CVS Hardwired Series – 60 Hz
A272-283
Rev. 3 12/2018
Power Conditioner
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 2
CONTENTS
1.0 Important Safety Instructions . . . . . . . . . . . . . . 4
2.0 Warnings Defined . . . . . . . . . . . . . . . . . . . . 4
3.0 Introduction . . . . . . . . . . . . . . . . . . . . . . 4
4.0 Installation Instructions . . . . . . . . . . . . . . . . . 5
4.1 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Mounting & Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.3 Mechanical Drawings & Dimensions . . . . . . . . . . . . . . . . . . . . . . . 6
4.4 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.0 Parallel & Three-Phase Connections . . . . . . . . . . 11
5.1 Parallel Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Three-Phase Connection Operation . . . . . . . . . . . . . . . . . . . . . . 11
6.0 Operating Notes & Data . . . . . . . . . . . . . . . . 12
6.1 Checking with Voltmeters . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.2 Load Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.3 Effect of Load Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.4 Operation with Switch-Mode Power Supplies . . . . . . . . . . . . . . . . . . 12
6.5 Effect of Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.6 Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.7 Input Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.8 Current Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.9 Operation with Motor Loads . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Page: 3
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
CONTENTS
7.0 Service & Maintenance . . . . . . . . . . . . . . . . 14
7.1 Service & Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2 Field Replacement of Capacitors . . . . . . . . . . . . . . . . . . . . . . . . 14
8.0 Troubleshooting . . . . . . . . . . . . . . . . . . . . 14
9.0 Specifications . . . . . . . . . . . . . . . . . . . . . 15
10.0 Warranty & Support . . . . . . . . . . . . . . . . . 15
10.1 Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.2 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 4
1.0 Important Safety Instructions
Please read all safety, installation, and operating instructions before attempting to install or operate the unit.
!
DANGER
High voltages are present inside the unit. Do not reach inside while it is energized. This unit contains no user-
serviceable parts.
2.0 Warnings Defined
DANGER
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. This
signal word is limited to the most extreme situations.
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
3.0 Introduction
The SolaHD Constant Voltage Sinusoidal (CVS) transformer provides voltage regulation and isolation
from both transverse and common mode noise for any type of load. It also suppresses transients with
ferroresonant, protects overloads, and serves as a dedicated line. It is the ultimate in ac power conditioning
equipment.
Page: 5
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
4.0 Installation Instructions
4.1 Receiving
Upon receipt, immediately inspect the unit for obvious signs of shipping damage and/or mishandling. If
damaged, photograph the unit, inform the carrier, and contact your SolaHD representative.
4.2 Mounting & Ventilation
These units are for use in an indoor humidity and temperature controlled environment. Mount the unit in
either a horizontal or vertical position. The unit should be located where contact with the transformer’s hot
surface is unlikely. If mounted in a vertical position (e.g. on a wall), steel mounting hardware must be selected
in accordance with Table 1. The wiring compartment should also be facing up
Table 1: Mounting Hardware
CVS Rated VA Steel Mounting Screws (Minimum Diameter)
120 VA #10 machine screws
250 VA 1/4 in. bolts
500–1000 VA 5/16 in. bolts
1500–7500 VA 3/8 in. bolts
All regulators generate a considerable amount of heat and depend on natural convection for adequate
cooling. It is important that ventilation openings not be obstructed. Mounting in a conned or poorly
ventilated space should be avoided, unless special provisions have been made for ventilation. For proper
ventilation, allow a minimum of 12 inches of clearance above the unit and minimum of 6 inches of clearance
on each side.
