royaume-Uni la réglementation de câblage IEE la plus récente (BS7671) et aux États-Unis les
méthodes de câblage NEC Classe 1.
Tension nominale. La tension maximale appliquée aux bornes de sortie relais et logiques ne doit pas dépasser 230 V CA+15 %. Le régulateur ne doit pas être raccordé à
une alimentation triphasée avec montage en étoile sans terre.
La pollution par conduction électrique comme la poussière de carbone DOIT être exclue de l'armoire de l'appareil. Si nécessaire, installer un filtre à air sur l'entrée d'air
de l'armoire. Lorsqu'il est probable que de la condensation se formera, inclure un chauffage à thermostat dans l'armoire.
Mise à la terre du blindage du capteur de température. Certaines installations prévoient généralement le remplacement du capteur de température, alors que le
régulateur est toujours sous tension. Dans ces circonstances et afin de renforcer la protection contre les chocs électriques, il est recommandé de mettre le blindage du
capteur de température à la terre. La mise à la terre du bâti de la machine n'est pas suffisante.
Exigences d’installation en matière de compatibilité électromagnétique Afin d'assurer la conformité avec la directive CME européenne, il est nécessaire de prendre
certaines précautions lors de l'installation:
Informations générales. Consulter le Guide d'installation CME, référence HA025464.
Sorties de relais. Il peut s'avérer nécessaire de monter un filtre adapté pour supprimer les émissions par conduction.
Installation sur table. Si une prise d'alimentation standard est utilisée, il est généralement nécessaire de respecter la norme sur les émissions commerciales et de
l'industrie légère. Pour respecter la norme des émissions par conduction, il faut installer un filtre secteur adapté.
Copyright Eurotherm
S.r.l. 2014
Bureaux à travers le monde
www.eurotherm.com/global
Coordonnées
Eurotherm Automation
Tél : (33) (0)4 78 66 45 00
www.eurotherm.tm.fr
Rechercher les contacts locaux
10
Code Description Availability
Range. Use or to change values.
P1
PRESSURE INPUT SELECTION
Always
Str Strain gauge (default)
0-20 mA, 4-20 mA, 0-5V, 0-10V
P2 PRESSURE INPUT ENGINEERING UNIT Always
OFF - all beacons are turned off
hGcN2 - beacon (kg/cm
2
) lit
PSI - beacon (PSI) lit (default)
bAr - beacon (Bar) lit
NPa - beacon (MPa) lit
P3 PRESSURE INPUT FULL SCALE VALUE Always From 10 to 99950. (default = 10000)
P4 PRESSURE INPUT LOW SCALE VALUE Always From -/+ 25% of Full scale value. (default = 0)
P5
PRESSURE INPUT DECIMAL POINT
POSITION
Always
nnnnn (default), nnnn.n, nnn.nn, nn.nnn, n.nnnn.
P6 PRESSURE INPUT FAIL SAFE Always Sets the alarm state in the event of an open sensor.
HI High (default) LO Low
P7 SHUNT CALIBRATION Always
Off disabled
On enabled (default)
P8 SHUNT VALUE If P7 = On From 40.0 to 100.0 %.
(default 80.0%)
P9 PRESSURE INPUT DISPLAY UPDATE TIME Always 0.050, 0.100, 0.250, 0.400 sec.
(default = 0.400)
P11 SECONDARY INPUT SELECTION If the secondary
input is fitted
Disabled, 0-20 mA, 4-20 mA, 0-5V, 0-10V, Str strain gauge
(default = 4-20)
P12 SECONDARY INPUT FUNCTION If P11 ≠ OFF
Alterable if P11 ≠
Str; otherwise it is
forced to rSP
rsp (the input acts as a remote setpoint).
DiffP (the input acts as the second sensor for differential
pressure measurement).
(default = rsp)
P19 SECONDARY INPUT FULL SCALE VALUE
If P11 ≠ OFF &
P12 = diff.P
From 0 to the full scale value (4000, 8000, 20000, 40000,
80000 or 99950, according to the pressure input full scale
value). (default = 10000)
P20 SECONDARY INPUT LOW SCALE VALUE From -/+ 25% of the ‘Secondary input full scale value’
parameter (SI.FSV) (default = 0)
P21 SECONDARY INPUT FAIL SAFE
If P11 ≠ OFF &
P12 = rSP
HI High LO Low (default)
P22 REMOTE SET POINT INPUT RANGE LOW
From 0 (default) to P3.
