Generac PowerPact Series G0065611 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
001036
Installation Guidelines
60 Hz Air-Cooled Generators
7 kW PowerPact™
SAVE THIS MANUAL FOR FUTURE REFERENCE
Para español , visita: http://www.generac.com/service-support/product-support-lookup
Pour le français, visiter : http://www.generac.com/service-support/product-support-lookup
Register your Generac product at:
WWW.GENERAC.COM
1-888-GENERAC
(888-436-3722)
(000209a)
WARNING
This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.
ii Installation Guidelines for 60 Hz PowerPact™
Use this page to record important information about your generator set.
Record the information found on your unit data label on this
page. The unit has a label plate affixed to the inside partition,
above the battery access panel as shown in Figure 2-2. For
directions on how to open the top lid and remove the front
panel, see the Owner’s Manual.
When contacting an Independent Authorized Service Dealer
about parts and service, always supply the complete model
number and serial number of the unit.
Operation and Maintenance: Proper maintenance and care
of the generator ensures a minimum number of problems
and keeps operating expenses at a minimum. It is the
operator’s responsibility to perform all safety checks, to
make sure that all maintenance for safe operation is
performed promptly. Generac recommends that the
equipment be checked periodically by an Independent
Authorized Service Dealer. Normal maintenance, service
and replacement of parts are the responsibility of the owner/
operator and, as such, are not considered defects in
materials or workmanship within the terms of the warranty.
Individual operating habits and usage may contribute to the
need for additional maintenance or service.
When the generator requires servicing or repairs, Generac
recommends contacting an Independent Authorized Service
Dealer for assistance. Authorized service technicians are
factory-trained and are capable of handling all service
needs.To locate the nearest Independent Authorized Service
Dealer, please visit the dealer locator at:
www.generac.com/Service/DealerLocator/.
Model:
Serial:
Prod Date Week:
Volts:
LPV Amps:
NG Amps:
Hz:
Phase:
Controller P/N:
(000005)
WARNING
California Proposition 65. This product contains or
emits chemicals known to the state of California to
cause cancer, birth defects, and other reproductive
harm.
(000004)
WARNING
California Proposition 65. Engine exhaust and some
of its constituents are known to the state of California
to cause cancer, birth defects, and other reproductive
harm.
Table of Contents
Installation Guidelines for 60 Hz PowerPact™ i
Section 1: Safety Rules & General
Information
Introduction ..........................................................1
Read This Manual Thoroughly ....................................1
How to Obtain Service .................................................1
Safety Rules .........................................................1
General Hazards .........................................................2
Exhaust Hazards .........................................................2
Electrical Hazards .......................................................3
Fire Hazards ................................................................3
Explosion Hazards ......................................................3
General Rules .......................................................4
Before You Begin ........................................................4
NEC Requirements .....................................................4
Standards Index ..........................................................4
Section 2:Unpacking and Inspection
General .................................................................7
Required Tools .....................................................7
Unpacking ............................................................7
Parts Shipped Loose ...........................................9
Section 3: Site Selection and Preparation
Installation Guidelines for Stationary
Air-Cooled Generators ..............................................12
Annex A — Explanatory Material ..............................12
Site Preparation .................................................13
Material Sufficient for Level Installation .....................13
Transportation Recommendations ............................14
Section 4: Generator Placement
Generator Placement .........................................15
Section 5: Fuel Conversion/Gas
Connections
Fuel Requirements and Recommendations ....17
BTU Content ..............................................................17
Fuel Pressure ............................................................17
Fuel Conversion .................................................17
Fuel Consumption .............................................18
Fuel Line Sizing .................................................19
Natural Gas Pipe Sizing ............................................19
LP Vapor Pipe Sizing ................................................19