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 6
4.3 Mechanical Drawings & Dimensions
FIGURE 1
Table 2: Dimensions—Figure 1
Hz
Catalog
Number
Dimensions in inches [mm]
Ship
Weight
lb. [kg]A B C D E F G H
60 23-13-030-2 6.12 [155.4] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 1.75 [44.4]
0.22 x 0.59
[5.6 x 15.0]
7.0 [3.2]
60 23-13-060-2 6.94 [176.3] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 1.75 [44.4]
0.22 x 0.59
[5.6 x 15.0]
9.0 [4.1]
60 23-22-112-2 8.12 [206.2] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 2.44 [62.0]
0.22 x 0.59
[5.6 x 15.0]
13.0 [5.9]
60 23-23-125-8 10.50 [266.7] 7.56 [192.0] 4.75 [120.6] 5.63 [143.0] 4.75 [120.6] 4.12 [104.6] 3.03 [77.0]
0.31 x 0.69
[7.9 x 17.5]
28.0 [12.7]
60 23-23-150-8 13.00 [330.2] 6.50 [165.1] 8.12 [206.2] 9.00 [228.6] 8.12 [206.2] 5.62 [142.7] 3.06 [77.7]
0.38 x 0.81
[9.7 x 20.6]
37.0 [16.8]
60 23-23-210-8 17.25 [438.2] 6.81 [173.0] 8.12 [206.2] 9.00 [228.6] 8.12 [206.2] 5.62 [142.7] 5.25 [133.4]
0.38 x 0.81
[9.7 x 20.6]
63.0 [28.6]
Page: 7
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
FIGURE 2
Table 3: Dimensions—Figure 2
Hz
Catalog
Number
Dimensions in inches [mm]
Ship
Weight
lb. [kg]A B C D E F G H
60 23-23-220-8 17.58 [446.5] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 3.88 [98.6] 5.19 [131.8]
0.44 x 0.69
[11.2 x 17.5]
109.0
[49.4]
60 23-23-230-8 18.96 [481.6] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 5.25 133.4] 5.19 [131.8]
0.44 x 0.69
[11.2 x 17.5]
142.0
[64.4]
60 23-23-250-8 28.53 [724.7] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 8.25 [209.5] 8.88 [225.6]
0.44 x 0.69
[11.2 x 17.5]
222.0
[100.7]
FIGURE 3
Table 4: Dimensions—Figure 3
Hz
Catalog
Number
Dimensions in inches [mm]
Ship
Weight
lb. [kg]A B C D E F G H
60 23-28-275-6 26.91 [683.5] 9.27 [235.6] 23.55 [598.2] 25.81 [655.6] 24.81 [630.2] 6.62 [168.1] 8.88 [225.6]
0.44 x 0.69
[11.2 x 17.5]
365.0
[165.6]
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 8
4.4 Electrical
CAUTION! All hardwired units should be installed in accordance with local and national electrical codes.
FIGURE 4
Table 5: Electrical Connections—Figure 4
Catalog Number Primary Voltage Interconnect Connect Lines to
23-13-030-2 120 H3 and H4 are NOT used H1 and H2
23-13-060-2 120 H3 and H4 are NOT used H1 and H2
23-22-112-2
120
H1 to H3
H2 to H4
H1 and H4
240 H2 to H3 H1 and H4
23-28-275-6
240
H1 to H3
H2 to H4
H1 and H4
480 H2 to H3 H1 and H4
Catalog Number Secondary Voltage Interconnect Connect Lines to
23-13-030-2 120 X1 and X2
23-13-060-2 120 X1 and X2
23-22-112-2 120 X1 and X2
23-28-275-6
120
X1 and X2 OR X3 and X2
240 X1 and X3
NOTE: Secondaries are not grounded. Ground X2 per code.
