Leviton DRC00-L0 Guide d'installation

Taper
Guide d'installation
GreenMax
®
Distributed Room Controller
Cat. No. DRC00-0L0
INSTALLATION INSTRUCTIONS
ENGLISH
DI-001-DRC00-02A
WARNINGS
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR
FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult an electrician.
CAUTIONS
Use this device with copper or copper clad wire only.
For indoor applications only.
Save these instructions.
The GreenMax Distributed Room Controller (DRC) comes in a Line Voltage and
Low Voltage LumaCAN™ powered product. The product manages all the energy
PDQDJHPHQWEXVLQHVVORJLFZLWKLQDVLQJOHURRPDQGLVIXOO\VHWXSDQGFRQ¿JXUHGXVLQJ
a Wi-Fi
®
enabled cell phone or tablet.
Only one room controller should be used per room. Each room requires one controller.
The LumaCAN network can span multiple rooms and connect multiple DRC devices
together; however it is important to pay particular attention to control and setup of rooms
to avoid cross room control.
Each GreenMax DRC Controller can connect to a variety of devices, such as DRC smart
SDFNVUHOD\SDQHOV,QWHOOHFW¿[WXUHV/XPLQD5)VHQVRUV'$/,GHYLFHVDQGRWKHU
GHYLFHV)RUVSHFL¿FFDSDELOLWLHVDQGFDSDFLWLHVUHIHUWRWKHSURGXFWGDWDVKHHW
Application Notes
WARNING: TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWER at circuit breaker or fuse and test
that power is off before wiring!
1. Mount the controller using one of the mounting options.
NOTE: To remove the controller from the DIN rail, pull
down on the tension spring and lift off.
Installation
a. Mounting on DIN rail
To remove
from DIN rail
DIN rail
mounting ears
b. Mounting with mounting ears
Low Voltage Input
1. Pinout:
Pin 1 - Signal Input
Pin 2 - Common
Pin 3 - +24 VDC
(V follows LumaCAN supply)
2. Detects 0-24VDC. Can be used as contact
closure, 0-10V photocell input, or dry contact.
2. Make all low voltage connections per the wiring diagram.
&RQ¿JXUDWLRQ
1. &RQ¿JXULQJWKHFRQWUROOHU
,QRUGHUWRFRQ¿JXUHDURRPZLWKWKH*UHHQ0D['5&LWLVQHFHVVDU\WRKDYHDQL26RU$QGURLG:L)LFDSDEOHGHYLFHZLWKWKH³*UHHQ0D['5&´$SSLQVWDOOHG&RQQHFWWRWKH*UHHQ0D[
'5&&RQWUROOHUDVD:L)L$FFHVVSRLQWWKHQXVHWKH$SSWRPRYHWKURXJKWKHFRQ¿JXUDWLRQSURFHVV
• Factory Default Access Point Name: GreenMax DRC-[serial number] (The serial number is printed on the product label, use only last four character.)
• Factory Default Security: WEP Security, Password: leviton0000
2. &KDQJLQJQHWZRUNFRQ¿JXUDWLRQ
,QVLWXDWLRQVZKHUHDZLUHOHVVDFFHVVSRLQWRUSDVVZRUGLVFKDQJHGEXWWKHFRQ¿JXUDWLRQRIWKH'5&QHHGVWRUHPDLQWKHVDPHXVHWKHIROORZLQJSURFHGXUHWRUHVHWWKHQHWZRUNDQG
reconnect to the device:
3UHVVDQGKROGWKH:L)LEXWWRQIRUVHFRQGVXQWLOWKH:L)L/('ÀDVKHVJUHHQUDSLGO\
• Release the button.
7KH/('ZLOOFRQWLQXHWRÀDVKJUHHQUDSLGO\XQWLOWKHUHVHWF\FOHLVFRPSOHWH7KH/('ZLOOJRGDUNWKHQEOLQNVORZO\LQGLFDWLQJWKDWLWLVUHDG\IRUFRQQHFWLRQXVLQJLWVIDFWRU\GHIDXOW
AP name and credentials.
NOTE:WKDWHYHQWKRXJK\RXFDQFRQQHFWWRLW\RXPXVWKDYHEHHQJUDQWHGDFFHVVE\WKHVLWHDGPLQLVWUDWRUWRXVHWKHDSSIRUFRQ¿JXUDWLRQ
3. LumaCAN
• Wire per the TIA-568B standard.
The sequence of network nodes, as described in the Construction Documents,
may be critical to ensure power distribution between nodes.
All LumaCAN wire segments must be tested and validated prior to powering up of the system.
The last device in each LumaCAN run must be terminated using an RJ45 terminator plug.
Each DRC is supplied with one terminator plug preinstalled in the smart pack.
Devices on LumaCAN follow daisy chain topology. Home Run topology supported with the
use of repeaters. Max 110 nodes per segment, max 250 nodes per sub-net.
• Perform voltage drop calculations on all networks.
To next device
From previous device
DI-001-DRC00-02A© 2018 Leviton Mfg. Co., Inc.
WEB VERSION
DI-001-DRC00-02A© 2018 Leviton Mfg. Co., Inc.
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper
use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty
excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused,
opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including
merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a
particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment,
lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada Ltd to the attention of the Quality Assurance Department,
165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
5
LuminaRF/Intellect/Zigbee Switch Actions
Action Feature Result
Press/Release <1 second Status indication
2QHEOLQNQRWFRQ¿JXUHG
Three blinks - network formed
10 second press Enable/disable UDSLGÀDVKHVZKHQWULJJHUHG
20 second press
Reset device to factory
default state
5DSLGFRQWLQXRXVÀDVKLQJ
reset triggered on release
>25 second press LED goes dark
When released, no action
will be taken
6
WiFi Switch Actions
Action Feature Result
Press/Release <1 second
(also can be done with power cycle)
Re-trigger SSID broadcast
SSID broadcast times out
after 15 minutes
10 second press Enable/disable WiFi
UDSLGÀDVKHVZKHQ
triggered
20 second press
5HVHW:L)LQHWZRUNFRQ¿JXUDWLRQ
to factory default state
5DSLGFRQWLQXRXVÀDVKLQJ
reset triggered on release
>25 second press LED goes dark
When released, no action
will be taken
SPECIFICATIONS
Catalog No. DRC00
Input Voltage +12-24 VDC
Standby Power 55-28 mA
Max Input Power 435-210 mA
Connections Low Voltage
• LumaCAN: (2) RJ-45, CAT6A or better, termination via provided jumper (LCTRM-RJ)
Aux In: 3-wire 2-part terminals, 26-18AWG (solid or stranded)
Mounting Surface via provided device mounting ears, or DIN rail mount (EN 60715 TH35 DIN rail)
Operating Temperature 0°C - 40°C (32°F - 104°F)
Storage Temperature -10°C - 85°C
Radios
• Wi-Fi 802.11 a/b/g/n/ networks @2.4 GHz with WPA or WPA2 security.
• 802.15.4 @2.4 GHz, 75' range
&HUWL¿FDWLRQV
FCC Part 15 Class B
See datasheet for additional compliance
IP Rating IP30
TROUBLESHOOTING
Issue Cause Resolution
Device is ON but is not
immediately operational.
This is normal operation. The device has a
7-10 second startup time before it is operational.
Wait a short time and device will be operational.
Status LED shows failure state
(solid RED)
Processor fails or failed application (RED)
Cycle power. If a power cycle does not restore proper operation, remove LumaCAN connections and cycle power again.
Do not reconnect LumaCAN until after normal operation is restored.
If a power cycle does not restore proper operation, remove LumaCAN connections and cycle power again.
Do not reconnect LumaCAN until after normal operation is restored.
Off-failure
Remove LumaCAN wires. If device starts up, there is either an over-current or short on the LumaCAN line.
Resolve the problem and reconnect.
INDUSTRY CANADA COMPLIANCE STATEMENT:
Contains IC: 2473B-ZBMG (Zigbee)
2473B-LB1GC or 772C-LB1GC (Wi-Fi)
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any
LQWHUIHUHQFHLQFOXGLQJLQWHUIHUHQFHWKDWPD\FDXVHXQGHVLUHGRSHUDWLRQRIWKHGHYLFH,03257$17$Q\FKDQJHVRUPRGL¿FDWLRQVQRWH[SUHVVO\DSSURYHGE\WKHSDUW\UHVSRQVLEOHIRUFRPSOLDQFHFRXOGYRLGWKHXVHU¶V
authority to operate this equipment. This Class B digital apparatus complies with Canadian ICES-003.
FCC COMPLIANCE STATEMENT:
Contains FCC ID: QGH-ZBMG (Zigbee)
QGH-LB1GC or VPYLB1GC (Wi-Fi)
The enclosed device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions:
(i.) This device may not cause harmful interference (ii.) This device must accept
any interference received, including interference that may cause undesired
RSHUDWLRQ$Q\FKDQJHVRUPRGL¿FDWLRQVQRWH[SUHVVO\DSSURYHGE\/HYLWRQFRXOG
YRLGWKHXVHUVDXWKRULW\WRRSHUDWHWKLVHTXLSPHQW
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in a residential
installation. This equipment generates uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Indicator Light and Switch Functions
TRADEMARK DISCLAIMER: The Leviton word mark and logo and the Greenmax, LumaCAN, Lumina, Intellect trademarks, are the property of Leviton Manufacturing Inc., Co. WIFI, Zigbee and DALI are third-party
trademarks, the property of their respective owners. Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, such use is not meant to
LPSO\DI¿OLDWLRQVSRQVRUVKLSRUHQGRUVHPHQW
1
2
LumaCAN Indicator
Indicator Feature
Solid GREEN LumaCAN enabled
Blink GREEN 7UDI¿F
OFF LumaCAN disabled
4
WiFi Indicator
Indicator Feature
Solid GREEN :L¿HQDEOHGQRWUDI¿F
Blink GREEN 1HWZRUNWUDI¿F
OFF WiFi disabled
3
LuminaRF/Intellect/Zigbee Indicator
Indicator Feature
Solid GREEN (QDEOHGQRWUDI¿F
Blink GREEN 1HWZRUNWUDI¿F
OFF Disabled
2
3
4
5
6
1
STATUS LED
Indicator Feature
Blink Rate (# blinks
per second)
Duration Possible Causes
RED
Duplicate LumaCAN address 2 8QWLOFRQÀLFWLVUHVROYHG
Another LumaCAN device
is using the same address
UI error didn't get value set in time 8
Until 60 seconds or
UI setting restarted
Took too long to enter
manual information
Possible processor failure after startup Solid
Until watchdog circuit
is no longer tripped
Application update failure,
processor failure
GREEN
Normal operating condition 1
In boot loader 4
Until entering actual
application
Application update failure if
alternating with RED LED.
OFF LumaCAN overcurrent or failure