CREE LIGHTING CPY250 Richmond Civic Upgrade Kit Guide d'installation

Taper
Guide d'installation
INSTALLATION INSTRUCTIONS
1 of 2 CI391X05R1_A
CPY Series
Richmond Series Upgrade Kit
Includes: CPY250 Luminaries
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. DANGER – RISK OF SHOCK – DISCONNECT POWER BEFORE INSTALLATION
DANGER – RISQUE DE CHOC – COUPER L’ALIMENTATION AVANT L’INSTALLATION
2. This LED upgrade product is UL Classied for use with Richmond and Whiteway Civic only. DO NOT install into any other
manufacturers luminaire. To maintain existing Luminaires’ UL listing, the LED Upgrade Kit must be UL Classied for use with the
manufacturer and model of existing luminaire. Consult CREE Customer support to see if other luminaires are classied to be used with
this LED Upgrade Kit.
Ce produit upgrade LED est classié UL pour une utilisation avec la série Richmand et Whiteway Civic seulement. Ne pas installez ce upgrade
LED dans le luminaire de tout autre fabricant. Pour maintenir la qualication UL des Luminaires existants, le kit LED upgrade doit être classié
UL pour une utilisation avec le fabricant et le modèle de luminaire existant. Consulter CREE Support Clientèle pour voir si les autres luminaires
peuvent être utilisés avec ce upgrade LED.
3. WARNING – Risk of re or electric shock. LED Upgrade Kit installation requires knowledge of luminaires electrical systems. If not
qualied, do not attempt installation. Product must be installed in accordance with NEC or your local electrical code. If you are not
familiar with these codes and requirements, contact a qualied electrician.
ATTENTION- Risque d’incendie ou de choc électrique. L’installation du kit upgrade LED exige la connaissance des systèmes électriques pour
luminaires. Si non qualié, ne tentez pas d’installation. Ce produit doit être installé conformément à NEC ou votre code électrique local. Si vous
n’êtes pas familier avec ces codes et ces exigences, veuillez contacter un électricien qualié.
4. WARNING – Risk of re or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of the LED
Upgrade Kit. Check for enclosed wiring and components.
ATTENTION - Risque d’incendie ou de choc électrique. Câblage électriques peuvent être endommagés lors du perçage pour l’installation du kit
upgrade LED. Vérier les ls et composants.
5. WARNING – Risk of re or electric shock. Check the existing wiring for damage before installing Upgrade Kit. Do not install if existing
wires are damaged.
ATTENTION- Risque d’incendie ou de choc électrique. Vériez si le câblage existant n’est pas endommagé avant l’installation du kit upgrade LED.
Ne pas installer si des ls sont endommagés.
6. WARNING – To prevent wiring damage or abrasion, do not expose wires to the edge of sheet metal or any other sharp objects.
ATTENTION - Pour éviter les dégâts de câblage par l’abrasion, ne pas mettre en contact les ls électriques avec des bords de tôle ou d’autres
objets pointus.
7. WARNING – Risk of re or electric shock. Install this kit only in the luminaires that have the construction features and dimensions shown
in the photographs and/or drawings.
ATTENTION - Risque d’incendie ou de choc électrique. Installez ce kit seulement dans les luminaires qui ont les caractéristiques de construction et
les dimensions dans les photographies ou les dessins de la page suivante.
8. Do not make or alter any holes in a wiring enclosure or electrical components during the kit installation.
Ne pas modier ou faire de trous dans une boite de câblage ou compartiment électrique lors de l’installation du kit.
9. Ensure that the existing luminaire is installed according to original manufacturers specication.
S’assurer que les luminaires sont installés selon les spécications du fabricant.
10. Only the holes indicated in the photographs or drawings may be made or altered as a result of the kit installation. Do not leave any other
holes open in a wiring enclosure or electrical component.
Seulement les trous indiqués dans les photographies ou les dessins peuvent être faits ou altérés pour l’installation du kit LED. Ne laissez aucun
