SolaHD MCR Hardwired Le manuel du propriétaire

Taper
Le manuel du propriétaire
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282
Rev. 4 02/2020
Power Conditioner
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 2
CONTENTS
1.0 Important Safety Instructions . . . . . . . . . . . . . . 4
2.0 Warnings Defined . . . . . . . . . . . . . . . . . . . . 4
3.0 Introduction . . . . . . . . . . . . . . . . . . . . . . 4
4.0 Installation Instructions . . . . . . . . . . . . . . . . . 5
4.1 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Mounting, Ventilation and Important Factors to Consider . . . . . . . . . . . . 5
4.3 Mechanical Drawings & Dimensions . . . . . . . . . . . . . . . . . . . . . . . 6
4.4 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.0 Parallel & Three-Phase Connections . . . . . . . . . . 17
5.1 Parallel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Three-Phase Connection Operation . . . . . . . . . . . . . . . . . . . . . . 17
6.0 Operating Notes & Data . . . . . . . . . . . . . . . . 18
6.1 Checking with Voltmeters . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2 Load Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.3 Effect of Load Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.4 Operation with Switch-Mode Power Supplies . . . . . . . . . . . . . . . . . 18
6.5 Effect of Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.6 Response Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.7 Input Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.8 Current Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.9 Operation with Motor Loads . . . . . . . . . . . . . . . . . . . . . . . . . 19
Page: 3
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
CONTENTS
7.0 Service & Maintenance . . . . . . . . . . . . . . . . 20
7.1 Service & Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.2 Field Replacement of Capacitors . . . . . . . . . . . . . . . . . . . . . . . 20
8.0 Troubleshooting . . . . . . . . . . . . . . . . . . . 20
9.0 Specifications . . . . . . . . . . . . . . . . . . . . . 21
10.0 Warranty & Support . . . . . . . . . . . . . . . . . 22
10.1 Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.2 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 4
1.0 Important Safety Instructions
Please read all safety, installation, and operating instructions before attempting to install or operate the unit.
!
DANGER
High voltages are present inside the unit. Do not reach inside while it is energized. This unit contains no user-
serviceable parts.
2.0 Warnings Defined
DANGER
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. This
signal word is limited to the most extreme situations.
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
3.0 Introduction
The SolaHD Micro/Mini Computer Regulator (MCR) provides voltage regulation and isolation from both
transverse and common mode noise for any type of load. It also suppresses transients with ferroresonant,
protects overloads, and serves as a dedicated line. It is the ultimate in ac power conditioning equipment.
Page: 5
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
4.0 Installation Instructions
4.1 Receiving
Upon receipt, immediately inspect the unit for obvious signs of shipping damage and/or mishandling. If
damaged, photograph the unit, inform the carrier, and contact your SolaHD representative.
4.2 Mounting, Ventilation and Important Factors to Consider
These units are for use in an indoor humidity and temperature controlled environment. Mount the unit in
either a horizontal or vertical position. The unit should be located where contact with the transformer’s hot
surface is unlikely. If mounted in a vertical position (e.g., on a wall), steel mounting hardware must be selected
in accordance with Table 1. The wiring compartment should also be facing up.
When utilizing MCR units, please consider these important factors:
• Motor or Inductive Loads: The MCR and CVS products have a fast response time and a built-in overload
protection which causes the output voltage to collapse during an overload condition. Due to this
protection function, the load must not draw more than the unit's rated capacity, even momentarily. For
this reason, care needs to be considered with highly inductive loads (e.g., motors, pumps, contactors,
solenoids, air conditioners, etc.).
You may size the conditioner based on the peak current rating, but you will need to meet the Minimum
Load requirement. This is the reason why SolaHD highly recommends only using these CVS and
MCR products for resistive or electronic loads.
• Minimum Load: Minimum loading of no less than 40% of the nominal rating because output voltage will
rise by 1% as the load is decreased. Units with less than 40% load may run hotter than those at close to full
load. This may result in overheating in the long run.
• Frequency: The output voltage varies linearly with changes in Input Frequency. A 1% change in input
frequency will yield a 1.5% change in output voltage. 60Hz models cannot be used with 50Hz application
and vice versa. This is also the reason why we don't recommend these units with generator source that has
varying input frequency.