Summary ............................................................ 19
Installing and Connecting Gas Lines .............. 20
Shutoff Valve .............................................................20
Flexible Fuel Line ......................................................20
Sediment Trap ...........................................................20
Checking Gas Line Connections ..................... 21
Section 6: Electrical Connections
Control Wiring ................................................... 25
Main AC Wiring .................................................. 26
Battery Requirements ....................................... 27
Battery Installation ............................................ 27
Section 7: Control Panel/Start-up/Testing
Control Panel Interface ..................................... 29
Control Panel ..................................................... 29
Generator Set-up ............................................... 30
Generator Activation ..................................................30
Before Initial Start-up ........................................ 30
Engine Oil Recommendations ...................................30
Before starting, complete the following: ....................31
Setting The Exercise Timer .......................................31
Check Manual Transfer Switch Operation ...... 31
Electrical Checks ............................................... 32
Generator Tests Under Load ............................ 32
Checking Automatic Operation ........................ 33
Installation Summary ........................................ 33
Shutting Generator Down While Under Load . 33
Section 8: Troubleshooting
Troubleshooting Guide ..................................... 35
Section 9: Quick Reference Guide
System Diagnosis ............................................. 37
Section 10: Accessories
Section 11: Diagrams
Wiring Diagram .................................................. 43
Table of Contents
Table of Contents
ii Installation Guidelines for 60 Hz PowerPact™
This page intentionally left blank.
Section 1: Safety Rules & General Information
Installation Guidelines for 60 Hz PowerPact™ 1
Section 1: Safety Rules & General Information
Introduction
Thank you for purchasing this compact, high
performance, air-cooled, engine-driven generator. It is
designed to automatically supply electrical power to
operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal
enclosure that is intended exclusively for outdoor
installation. This generator will operate using either vapor
withdrawn liquid propane (LP) or natural gas (NG).
NOTE: When sized properly, this generator is suitable for
supplying typical residential loads such as induction
motors (sump pumps, refrigerators, air conditioners,
furnaces, etc.), electronic components (computer,
monitor, TV, etc.), lighting loads and microwaves.
Read This Manual Thoroughly
If any portion of this manual is not understood, contact
the nearest Independent Authorized Service Dealer for
starting, operating and servicing procedures.
This manual must be used in conjunction with the
appropriate Owner’s Manual.
SAVE THESE INSTRUCTIONS: The manufacturer
suggests that this manual and the rules for safe operation
be copied and posted near the unit installation site.
Safety should be stressed to all operators and potential
operators of this equipment.
Throughout this publication and on tags and decals
affixed to the generator, DANGER, WARNING, and
CAUTION blocks are used to alert personnel to special
instructions about a particular operation that may be
hazardous if performed incorrectly or carelessly. Observe
them carefully. Their definitions are as follows:
NOTE: Notes provide additional information important to
a procedure or component.
These safety warnings cannot eliminate the hazards they
indicate. Observing safety precautions and strict
compliance with the special instructions while performing
the action or service are essential to preventing accidents.
The operator is responsible for proper and safe use of
the equipment. The manufacturer strongly recommends
that if the operator is also the owner, to read the Owner’s
Manual and thoroughly understand all instructions before
using this equipment. The manufacturer also strongly
recommends instructing other users to properly start and
operate the unit. This prepares them if they need to
operate the equipment in an emergency.
How to Obtain Service
When the generator requires servicing or repairs, Generac
recommends contacting an Independent Authorized
Service Dealer (IASD) for assistance. Service technicians
are factory-trained and are capable of handling all service
needs. For assistance locating a dealer, go to
www.generac.com/Service/DealerLocator/.
When contacting an IASD about parts and service, always
supply the complete model number and serial number of
the unit as given on its data decal, which is located on the
generator. Refer to
Figure 2-2
for decal location. Record
the model number and serial numbers in the spaces
provided on the inside front cover of this manual.