P23 REMOTE SET POINT INPUT RANGE HIGH
From 0 to P3 (default)
P24 SECONDARY INPUT SAMPLE TIME
P12 = rSP
0.100, 0.200, 0.500 (default), 1.000 second
P35 CONTROL OUTPUT SELECTION Always 0-20mA, 4-20mA, 0-10V (default), -10.10V, 0-5V
P36 CONTROL OUTPUT RANGE LOW Always From -10000 to P37 (default = 0)
P37 CONTROL OUTPUT RANGE HIGH Always From P36 to 10000 (default =100.0)
P38
CONTROL OUTPUT DECIMAL POINT
POSITION
Always
Use or keys to select the position of the decimal point
P39 CONTROL OUTPUT MANUAL MODE
INDICATION
Always 100.0% (default) or
rPN - scaled with P36/P37 parameters (RPM indication)
P40 DIRECT/REVERSE SELECTION FOR
CONTROL OUTPUT
Always
r d, r r, d d, d r. (default = r d)
See User Manual for further details.
P55 RETRANSMISSION OUTPUT SELECTION If retrans. fitted OFF, 0-20mA, 4-20mA, 0-10V (default), -10 to +10V, 0-5V
P56 RETRANSMISSION OUTPUT RANGE LOW
If P55 ≠ OFF
0 to P3. (default = 0)
P57 RETRANSMISSION OUTPUT RANGE HIGH
If P55 ≠ OFF 0 to P3. (default = P3)
P61 ALARM 1 INPUT CHANNEL LINK Always
OFF disabled
ProC process alarm (default)
Band band alarm
dev deviation alarm
P62 ALARM 1 TYPE
If P61 ≠ OFF HI High, LO low, InhIb low with mask at
start-up (default)
P63 ALARM 1 RESET MODE
If P61 ≠ OFF AUto automatic reset (default) Latch manual reset
P64 ALARM 1 FAILSAFE MODE
If P61 ≠ OFF FS fail safe mode (default)
nFS non- fail safe mode
P65 ALARM 2 INPUT CHANNEL LINK Always As P61
P66 ALARM 2 TYPE
If P65 ≠ OFF As P62 (default = HI)
P67 ALARM 2 RESET MODE
If P65 ≠ OFF
As P63
P68 ALARM 2 FAILSAFE MODE
If P65 ≠ OFF
As P64
P69 ALARM 3 INPUT CHANNEL LINK Always As P61
P70 ALARM 3 TYPE
If P69 ≠ OFF As P62 (default = HI)
P71 ALARM 3 RESET MODE
If P69 ≠ OFF
As P63
P72 ALARM 3 FAILSAFE MODE
If P69 ≠ OFF
As P64
P81 LOGIC INPUT CONFIGURATION
This parameter configure the logic input
on terminals 23 and 24
Always
OFF disabled
AL alarm reset
P peak reset
AL-P alarm + peak reset (default)
CAL.0 zero calibration
ALL zero calibration, alarm and peak reset
P82 LOGIC INPUT STATUS
If P81 ≠ OFF CLOSE active (default)
OPEn inactive
P83 PEAK DETECTION Always
OFF disabled
HI maximum peak (default)
LO minimum peak
P84 LINE FREQUENCY Always
50 (Hz), 60 (Hz), Auto automatic detection (default)
P85 LINE FREQUENCY READOUT When P84 = Auto
50 (Hz), 60 (Hz), und.50 automatic detection inoperable
P86 MANUAL/AUTO START-UP Always
AUto automatic
Nan manual (default)
P87 MANUAL/AUTO TRANSFER Always
BUNpL bumpless (default)
SP setpoint modification mode
P91 SERIAL COMMUNICATION INTERFACE
ADDRESS
Modbus only
OFF disabled (default)
1 to 255
P92 PROTOCOL TYPE
If P91 ≠ OFF NodbS modbus (default)
JbUS Jbus
P93 COMMUNICATION TYPE
If P91 ≠ OFF 8nonE (default) 8EvEn, 8 odd
P94 COMMUNICATION BAUD RATE
If P91 ≠ OFF
600, 1200, 2400, 4800, 9600, 19200 (default = 19200)
P98 LEVEL 2 PASS CODE Always 0 to 9999 (0 = no password) (default = 2)
(default = 4)
P99 CONFIGURATION PASS CODE Always
rEc.L
RECOVERY POINT Always
nonE (default),
fAct to restore factory settings
See the User Manual HA031861 for a further explanation of P codes.
To access and leave Configuration Level follow the procedure described in section 7.
Configuration Level ‘P’ Codes
The display will show ConF. Press to select the ‘P’ code from the following table (or to scroll back).
8
Pressure Transducer Calibration
This section describes how to calibrate the instrument to the particular pressure
transducer being used. The instrument should be powered up for at least 15
minutes and allow the transducer to reach operating conditions.