Table 1: Mounting Hardware
MCR Rated VA Steel Mounting Screws (Minimum Diameter)
120 VA #10 machine screws
250 VA 1/4 in. bolts
500–1000 VA 5/16 in. bolts
1500–10000 VA 3/8 in. bolts
15000 VA 1/2 in. bolts
All regulators generate a considerable amount of heat and depend on natural convection for adequate
cooling. It is important that ventilation openings not be obstructed. Mounting in a conned or poorly
ventilated space should be avoided, unless special provisions have been made for ventilation. For proper
ventilation, allow a minimum of 12 inches of clearance above the unit and minimum of 6 inches of clearance
on each side.
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 6
4.3 Mechanical Drawings & Dimensions
FIGURE 1
C
A
G
F
B
D
E
H
Table 2: Dimensions—Figure 1
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]A B C D E F G H
60 63-23-112-4 8.62 [219] 5.19 [132] 3.31 [84] 4.00 [102] 3.50 [89] 3.00 [76] 2.90 [74] 0.22 x 0.59 [6 x 15] 15 [6.80]
50 63-23-612-8 9.09 [231] 7.44 [189] 4.50 [114] 5.39 [137] 4.76 [121] 4.13 [105] 2.17 [55] 0.31 x 0.69 [8 x 18] 18 [8.08]
60 63-23-125-4 9.88 [251] 7.44 [189] 4.50 [114] 5.62 [143] 4.76 [121] 4.13 [105] 3.06 [78] 0.31 x 0.69 [8 x 18] 27 [12.25]
50 63-23-625-8 10.59 [269] 7.44 [189] 4.50 [114] 5.39 [137] 4.76 [121] 4.13 [105] 2.17 [55] 0.31 x 0.69 [8 x 18] 27 [12.24]
60 63-23-150-8 12.69 [322] 6.44 [164] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 3.06 [78] 0.38 x 0.81 [10 x 21] 37 [16.78]
60 63-31-150-8 12.69 [322] 6.44 [164] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 3.06 [78] 0.38 x 0.81 [10 x 21] 38 [17.24]
50 63-23-650-8 13.27 [337] 6.44 [164] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 3.58 [91] 0.38 x 0.81 [10 x 21] 40 [18.14]
60 63-23-175-8 13.69 [348] 6.44 [164] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 3.06 [78] 0.38 x 0.81 [10 x 21] 52 [23.59]
60 63-23-210-8 16.75 [425] 6.44 [164] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 5.25 [133] 0.38 x 0.81 [10 x 21] 62 [28.12]
60 63-23-210-C8 16.75 [425] 6.79 [172] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 5.25 [133] 0.38 x 0.81 [10 x 21] 62 [28.12]
60 63-32-210-8 16.75 [425] 6.44 [164] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 5.25 [133] 0.38 x 0.81 [10 x 21] 62 [28.12]
50 63-23-710-8 17.95 [456] 6.79 [172] 7.78 [198] 9.00 [229] 8.12 [206] 5.62 [143] 5.83 [148] 0.38 x 0.81 [10 x 21] 62 [28.12]
Page: 7
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
FIGURE 2
F G
C
E
D
B
A
H
Table 3: Dimensions—Figure 2
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]A B C D E F G H
60 63-23-215-8 16.44 [418] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 3.00 [76] 5.19 [132] 0.44 x 0.69 [11 x 18] 95 [43.10]
60 63-23-215-C8 16.44 [418] 9.37 [238] 10.56 [268] 12.75 [324] 11.75 [298] 3.00 [76] 5.19 [132] 0.44 x 0.69 [11 x 18] 95 [43.10]
60 63-23-220-8 17.31 [440] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 3.88 [99] 5.19 [132] 0.44 x 0.69 [11 x 18] 109 [49.44]
60 63-23-220-C8 17.31 [440] 9.37 [238] 10.56 [268] 12.75 [324] 11.75 [298] 3.88 [99] 5.19 [132] 0.44 x 0.69 [11 x 18] 109 [49.44]
60 63-32-220-8 17.31 [440] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 3.88 [99] 5.19 [132] 0.44 x 0.69 [11 x 18] 109 [49.44]