Table 6: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-13-030-2 30 60
23-13-060-2 60 85
23-22-112-2 120 136
23-28-275-6 7500 2407
Page: 9
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Table 7: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
23-13-030-2 1 A/14 AWG --- --- --- --- 14 AWG --- ---
23-13-060-2 2 A/14 AWG --- --- --- --- 14 AWG --- ---
23-22-112-2 3 A/14 AWG --- 3 A/14 AWG --- --- 14 AWG --- ---
23-28-275-6 --- --- 60 A/6 AWG 30 A/10 AWG --- 4 AWG 8 AWG 8 AWG
FIGURE 5
Table 8: Electrical Connections—Figure 5
Catalog Numbers Primary Voltage Interconnect Connect Lines to
23-23-125-8
120
H1 to H3 to H5 to H7
H2 to H4 to H6 to H8
H1 and H2
240
H2 to H3 H6 to H7
H1 to H5 H4 to H8
H1 and H4
480
H2 to H3 H4 to H5
H6 to H7
H1 and H8
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2
Table 9: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-23-125-8 250 225
Table 10: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
23-23-125-8 6 A/14 AWG --- 3 A/14 AWG 1 A/14 AWG --- 14 AWG --- ---
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 10
FIGURE 6
Table 11: Electrical Connections—Figure 6
Catalog Number Primary Voltage Interconnect Connect Lines to
23-23-150-8
23-23-210-8
23-23-220-8
23-23-230-8
23-23-250-8
120
H1 to H3 to H6 to H8
H2 to H5 to H7 to H10
H1 and H2
208
H2 to H3 H7 to H8
H1 to H6 H4 to H9
H1 and H4
240
H2 to H3 H7 to H8
H1 to H6 H5 to H10
H1 and H5
480
H2 to H3 H5 to H6
H7 to H8
H1 and H10
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2 OR X3 and X2
240 --- X1 and X3
Table 12: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-23-150-8 500 280
23-23-210-8 1000 519
23-23-220-8 2000 1229
23-23-230-8 3000 1331
23-23-250-8 5000 2117
Table 13: Fusing & Wiring
Catalog
Number
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
23-23-150-8 10 A/14 AWG 6 A/14 AWG 6 A/14 AWG 3 A/14 AWG --- 14 AWG
23-23-210-8 15 A/14 AWG 10 A/14 AWG 10 A/14 AWG 6 A/14 AWG --- 14 AWG
23-23-220-8 30 A/10 AWG 20 A/12 AWG 15 A/14 AWG 10 A/14 AWG --- 10 AWG 14 AWG
23-23-230-8 45 A/8 AWG 25 A/10 AWG 25 A/10 AWG 15 A/14 AWG --- 8 AWG 12 AWG
23-23-250-8 80 A/4 AWG 40 A/8 AWG 40 A/8 AWG 20 A/12 AWG --- 8 AWG* 10 AWG
*Leads in the wiring compartment must have 105°C sleeving
Page: 11
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
5.0 Parallel & Three-Phase Connections
5.1 Parallel Operation
Units of the same SolaHD catalog number may be connected in parallel to obtain a larger load capacity. Both
input and output connections must be made in parallel (see Figure 6). The SolaHD catalog number must end
in -8 or -C8 and must be larger than 1 kVA. No portable units can be paralleled.
All input and output paralleling wires must be tied together in an external paralleling “box” provided by the
user. Do not attempt to jumper the wires of one unit to the terminal block of the other unit. The terminal
block may not be rated to carry the total currents of both units. The input of each unit must be properly and
separately fused.
CAUTION! Failure to adhere to these requirements may damage the windings.
For units smaller than 5 kVA: When connecting in parallel the 208 Volt windings, other output voltage ratings
(120 V, 240 V) can’t be paralleled at the same time and vice versa. It is suggested that the installer remove X2
grounding on each unit, then connect X2 from each unit to one location and ground at that location only.
5.2 Three-Phase Connection Operation
Loads requiring 4-wire WYE connection may be served by three ferroresonant power conditioners with the
same SolaHD catalog number. The inputs must be connected in Delta. Input fuses must be connected in the
primary of each unit, not in the three-phase lines. The outputs must be connected in WYE with the neutral
solidly connected to a WYE load. Alternatively, these three outputs may serve three independent single-phase
loads. Phase angles may vary somewhat from 120 degrees even with balanced loading.