Calibration of pressure transducers connected to the Primary Input and fitted with an internal shunt resistor.
In configuration level set the relevant ‘P’ codes for the transducer being calibrated, for example:
P1
= Str
P5 = the required decimal point position
P2 = pressure units e.g. psi P6 = As selected - usually high
P3 = full scale range of the strain gauge, e.g. 10000 psi P7
= On. Shunt calibration enabled, if the pressure transducer is
fitted with an internal shunt resistor.
P4 = the minimum scale range of the strain gauge, e.g. 0 psi P8 = the correct percentage (80% for a typical transducer).
In Level 2
1. Select Lo.C (low calibration for the primary input)
2. Use or to switch upper display from OFF to On.
3. Then press to start the calibration.
4. The instrument shows the progress of the calibration
5. Select Hi.C (span calibration for the primary input. Note this is 80% of span as set by P8.)
6. Use or to switch upper display from OFF to On.
7. Then press to start the calibration.
8. The instrument shows the progress of the calibration
Calibration of pressure transducers with an external shunt resistor
Connect the external shunt resistor (value as specified by the transducer manufacturer) across terminals 17 (Cal1) and 14 (Cal2).
Ensure that the full scale and low scale values have been set to match the range of the transducer, the Shunt function is On and P8 is set to
the correct percentage as listed above.
In Level 2, repeat steps 1 to 8 above.
Calibration of an amplified pressure transducers with an internal shunt resistor
In configuration level ensure that P7 is set to OFF, then repeat steps 1 to 8 above.
Calibration of pressure transducer connected to the secondary input
This is the same as above but in Level 2 use the Lo.2.C (zero calibration) and Hi.2.C (Span calibration) parameters instead of Lo.C and Hi.C.
9
GB
To change the operating mode, follow the steps below:
1. Press and hold until the lower display shows “GoTo
(approximately 4 seconds)
2. Press
or to select the desired operating level on the
upper display:
LEv1 Normal operative mode Level 1
LEv2 Normal operative mode Level 2
ConF Configuration level
Mnem. Parameter Availability
SP
SETPOINT see ‘Level 1 Parameters’
AL.NAS
ALARMS MASK RESET
A-N
AUTO/MANUAL SELECTION
Lr.SP
LOCAL/REMOTE SET POINT SELECTION
If P12 = rSP The last selection is restored at power up. Default = LoC
SP.Lo
SET POINT LIMIT LOW Always
Range 0 to SP.H.i (Default = 0)
SP.Hi
SET POINT LIMIT HIGH Always
Range SP.Lo to P3. (Default = P3)
SP.rr
SET POINT RAMP Always To limit the rate of change of setpoint. (Default = OFF).
AL1
ALARM 1 THRESHOLD If P61 ≠ OFF see ‘Level 1 Parameters’
A1.HS
ALARM 1 HYSTERESIS If P61 ≠ OFF Range 0.1 to 10.0%. (Default = 1.0).
AL2
ALARM 2 THRESHOLD If P65 ≠ OFF see ‘Level 1 Parameters’
A2.HS
ALARM 2 HYSTERESIS If P65 ≠ OFF Range 0.1 to 10.0%. (Default = 1.0).
AL3
ALARM 3 THRESHOLD If P69 ≠ OFF see ‘Level 1 Parameters’
A3.HS
ALARM 3 HYSTERESIS If P69 ≠ OFF Range 0.1 to 10.0%. (Default = 1.0).
Pi.vAL
PRIMARY PRESSURE INPUT VALUE see ‘Level 1 Parameters’
Si.vAL
SECONARY PRESSURE INPUT VALUE
Lo.C
ZERO CALIBRATION Always
Use or to switch upper display from OFF to On.
Then press to start the calibration.
It is also possible to select CLEAr to delete field
calibration and restore factory calibration.
Default: Zero calibration: 0
Span calibration: Full scale for linear input; 33.3mV for
strain gauge.
Lo.2.C
ZERO CALIBRATION FOR SECONDARY INPUT If P11 ≠ OFF
& P12 =
diff.P
Hi.C
SPAN CALIBRATION Always
Hi.2.C
SPAN CALIBRATION FOR SECONDARY INPUT
If P11 ≠ OFF &
P12 = diff.P
tUne
AUTO TUNE Always In manual mode start the TUNE algorithm. In auto it
enables the ADAPTIVE function. (Default = OFF)
Pb
PROPORTIONAL BAND Always Range 1 to 10000%. (Default 100).
Ti
INTEGRAL TIME Always Range 0.1 to 99.9s. (Default = 5.0).