Safety Rules
Study these SAFETY RULES carefully before installing,
operating or servicing this equipment. Become familiar
with this Installation Manual and with the unit. The
generator can operate safely, efficiently and reliably only
if it is properly installed, operated and maintained. Many
accidents are caused by failing to follow simple and
fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual and on tags and decals affixed to the unit are,
therefore, not all-inclusive. If using a procedure, work
method, or operating technique the manufacturer does not
specifically recommend, verify that it is safe for others.
Also, make sure the procedure, work method or operating
technique utilized does not render the generator unsafe.
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
(000001)
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
Section 1: Safety Rules & General Information
2 Installation Guidelines for 60 Hz PowerPact™
General Hazards
Inspect the generator regularly, and contact the nearest
Independent Authorized Service Dealer for parts needing
repair or replacement.
(000190)
DANGER
Loss of life. Property damage. Installation must always
comply with applicable codes, standards, laws and
regulations. Failure to do so will result in death
or serious injury.
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000191)
DANGER
(000209a)
WARNING
This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.
WARNING
This unit is not intended for use as a prime power
source. It is intended for use as an intermediate power
supply in the event of temporary power outage only.
See individual unit specifications for required
maintenance and run times pertaining to use.
(000247)
(000187)
WARNING
(000115)
WARNING
Moving Parts. Do not wear jewelry when
starting or operating this product. Wearing
jewelry while starting or operating this product
could result in death or serious injury.
(000111)
WARNING
Moving Parts. Keep clothing, hair, and
appendages away from moving parts. Failure
to do so could result in death or serious injury.
(000108)
WARNING
Hot Surfaces. When operating machine, do not
touch hot surfaces. Keep machine away from
combustibles during use. Hot surfaces
could result in severe burns or fire.
(000146)
WARNING
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
WARNING
Risk of injury. Do not operate or service this
machine if not fully alert. Fatigue can impair the
ability to service this equipment and could result
in death or serious injury.
(000215)
WARNING
Injury and equipment damage. Do not use
generator as a step. Doing so could result in falling,
damaged parts, unsafe equipment operation,
and could result in death or serious injury.
(000216)
Section 1: Safety Rules & General Information
Installation Guidelines for 60 Hz PowerPact™ 3
Exhaust Hazards
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or permit
even partial blockage of ventilation provisions, as
this can seriously affect safe operation of the
generator. The generator must be installed and
operated outdoors only.
Electrical Hazards
Fire Hazards
Asphyxiation. Running engines produce
carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER
(000178a)
Asphyxiation. Always use a battery operated carbon
monoxide alarm indoors and installed according to
the manufacturer’s instructions. Failure to do so
could result in death or serious injury.
WARNING
(000144)
DANGER
Electrocution. Contact with bare wires,
terminals, and connections while generator
is running will result in death or serious injury.
(000150)
DANGER
Electrocution. Never connect this unit to the electrical
system of any building unless a licensed electrician
has installed an approved transfer switch. Failure to
do so will result in death or serious injury.
(000131a)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator when electrical utility is the primary
power source. Failure to do so will result in death,
serious injury, and equipment damage.
(000152)
DANGER
Electrocution. Verify electrical system is
properly grounded before applying power.
Failure to do so will result in death or serious
injury.
WARNING
Fire hazard. Do not obstruct cooling and
ventilating airflow around the generator. Inadequate
ventilation could result in fire hazard, possible
equipment damage, death or serious injury.
(000217)
WARNING
Fire and explosion. Installation must comply
with all local, state, and national electrical
(000218)
building codes. Noncompliance could result in unsafe
operation, equipment damage, death or serious injury.
WARNING
Fire hazard. Use only fully-charged fire
(000219)
extinguishers rated “ABC” by the NFPA. Discharged or
improperly rated fire extinguishers will not extinguish
electrical fires in automatic standby generators.
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
Section 1: Safety Rules & General Information
4 Installation Guidelines for 60 Hz PowerPact™
Comply with regulations the Occupational Safety and
Health Administration (OSHA) has established. Also,
verify that the generator is installed in accordance with
the manufacturer’s instructions and recommendations.