This circuit arrangement is not intended to serve single-phase line-to-line loading or three-phase Delta
loading. Outputs must serve three independent, single-phase loads of the same total Volt-Amphere (VA)
rating. Connections should be made in one of two ways as shown in Figure 6.
The outputs of the unit are isolated from the input lines. Voltage generated by internal leakage currents will
occur with respect to ground, which can have undesirable effects in electronic equipment. Therefore, if circuit
“B” is used, it is suggested that the installer remove X2 grounding on -8 units, then connect all X2 from each
phase to one location and ground at that location only. This is not required for circuit “A” and will not affect
regulation or the ability to reject power line noise or transients.
CV
Trans
Load
CV
Trans
Load
CV
Trans
Load
(A) Isolated Single-Phase Loads
A
B
C
CV
Trans
Load
CV
Trans
Load
CV
Trans
Load
(B) Separte Single-Phase Loads
In Grounded WYE
A
B
C
Unit A
Unit B
Input
Input
Output
Output
Ac Single-Phase
Input
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 12
6.0 Operating Notes & Data
DANGER! High voltages are present inside the unit. Do not reach inside while it is energized. To measure
voltage, de-energize the unit, connect the meter, and then re-energize the unit.
6.1 Checking with Voltmeters
All input and output voltage measurements should be made with a true RMS voltmeter. A certain amount of
harmonics in the output may cause other types—particularly rectier types—to give inaccurate indications.
6.2 Load Regulation
Changes in output voltage resulting from changes in resistive loads, from no load to full load (100% pF), are
approximately 4%.
6.3 Effect of Load Power Factor
“Median” value of output voltage will vary from the label rating if the load has a power factor different
from the unit’s design. Load regulation will also be greater as the inductive load power factor is decreased.
However, the resulting median values of output voltage will be regulated against supply line changes at any
reasonable load or load power factor.
FIGURE 7
6.4 Operation with Switch-Mode Power Supplies
If an CVS is used as a source for a switch-mode power supply, a slight amount of ringing may be noticed on the
sine wave output of the unit at half cycle intervals for a short duration. This ringing occurs at the point when
the switch-mode power supply current demand drops to zero. The ringing need not be a cause for concern
since it is of relatively low magnitude and frequency. Both series have been tested with a variety of switch-
mode power supplies and it has been determined that the ringing does not affect the dc outputs, nor has it
been found to degrade the components of any switch-mode power supply.
Page: 13
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
6.5 Effect of Frequency
Changes in the frequency of the supply voltage will be directly reected in the output voltage. A change of
about 1.5% in output voltage will occur for every 1% change in input frequency, and in the same direction as
the frequency change.
6.6 Response Time
An important advantage of the SolaHD principle of static magnetic regulation is its exceedingly fast response
time compared with other types of ac regulators. Transient changes in supply voltage are usually corrected
with 1-1/2 cycles or less; the output voltage will not uctuate more than a few percent.
6.7 Input Characteristics
The CVS’s transformer includes a resonant circuit, which is energized whether it is serving a load or not.
Therefore, the input current at no load is approximately 35% of the full-load level, even at light or no load.
Input power factor will average 90–100% at full load, but may drop to about 75% at half load and 25% at no
load. In any case, it is always leading.
6.8 Current Limitations
When the load is increased beyond the CVS’s rated value, a point is reached where the output voltage
suddenly collapses and will not regain its normal value until the load is partially released. Under short-circuit
conditions, the load current is limited to approximately twice of the rated full-load value, and the input power
to less than 10% of normal. The unit will protect both itself and its load against damage from excessive fault
currents. Fusing of load circuits is not necessary.
6.9 Operation with Motor Loads
Because of the current-limiting effect described above, special attention should be given to motor
applications. In general, the regulator must have a load rating nearly equal to the maximum power drawn
during the starting cycle. This may run from two to eight times the normal (running) rating of the motor. In
doubtful cases, it is advisable to measure the actual starting current.
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
Page: 14
7.0 Service & Maintenance
7.1 Service & Maintenance
The unit is a simple, rugged device with no moving parts. Routine service and/or maintenance is not required.