Td
DERIVATIVE TIME
Always
Range 0.0 to 99.9s. (Default = 0.0).
iP
INTEGRAL PRE LOAD Always Range 0.0 to 100%. (Default = 50.0).
oP.Hi
CONTROL OUTPUT LIMITER Always Range 10.0 to 100.0. (Default = 100.0).
Ctr.t
TYPE OF CONTROL Always PI or PID. (Default = PI).
Ctr.FL
FILTER FOR DISPLAY AND CONTROLLER Always Range OFF, 0.5, 1, 2, 4, 8, 16 sec. (Default = 1 sec).
ASb
AUTOMATIC STAND-BY Always Range On or OFF. (Default = OFF)
ASb.PL
AUTOMATIC STAND-BY PRESSURE LOW LIMIT
If ASb = On
Range 0 to 15%. (Default = 5%).
ASb.rT
AUTOMATIC STAND-BY RECOVERY TIME
If ASb = On
Range 0 to 60 then
OFF (output is frozen).
A1.FL
ALARM 1 FILTER If P61 ≠ OFF Range OFF, 0.4, 1, 2, 3, 4, 5 sec. (Default = 0.4 sec).
A2.FL
ALARM 2 FILTER If P65 ≠ OFF
A3.FL
ALARM 3 FILTER If P69 ≠ OFF
ro.FL
RETRANSMISSION OUTPUT FILTER If P55 ≠ OFF
At.t
TIME OF SMART FUNCTION
These parameters apply when the TUnE function is
active.
See User Manual HA031861 for further details
At.StP
STEP FOR SMART FUNCTION
At.iP
AUTOMATIC SELECTION OF THE INTEGRAL PRE LOAD VALUE
At.AFL
AUTOMATIC SELECTION OF THE FILTER TIME CONSTANT
At.t0
PROCESS TIME DELAY
At.Pt
PROCESS TIME CONSTANT
At.PG
PROCESS GAIN
At.t1
START TIME OF SMART FUNCTION
At.t2
STOP TIME OF SMART FUNCTION
At.AdS
ADAPTIVE STEP
Level 1 and 2 Parameters
To Select Other Levels of Operation
3. Confirm the choice by pressing .
4. Enter the passcode (if configured) using or . LEv2
default 2. Conf default 4.
5. Press
to accept the value. If passcodes are not
configured the selected level will be entered at 3 above.
When the level has been chosen, press to scroll through
the parameters and
or to change their values.
7
This instrument is intended for industrial temperature and process control applications within the requirements of the European Directives on Safety and EMC.
Information contained here is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be
held liable for errors contained herein.
Safety and EMC protection can be seriously impaired if the unit is not used in the manner specified. The installer must ensure the safety and EMC of the installation.
This instrument complies with the European Low Voltage Directive 2006/95/EC, by application of safety standard EN 61010.
Unpacking and storage. If on receipt, the packaging or unit is damaged, do not install but contact your supplier. If being stored before use, protect from humidity and
dust in an ambient temperature range of -20
O
C to +70
O
C.
Electrostatic discharge precautions. Always observe all electrostatic precautions before handling the unit.
Service and repair. This instrument has no user serviceable parts. Contact your supplier for repair.
Cleaning. Isopropyl alcohol may be used to clean labels. Do n
ot use water or water based products. A mild soap solution may be used to clean other exterior surfaces.
Electromagnetic compatibility. This instrument conforms to the essential protection requirements of the EMC Directive 2004/108/EC, by the application of a Technical
Construction File. It satisfies the general requirements of the industrial environment defined in EN 61326-1.
Caution: Charged capacitors. Before removing an instrument from its sleeve, disconnect the supply and wait at least two minute
s to allow capacitors to discharge. Avoid
touching the exposed electronics of an instrument when withdrawing it from the sleeve.
Symbols. If symbols are used on the instrument, they have the following meaning:
W Refer to manual. D Risk of electric shock. O Take precautions against static.
{
Protected by DOUBLE INSULATION
Installation Category and Pollution Degree. This unit has been designed to conform to EN61010 standard installation category and pollution degree, defined as follows:-
Installation Category II (CAT II). The rated impulse voltage for equipment on nominal 230V supply is 2500V.
Measurement Category I (CAT 1). Circuits withstand a 1500Vrated impulse voltage.
Pollution Degree 2. Normally only non-conductive pollution occurs. However, a temporary conductivity caused by condensation must be expected.
Personnel. Installation must only be carried out by suitably qualified personnel
Enclosure of Live Parts. To prevent hands or metal tools touching parts that may be electrically live, the unit must be installed in an enclosure
Safety and EMC
10
Wiring. It is important to connect the unit in accordance with the data in this sheet. Always use copper cables. Wiring must comply with all local wiring regulations, i.e.