Following proper installation, do nothing that might alter a
safe installation and render the unit in noncompliance
with the aforementioned codes, standards, laws and
regulations.
Explosion Hazards
General Rules
Follow all safety precautions in the Owner’s
Manual, Installation Guidelines manual and other
documents included with your equipment.
Refer to NFPA 70E for safety equipment required
when working with a live system.
Never energize a new system without opening all
disconnects and breakers.
Always consult your local code for additional
requirements for the area in which the unit is being
installed.
Improper installation can result in personal injury and
damage to the generator. It may also result in the
warranty being suspended or voided. All the instructions
listed below must be followed including location
clearances and pipe sizes.
WARNING
required safety equipment could result in
death or serious injury.
(000221)
Risk of electrocution. Refer to NFPA 70E for
safety equipment required when working with
with a live electrical system. Failure to use
(000147)
WARNING
Risk of Fire. Unit must be positioned in a
manner that prevents combustible material
accumulation underneath. Failure to do so
could result in death or serious injury.
(000192)
DANGER
(000151)
DANGER
Connection of fuel source must be done by a qualified
professional technician or contractor. Incorrect installation
of this unit will result in death, serious injury, and damage
to equipment and property damage.
(000174)
DANGER
Risk of fire. Allow fuel spills to completely dry
before starting engine. Failure to do so will
result in death or serious injury.
(000110)
WARNING
Risk of Fire. Hot surfaces could ignite
combustibles, resulting in fire. Fire could
result in death or serious injury.
(000190)
DANGER
Loss of life. Property damage. Installation must always
comply with applicable codes, standards, laws and
regulations. Failure to do so will result in death
or serious injury.
(000131a)
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator when electrical utility is the primary
power source. Failure to do so will result in death,
serious injury, and equipment damage.
(000182)
WARNING
Section 1: Safety Rules & General Information
Installation Guidelines for 60 Hz PowerPact™ 5
Before You Begin
Contact the local inspector or City Hall to be aware
of all federal, state and local codes that could
impact the installation. Secure all required permits
before starting the job.
Carefully read and follow all of the procedures and
safety precautions detailed in the installation guide.
If any portion of the installation manual, technical
manual or other factory-supplied documents is not
completely understood, contact an Independent
Authorized Service Dealer for assistance.
Fully comply with all relevant NEC, NFPA and
OSHA standards as well as all federal, state and
local building and electric codes. As with any
generator, this unit must be installed in accordance
with current NFPA 37 and NFPA 70 standards as
well as any other federal, state, and local codes for
minimum distances from other structures.
Verify the capacity of the natural gas meter or the
LP tank in regards to providing sufficient fuel for
both the generator and other household and
operating appliances.
NEC Requirements
Local code enforcement may require that Arc Fault
Circuit Interrupters (AFCIs) be incorporated into the
transfer switch distribution panel. The Transfer Switch
provided with this generator has a distribution panel that
will accept AFCIs (pre-wired transfer switches only).
Siemens Part No. Q115AF - 15A or Q120AF - 20A can
be obtained from a local electrical wholesaler and will
simply replace any of the single pole circuit breakers
supplied in the pre-wired transfer switch distribution
panel.
Standards Index
Strictly comply with all applicable national, state and local
laws, as well as codes or regulations pertaining to the
installation of this engine-generator power system. Use
the most current version of applicable codes or standards
relevant to the local jurisdiction, generator used, and
installation site.
NOTE: Not all codes apply to all products and this list is
not all-inclusive. In the absence of pertinent local laws
and standards, the following publications may be used as
a guide (these apply to localities which recognize NFPA
and IBC).
1. National Fire Protection Association (NFPA) 70:
The NATIONAL ELECTRIC CODE (NEC) *
2.