50 63-23-720-8 17.60 [447] 9.37 [238] 10.56 [268] 12.75 [324] 11.75 [298] 4.21 [107] 5.00 [127] 0.44 x 0.69 [11 x 18] 112 [50.81]
60 63-23-230-8 18.69 [475] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 5.25 [133] 5.19 [132] 0.44 x 0.69 [11 x 18] 142 [64.41]
60 63-23-230-C8 18.69 [475] 9.37 [238] 10.56 [268] 12.75 [324] 11.75 [298] 5.25 [133] 5.19 [132] 0.44 x 0.69 [11 x 18] 142 [64.41]
60 63-32-230-8 18.69 [475] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 5.25 [133] 5.19 [132] 0.44 x 0.69 [11 x 18] 142 [64.41]
50 63-23-730-8 26.65 [677] 9.37 [238] 10.59 [269] 12.75 [324] 11.75 [298] 6.06 [154] 3.70 [94] 0.44 x 0.69 [11 x 18] 160 [72.59]
60 63-23-250-8 28.19 [716] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 222 [100.70]
60 63-23-250-C8 28.19 [716] 9.37 [238] 10.56 [268] 12.75 [324] 11.75 [298] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 222 [100.70]
60 63-29-250-8 28.19 [716] 9.03 [229] 10.56 [268] 12.75 [324] 11.75 [298] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 222 [100.70]
50 63-23-750-8 30.00 [762] 9.37 [238] 10.59 [269] 12.76 [324] 11.75 [298] 9.37 [238] 3.70 [94] 0.44 x 0.69 [11 x 18] 242 [109.79]
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 8
FIGURE 3
C
E
D
B
A
F G
H
Table 4: Dimensions—Figure 3
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]A B C D E F G H
60 63-28-275-8 26.56 [675] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 6.62 [168] 8.88 [226] 0.44 x 0.69 [11 x 18] 362 [164.20]
60 63-29-275-8 26.56 [675] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 6.62 [168] 8.88 [226] 0.44 x 0.69 [11 x 18] 362 [164.20]
50 63-28-775-8 27.99 [711] 9.37 [238] 24.49 [622] 25.81 [656] 24.81 [630] 7.36 [187] 3.70 [94] 0.44 x 0.69 [11 x 18] 390 [176.94]
60 63-28-310-8 28.19 [716] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 446 [202.30]
60 63-29-310-8 28.19 [716] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 446 [202.30]
50 63-28-810-8 30.00 [762] 9.37 [238] 24.49 [622] 25.81 [656] 24.81 [630] 9.37 [238] 3.70 [94] 0.44 x 0.69 [11 x 18] 486 [220.50]
Page: 9
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
FIGURE 4
C
E
D
B
A
F G
H
Table 5: Dimensions—Figure 4
Hz
Catalog
Number
Dimensions in inches [mm]
Ship Weight
lb. [kg]A B C D E F G H
60 63-28-275-8 26.56 [675] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 6.62 [168] 8.88 [226] 0.44 x 0.69 [11 x 18] 362 [164.20]
60 63-29-275-8 26.56 [675] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 6.62 [168] 8.88 [226] 0.44 x 0.69 [11 x 18] 362 [164.20]
50 63-28-775-8 27.99 [711] 9.37 [238] 24.49 [622] 25.81 [656] 24.81 [630] 7.36 [187] 3.70 [94] 0.44 x 0.69 [11 x 18] 390 [176.94]
60 63-28-310-8 28.19 [716] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 446 [202.30]
60 63-29-310-8 28.19 [716] 9.03 [229] 22.81 [579] 25.81 [656] 24.81 [630] 8.25 [210] 8.88 [226] 0.44 x 0.69 [11 x 18] 446 [202.30]
50 63-28-810-8 30.00 [762] 9.37 [238] 24.49 [622] 25.81 [656] 24.81 [630] 9.37 [238] 3.70 [94] 0.44 x 0.69 [11 x 18] 486 [220.50]
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 10
4.4 Electrical
CAUTION! All hardwired units should be installed in accordance with local and national electrical codes.