UK, the latest IEE wiring regulations, (BS7671), and USA, NEC Class 1 wiring methods.
Voltage rating. The maximum voltage applied to the relay and logic output terminals must not exceed 230Vac +15%. The controller must not be wired to a three phase
supply with an unearthed star connection.
Electrically Conductive pollution e.g. carbon dust, MUST be excluded from the unit enclosure. Where necessary, fit an air filter to the air intake of the enclosure. Where
condensation is likely, include a thermostatically controlled heater in the enclosure.
Grounding of the temperature sensor shield.
In some installations it is common practice to replace the temperature sensor while the controller is still powered up. Unde
r
these conditions, as additional protection agai
nst electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through
the framework of the machine.
Installation Requirements for EMC. To comply with European EMC directive certain installation precautions are necessary:-
General guidance. Refer to EMC Installation Guide, Part no. HA025464.
Relay outputs. It may be necessary to fit a suitable filter to suppress conducted emissions.
Table top installation. If using a standard power socket, compliance with commercial and light industrial emissions standard is usually required. To comply with
conducted emissions standard, a suitable mains filter must be installed.
All rights are strictly reserved. Reproduction, distribution
or storage of this document in any manner is prohibited
without prior written consent from Eurotherm.
Information in this document may change without notice
and is intended for guidance only. Eurotherm will accept
no responsibility for any loses arising from errors in this
document.
Copyright Eurotherm S.r.l. 2014
Worldwide Offices
www.eurotherm.com/global
Contact Details
Scan for local contacts
Eurotherm Limited
Faraday Close,
Durrington,
Worthing,
West Sussex,
UK
BN13 3PL.
Sales Enquiries
T +44 (01903) 695888
F 0845 130 9936
General Enquiries
T +44 (01903) 268500
F 0845 265982
*HA031859EF*
Ce guide a pour but de décrire l'installation et le
fonctionnement général.
Pour obtenir des informations complémentaires et la
spécification technique complète, consulter le Manuel
utilisateur référence HA031861, que l'on peut télécharger
sur www.eurotherm.co.uk.
Guide de prise en main du régulateur de process P304
c
Le P304c est un régulateur de pression et de process à
microprocesseur basé sur la gamme d'instruments Piccolo.
Il convient à un grand nombre de procédés, y compris le
contrôle et l'indication de la pression de fonte en extrusion.
Deux entrées de process sont disponibles ; elles sont
configurables par l'utilisateur pour les jauges de contrainte
350, à tension ou intensité. Une alimentation 24 V cc
fournit la tension à deux ou quatre transducteurs filaires.
Deux sorties tension ou mA peuvent être configurées pour
la régulation ou pour la retransmission des mesures de
process.
On peut rattacher trois alarmes à la variable mesurée pour
fournir une indication et des asservissements des alarmes
hors tolérances.
La communication numérique EIA485 3-fils utilise la
communication avec le protocole Modbus/Jbus.
On peut définir les paramètres de configuration et de mise
en service par le biais des touches de la face avant
(protégées par différents niveaux d'accès).
Description
Déballage
L’emballage contient :
gulateur P304c monté dans son boîtier
2 x clips de fixation pour montage en panneau
Manuel d'installation en anglais, français, allemand et italien
Joint d'étanchéité
Référence HA031859EF/2 CN31907 07/14
1
FR
Dimensions
96 mm
(3.78in)
15mm
128 mm 96 mm
Le clavier comporte de cinq boutons poussoir, portant les désignations suivantes :
Auto/Man
Appuyer pendant plus de 1 seconde pour passer entre le mode automatique et le mode manuel et vice-versa. Le mode
automatique désigne le contrôle normal en boucle fermée ; le mode manuel signifie que la sortie peut être augmentée ou
abaissée manuellement au moyen des touches ou .
PAGE
Appuyer pendant plus de 4 secondes pour sélectionner le niveau de fonctionnement (voir la section 7). Pendant la
modification des paramètres, ce bouton est utilisé pour revenir
au paramètre précédent sans mémoriser les changements
de paramètres.
SCROLL
Pendant la modification des paramètres, ce bouton est utilisé pour passer au paramètre suivant et mémoriser les
changements de paramètres.
Réduire ou modifier une valeur de paramètre. En mode manuel, il est utilisé pour réduire la valeur de sortie. Lorsqu'on le
presse pendant plus de 3 secondes en mode automatique, il permet d'accéder au paramètre de consigne pour le réduire.
Augmenter ou modifier une valeur de paramètre.
