Toshiba RAS-M05G3KVSG-E Manuel utilisateur

Catégorie
Climatiseurs split-system
Taper
Manuel utilisateur
AIR CONDITIONER (MULTIPLE TYPE)
INSTALLATION MANUAL
Indoor unit
R32
ENGLISH
1144250101
RAS-M05G3KVSG-E
RAS-M05G3KVSGB-E
PRECAUTIONS FOR SAFETY ...........................................................................................................................................1
ACCESSORY PARTS .........................................................................................................................................................5
INSTALLATION DIAGRAM OF INDOOR UNIT ..................................................................................................................6
Optional Installation Parts ...............................................................................................................................................6
INDOOR UNIT .....................................................................................................................................................................7
Installation Place .............................................................................................................................................................7
Cutting a Hole and Mounting Installation Plate ...............................................................................................................7
Wiring Connection ...........................................................................................................................................................8
Piping and Drain Hose Installation ..................................................................................................................................8
Indoor Unit Fixing ............................................................................................................................................................9
Drainage .........................................................................................................................................................................9
OTHERS ............................................................................................................................................................................ 10
Gas Leak Test ............................................................................................................................................................... 10
Remote Control A-B Selection ...................................................................................................................................... 10
Test Operation .............................................................................................................................................................. 10
Auto Restart Function Setting ...................................................................................................................................... 10
APPENDIX ........................................................................................................................................................................11
CONTENTS
EN
1
PRECAUTIONS FOR SAFETY
Before installation, please read these precautions for safety carefully.
Be sure to follow the precautions provided here to avoid safety risks. The symbols
and their meanings are shown below.
WARNING : It indicates that incorrect use of this unit may cause severe injury or
death.
CAUTION : It indicates that incorrect use of this unit may cause personal injury
(*1), or property damage (*2).
*1: Personal injury means a slight accident, burn, or electrical shock
which does not require admission or repeated hospital treatment.
*2: Property damage means greater damage which affects assets or
resources.
For general public use
Power supply cord and connecting cable of appliance use shall be at least
polychloroprene sheathed fl exible cord (design H07RN-F) or cord designation
60245 IEC66. (Shall be installed in accordance with national wiring regulations.)
This appliance must be connected to the main power supply by means of a circuit
breaker or a switch with a contact separation of at least 3 mm in all poles.
CAUTION To disconnect the appliance from the main power supply
Read the precautions in
this manual carefully before
operating the unit.
This appliance is fi lled with
R32.
QWarning indications on the air conditioner unit
Warning indication
CAUTION
BURST HAZARD
Open the service valves
before the operation,
otherwise there might be
the burst.
Description
CAUTION
BURST HAZARD
Open the service valves before the operation,
otherwise there might be the burst.
2
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL
WORK. MAKE SURE ALL POWER SWITCHES ARE OFF.
FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING
CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED
BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR
GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR
EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE
HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT
SOURCES SUCH AS RADIATORS, HEATERS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER
PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED
REFRIGERANT (R32) WITH ANY OTHER GASEOUS BODY INTO THE
REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE
REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE
BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF
THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE
DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR
INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR
SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or bypassing any of
the safety interlock switches.
Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply
cord.
Also, make sure the equipment is properly earthed.
Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your dealer
immediately.
3
WARNING
Do not use any refrigerant different from the one specifi ed for complement or
replacement.
Otherwise, abnormally high pressure may be generated in the refrigeration
cycle, which may result in a failure or explosion of the product or an injury to
your body.
Do not use means to accelerate the defrosting process or to clean, other than
those recommended by the manufacturer.
The appliance shall be stored in a room without continuously operating ignition
sources (for example: open fl ames, an operating gas appliance or an operating
electric heater).
Be aware that refrigerants may not contain an odour.
Do not pierce or burn as the appliance is pressurized. Do not expose the
appliance to heat, fl ame, sparks, or other sources or ignition. Else, it may
explode and cause injury or death.
 $VSHFLDOWRROIRUWKH5UHIULJHUDQWLVUHTXLUHGIRULQVWDOODWLRQ
 7KLFNQHVVRIFRSSHUSLSHVXVHGPXVWEHPRUHWKDQPP1HYHUXVHFRSSHU
SLSHVWKLQQHUWKDQPP
 $IWHUFRPSOHWLRQRILQVWDOODWLRQRUVHUYLFHFRQILUPWKHUHLVQROHDNDJHRI
refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire.