NFPA 10: Standard for Portable Fire Extinguishers *
3. NFPA 30: Flammable and Combustible Liquids
Code *
4. NFPA 37: Standard for Stationary Combustion
Engines and Gas Turbines *
5. NFPA 54: National Fuel Gas Code *
6. NFPA 58: Standard for Storage and Handling Of
Liquefied Petroleum Gases *
7. NFPA 68: Standard On Explosion Protection By
Deflagration Venting *
8. NFPA 70E: Standard For Electrical Safety In The
Workplace *
9. NFPA 110: Standard for Emergency and Standby
Power Systems *
10. NFPA 211: Standard for Chimneys, Fireplaces,
Vents, and Solid Fuel Burning Appliances *
11. NFPA 220: Standard on Types of Building
Construction *
12. NFPA 5000: Building Code *
13. International Building Code **
14. Agricultural Wiring Handbook ***
15. Article X, NATIONAL BUILDING CODE
16. ASAE EP-364.2 Installation and Maintenance of
Farm Standby Electric Power ****
This list is not all-inclusive. Check with the Authority
Having Local Jurisdiction (AHJ) for any local codes or
standards which may be applicable to your jurisdiction.
The above listed standards are available from the
following internet sources:
* www.nfpa.org
** www.iccsafe.org
*** www.rerc.org Rural Electricity Resource Council P.O.
Box 309 Wilmington, OH 45177-0309
**** www.asabe.org American Society of Agricultural &
Biological Engineers 2950 Niles Road, St. Joseph, MI
49085
(000209a)
WARNING
This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.
Section 1: Safety Rules & General Information
6 Installation Guidelines for 60 Hz PowerPact™
This page intentionally left blank.
Section 2: Unpacking and Inspection
Installation Guidelines for 60 Hz PowerPact™ 7
Section 2: Unpacking and Inspection
General
NOTE: After unpacking, carefully inspect the contents for
damage. It is advised to unpack and inspect the unit
immediately upon delivery to detect any damage that
may have occurred in transit. Any claims for shipping
damage need to be filed as soon as possible with the
freight carrier. This is especially important if the generator
will not be installed for a period of time.
This standby generator set is ready for installation
and has a weather protective enclosure that is
intended for outdoor installation only.
This UL listed standby generator set may be
packaged with an automatic transfer switch with
built-in load center. The combination transfer
switch and load center may be pre-wired with a two
foot and 30 foot conduit. The prewired switch is
rated for indoor use only. Circuit breakers for
emergency circuit connections are included.
This UL listed, 2-pole switch is rated at 30 amps,
rated at 250 volts maximum.
If any loss or damage is noted at time of delivery,
have the person(s) making the delivery note all
damage on the freight bill or affix their signature
under the consignor’s memo of loss or damage.
If a loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for
claim procedures.
“Concealed damage” is understood to mean
damage to the contents of a package that is not
evident at the time of delivery, but is discovered
later.
Required Tools
General SAE and Metric hand tools
Wrenches
Sockets
Screwdrivers
Standard electrician’s hand tools
Drill and bits for mounting and routing conduits
Pliers
Needle Nose Pliers (for fuel conversion)
4mm and 6mm Allen wrenches
3/16 Allen wrench (test port on fuel regulator)
Manometer (for fuel pressure checks)
Meter capable of measuring AC/DC Voltage and
Frequency
Unpacking
1. Remove cardboard carton.
2. If equipped, the optional transfer switch will be
visible on top of the generator.
3. Remove the wood frame. Lift the transfer switch, if
present, off the generator.
Figure 2-1. Crated Generator
4. There are four fasteners securing the top lid.
Remove the four Allen fasteners and lift the top lid
from the generator enclosure.
5. Once the lid is open, remove the front panel by lift-
ing it up and out. Also open the door covering the
customer connection area.
6. Perform a visual inspection for any hidden freight
damage.