En mode manuel, il est utilisé pour augmenter la valeur de sortie. Lorsqu'on le presse pendant plus de 3 secondes en
mode automatique, il permet d'accéder au paramètre de consigne pour l'augmenter.
En mode automatique, quand il est pressé pendant moins de 3 secondes, on l'utilise pour faire basculer l'affichage
inrieur entre la consigne ‘SP’, la valeur de déviation ‘Dev’, la valeur de sortie OP%’, la valeur de sortie ‘RPM’ et la valeur
pic ‘Crête’ (si cette fonction est activée).
Au moment de la mise en route, l'affichage inférieure indique la consigne si le mode automatique est sélectionné ou, en
mode manuel, la valeur de sortie.
+
Pour réinitialiser la valeur crête mémorisée et réarmer les alarmes. Cette fonction est désactivée quand l'appareil est
contrôlé par liaison série.
+ ou
+
Saute à la valeur du paramètre max ou min quand l'instrument est en monde manuel.
+ ou
+
Utilisé uniquement à la mise sous tension quand l'instrument détecte une erreur de paramètre, voir la section CODES
D'ERREUR du manuel pour obtenir d'autres informations.
Note :
Les actions exigeant d'appuyer sur au moins deux boutons poussoir doivent respecter exactement la séquence indiquée.
Clavier
Algorithme de réglage
clignotant = première étape activée
allumé = deuxième étape activée
Mise sous tension
Une séquence rapide de démarrage avec un auto-test
illumine tous les segments de l'afficheur puis affiche le
numéro de la version du logiciel et le type de l'instrument
(P304c).
L'affichage revient alors au niveau opérateur 1 ; une vue
typique est présentée ci-dessous.
Valeur mesurée (PV)
Paramètre sélectionné
En mode automatique, appuyer sur pour choisir :
SP (consigne) ; Dev (déviation SP -
PV) ;
OP%
(puissance de sortie) ;
RPM
(valeur de sortie mise à l'échelle des tours par
minute) ; Peak
(valeur crête)
Bar Graph - variable mesurée.
Les valeurs de consigne des
alarmes sont affichées.
Le premier segment clignote
pour une pression inférieure à
zéro.
Le dernier segment clignote
pour une pression supérieure
à la valeur pleine échelle.
Unité
kg/cm
2
, psi, bar, MPa
État indication
5
Toute alarme
active (rouge)
Alarme 1, 2
ou 3 active
Mode
manuel
sélectionné
Appareil
contrôlé par
liaison série
Consigne
déportée
sélectionnée
Man Tune Rem RSP
ALM
1 3 3
3
Branchements des bornes arrière
Sorties d'alarme - AL1 AL2 et AL3
AL1 et AL2
Relais inverseur : 264 V ca, 2 A max (charge
résistive), 12 V cc, 100 mA min
AL3 Relais normalement ouvert : 264 V ca, 2 A max
(charge résistive), 12 V cc, 100 mA min
Sélectionnable au clavier : - Mesure de process /
alarme de déviation / Bande / Haute / Basse / Basse
inhibée au démarrage, - Réinitialisation auto/manuel
Par défaut les relais sont désactivés en cas d'alarme
Entrées principales et secondaires
m/A ; 0-20 mA, 420 mA
Volt ; 0-5 V cc, 0-10 V cc
Jauge de contrainte ; de 340 à 5000, 1-4
mV/V, EXC excitation 10 V +7 %
Précautions
Ne pas acheminer les câbles d'entrée avec
les câbles d'alimentation
Câble de terre blindé à un seul point
Entrée de capteur non isolée de l'entrée de
réinitialisation
Sorties
Analogique : 0/10 V, -10/+10 V, 0/5 V charge 5 K ;
0/20 mA, 4-20 mA charge max 500, toutes en cc
OUT1 régulation : OUT2 - Retransmission
Communications numérique
EIA485 Modbus/Jbus (mode RTU)
Adresse : 1 à 255
Vitesse en Baud : 600 à 19200
Format : 1 bit de début, 8 bits de données avec ou
sans parité, 1 bit de fin
Parité : Paire/Impaire
Un port de configuration CPI est également disponible
Alimentation DC de transmetteur (TPSU) (option)
24 V cc +10 % <28 mA
Entrées logiques (contact sec)
DIG1 - Ouvert = Auto ; fermé = Manuel
DIG2 - Augmentation de la valeur de sortie
DIG3 - Diminution de la valeur de sortie
DIG4 - Réglage de la sortie de régulation sur 0
Les touches Auto/Man de la face avant sont
désactivées.
RESET - programmable pour alarme, valeur crête,
calibration du zéro ou réinitialisation de tout.