For Catalog Numbers 63-23-112-4 & 63-23-125-4
FIGURE 5
60 Hz
Table 6: Electrical Connections—Figure 5
Catalog Number Primary Voltage Connect Lines to
63-23-112-4
63-23-125-4
120 H1 and H2
208 H1 and H3
240 H1 and H4
480 H1 and H5
Secondary Voltage Connect Lines to
120 X1 and X2
Table 7: Product Parameters Table 7: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
63-23-112-4 120 136
63-23-125-4 250 225
Table 8: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
63-23-112-4 3 A/14 AWG 3 A/14 AWG 3 A/14 AWG 1 A/14 AWG --- 14 AWG --- ---
63-23-125-4 6 A/14 AWG 3 A/14 AWG 3 A/14 AWG 1 A/14 AWG --- 14 AWG --- ---
Page: 11
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
For Catalog Numbers 63-23-150-8, 63-23-175-8, 63-23-210-8*, 63-23-215-8*, 63-23-220-8*,
63-23-230-8*, & 63-23-250-8*
FIGURE 6
60 Hz
Table 9: Electrical Connections—Figure 6
Catalog Numbers Primary Voltage Connect Lines to
63-23-150-8
63-23-175-8
63-23-210-8
*
63-23-215-8*
63-23-220-8*
63-23-230-8*
63-23-250-8*
120 H1 and H2
208 H1 and H3
240 H1 and H4
480 H1 and H5
Secondary Voltage Connect Lines to
120 X1 and X2
208 X4 and X5
240 X1 and X3
Table 10: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C ambient
63-23-150-8 500 280
63-23-175-8 750 444
63-23-210-8* 1000 519
63-23-215-8* 1500 686
63-23-220-8* 2000 1229
63-23-230-8* 3000 1331
63-23-250-8* 5000 2117
Table 11: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
63-23-150-8 10 A/14 AWG 6 A/14 AWG 6 A/14 AWG 3 A/14 AWG --- 14 AWG
63-23-175-8 15 A/14 AWG 10 A/14 AWG 6 A/14 AWG 3 A/14 AWG --- 14 AWG
63-23-210-8
* 15 A/14 AWG 10 A/14 AWG 10 A/14 AWG 6 A/14 AWG --- 14 AWG
63-23-215-8
* 25 A/10 AWG 15 A/14 AWG 15 A/14 AWG 10 A/14 AWG --- 12 AWG 14 AWG
63-23-220-8
* 30 A/10 AWG 20 A/12 AWG 15 A/14 AWG 10 A/14 AWG --- 10 AWG 14 AWG
63-23-230-8
* 45 A/8 AWG 25 A/10 AWG 25 A/10 AWG 15 A/14 AWG --- 8 AWG 12 AWG
63-23-250-8
* 80 A/4 AWG 40 A/8 AWG 40 A/8 AWG 20 A/12 AWG --- 8 AWG** 10 AWG
*Canadian option: For cULus units, replace “– 8” sufx (UL only model) with “– C8” (cULus model).
**Leads in the wiring compartment must have 105°C sleeving.
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 12
For Catalog Numbers 63-31-150-8, 63-32-210-8, 63-32-220-8, & 63-32-230-8
FIGURE 7
60 Hz
Table 12: Electrical Connections—Figure 7
Catalog Number Primary Voltage Connect Lines to
63-31-150-8
63-32-210-8
63-32-220-8
63-32-230-8
600 H1 and H2
Secondary Voltage Connect Lines to
120 X1 and X2 OR X3 and X2
208 X4 and X5
240 X1 and X3
Table 13: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
63-31-150-8 500 280
63-32-210-8 1000 519
63-32-220-8 2000 1229
63-32-230-8 3000 1331
Table 14: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
63-31-150-8 --- --- --- --- 2 A/14 AWG 14 AWG
63-32-210-8 --- --- --- --- 3 A/14 AWG 14 AWG
63-32-220-8 --- --- --- --- 10 A/14 AWG 10 AWG 14 AWG
63-32-230-8 --- --- --- --- 15 A/12 AWG 8 AWG 12 AWG
Page: 13
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
For Catalog Numbers 63-28-275-8, 63-28-310-8, & 63-28-315-8
FIGURE 8
60 Hz
Table 15: Electrical Connections—Figure 8
Catalog Number Primary Voltage Connect Lines to
63-28-275-8
63-28-310-8
63-28-315-8
208 H2 and H3
240 H2 and H4
480 H1 and H4
Secondary Voltage Connect Lines to
120 X1 and X2 OR X3 and X2
208 X4 and X5
240 X1 and X3
Table 16: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
63-28-275-8 7500 2407
63-28-310-8 10000 3209
63-28-315-8 15000 4813
Table 17: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
