TE-6300M Series Well Insertion Temperature Sensors Installation Instructions 1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
Installation
Dimensions
Mounting
Location Considerations
Consider the following mounting location guidelines:
Avoid areas subject to the effects of excessive
vibration, electrical noise, direct sunlight, or radiant
heat.
Keep electrical wiring as short as possible to
minimize temperature error.
Mounting the Temperature Sensor
See Figure 2 and mount the temperature sensor:
IMPORTANT: The TE-6300M Series Well Insertion
Temperature Sensors are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
sensor could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the sensor.
IMPORTANT : Le TE-6300M Series Well Insertion
Temperature Sensor est destiné à transmettre des
données entrantes à un équipement dans des
conditions normales de fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement du sensor
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du sensor.
IMPORTANT: Do not install the TE-6300M Series
Well Insertion Temperature Sensor in ambient
temperatures beyond the specified -50 to 220°F
(-46 to 104°C) temperature range. Installing the
temperature sensor in ambient temperatures
beyond this range may damage the unit and void the
warranty.
Figure 1: Sensor Dimensions, in. (mm)
F
I
G
:
s
n
s
_
d
i
m
1.80 (45.7)
0.875
(22.2)
Side View
1.20
(30.5)
1.87 (47.5)
1.87
(47.5)
0.60 (15.2)
Front View
4.73 (120.1) maximum
7.73 (196.3) maximum
Figure 2: Installing the Well Insertion Sensor
F
I
G
:
s
n
s
_
i
n
s
t
or
Sensor
Probe
TE-6300W-101
TE-6300W-102
Thermowell
Direct Mount for
6 in. (152 mm) Probe Models
Set Screw
1/2 in.
NPT
Threaded Mount for
8 in. (203 mm) Probe Models
Well Adaptor
Set Screw
TE-6300W-110 Thermowell
TE-6300M Series Well Insertion Temperature Sensors
Installation Instructions
TE-631xM, TE-635xM,
TE-634xM, TE-636xM
Part No. 24-4034-182, Rev. G
Issued March 2016
24- 4034- 182, Rev. G
TE-6300M Series Well Insertion Temperature Sensors Installation Instructions2
Note: The Johnson Controls® TE-6300W-101
thermowell contains thermal compound. The
TE-6300W-102 and TE6300W-110 do not contain
thermal compound. Add thermal compound
(F-1000-182, or equivalent) before inserting the probe
if the well does not include thermal compound. For
proper sensor function, mount the well so that any
condensation that forms drains out of the probe.
1. If the thermowell is:
Direct Mount (TE-63xAM-2), loosen the set
screw
Threaded (TE-63x2M), screw the well adaptor
into the thermowell and loosen the well adaptor
set screw
2. Insert the sensor probe into the thermowell until it
touches the bottom.
3. Pull back the probe approximately 1/8 in. (3 mm)
and then tighten the set screw.
4. Wire the sensor to the controller.
5. Reposition the cover and tighten the cover screws.
Wiring
For 1k ohm nickel temperature sensors, wire resistance can
cause about 1F° (0.56C°) of error for every 250 ft (76 m) run
of 18 AWG (1.0 mm diameter) wire, or every 100 ft (31 m) run
of 22 AWG (0.6 mm diameter) wire.
For 1k ohm platinum temperature sensors, wire resistance
can cause about 1F (0.56C) of error for every 150 ft (46 m)
run of 18 AWG (1.0 mm diameter) wire, or every 50 ft (15 m)
run of 22 AWG (0.6 mm diameter) wire. To minimize error
due to field wiring, limit total resistance of all nickel
temperature sensor wiring to 3 ohms, and all platinum
temperature sensor wiring to 2 ohms.The 2.2k and 10k ohm
thermistor applications permit wiring to be relatively long
before wire resistance adds significantly to total resistance
measured at the controller. As a general rule, a 150 ft (46 m)
two-wire 18 AWG (1.0 mm diameter) run contributes 2 ohms
of error, or less than 1F (0.56C) error over the sensor
operating temperature range.
Refer to the appropriate controller documentation for
recommended sensor wiring. Secure the wiring bushing or
conduit only to the temperature sensor base. See Table 1 for
an explanation of the lead wiring color convention
Repair Information
If the TE-6300M Series Well Insertion Temperature Sensor
fails to operate within its specifications, replace the unit. For a
replacement sensor, contact the nearest Johnson Controls
representative.
Table 1: Lead Wiring Color Code
Sensor Type Lead Color
1k ohm Nickel White
1k ohm Platinum White with Blue Stripe
2.2k ohm Thermistor Red
10k ohm Thermistor White with Green Stripe
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
MISE EN GARDE : Risque de dégâts
matériels.
Ne pas mettre le système sous tension
avant d'avoir vérifié tous les raccords de
câblage. Des fils formant un court-circuit
ou connectés de façon incorrecte
risquent d'endommager
irrémédiablement l'équipement.
IMPORTANT: Use copper conductors only. Make
all wiring connections in accordance with local,
national, and regional regulations. Do not exceed
the TE-6300M Series Well Insertion Temperature
Sensor’s electrical ratings.
Published in U.S.A. www.johnsoncontrols.com
TE-6300M Series Well Insertion Temperature Sensors Installation Instructions 3
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Technical Specifications
TE-6300M Series Well Insertion Temperature Sensors
Models TE-631xM Thin-Film Nickel Temperature Sensor
TE-635xM Thin-Film Platinum Temperature Sensor
TE-634xM 2.2k ohm Thermistor Temperature Sensor
TE-636xM 10k ohm Thermistor Temperature Sensor
Sensor
Reference
Resistance
Nickel 1k ohms at 70°F (21°C)
Platinum 1k ohms at 32°F (0°C)
2.2k ohm
Thermistor
2,252 ohms at 77°F (25°C)
10k ohm
Thermistor
10k ohms at 77°F (25°C)
Sensor
Accuracy
Nickel 0.34F° at 70F (0.19C at 21C)
Platinum 0.35° at 70°F (0.19C° at 21°C), DIN Class A
2.2k ohm
Thermistor
0.36F° (0.2C°) in the Range 32 to 158°F (0 to 70°C)
10k ohm
Thermistor
0.9F° (0.5C°) in the Range 32 to 158°F (0 to 70°C)
Sensor
Temperature
Coefficient
Nickel Approximately 3 ohms/F° (5.4 ohms/C°)
Platinum Approximately 2 ohms/F° (3.9 ohms/C°) 3850 ppm/K
2.2k ohm
Thermistor
Nonlinear, Negative Temperature Coefficient (NTC)
10k ohm
Thermistor
Nonlinear, NTC, Johnson Controls Type II
Electrical Connections 22 AWG (0.6 mm Diameter) x 6 in. (150 mm) Long Lead Wires
Materials Well Adaptor 0.875 in. (22.2 mm) Hex Brass
Probe 0.25 in. (6.4 mm) Outside Diameter x 5 in. (127 mm) or 8 in. (203 mm) Long
Stainless Steel
Enclosure Corrosion-Resistant Steel
Operating Temperature -50 to 220°F (-46 to 104°C)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the
local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
  • Page 1 1
  • Page 2 2
  • Page 3 3

Johnson Controls TE-631xM Guide d'installation

Taper
Guide d'installation

dans d''autres langues