Schéma de principe et limites d'isolation
Clavier
affichage
CPU
PSU
principal
Entrée
logique
Limites
d'isolation
renforcées
Limites
d'isolation
Alarme 1
O/P
Alarme 3
O/P
Alarme 2
O/P
Secondaire
An O/P
TPSU
Principal
An I/P
Secondaire
An I/P
Interface
CPI
Communication
Modbus
EIA485
Principal
An O/P
4 x entrées
logiques
Fusibles
L'entrée de l'alimentation électrique n'est pas
protégée par un fusible.
Les fusibles doivent être montés extérieurement
Calibre recommandé pour les fusibles externes :
Pour 24 V CA/CC, type de fusible : T, 2 A 250 V
Pour 100-230 V ca, type de fusible : T, 2 A 250 V
Alimentation basse tension, en
option
24 V ca (14 à 30 V ca) 50/60 Hz
24 V cc (14 à 32 V cc) taux
résiduel 5 % max
18 VA à 24 V ca ; 12 W à 24 V cc.
La polarité n'est pas importante.
Alimentation électrique (PSU)
N'utiliser que des conducteurs en cuivre.
Un interrupteur ou disjoncteur doit être inclus
dans l’installation
que ce dernier doit être situé à proximité
immédiate de l'équipement et facilement
accessible par l'opérateur
qu'il doit être clairement identifié comme
dispositif de sectionnement de l'équipement.
Notes : Un seul interrupteur ou disjoncteur peut
commander plusieurs instruments.
Un branchement de terre (masse) n'est pas requis.
Alimentation haute tension
100 à 230 V ca +15 %, 50/60 Hz,
22 VA à 50 Hz ; 27 VA à 60 Hz
S'assurer que la tension est correcte pour l'instrument, et qu'elle est connectée aux bornes correctes
SIG-
NO
C
NC
NO
C
NC
SIG+
CAL2
3 -
4 +
5 +
6 +
7 -
8
10 +
11 -
EXC+
SIG+
SIG-
CAL2
56 +
57 -
58 +
59 -
60
61
45
46
47
48
49
50
12 +
13 -
14
16 +
17 -
18 +
19 +
21 +
22 -
mA
VOLT
EXC+
EXC-
CAL1
RESET
SOR1
mA/V
ALARME2
C
NO
L/24 V
N/24 V
SOR2
mA/V
A/A’
B/B’
Com
EIA485
mA
VOLT
23
24
Sortie
secondaire
Entrée
principale
ALARME3
EXC-
CAL1
51
52
53
54
ALARME1
TPSU
ALIMEN.
DIG1
DIG3
DIG4
62
63
64
65
66
DIG2
2
Code de commande
1. Choisir un emplacement offrant un minimum de vibrations et dont la
température ambiante est comprise entre 0 et 50
O
C et l’humidité
ambiante entre 0 et 85 %, sans condensation.
2. Préparer une découpe dans le panneau de montage, aux dimensions
indiquées.
4. Détacher les fixations de montage
du panneau (3) et faire coulisser le
joint d'étanchéité (1) sur le boîtier.
5. Faire glisser le boîtier de
l'instrument (2) dans la découpe.
6. Fixer les clips de montage du
panneau. Au moyen d'un
tournevis, serrer la tige filetée à un
couple entre 0,3 et 0,4 Nm.
7. Pour retirer le contrôleur de son
boîtier, écarter les pattes
d'ancrage (4) et tirer le contrôleur
vers l'avant pour l'extraire. Lors de
la remise en place, s’assurer que
les pattes d’ancrage sont bien
engagées pour maintenir
l'intégrité du joint.
3. Si l'on monte plus d’un
instrument sur le même
panneau, la distance minimale
entre eux doit être respectée
comme indiqué.
Installation
(2)
(3)
(3)
(4)
(4)
(1)
1. Fonction
CC
Régulateur de pression
Numéro du modèle
P304c
2. Tension d'alimentation
VH 100 - 230 Vca 50/60 Hz
VL 24 Vac / Vdc
3. Seconde entrée
XXX Sans
RSP
Consigne analogique ou seconde
entrée PV (montage en pression
différentielle)
4. Options
SDXX
TPSU transmetteur 24 Vcc +
retransmission analogique
SD4L
TPSU transmetteur 24 Vcc +
retransmission analogique
+ RS 485 + 4 entrées logiques
5. Étiquette perso.
XXXXX Sans
6. Spéciaux
XXXXX Sans
L'illustration n'est pas
à l'échelle
4,92in 4,92in
92 x 92 mm
Mnémonique Nom Disponibilité Explication
SP
CONSIGNE Toujours
Plage SP.LO à SP.Hi.