63-28-275-8 --- 60 A/6 AWG 60 A/8 AWG 30 A/10 AWG --- 4 AWG 8 AWG 8 AWG
63-28-310-8 --- 80 A/3 AWG 80 A/4 AWG 40 A/8 AWG --- 3 AWG 6 AWG 8 AWG
63-28-315-8 --- 125 A/1 AWG 110 A/2 AWG 60 A/4 AWG --- 0 AWG 4 AWG 4 AWG
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 14
For Catalog Numbers 63-29-250-8, 63-29-275-8, 63-29-310-8, & 63-29-315-8
FIGURE 9
60 Hz
Table 18: Electrical Connections—Figure 9
Catalog Number Primary Voltage Interconnect Connect Lines to
63-29-250-8
63-29-275-8
63-29-310-8
63-29-315-8
208
H1 to H4
H2 to H5
H1 and H5
240
H1 to H4
H3 to H6
H1 and H6
480 H3 to H4 H1 and H6
600 H3 to H4 H1 and H7
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2 OR X3 and X2
208 --- X4 and X5
240 --- X1 and X3
Table 19: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
63-29-250-8 5000 2117
63-29-275-8 7500 2407
63-29-310-8 10000 3209
63-29-315-8 15000 4813
Table 20: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
63-29-250-8 --- 40 A/8 AWG 40 A/8 AWG 20 A/12 AWG 15 A/12 AWG 8 AWG
** 10 AWG
63-29-275-8 --- 60 A/6 AWG 60 A/6 AWG 30 A/10 AWG 25 A/10 AWG 4 AWG 4 AWG 4 AWG
63-29-310-8 --- 80 A/3 AWG 80 A/4 AWG 40 A/8 AWG 30 A/10 AWG 3 AWG 6 AWG 8 AWG
63-29-315-8 --- 125 A/1 AWG 110 A/2 AWG 60 A/4 AWG 50 A/8 AWG 0 AWG 4 AWG 4 AWG
**Leads in the wiring compartment must have 105°C sleeving.
Page: 15
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
For Catalog Numbers 63-23-612-8, 63-23-625-8, 63-23-650-8, 63-23-710-8, 63-23-720-8, 63-23-730-8,
63-23-750-8, 63-28-775-8, 63-28-810-8, 63-28-815-8
FIGURE 10
50 Hz
Table 21: Electrical Connections—Figure 10
Unit Input Volts Input Terminals Jumper Connection Output Connection
250 to 5000 VA
90-130 H1-H4 (H1-H3) (H2-H4)
(All Models)
110-X1-X2 OR X2-X3
120 X4-X2 OR X2-X5
220-X1-X3
240 X4-X5
182-260 H1-H4 (H2-H3)
310-450 H1-H5 (H2-H3)
7500 VA
180-260 H1-H5 (H1-H3) (H2-H5)
310-450 H1-H4 (H2-H3)
10000-15000 VA
180-260 H1-H4 (H2-H3)
310-450 H1-H5 (H2-H3)
Table 22: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
63-23-612-8 120 85
63-23-625-8 250 160
63-23-650-8 500 300
63-23-710-8 1000 525
63-23-720-8 2000 825
63-23-730-8 3000 1263
63-23-750-8 5000 2105
63-28-775-8 7500 4105
63-28-810-8 10000 4210
63-28-815-8 15000 4815
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 16
Table 23: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
110–120 220–240 380–415 110–120 220–240
63-23-612-8 3 A/1,0 mm
2
1,5 A/1,0 mm
2
0,8 A/1,0 mm
2
1,0 mm 1,0 mm
63-23-625-8 6 A/1,0 mm
2
3 A/1,0 mm
2
1 A/1,0 mm
2
1,0 mm 1,0 mm
63-23-650-8 10 A/1,5 mm
2
6 A/1,0 mm
2
3 A/1,0 mm
2
1,0 mm 1,0 mm
63-23-710-8 15 A/2,5 mm
2
10 A/1,5 mm
2
6 A/1,0 mm
2
1,5 mm 1,0 mm
63-23-720-8 30 A/6,0 mm
2
15 A/2,5 mm
2
10 A/1,5 mm
2
4,0 mm 1,5 mm
63-23-730-8 45 A/16,0 mm
2
25 A/4,0 mm
2
15 A/2,5 mm
2
6,0 mm 2,5 mm
63-23-750-8 80 A/25,0 mm
2
40 A/10,0 mm
2
20 A/4,0 mm
2
16,0 mm 4,0 mm
63-28-775-8 --- 60 A/16,0 mm
2
30 A/6,0 mm
2
25,0 mm 10,0 mm
63-28-810-8 --- 80 A/25,0 mm
2
40 A/10,0 mm
2
35,0 mm 16,0 mm
63-28-815-8 --- 110 A/50,0 mm
2
60 A/16,0 mm
2
45,0 mm 25,0 mm
Page: 17
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
5.0 Parallel & Three-Phase Connections
5.1 Parallel Operation
Units of the same SolaHD catalog number may be connected in parallel to obtain a larger load capacity. Both
input and output connections must be made in parallel (see Figure 11). The SolaHD catalog number must end
in -8 or -C8 and must be larger than 1 kVA. No portable units can be paralleled.