If a problem does occur, please refer to “8.0 Troubleshooting” or contact SolaHD Technical Support for
assistance.
7.2 Field Replacement of Capacitors
Capacitors used in our units are the highest commercial grade, with each one given a rigid acceptance test
upon receipt. SolaHD guarantees free replacement of any capacitors which fail within one year of sale. Older
units can be replaced at a moderate charge.
NOTE: It may be possible to test and identify defective capacitors in the eld. Please contact SolaHD Technical
Support at 1.800.377.4384 or 1.847.268.6651 for further assistance.
8.0 Troubleshooting
Table 14: Troubleshooting
Problem Action
Nominal voltage too high
1. The load may be considerably less than the full rating. See “6.2 Load Regulation”.
2. The load may have a leading power factor.
Nominal voltage too low
1. The load power factor may be lagging.
2. The unit may be slightly overloaded. See “6.8 Current Limitations”.
Unit does not regulate closely
1. The unit may be slightly overloaded. See “6.8 Current Limitations”.
2. The actual line voltage swings may be outside the rate range of the unit, particularly on
the low side.
3. On varying loads, a certain amount of load regulation may be mixed with the line voltage
regulating action. See “6.2 Load Regulation”.
Output voltage is very low (20–60 V)
1. Unsuspected or unplanned overloads of substantial size may occur intermittently (motor-
starting currents, solenoid inrush currents, etc.). See “6.8 Current Limitations”.
2. One or more capacitors in the regulator may be defective.
No output voltage
1. Check power source breakers or fuses.
2. Check input switch.
3. Check continuity between input terminals, and also between output terminals.
Transformer operating temperature
1. The transformer used in the unit is designed to operate at high ux density and relatively
high temperatures. After connection to the line for 30 minutes or so, the transformer core
structure may be too hot to touch with your bare hands. This is normal and should not
cause concern.
Unit is operating, but does not appear
to have the correct output
The steps below will usually establish whether the apparent poor performance is due to a
fault in the unit or to some peculiarity of the working load.
1. Disconnect the working load.
2. Connect a dummy load of lamps, heaters, or other resistive loads (substantially equal to
the full load rating of the regulator) directly across the output terminals.
3. Measure the output voltage of the regulator (using a true RMS type voltmeter) directly
across the output terminals.
Support
Please contact SolaHD Technical Support at 1.800.377.4384/1.847.268.6651 or by e-mail at solahd.technicalservices@emerson.com
for further assistance.
Page: 15
CVS Hardwired Series – 60 Hz
A272-283 Rev. 3 12/2018
9.0 Specifications
Table 15: General Specifications
Phase Single
Frequency 60 Hz
Output Voltage Regulation ±1% for an input line variation of +10% to -20%
Output Harmonic Distortion Less than 3% total RMS content at full load
Efficiency Up to 92% at full load (typical) – model dependent
Noise Reduction Common mode noise rejection exceeds 40 dB; Transverse noise rejection exceeds 40 dB
Voltage Surge Suppression Meets ANSI/IEEE C62.41 Category A & B waveforms (formerly IEEE 587-1980)
Ambient Temperature Operating: -20°C to +50°C; Storage: -20°C to +85°C
Humidity <95% non-condensing
Directives RoHS complaint
Certifications
UL 1012, CSA C22.2 No. 107.1
Model Certification
23-13-030-2
cULus
23-13-060-2
23-22-112-2
23-23-125-8
23-23-150-8
23-23-220-8
23-23-230-8
23-23-250-8
23-28-275-6
Warranty 10 year limited warranty
10.0 Warranty & Support
10.1 Warranty Information
Please refer to the “Terms & Conditions of Sale”.