 :KHQWKHLQGRRUXQLWLVFRQQHFWHGZLWKPXOWLVSOLW5RXWGRRUXQLW00
DQG0
 3OHDVHVHH,06RXWGRRUXQLWLQVWDOODWLRQPDQXDODQGFRQVXOW\RXUGHDOHUDERXW
the minimum floor area.
 &RPSO\ZLWKQDWLRQDOJDVUHJXODWLRQV
WARNING
After installation work, make sure below before operation.
- Connection pipes are connected properly and no leakage.
- Packed valves are fully open.
5XQQLQJFRPSUHVVRUZLWKRXWRSHQSDFNHGYDOYHVPD\FDXVHDEQRUPDOKLJK
pressure and parts failure.
Leakage at connection piping may suck air and make further high pressure
cause burst and injure.
During pump down work make sure below process.
- Don’t mix air into the refrigerant cycle.
- Stop the compressor before removing piping after packed valves are
fully closed.
5HPRYLQJSLSLQJXQGHUWKHFRPSUHVVRUUXQQLQJDQGSDFNHGYDOYHVRSHQ
air might be sucked and refrigeration cycle pressure becomes abnormally high,
and it causes burst or injury on persons.
4
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to
the local power supplier before installation. If you experience any problems or if the
installation is not accepted by the supplier, the service agency will take adequate
countermeasures.
Ŷ Important information regarding the refrigerant used
This product contains À uorinated greenhouse gases.
Do not vent gases into the atmosphere.
Refrigerant type: R32
GWP(1) value: 675 * (ex. R32 ref. AR4)
(1)GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate.
* This value is based on F gas regulation 517/2014
CAUTION
Exposure of unit to water or other moisture before installation could result in
electric shock.
Do not store it in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install the unit at place where leakage of À ammable gas may occur.
In case gas leaks and accumulates at surrounding of the unit, it may cause of
¿ re.
Do not install in a place that can increase the vibration of the unit. Do not
install in a place that can amplify the noise level of the unit or where noise and
discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read this installation manual carefully before installing the unit. It contains
further important instructions for proper installation.
The manufacturer shall not assume any liability for the damage caused by not
observing the description of this manual.
01_1118350181-EN.indd 4 11/12/2562 BE 3:52 PM
5
ACCESSORY PARTS
Indoor Unit
eman traP.oNeman traP.oN
1
Installation plate × 1
2
Wireless remote control × 1
3
Battery × 2
4
Remote control holder × 1
5
Toshiba Ultra pure fi lter × 2
6
Mounting screw × 6
7
Flat head wood screw × 2
8
Owner’s Manual × 1
9
Installation Manual × 1
!
Air fi lters
Clean every 2 weeks.
1. Open the air inlet grille.
2. Remove the air fi lters.
3. Vacuum or wash and then dry them.
4. Reinstall the air fi lters and close the air inlet grille.
Filter
Maintenance & Shelf-life
Clean every 3-6 months when dust tuck or covers the fi lter.
1. Recommend to use vacuum to clean by sucking the dusts which stick or dip inside the fi lter or use the blower to blow the dust go out through the fi lter.
2. If necessary to use water to clean, simply use the plain water to wash the fi lter, dry with the sunlight for 3-4 hours or until it completely dry.
Nevertheless, use hair drier to dry it. However, washing with water, it may reduce the performance of the fi lter.
3. Replace every 2 years or sooner. (contact your dealer to purchase new fi lter) (P/N : RB-A622DA)
Note: Filter life depends on the level of impurities in your operating environment. Higher levels of impurities may require more frequent cleaning and
replacement. In all cases, we recommend an additional set of fi lters to improve the purifying and deodorizing performance of your air conditioner.
B Label × 1
Filter
6
INSTALLATION DIAGRAM OF INDOOR UNIT
Part
code Parts name Q’ty
A
Refrigerant piping
Liquid side : Ø6.35 mm
Gas side : Ø9.52 mm
One
each
BPipe insulating material
(polyethylene foam, 6 mm thick) 1
CPutty, PVC tapes One
each
Optional Installation Parts
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Right
Rear
right
Bottom
right
Rear
left Bottom left
Left
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm thick heat resisting
polyethylene foam
1
3
Batteries
Shield pipe
(Attach to the front panel.)