All input and output paralleling wires must be tied together in an external paralleling “box” provided by the
user. Do not attempt to jumper the wires of one unit to the terminal block of the other unit. The terminal
block may not be rated to carry the total currents of both units. The input of each unit must be properly and
separately fused.
CAUTION! Failure to adhere to these requirements may damage the windings.
For units smaller than 5 kVA: When connecting in parallel the 208 Volt windings, other output voltage ratings
(120 V, 240 V) can’t be paralleled at the same time and vice versa. It is suggested that the installer remove X2
grounding on each unit, then connect X2 from each unit to one location and ground at that location only.
5.2 Three-Phase Connection Operation
Loads requiring 4-wire WYE connection may be served by three ferroresonant power conditioners with the
same SolaHD catalog number. The inputs must be connected in Delta. Input fuses must be connected in the
primary of each unit, not in the three-phase lines. The outputs must be connected in WYE with the neutral
solidly connected to a WYE load. Alternatively, these three outputs may serve three independent single-phase
loads. Phase angles may vary somewhat from 120 degrees even with balanced loading.
This circuit arrangement is not intended to serve single-phase line-to-line loading or three-phase Delta
loading. Outputs must serve three independent, single-phase loads of the same total Volt-Amphere (VA)
rating. Connections should be made in one of two ways as shown in Figure 11.
The outputs of the unit are isolated from the input lines. Voltage generated by internal leakage currents will
occur with respect to ground, which can have undesirable effects in electronic equipment. Therefore, if circuit
“B” is used, it is suggested that the installer remove X2 grounding on -8 units, then connect all X2 from each
phase to one location and ground at that location only. This is not required for circuit “A” and will not affect
regulation or the ability to reject power line noise or transients. s.
FIGURE 11
CV
Trans
Load
CV
Trans
Load
CV
Trans
Load
(A) Isolated Single-Phase Loads
A
B
C
CV
Trans
Load
CV
Trans
Load
CV
Trans
Load
(B) Separte Single-Phase Loads
In Grounded WYE
A
B
C
Unit A
Unit B
Input
Input
Output
Output
Ac Single-Phase
Input
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 18
6.0 Operating Notes & Data
DANGER! High voltages are present inside the unit. Do not reach inside while it is energized. To measure
voltage, de-energize the unit, connect the meter, and then re-energize the unit.
6.1 Checking with Voltmeters
All input and output voltage measurements should be made with a true RMS voltmeter. A certain amount of
harmonics in the output may cause other types—particularly rectier types—to give inaccurate indications.
6.2 Load Regulation
Changes in output voltage resulting from changes in resistive loads, from no load to full load (100% pF), are
approximately 4%.
6.3 Effect of Load Power Factor
“Median” value of output voltage will vary from the label rating if the load has a power factor different
from the unit’s design. Load regulation will also be greater as the inductive load power factor is decreased.
However, the resulting median values of output voltage will be regulated against supply line changes at any
reasonable load or load power factor.
FIGURE 12
6.4 Operation with Switch-Mode Power Supplies
If an MCR is used as a source for a switch-mode power supply, a slight amount of ringing may be noticed on
the sine wave output of the unit at half cycle intervals for a short duration. This ringing occurs at the point
when the switch-mode power supply current demand drops to zero. The ringing need not be a cause for
concern since it is of relatively low magnitude and frequency. Both series have been tested with a variety of
switch-mode power supplies and it has been determined that the ringing does not affect the dc outputs, nor
has it been found to degrade the components of any switch-mode power supply.