10.2 Technical Support
Phone: 1.800.377.4384 or 1.847.268.6651
E-mail: solahd.technicalservices@emerson.com
Web site: www.solahd.com
While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Grp LLC d/b/a Appleton Group assumes no
responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Série CVS câblée – 60 Hz
A272-283
Rev. 3 12/2018
Conditionneur de Puissance
Série CVS câblée – 60 Hz
A272-283 Rev. 3 12/2018
Page: 18
SOMMAIRE
1.0 Consignes de sécurité importantes . . . . . . . . . . 20
2.0 Définitions des avertissements . . . . . . . . . . . . 20
3.0 Introduction . . . . . . . . . . . . . . . . . . . . . 20
4.0 Instructions d’installation . . . . . . . . . . . . . . . 21
4.1 Réception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Montage et ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.3 Dimensions et caractéristiques physiques . . . . . . . . . . . . . . . . . . . 22
4.4 Branchements électriques . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.0 Branchements en parallèle et branchements triphasés 27
5.1 Fonctionnement en parallèle . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.2 Fonctionnement en branchement triphasé . . . . . . . . . . . . . . . . . . 27
6.0 Remarques et informations sur le fonctionnement. . . 28
6.1 Vérications à l’aide de voltmètres . . . . . . . . . . . . . . . . . . . . . . 28
6.2 Régulation de la charge . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.3 Effets du facteur de puissance de charge . . . . . . . . . . . . . . . . . . . 28
6.4 Utilisation avec des alimentations à découpage . . . . . . . . . . . . . . . . 28
6.5 Effets de la fréquence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.6 Temps de réponse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.7 Caractéristiques de l’entrée . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.8 Limitations du courant . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.9 Utilisation avec des charges de moteur . . . . . . . . . . . . . . . . . . . . 29
Série CVS câblée – 60 Hz
A272-283 Rev. 3 12/2018
Page: 19
SOMMAIRE
7.0 Dépannage et entretien . . . . . . . . . . . . . . . . 30
7.1 Dépannage et entretien . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.2 Remplacement des condensateurs sur place . . . . . . . . . . . . . . . . . . 30
8.0 Dépannage . . . . . . . . . . . . . . . . . . . . . . 30
9.0 Spécifications . . . . . . . . . . . . . . . . . . . . . 31
10.0 Garantie et assistance . . . . . . . . . . . . . . . . 31
10.1 Informations relatives à la garantie . . . . . . . . . . . . . . . . . . . . . . 31
10.2 Assistance technique . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Série CVS câblée – 60 Hz
A272-283 Rev. 3 12/2018
Page: 20
1.0 Consignes de sécurité importantes
Lire l’intégralité des instructions relatives à la sécurité, l’installation et le fonctionnement avant d’essayer
d’installer ou d’utiliser l’appareil.
!
DANGER
Des tensions élevées sont présentes dans l’appareil. Ne pas toucher l’intérieur lorsqu’il est sous tension.
Cet appareil contient des pièces ne pouvant pas être réparées par l’utilisateur.
2.0 Warnings Defined
DANGER
Signale une situation de danger imminent qui entraînera des blessures graves, voire mortelles, si elle n’est pas
évitée. L’emploi de ce terme est limité aux situations les plus extrêmes.
MISE EN GARDE
Indique une situation potentiellement dangereuse susceptible d’entraîner des blessures graves, voire
mortelles, si elle n’est pas évitée.
ATTENTION
Signale une situation de danger potentiel susceptible d’entraîner des blessures légères ou modérées si elle
n’est pas évitée. Ce terme peut aussi servir à mettre en garde contre des pratiques dangereuses.
3.0 Introduction
CVS de SolaHD assure la régulation de la tension et isole les bruits de mode transversal et commun
pour n’importe quel type de charge. Il élimine également les transitoires des appareils ferrorésonants,
protège contre les surcharges et sert de ligne dédiée. Il constitue le parfait équipement en matière de
conditionnement d’alimentation en courant alternatif.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

SolaHD CVS Hardwired Series a272-283 - 60 Hz Le manuel du propriétaire

Taper
Le manuel du propriétaire