AL.NAS
RÉINITIALISATION DU
MASQUE ALARMES
Seulement si au moins une alarme
est configurée avec une inhibition
au démarrage
Utiliser ou pour faire passer l'affichage supérieur de OFF à
rESEt, puis appuyer sur
pour restaurer le masque d'alarme.
A-N
SÉLECTION
AUTO/MANUEL
Uniquement si un clavier externe
est installé
Peut être sélectionné par les entrées logiques des bornes 62 et 63 ou
sélectionner LoCAL pour utiliser le bouton frontal ou CnCt pour un
contrôle externe. Défaut = LoCaL
AL1
SEUIL ALARME 1 Seulement si P61 ≠ OFF Utilisé pour définir le point auquel l'alarme est activée.
Plage de réglage de 0 jusqu'à la valeur pleine échelle de l'entrée de
pression pour le process et l'alarme de bande.
Depuis les valeurs pleine échelle de l’entrée. pression à entrée +
pression pour l'alarme de déviation.
On peut élargir la limite haute à 110 % de l'échelle.
Par défaut AL1 5%, AL2 60 %, AL3 80 % de la plage.
AL2
SEUIL ALARME 2 Seulement si P65 ≠ OFF
AL3
SEUIL ALARME 3 Seulement si P69 ≠ OFF
Pi.vAL
VALEUR D'ENTRÉE
PRESSION PRINCIPALE
Seulement si P11 ≠ OFF
et
P12 = diff.P
Cette valeur est à lecture seule et indique la pression mesurée si le
transducteur est connecté aux bornes d'entrée principales.
Si.vAL
VALEUR D'ENTRÉE
PRESSION SECONDAIRE
Cette valeur est à lecture seule et indique la pression mesurée si le
transducteur est connecté aux bornes d'entrée secondaires.
Niveaux de fonctionnement
Il y a trois types de fonctionnement :
Niveau 1. Conçu pour l'utilisation au quotidien ; pas de mot de
passe.
Niveau 2. Les paramètres disponibles au niveau 1 sont aussi
disponibles au niveau 2. Le niveau 2 contient des paramètres
supplémentaires destinés à la mise en service et aux paramètres
plus étendues.
Mode configuration. Le niveau de configuration définit toutes les
caractéristiques de l'instrument ; il fait appel à une liste de codes P.
Chaque code P est associé à une fonctionnalité spécifique de
l'instrument, telle que le Type d'entrée, Plage de mesure, Sorties,
Alarmes, Communication numérique etc.
Une fois le niveau Configuration saisi, on peut sélectionner deux
autres niveaux :
Calibration instrument (ICAL)
Ils sont décrits dans le manuel HA031861.
Une fois mis en route, l'instrument
passe au niveau 1.
Appuyez sur pour faire défiler
la liste des paramètres disponibles
à ce niveau.
Les valeurs des paramètres sont
ajustées au moyen des touches
et , du moment que le
paramètre n'est pas lecture seule
ou n'a pas été bloqué aux autres
niveaux.
Fonctionnement niveau 1
Paramètres Niveau 1
6
Câblage
Cette section présente les câblages type
des capteurs d'entrée
Jauge de contrainte
La résistance d'étalonnage peut être montée en interne ou en externe sur certains transducteurs
mA-
-
+
4 fils
4-20mA ou
0-20mA
mA+
-
+
Transmetteur 4 fils
Alimentation
d'entrée du
transmetteur
Alimentation
transmetteur
(TPSU)
+
-
3/17
4/18
58
59
Diamètres de fil
Les bornes à vis acceptent des
fils de 0,5 à 1,5 mm (16 à 22
AWG). Les capots articulés
empêchent tout contact
accidentel entre les mains ou
un outil en métal et les fils sous
tension.
Les vis des bornes arrière
doivent être serrées entre 0.3
et 0.4 Nm.
4
-
Transmetteur 2 fils
+
3/17
4/18
58
59
mA-
mA+
Alimentation
transmetteur
(TPSU)
-
+
2 fils
4-20mA
Le diagramme présente un transducteur
de pression avec résistance d'étalonnage
interne.
Pour les transducteurs sans résistance
interne, connecter une résistance externe
entre les bornes 14 et 13.
La résistance est activée uniquement
quand on réalise l'étalonnage du
transducteur. Se reporter au manuel.
Pour les numéros de bornes du
transmetteur, se référer aux données
constructeur.
CAL2
SIG-
EXC+
Rcal
CAL1
SIG+
10/16
11/17
8/14
7/13
6/12
EXC-
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Eurotherm P304 Guide d'installation

Taper
Guide d'installation

dans d''autres langues