Page: 19
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
6.5 Effect of Frequency
Changes in the frequency of the supply voltage will be directly reected in the output voltage. A change of
about 1.8% in output voltage will occur for every 1% change in input frequency, and in the same direction as
the frequency change.
6.6 Response Time
An important advantage of the SolaHD principle of static magnetic regulation is its exceedingly fast response
time compared with other types of ac regulators. Transient changes in supply voltage are usually corrected
with 1-1/2 cycles or less; the output voltage will not uctuate more than a few percent.
6.7 Input Characteristics
The MCR’s transformer includes a resonant circuit, which is energized whether it is serving a load or not.
Therefore, the input current at no load is approximately 35% of the full-load level, even at light or no load.
Input power factor will average 90–100% at full load, but may drop to about 75% at half load and 25% at no
load. In any case, it is always leading.
6.8 Current Limitations
When the load is increased beyond the MCR’s rated value, a point is reached where the output voltage
suddenly collapses and will not regain its normal value until the load is partially released. Under short-circuit
conditions, the load current is limited to approximately twice of the rated full-load value, and the input power
to less than 10% of normal. The unit will protect both itself and its load against damage from excessive fault
currents. Fusing of load circuits is not necessary.
6.9 Operation with Motor Loads
Because of the current-limiting effect described above, special attention should be given to motor
applications. In general, the regulator must have a load rating nearly equal to the maximum power drawn
during the starting cycle. This may run from two to eight times the normal (running) rating of the motor. In
doubtful cases, it is advisable to measure the actual starting current.
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
Page: 20
7.0 Service & Maintenance
7.1 Service & Maintenance
The unit is a simple, rugged device with no moving parts. Routine service and/or maintenance is not required.
If a problem does occur, please refer to “8.0 Troubleshooting” or contact SolaHD Technical Support for
assistance.
7.2 Field Replacement of Capacitors
Capacitors used in our units are the highest commercial grade, with each one given a rigid acceptance test
upon receipt. SolaHD guarantees free replacement of any capacitors which fail within one year of sale. Older
units can be replaced at a moderate charge.
NOTE: It may be possible to test and identify defective capacitors in the eld. Please contact SolaHD Technical
Support at 1.800.377.4384 or 1.847.268.6651 for further assistance.
8.0 Troubleshooting
Table 24: Troubleshooting
Problem Action
Nominal voltage too high
1. The load may be considerably less than the full rating. See “6.2 Load Regulation”.
2. The load may have a leading power factor.
Nominal voltage too low
1. The load power factor may be lagging.
2. The unit may be slightly overloaded. See “6.8 Current Limitations”.
Unit does not regulate closely
1. The unit may be slightly overloaded. See “6.8 Current Limitations”.
2. The actual line voltage swings may be outside the rate range of the unit, particularly on
the low side.
3. On varying loads, a certain amount of load regulation may be mixed with the line voltage
regulating action. See “6.2 Load Regulation”.
Output voltage is very low (20–60 V)
1. Unsuspected or unplanned overloads of substantial size may occur intermittently (motor-
starting currents, solenoid inrush currents, etc.). See “6.8 Current Limitations”.
2. One or more capacitors in the regulator may be defective.
No output voltage
1. Check power source breakers or fuses.
2. Check input switch.
3. Check continuity between input terminals, and also between output terminals.
Transformer operating temperature
1. The transformer used in the unit is designed to operate at high ux density and relatively
high temperatures. After connection to the line for 30 minutes or so, the transformer core
structure may be too hot to touch with your bare hands. This is normal and should not
cause concern.
Unit is operating, but does not appear
to have the correct output
The steps below will usually establish whether the apparent poor performance is due to a
fault in the unit or to some peculiarity of the working load.
1. Disconnect the working load.
2. Connect a dummy load of lamps, heaters, or other resistive loads (substantially equal to
the full load rating of the regulator) directly across the output terminals.
3. Measure the output voltage of the regulator (using a true RMS type voltmeter) directly
across the output terminals.
Support
Please contact SolaHD Technical Support at 1.800.377.4384/1.847.268.6651 or by e-mail at solahd.technicals[email protected]om
for further assistance.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46