trou ouvert dans le compartiment électrique.
11. Once the Upgrade Kit is installed, the luminaire can no longer accept HID lamps and shall not be converted back to an HID luminaire.
Une fois le kit upgrade LED installé, l’appareil peut ne plus accepter les lampes HID et ne pourra pas être retransformé en luminaire HID.
12. No user maintenance is required. Do not remove the enclosure cover after installation.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
#
HOUSING SIZES:
NOTE: Ensure the sizes of the existing luminaire housings are
approximately as follows:
Richmond: 21-3/5”L X 12”W X 13-4/5”H
Whiteway Civic: 20-9/10”L X 10-9/10”W X 13-2/5”H
*This fixture must be surface mounted
UPGRADE KIT LIST OF COMPONENTS:
NOTE: This kit is used only with the standard CPY250
luminaire that is sold separate from the kit.
1. Upgrade assembly Panel
2. (8) - Mounting screws
3. (4) - Nuts
4. (4) - Sealing Washers
5. (2) - Hooks
6. (2) - 9" Cable
2 of 2 CI391X05R1_A
www.creelighting.com
© 2023 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content is
subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree® and the Cree Lighting logo are
registered trademarks of Cree, Inc. NEMA® is a registered trademark of the National Electrical Manufacturers Association.
TO INSTALL:
NOTE: DO NOT lift luminaire by the power leads.
STEP 1:
Disconnect power to fixture.
STEP 2:
Verify the existing housing model.
STEP 3:
Open and remove lens frame assembly. Remove door mounting hardware,
lamp, reflector, ballast cover and socket assembly. Disconnect incoming power
leads.
Note: Existing ballast and capacitor may be left in fixture if they do not
interfere with the LED upgrade module and if the existing luminaire is not
supported solely by the j-box. If removed, components should be recycled
according to all local, state, and/or federal ordinances.
STEP 4:
Check the caulk between the Canopy and the existing luminaire housing. Add
caulk as needed to ensure water tight installation.
STEP 5:
Locate the center of the right side housing flange and pre drill (2) holes 12”
apart using a 1/4” bit. See Figure 1 and 2.
STEP 6:
Attach CPY250 luminaire and the provided cables to the panel using the (4)
supplied machine screws and nuts as shown in Figure 2. These cables will
allow for hands-free wiring and support during installation.
STEP 7:
Attach (2) hooks on ends of cables to the holes drilled in Step 3 on housing
flanges. See Figure 3.
STEP 8:
Make wiring connections as shown in the Electrical Connections Section.
NOTE: Ground connection should include previous luminaire ground. Verify
that the supply voltage is within the fixtures voltage rating.
STEP 9:
Rotate panel to horizontal position and push upward into the existing luminaire
housing ensuring that no wires are pinched. Slide panel bracket over housing
flange. Once positioned, secure to housing using (4) supplied mounting screws
and sealing washers, ensure the rubber side of the washers is towards the
panel. See Figure 3.
F1
3
2
ELECTRICAL CONNECTIONS
STEP 1:
Using 90°C minimum rated wire connectors, make the following electrical
connections:
a. Connect supply ground conductor to fixture (green) ground wire and mounting
plate (green) ground wire with wire connector.
b. Connect supply voltage conductor to fixture black wire with wire connector
c. Connect supply neutral conductor to fixture white wire with wire connector.
d. If Dimming is an option; connect the violet dimming positive lead to the supply
dimming positive lead.
e. If Dimming is an option; connect the pink dimming negative lead to the supply
dimming negative lead
LINE
OR HOT 1
GREEN
LINE-BLACK
GROUND-GREEN
NEUTRAL-WHITE
DIM (-) PINK
DIM (+) VIOLET
NEUTRAL
OR HOT 2
VIOLET
PINK
SUPPLY WIRING
(DIMMING OPTIONAL)
LUMINAIRE
1
Housing Flange
Panel
(4) Supplied Screws
Panel Bracket
(4) Supplied
Mounting Screws
  • Page 1 1
  • Page 2 2

CREE LIGHTING CPY250 Richmond Civic Upgrade Kit Guide d'installation

Taper
Guide d'installation