001113
Section 2: Unpacking and Inspection
8 Installation Guidelines for 60 Hz PowerPact™
Figure 2-2. Inspect for Damage
A. Controller Lid F. Control Panel K. Air Box
B. Top Lid G. Data Label L. Spark Plug
C. Customer Connection Box H. Battery Access Panel M. Exhaust Enclosure
D. Front Panel I. Oil Drain Hose N. Alternator
E. Circuit Breaker J. Oil Fill / Dipstick O. Starter Motor
001037
E
A
D
H
G
C
F
B
K
L
M
I
J
N
O
Section 2: Unpacking and Inspection
Installation Guidelines for 60 Hz PowerPact™ 9
Parts Shipped Loose
Parts shipped loose are located in a clear plastic bag
inside the unit, in front of the engine or under the
alternator. The flex fuel line (A) is tied to either the battery
wires or the alternator can.
Flex Fuel Line (A)
Battery Terminal Cap (B)
LP Fuel Jet (C)
Fuel Jet O-ring (D)
Decal - Service Entrance (Not Shown)
Decal - Warning (Not Shown)
MLCB Terminal Caps (E)
Owner’s and Installation Manual (Not Shown)
Battery Bracket (F)
M6 x 1 16mm Thread Forming Screw (for Battery
Bracket) (G)
2 sets of Bolts, Nuts and Washers (for connecting
battery cables) (H)
Figure 2-3. Parts Shipped Loose
A
E
B
C
D
F
H
G
Section 2: Unpacking and Inspection
10 Installation Guidelines for 60 Hz PowerPact™
This page intentionally left blank.
Section 3: Site Selection and Preparation
Installation Guidelines for 60 Hz PowerPact™ 11
Section 3: Site Selection and Preparation
Site Selection
Figure 3-1. Installation Guidelines
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air is
always available (Figure 3-1). Consider these factors:
The installation of the generator must comply
strictly with NFPA 37, NFPA 54, NFPA 58 and
NFPA 70 standards.
Install the unit where air inlet and outlet openings
will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or
drifting, consider using a windbreak to protect the
unit.
Install the generator on high ground where water
levels will not rise and endanger it. It should not
operate in or be subjected to standing water.
Allow sufficient room on all sides of the generator
for maintenance and servicing. This unit must be
installed in accordance with any codes that are in
place in your country or local jurisdiction for
minimum distances from other structures.
Clearance from the ends and front of the generator
must be 3 ft (0.91 m). This includes shrubs, bushes
and trees. Clearance from the back of the
generator must be a minimum of 18 in (457 mm).
000607
No operable windows or openings in the wall permitted
within 5 feet (1.52 m) from any point of the generator.
Top of Generator
3 ft (0.91 m)
5 ft
(1.52 m)
Existing Wall
18 in (457 mm)
Minimum Distance
5 ft (1.52 m)
Minimum Distance
5 ft (1.52 m)
Minimum Distance
These guidelines are based upon fire testing of
the generator enclosure and the manufacturer’s
requirement for air flow for proper operation.
Local codes may be different and more restrictive
than what is described here.
Allow sufficient room on all sides of the
generator for maintenance and servicing.
Clearance from the ends and front of the
generator must be 3 ft (0.91 m). This includes
shrubs, bushes and trees. Clearance from the
back of the generator must be a minimum of 18
in (457 mm). Clearance at the top should be a
minimum of 5 ft (1.52 m) from any structure,
overhang or projections from the wall.
DO NOT install under wooden decks or
structures unless there is at least 5 ft (1.52 m)
of clearance above the generator.
Clearance from operable windows,
doors or any openings in the wall.
3 ft (0.91 m)
3 ft (0.91 m)
NOTE: Removable fence panels for servicing
cannot be placed less than 18 in (457 mm) in
front of the generator.