Hook
Installation
plate
Hook
65 mm or more
300 mm or more
300 mm or more
Make sure to run the drain hose sloped
downward.
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
5
Filter
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
For the rear left, bottom left and left piping
Wall
7Flat head
wood screw
4Remote control
holder
2Wireless
remote control
Air fi lter
7
INDOOR UNIT
Installation Place
Direct sunlight to the indoor unit’s wireless receiver should be avoided.
The microprocessor in the indoor unit should not be too close to RF
noise sources.
(For details, see the owner’s manual.)
Remote control
A place where there are no obstacles such as a curtain that may block the
signal from the indoor unit
Do not install the remote control in a place exposed to direct sunlight or
close to a heating source such as a stove.
Keep the remote control at least 1 m apart from the nearest TV set or
stereo equipment. (This is necessary to prevent image disturbances or
noise interference.)
The location of the remote control should be determined as shown below.
Cutting a Hole and Mounting
Installation Plate
NOTE
When drilling a wall that contains a metal lath, wire lath or metal plate, be
sure to use a pipe hole brim ring sold separately.
Cutting a hole
When installing the refrigerant pipes from the rear
1. After determining the pipe hole position on the mounting plate (¨), drill
the pipe hole (Ø65 mm) at a slight downward slant to the outdoor side.
A place which provides the spaces around the indoor unit as shown in the
diagram
A place where there are no obstacles near the air inlet and outlet
A place which allows easy installation of the piping to the outdoor unit
A place which allows the front panel to be opened
The indoor unit shall be installed at least 2.5 m height. Also, it must be
avoided to put anything on the top of the indoor unit.
CAUTION
°
°
°
(Side view) (Top view)
Indoor unit
Reception range
Remote
control
Remote
control
Reception
range
Indoor unit
The center of the pipe hole
is above the arrow.
Pipe hole
Ø65 mm
120 mm
6
When the installation plate is directly mounted
on the wall
1. Securely fi t the installation plate onto the wall by screwing it in the upper
and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, use
the anchor bolt holes as illustrated in the below fi gure.
3. Install the installation plate horizontally in the wall.
When installing the installation plate with a mounting screw, do not use
the anchor bolt holes. Otherwise, the unit may fall down and result in
personal injury and property damage.
CAUTION
Failure to fi rmly install the unit may result in personal injury and property
damage if the unit falls.
In case of block, brick, concrete or similar type walls, make 5 mm dia.
holes in the wall.
Insert clip anchors for appropriate mounting screws 6.
NOTE
Secure four corners and lower parts of the installation plate with 4 to 6
mounting screws to install it.
CAUTION
Installation plate
(Keep horizontal direction.)
5 mm dia. hole
Clip anchor
(local parts)
Mounting screw
Ø4 mm x 25 S
Anchor bolt
Projection
15 mm or less
Mounting the installation plate
144
50 50
300
65 103
300
6
1
Hook
Hook Hook
Pipe hole
Pipe hole
Installation
plate
Mounting screw
Weight
Indoor unit Thread
Air inlet grille
Horizontal louver
50
70
6565*
135
400
Space allows for moving range of the air inlet grille and horizontal louver
in operation above curtain rails, window cornice or other objects.
Distance between
bottom of indoor unit
to maximum horizontal
louver opening Curtain rails,
window cornice
or other objects
(Unit : mm)

293
If have curtain rails, window cornice or other objects, allow space from
the indoor unit should be 65 mm or more.
If allow space is less than 65 mm, this can affect the opening and
closing of the air inlet grille and the horizontal louver.
However, there should be no objects in the air outlet position.
It will block the air direction and drop performance.
CAUTION
flow
8
:LULQJ&RQQHFWLRQ
 ,QGRRUXQLW
Wiring of the connecting cable can be carried out without removing the
front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3.
Insert the connecting cable (according to the local cords) into the pipe hole
on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so
that it protrudes about 20 cm from the front.
5.
Insert the connecting cable fully into the terminal block and secure it tightly
with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the
indoor unit.
