5
COMBUSTION AND VENTILATION AIR
WARNING: This boiler must be supplied with
combustion and ventilation air in accordance with the
latest revision of Section 9.3, Air for Combustion &
Ventilation, of the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 for gas boilers or ANSI/NFPA 31 Installation of
Oil Burning Equipment for oil boilers. Canadian
installations must comply with CAN/CSA B149.1 Natural
Gas and Propane Installation Code for gas boilers or
CSA B140.7 Oil Burning Equipment for oil boilers. All
applicable local building codes must be adhered to.
Failure to provide adequate combustion air for this
boiler can result in excessive levels of carbon monoxide
which can result in severe personal injury or death!
To operate properly and safely this boiler requires a
continuous supply of air for combustion. An adequate supply of
air must be available to replace the air used by the combustion
process. NEVER store objects on or around the boiler.
CAUTION: Never use an exhaust fan in the boiler room.
The boiler room must never be under a negative pressure
or improper burner operation will occur!
NOTE: If mechanical combustion air supply is required,
the system must be approved by the local authorities,
and should provide at least 30 CFM per gallon of oil and
.35 CFM/1,000 BTU HR (.034 m3/min per kw) of gas input
to the boilers.
All Air From Inside The Buidling
If the boiler is to be located in a conned space minimum
clearances of 24 in., 610 mm must be maintained between
the boiler and any adjacent construction. When installed in a
conned space, two permanent openings communicating with
an additional room(s) are required. The combined volume of
these spaces must have sufcient volume to meet the criteria
for an unconned space. The total air requirements of all
fuel burning equipment or any type of exhaust fan must be
considered when making this determination.
Each opening must have a minimum free area of 1 in2/1000
Btu/hr, 140 in2/GPH, 2200 mm2/kW based on the total input
rating of ALL fuel burning equipment in the conned area.
Each opening must be no less than 100 in2, 64,516 mm2 in
size. The upper opening must be within 12 in., 305 mm of,
but not less than 3 in., 76 mm from, the top of the enclosure.
The bottom opening must be within 12 in., 305 mm of, but
not less than 3 in., 76 mm from, the bottom of the enclosure.
All Air From Outside The Building
When installed in a conned space two permanent openings
communicating directly with, or by ducts to, the outdoors or
spaces that freely communicate with the outdoors must be
present. The upper opening must be within 12 in., 305 mm of,
but not less than 3 in., 76 mm from, the top of the enclosure.
The bottom opening must be within 12 in., 305 mm of, but not
less than 3 in., 76 mm from, the bottom of the enclosure.
SERIES 19HE BOILER
INSTALLATION INSTRUCTIONS
Where directly communicating with the outdoors or
communicating with the outdoors through vertical ducts, each
opening shall have a minimum free area of 1 in2/4000 Btu/hr,
35 in2/GPH, 550 mm2/kW of the total input rating of all of the
equipment in the enclosure.
Where communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
in2/2000 Btu/hr, 70 in2/GPH, 1100 mm2/ kW of the total input
rating of all of the equipment in the enclosure. When ducts
are used, they must have the same cross-sectional area as
the free area of the opening to which they connect. When
calculating the free area necessary to meet the make-up air
requirements of the enclosure, consideration must be given
to the blockage effects of louvers, grills and screens. Screens
must have a minimum mesh size of 1/4 in, 6.4mm. If the free
area through a louver or grill is not known the louver or grille
should be sized per Table 1.
Table 1 - Make-up Air Louver Sizing
Required Cross Sectional Louver Area (in2)
Ventilation air, if required, must be in addition to the
combustion air quantities called for above.
CHIMNEY & VENT PIPE CONNECTIONS
WARNING: The vent installation must be in
accordance with the latest revision of Part 7, Venting
of Equipment, of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 for gas boilers or ANSI/NFPA 31
Installation of Oil Burning Equipment for oil boilers
and the ASHRAE Equipment Handbook on Venting.
Canadian installations must comply with CAN/CSA
B149.1 Natural Gas and Propane Installation Code for
gas boilers or CSA B140.7 Oil Burning Equipment for
oil boilers. All applicable local building codes must be
adhered to. Improper venting of this boiler can result
in excessive levels of carbon monoxide which can
result in severe personal injury or death!
CAUTION: The products of combustion from a 19HE
must be safely vented to the outdoors while ensuring
that the ue gases do not cool prematurely. It's critical
that the chimney system be properly designed to handle
the relatively cool ue gas temperatures. An oversized or
uninsulated chimney will cause the moisture in the ue
gases to condense resulting in damage to the chimney
system unless it's specically designed for condensate. If
this is the case a suitable condensate drain must be used
to protect the boiler from condensate.
NOTE: Our warranty does not cover corrosion damage to
the boiler or its vent system caused by ue gas condensate!
Input
(MBH)
1/4", 6.4 mm
Wire Screen
Metal Louvers
75% Free Area
Wooden Louvers
25% Free Area
in2cm2in2cm2in2cm2
400 100 645 133 860 400 2581
600 150 968 200 1289 600 3871
800 200 1290 266 1720 800 5162
1000 250 1613 333 2148 1000 6452
1200 300 1936 400 2578 1200 7742
1400 350 2258 467 3007 1400 9033
1600 400 2581 533 3437 1600 10,323
1800 450 2903 600 3866 1800 11,614
2000 500 3226 666 4296 2000 12,904