nVent RAYCHEM JBM-100-A Multiple-Entry Power-Tee Connection Manuel utilisateur

Taper
Manuel utilisateur

©2001 www.nVent.com
APPROVALS
Power Connection, Powered Splice, Powered Tee, Dual
Power Connection, Splice or Tee with Junction Box
DESCRIPTION











RAYCHEM






TOOLS REQUIRED
   
   
   
 
 
 


®
 





IECEx 
 
 
 
 
 
 
 




 
 
 
 
Hazardous Locations
 | 1
This component is an electrical device that must
be installed correctly to ensure proper operation
and to prevent shock or fire. Read these important
warnings and carefully follow all of the installation
instructions.
To minimize the danger of fire from sustained
electrical arcing if the heating cable is
damaged or improperly installed, and to
comply with the requirements of nVent,
agency certifications, and national electrical
codes, ground-fault equipment protection
must be used. Arcing may not be stopped by
conventional circuit breakers.
The power connection may be powered by more
than one circuit. Be sure all power sources are
de-energized before opening box.
Component approvals and performance are
based on the use of nVent specified parts only.
Do not use substitute parts or vinyl electrical
tape.
The black heating cable core and fibers are
conductive and can short. They must be
properly insulated and kept dry.
Damaged bus wires can overheat or short. Do
not break bus wire strands when scoring the
jacket or core.
Keep components and heating cable ends dry
before and during installation.
Use only fire-resistant insulation materials,
such as fiberglass wrap or flame-retardant
foam.
HEALTH HAZARD: Prolonged or repeated contact
with the sealant in the core sealer may cause skin
irritation. Wash hands thoroughly. Overheating or
burning the sealant will produce fumes that may
cause polymer fume fever. Avoid contamination
of cigarettes or tobacco. Consult MSDS VEN 0058
for further information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300
Non-emergency health and safety information:
(800) 545-6258.
Ce composant électrique doit être installé
correctement pour éviter les risques d'incendie
ou de chocs électriques. Lire ces avertissements
importants et suivre attentivement toutes les
instructions d'installation.
• Pour réduire le danger d'incendie causé par un
arc électrique entretenu, si le câble chauffant
est endommagé ou mal installé, et pour
respecter les exigences de nVent et celles des
codes applicables, il est impératif d'utiliser
une protection par disjoncteur différentiel. Les
disjoncteurs ordinaires ne sont pas toujours
capables de supprimer les arcs électriques.
• Les approbations et les performances des
composants sont basées sur l'utilisation des
pièces nVent spécifiées seulement. N'utilisez
pas de pièces de rechange ou de ruban isolant
en vinyle.
• Le noyau et les fibres du câble chauffant noir
sont conducteurs et peuvent provoquer un
court-circuit. Ils doivent être correctement
isolés et gardés à sec.
• Les fils omnibus endommagés peuvent
surchauffer ou subir un court-circuit.
• Ne brisez jamais les fils omnibus lorsque vous
incisez la gaine ou le noyau.
• Maintenez les composants et les extrémités
des câbles chauffants secs avant et pendant
l'installation.
• Les fils omnibus peuvent provoquer un court-
circuit s'ils se touchent. Les garder à l'écart les
uns des autres
• N'utilisez que des matériaux isolants
ininflammables, par exemple une gaine de fibre
de verre ou de la mousse ignifuge.
• Laissez ces instructions d'installation à
l'utilisateur pour qu'il puisse les consulter.
DANGER POUR LA SANTÉ : Le contact prolongé
ou répété avec le produit d'étanchéité du noyau
peut provoquer une irritation de la peau. Lavez-
vous les mains soigneusement. La surchauffe et
la combustion du produit d'étanchéité produira
des vapeurs qui peuvent causer la fièvre des
vapeurs de polymères. Évitez la contamination
des cigarettes ou du tabac. Consultez la fiche
technique santé-sécurité (FTSS) VEN 0058 pour
obtenir de plus amples informations.
Téléphone en cas d'urgence 24 heures sur 24 de
CHEMTREC : (800) 424-9300
Renseignements non urgents en matière de santé
et de sécurité : (800) 545-6258
WARNING:
CAUTION:
AVERTISSEMENT:
MISE EN GARDE:
ADDITIONAL MATERIALS REQUIRED
   
OPTIONAL MATERIALS
 

 

A
D
C
B
H
G
F
E
I
J
KIT CONTENTS
Item Qty Description
  
  
  
  
  
  
  
H 1 Lid
  
  