5 ft
(1.52 m)
Section 3: Site Selection and Preparation
12 Installation Guidelines for 60 Hz PowerPact™
Clearance at the top should be a minimum of 5 ft
(1.52 m) from any structure, overhang or
projections from the wall.
DO NOT install under wooden decks or structures
unless there is at least 5 ft (1.52 m) of clearance
above the generator.
Install the unit where rain gutter downspouts, roof
run-off, landscape irrigation, water sprinklers or
sump pump discharge do not flood the unit or
spray the enclosure, including any air inlet or outlet
openings.
Install the unit where services will not be affected
or obstructed, including concealed, underground or
covered services such as electrical, fuel, phone, air
conditioning or irrigation. This could affect
Warranty Coverage.
Where strong prevailing winds blow from one
direction, face the generator air inlet openings to
the prevailing winds.
Install the generator as close as possible to the fuel
supply to reduce the length of piping. REMEMBER
THAT LAWS OR CODES MAY REGULATE THE
DISTANCE AND LOCATION. In the absence of
local codes regarding placement or clearance, we
recommend following these guidelines.
Install the generator as close as possible to the
transfer switch. REMEMBER THAT LAWS OR
CODES MAY REGULATE THE DISTANCE AND
LOCATION.
The generator must be installed on a level surface.
The generator must be level within 0.5 in (13 mm)
all around.
The generator is typically placed on pea gravel,
crushed stone or a concrete pad. Check local
codes to see what type is required. If a concrete
pad is required, all applicable codes should be
followed.
Installation Guidelines for Stationary Air-Cooled
Generators
The National Fire Protection Association has a standard
for the installation and use of stationary combustion
engines. That standard is NFPA 37. Its requirements limit
the spacing of an enclosed generator set from a structure
or wall (Figure 3-1).
NFPA 37, Section 4.1.4, Engines Located Outdoors:
Engines, and their weatherproof housings if provided,
that are installed outdoors shall be located at least 5 ft
(1.52 m) from openings in walls and at least 5 ft (1.52 m)
from structures having combustible walls. A minimum
separation shall not be required where the following
conditions exist:
1. The adjacent wall of the structure has a fire
resistance rating of at least 1 hour.
2. The weatherproof enclosure is constructed of
noncombustible materials and it has been
demonstrated that a fire within the enclosure will
not ignite combustible materials outside the
enclosure.
Annex A — Explanatory Material
A4.1.4 (2) Means of demonstrating compliance are by
means of full scale fire test or by calculation procedures.
Because of the limited spaces that are frequently
available for installation, it has become apparent that
exception (2) would be beneficial for many residential
and commercial installations. With that in mind, the
manufacturer contracted with an independent testing
laboratory to run full scale fire tests to assure that the
enclosure will not ignite combustible materials outside
the enclosure.
NOTE: Southwest Research Institute testing
approves 18 in (457 mm) installation minimum from
structure. Southwest Research is a nationally
recognized third party testing and listing agency.
The criteria was to determine the worst case fire scenario
within the generator and to determine the ignitability of
items outside the engine enclosure at various distances.
The enclosure is constructed of non-combustible
materials, and the results and conclusions from the
independent testing lab indicated that any fire within the
generator enclosure would not pose any ignition risk to
nearby combustibles or structures, with or without fire
service personnel response.
Figure 3-2. Southwest Research Institute Decal
The Southwest Research Institute Decal is located inside
the generator, next to the generator’s data decal.
http://www.swri.org/4org/d01/fire/listlab/listprod/director.htm
000609
Section 3: Site Selection and Preparation
Installation Guidelines for 60 Hz PowerPact™ 13
Based on this testing and the requirements of NFPA 37,
Sec 4.1.4, the guidelines for installation of the generators
listed above are changed to 18 in (457 mm) from the
back side of the generator to a stationary wall or building.