Cord clamp
Terminal cover
Screw
Screws
Air inlet grille
Front panel
3
Earth line
50 mm
10 mm
70 mm
10 mm
Stripping length of the Connecting cable
How to remove the drain cap
Clip the drain cap by needle-nose
pliers and pull out.
How to remove the drain hose
The drain hose can be removed by removing the
screw securing the drain hose and then pulling out
the drain hose.
When removing the drain hose, be careful of any
sharp edges of steel plate. The edges can injuries.
To install the drain hose, insert the drain hose
fi rmly until the connection part contacts with heat
insulator, and then secure it with original screw.
How to fi x the drain cap
1) Insert hexagon wrench (4 mm)
in a center head.
2) Firmly insert the drain cap.
Firmly insert the drain hose and drain cap; otherwise, water may leak.
CAUTION
Drain hose
Piping and Drain Hose Installation
* Since dewing results in a machine trouble, make sure to insulate both
connecting pipes. (Use polyethylene foam as insulating material.)
Piping and drain hose forming
1. Die-cutting front panel slit
Cut out the slit on the left or right side of the front panel for the left or right
connection and the slit on the bottom left or right side of the front panel
for the bottom left or right connection with a pair of nippers.
Rear right
Rear left
Bottom left
Left
Bottom right
Right
Die-cutting
back body slit
Changing
drain hose
Piping preparation
2. Changing drain hose
For leftward connection, bottom-leftward connection and rear leftward
connection’s piping, it is necessary to change the drain hose and drain
cap.
Do not apply lubricating oil
(refrigerant machine oil)
when inserting the drain
cap. Application causes
deterioration and drain
leakage of the plug.
Insert a hexagon wrench
(4 mm).
No gap
Connecting cable
connect to 1 2 3
Earth line
Connecting cable
Terminal block (1 2 3)
9
Drain
guide
Space for pipes
Wall
Shield pipe
Inside the room
Drain hose Extension drain hose
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
CAUTION
2. Put water in the drain pan and make sure that the water is drained out of
doors.
3. When connecting extension drain hose, insulate the connecting part of
extension drain hose with shield pipe.
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the
connecting pipes to the auxiliary pipes and wrap the facing tape around
them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape
tightly. In case of leftward piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Indoor unit
Connecting cable
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not stick out of the rear
plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to one
another and cut off the insulating tape wound on the connecting pipe
to avoid double-taping at the joint; moreover, seal the joint with the
vinyl tape, etc.
Since dewing results in a machine trouble, make sure to insulate both
connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it, not to crush it.
Do not form the
drain hose into
a wavy shape.
Do not rise the
drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
Do not put the
drain hose end
in the drainage ditch.
1
Hook here.
Installation plate
Hook Press
(unhook)
Push Push
Indoor Unit Fixing
For detaching the indoor unit
from the installation plate, pull
the indoor unit toward you while
pushing its bottom up at the
specifi ed parts.
1. Pass the pipe through the hole in the wall and hook the indoor unit on the
installation plate at the upper hook.
2. Swing the indoor unit to right and left to confi rm that it is fi rmly hooked up
on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on
the installation plate. Pull the indoor unit toward you to confi rm that it is
fi rmly hooked up on the installation plate.
Drainage
1. Run the drain hose sloped downwards.
NOTE
The hole should be made at a slight downward slant on the outdoor side.
Left-hand connection with piping
Bend the connecting pipe so that it is laid within 43 mm above the wall
surface. If the connecting pipe is laid exceeding 43 mm above the wall
surface, the indoor unit may unstably be set on the wall.
When bending the connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connecting pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (fi gure)
260 mm
210 mm
43 mm
Liquid side
Gas side
(To the forefront of fl are)
Outward form of indoor unit
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
Use the handle of screwdriver, etc.
In case of bottom right or bottom left piping
After scribing slits of the front panel
with a knife or a making-off pin, cut
them with a pair of nippers or an
equivalent tool.
Slit
In case of right or left piping
After scribing slits of the front panel
with a knife or a making-off pin, cut
them with a pair of nippers or an
equivalent tool.
Slit
10
2
1
OTHERS
Gas Leak Test
Remote Control A-B Selection
Check the fl are nut connections for the gas leak with a gas leak detector
or soap water.
Check places for
the indoor unit.
Check places for
the outdoor unit.
Test Operation
To switch the TEST RUN (COOL) mode, press [RESET] button for
10 seconds. (The beeper will make a short beep.)
Auto Restart Function Setting
The product is shipped with Auto Restart function in the ON position.
Turn it OFF if this function is not required.
This product is designed so that, after a power failure, it can restart
automatically in the same operating mode as before the power failure.
Information
How to turn OFF the Auto Restart Function
How to turn ON the Auto Restart Function
 3UHVVDQGKROGWKH>23(5$7,21@EXWWRQRQWKHLQGRRUXQLWIRUVHFRQGV
EHHSVRXQGVEXW23(5A7,21ODPSGRHVQRWEOLQN
 3UHVVDQGKROGWKH>23(5$7,21@EXWWRQRQWKHLQGRRUXQLWIRUVHFRQGV
EHHSVRXQGVDQG23(5A7,21ODPSEOLQNWLPHVHFIRUVHFRQGV
NOTE
 ,QFDVHRI21WLPHURU2))WLPHUDUHVHW$8725(67$5723(5$7,21
does not activate.
Adhesion of B label (When setting to B)
 %HVXUHWRDGKHUHWKH%ODEHO! on the cover terminal same as the below
figure.
%/DEHO
B
To separate using of remote control for each indoor unit in case of 2
air conditioner are installed near.
Remote Control B Setup.
1. 3UHVV>5(6(7@EXWWRQRQWKHLQGRRUXQLWWRWXUQWKHDLUFRQGLWLRQHU21
2. 3RLQWWKHUHPRWHFRQWURODWWKHLQGRRUXQLW
 3XVKDQGKROGEXWWRQRQWKH5HPRWH&RQWUROE\WKHWLSRIWKHSHQFLO
³´ZLOOEHVKRZQRQWKHGLVSOD\3LFWXUH1).
4. 3UHVVGXULQJSXVKLQJ³%´ZLOOVKRZRQWKHGLVSOD\DQG³´
will disappear and the air conditioner will turn OFF. 7KH5HPRWH&RQWURO%
LVPHPRUL]HG3LFWXUH2).
Note : 1. Repeat above step to reset Remote Control to be A.
2. Remote Control A have not “A” display.
 Default setting of Remote Control from factory is A.
When two indoor units are installed in the same room or adjacent two
rooms, if operating a unit, two units may receive the remote control signal
VLPXOWDQHRXVO\DQGRSHUDWH,QWKLVFDVHWKHRSHUDWLRQFDQEHSUHVHUYHG
E\VHWWLQJHLWKHURQHUHPRWHFRQWUROWR%VHWWLQJ%RWKDUHVHWWR A setting
in factory shipment.)
The remote control signal is not received when the settings of indoor unit
and remote control are different.
There is no relation between AVHWWLQJ%VHWWLQJDQG AURRP%URRPZKHQ
connecting the piping and cables.
MODE
23(5A7,21
RESET%XWWRQ
11
APPENDIX
APPENDIX
Work instructions
The existing R22 and R410A piping can be reused for
inverter R32 product installations.
WARNING
Con¿rming the existence of scratches or dents on
the existing pipes and con¿rming the reliability of
the pipe strength are conventionally referred to the
local site.
If the speci¿ed conditions can be cleared, it is
possible to update existing R22 and R410A pipes
to those for R32 models.
Basic conditions needed to reuse existing
pipes
Check and observe the presence of three conditions in
the refrigerant piping works.
1. Dry (There is no moisture inside of the pipes.)
2. Clean (There is no dust inside of the pipes.)
3. Tight (There are no refrigerant leaks.)
Restrictions for use of existing pipes
In the following cases, the existing pipes should
not be reused as they are. Clean the existing pipes
or exchange them with new pipes.
1. When a scratch or dent is heavy, be sure to use new
pipes for the refrigerant piping works.
2. When the existing pipe thickness is thinner than the
speci¿ed “Pipe diameter and thickness,” be sure to
use new pipes for the refrigerant piping works.
yThe operating pressure of R32 is high (1.6 times
that of R22). If there is a scratch or dent on the pipe
or a thinner pipe is used, the pressure strength may
be inadequate, which may cause the pipe to break
in the worst case.
* Pipe diameter and thickness (mm)
Pipe outer diameter Ø6.4 Ø9.5 Ø12.7
Thickness R32, R410A 0.8 0.8 0.8
R22
3. When the outdoor unit was left with the pipes
disconnected, or the gas leaked from the pipes and
the pipes were not repaired and re¿lled.
yThere is the possibility of rain water or air, including
moisture, entering the pipe.
4. When refrigerant cannot be recovered using a
refrigerant recovery unit.
yThere is the possibility that a large quantity of dirty
oil or moisture remains inside the pipes.
5. When a commercially available dryer is attached to the
existing pipes.
yThere is the possibility that copper green rust has
been generated.
6. When the existing air conditioner is removed after
refrigerant has been recovered.
Check if the oil is judged to be clearly different from
normal oil.
yThe refrigerator oil is copper rust green in color:
There is the possibility that moisture has mixed with
the oil and rust has been generated inside the pipe.
yThere is discolored oil, a large quantity of residue,
or a bad smell.
yA large quantity of shiny metal dust or other wear
residue can be seen in the refrigerant oil.
7. When the air conditioner has a history of the
compressor failing and being replaced.
yWhen discolored oil, a large quantity of residue,
shiny metal dust, or other wear residue or mixture of
foreign matter is observed, trouble will occur.
8. When temporary installation and removal of the air
conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air
conditioner is other than the following oil (Mineral oil),
Suniso, Freol-S, MS (Synthetic oil), alkyl benzene
(HAB, Barrel-freeze), ester series, PVE only of ether
series.
yThe winding-insulation of the compressor may
deteriorate.
NOTE
The above descriptions are results have been con¿rmed
by our company and represent our views on our air
conditioners, but do not guarantee the use of the existing
pipes of air conditioners that have adopted R32 in other
companies.
Curing of pipes
When removing and opening the indoor or outdoor unit for
a long time, cure the pipes as follows:
yOtherwise rust may be generated when moisture or
foreign matter due to condensation enters the pipes.
yThe rust cannot be removed by cleaning, and new
pipes are necessary.
Placement
location Term Curing manner
Outdoors 1 month or more Pinching
Less than 1 month Pinching or taping
Indoors Every time
Are there scratches or dents on the existing pipes?
Is it possible to operate the existing air conditioner?
yAfter the existing air conditioner is operated in cooling
mode for approx. 30 minutes or longer,* recover the
refrigerant.
yFor cleaning the pipes and recovering oil
yRefrigerant recovery: Pump down method
yRemove the existing air conditioner from the piping
and carry out Àushing (nitrogen pressure 0.5 MPa) to
remove any remains inside of the pipe.
Note: In case of twin pipes, also be sure to Àush the
branching pipe.
Connect the indoor / outdoor units to the existing pipe.
yUse a Àare nut attached to the main unit for the indoor
/ outdoor units. (Do not use the Àare nut of the existing
pipe.)
yRe-machine the Àare machining size to size for R32.
y(Airtight test), Vacuum dry, Refrigerant charge, Gas
leak check
Test run
Was largely discolored oil or a large quantity
of remains discharged? (When the oil deteriorates,
the color of the oil changes to a muddy
or black color.)
Existing pipes: Cannot be used.
yUse new pipes.
Clean the pipes or use new pipes.
Piping necessary to change the Àare nut / machining
size due to pipe compression
1) Flare nut width: H
H
(mm)
Copper pipe
outer diameter Ø6.4 Ø9.5 Ø12.7
For R32, R410A 17 22 26
For R22 Same as above 24
2) Flare machining size: A
A
(mm)
Copper pipe
outer diameter Ø6.4 Ø9.5 Ø12.7
For R32, R410A 9.1 13.2 16.6
For R22 9.0 13.0 16.2
Becomes a little larger for R32
Do not apply refrigerator oil to the Àare surface.
(If there is discharge of remains, it is judged that a
large quantity of remains are present.)
YES
YES
NO
NO
NO
YES
Nitrogen gas pressure 0.5 MPa
01_1118350181-EN.indd 12 11/12/2562 BE 3:52 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Toshiba RAS-M05G3KVSG-E Manuel utilisateur

Catégorie
Climatiseurs split-system
Taper
Manuel utilisateur

dans d''autres langues