Inner jacket
Outer jacket
Spacer
Conductive
fiber
Bus wire
Braid
Bus wire
Conductive
core
Inner jacket
Braid
Outer
jacket
Clear jacket
Inner jacket
Braid
Outer
jacket
Heating element
Insulated bus wire
Bus wire
connection
VPL
Go to Step 1A
XTV-CT, KTV-CT
Go to Step 1B
BTV-CR, BTV-CT, QTVR-CT
Go to Step 1B
HTV-CT
Go to Step 1B
Outer Jacket
Braid
Conductive Core + Electrical Insulation
Bus Wire
Inner jacket
Outer jacket
Spacer
Conductive
fiber
Bus wire
Braid
Bus wire
Conductive
core
Inner jacket
Braid
Outer
jacket
Clear jacket
Inner jacket
Braid
Outer
jacket
Heating element
Insulated bus wire
Bus wire
connection
VPL
Go to Step 1A
XTV-CT, KTV-CT
Go to Step 1B
BTV-CR, BTV-CT, QTVR-CT
Go to Step 1B
HTV-CT
Go to Step 1B
Outer Jacket
Braid
Conductive Core + Electrical Insulation
Bus Wire
HEATING CABLE TYPES
 

 | 3
24 in
(60 cm)
12 in
(30 cm)
Align heating
cable indentations
Centerline of
connection
12 in (30 cm) minimum Indentation
(bus wire
connection)
Cut at 45
angle
VPL
18 in
(45 cm)
Box nut
2
24 in
(60 cm)
Centerline of
connection
BTV, QTVR, XTV, KTV, HTV
 

• Af


 



 




Go to Step 2
Go to Step 2
Do not remove box nut from
stand. 


needed.
 

 

1A 1B
7 1/2 in
(190 mm)
Do not cut braid.
3
 
 

XTV, KTV
VPL
Go to Step 5B
Go to Step 5A
Go to Step 5C
BTV, QTVR
Go to Step 5D
HTV
4
 

1/2 in
(13 mm)
6 in
(152 mm)
VPL
6 in
(152 mm)
 


 


 
 


 


 



 


 


 


 

Go to Step 6
5A
6 1/2 in
(165 mm)
XTV, KTV
 

 

 


 


 
 

 

 


 
Go to Step 6
5B

1/4 in
(5 mm)
6 1/2 in
(165 mm)
BTV, QTVR
 

 


 


 


 
 
 
 

 
 
 

 
Go to Step 6
5C
6 1/2 inches
(165 mm)
180°
180°
6 1/2 inches
(165 mm)
HTV
5D
 


 


Bend heating



 



 

 





 




 


 
 Go to Step 6
 


5/8 in
(15 mm)
JBM-SPA
adapter
for small
pipes Position
adapter
this side
up.
Glass cloth tape
Pipe strap
O-ring
6
8
9 10
1 1/4 in
(32 mm)
7
 

 

 

 .
 


 


needed.
 



Note: 



 



 
stand.
 



Optional: Knock
out drain hole
if installed on
bottom of pipe.
Make sure the bus
wires do not kink,
bunch, or crossover.
1/2 in
(13 mm)
1/2 in
(13 mm)
11
13
15 16
Tubes
Make sure all strands
go into the tubes.
12
14
 



 


 

 
 

 


 


 




CAUTION: Health Hazard.
Wash hands after contact with sealant. Consult
material safety data sheet VEN 0058.
AVERTISSEMENT: risque pour la santé. Se laver les
mains après tout contact avec le produit d’étanchéité.
Consulter la fiche de données de sécurité VEN 0058.
Note: 





1
2
Screwdriver slot
Wire hole
Wire
17





 1



1
2



 

 

 
 

 
 

L1
L2 or N
Power
supply
L1
L2 or N
Power
supply
Power connection for
one heating cable.
Power connection for two
or three heating cables.
Remove
jumper
Remove
jumper
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Power supply
Power connection for two
heating cable circuits.
L2 or N L2 or N
L1 L1
Make sure
conductors
are not
exposed.
Watertight
conduit seal
3/4 in lock nut
1/2 in
(13 mm)
Power and ground wires
Conduit
drain
18A
18C
19A
L1
L2 or N
18B
 


 





Splice Wiring Tee Wiring
Power Connection Wiring
If used as a power connection
WARNING: Shock or fire hazard. When the power connection is energized by two circuits, the L1 and
L2 jumpers must be removed to prevent an electrical short.
AVERTISSEMENT: risque d’électrocution et d’incendie. Lorsque le raccordement électrique est
alimenté par deux circuits, les cavaliers L1 et L2 doivent être enlevés afin d’éviter un court-circuit.
10 | 
3/4 in lock nut
O-ring
Box plug
Weather seal
©2001 www.nVent.com
19B
20
 
 
 
 

 
If used as a splice or tee connection
WARNING: Explosion Hazard- Substitution of Components May
Impair Suitablity for Class I Division 2 (Zone 2)
WARNING: Explosion Harzard- Do not disconnect equipment unless
power has been switched off or the area is known to be Non-Hazardous.
AVERTISSEMENT- Risque d’explosion. La substitution de composants
peut rendre ce matériel inacceptable pour les emplacements de
classe i, division 2 (zone 2).
AVERTISSEMENT - Risque d’explosion. Ne pas débrancher l’appareil
à moins d’avoir coupé l’alimentation électrique ou à moins qu’il ne
s’agisse d’un emplacement non dangereux
 | 11
North America
 ...
 ...

Europe, Middle East, Africa
 ...
 ...

Asia Pacific
 ...
 ...

Latin America
 ...
 ...

nVent.com/RAYCHEM
©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their
respective owners. nVent reserves the right to change specifications without notice.