For adequate maintenance and airflow clearance, the
area above the generator should be at least 5 ft (1.52 m)
with a minimum of 3 ft (0.91 m) at the front and ends of
the enclosure. This would include trees, shrubs and
bushes. Vegetation not in compliance with these
clearance parameters could obstruct air flow. In addition,
exhaust fumes from the generator could inhibit plant
growth. See Figure 3-1 and the installation drawing
within the Owner’s Manual for details.
If the generator is not set to the OFF mode, it can crank
and start as soon as the battery cables are connected. If
the utility power supply is not turned off, sparking can
occur at the battery posts and cause an explosion.
Site Preparation
Locate the mounting area as close as possible to
the transfer switch and fuel supply.
Leave adequate room around the area for service
access (check local code), and place high enough
to keep rising water from reaching the generator.
Choose an open space that will provide adequate
and unobstructed airflow.
Place the unit so air vents won’t become clogged
with leaves, grass, snow or debris. Make sure
exhaust fumes will not enter the building through
eaves, windows, ventilation fans or other air
intakes (see Site Selection).
Select the type of base, such as but not limited to
gravel or concrete, as desired or as required by
local laws or codes. Verify your local requirements
before selecting.
Material Sufficient for Level Installation
Dig a rectangular area approximately 5 in (127
mm) deep [A] and about 6 in (152 mm) longer and
wider [B] than the footprint of the generator. Fill
with 4 in (102 mm) of pea gravel [C], crushed stone
or any other non-combustible material sufficient for
level installation. Compact and level the material. A
concrete pad can be poured if desired or required.
The pad should be 4–5 in (102–127 mm) thick and
extend 6 in (152 mm) beyond the outside of the
generator in all directions.
Figure 3-3. Compacted Gravel Pad
NOTE: If a concrete pad is required, follow all applicable
Federal, State or local codes.
Figure 3-4. Poured or Pre-formed Concrete Pad
Asphyxiation. Running engines produce
carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000191)
DANGER
001184
A
B
C
000611a
Section 3: Site Selection and Preparation
14 Installation Guidelines for 60 Hz PowerPact™
Transportation Recommendations
1. Use a two wheeled hand cart or metal rails to carry
the generator (including the wooden pallet) to the
installation site. Place cardboard between the hand
cart and the generator to prevent any damage or
scratches to the generator.
2. Remove bolts from the pallet brackets (A).
Figure 3-5. Generator on Pallet
3. Lift the generator from the wooden pallet.
NOTE: Be extremely careful when removing the
generator from the pallet. Dragging it off the pallet WILL
damage the base!
4. Unhook and remove the brackets from the
generator.
A
Section 4: Generator Placement
Installation Guidelines for 60 Hz PowerPact™ 15
Section 4: Generator Placement
Generator Placement
This generator comes with two composite pads. These
composite pads elevate the generator and help prevent
water from pooling around the bottom of the generator
(Figure 4-1). Therefore, they should not be removed
from the generator under ANY circumstances.
The generator with composite pads can be placed on 4 in
(102 mm) of pea gravel that is compacted or on a
concrete pad. Check local codes to see what type of site
base is required. If a concrete pad is required, all federal,
state and local codes should be followed. Place the
generator and position correctly as per the dimensional
information given in Site Preparation .
NOTE: Generator must be level within 0.5 in (13 mm).
Figure 4-1. Composite Pads
NOTE: When mounting the generator to concrete, there
are four mounting holes inside the generator enclosure
for securing the generator. DO NOT remove the
composite pads while mounting the generator to
concrete. See Figure 4-2.
The use of 5/16” (or M8) lag bolts is recommended (not
supplied) for securing the generator to a concrete pad.
Figure 4-2. Mounting Hole Location
NOTE: The top of the generator carton has a template
that can be used to mark the concrete pad to pre-drill the
mounting holes.
001119
001122
Section 4: Generator Placement
16 Installation Guidelines for 60 Hz PowerPact™
This page intentionally left blank.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156

Generac PowerPact Series G0065611 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur