3.3 MOUNTING THE INVERTER/CHARGER
Before connecting any wires to the Inverter/Charger the unit must be mounted securely in a location which meets the
requirements detailed in section 3.2.
The GP-IC-2000 weighs: 39 lbs (17.6kg). The GP-IC-3000 weighs: 52lbs (23.6kg). Take the necessary precautions required whilst lifting,
moving and installing the unit. It is recommended to use two people whilst mounting the unit. All mounting surfaces and hardware
must be capable of supporting at least twice the weight of the Inverter/Charger.
The Inverter/Charger base can reach high temperatures and should be mounted on a noncombustible surface.
IC Series Inverter Chargers must be mounted in the positions highlighted below to meet regulatory requirements.
After determining the mounting position use the dimensions on page 10 or use the base of the Inverter/Charger to mark the mounting
screw locations. Mount the unit with the appropriate mounting hardware (not supplied). Ensure the unit is fastened securely.
(304mm)
12”
(51mm)
2”
(124mm)
4.9”
(124mm)
4.9”
(346mm)
13.6”
(7mm) (13mm)
.28”
(321mm)
12.6”
.51”
(205mm)
8.1”
(349mm)
13.7”
(378mm)
14.9”
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
BATTERY
TEMP
REMOTE
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
Temperature Sensor
®
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120 V
AC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120 V
AC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120 V
AC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
WALL MOUNT, DC TERMINALS RIGHTHORIZONTAL MOUNT, BASE UPHORIZONTAL MOUNT, BASE DOWN
(304mm)
12”
(51mm)
2”
(124mm)
4.9” (124mm)
4.9”
(346mm)
13.6”
(7mm) (13mm)
.28”
(321mm)
12.6”
.51”
(205mm)
8.1”
(349mm)
13.7”
(378mm)
14.9”
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
BATTERY
TEMP
REMOTE
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
Temperature Sensor
®
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds)● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
3.3.1 MOUNTING THE DRIP SHIELD
The IC Series Inverter/Charger is Marine UL listed. In order to properly mount the Inverter/Charger in a marine application, you
must use a drip shield. Please follow the installation instructions below.
Step 1
Use the screws to mount the Drip Shield on the wall.
Step 1
Use the screws to mount the product on the wall, and the product mounng required as follow:
a. The mounng height from the ground to product requires at least 70 cm.
b. The bulkhead size requires at least longer 20cm than the product each side.
Wall Mount
Ceiling Mount
Step 2
Use the screws to mount the product under the Drip Shield.
Please make sure the height from the ground to product
at least 70 cm.
Drip shield
28”
Bulkheads
28”
8”
8”
8”
8”
Step 1
Use the screws to mount the Drip Shield on the wall.
Step 1
Use the screws to mount the product on the wall, and the product mounng required as follow:
a. The mounng height from the ground to product requires at least 70 cm.
b. The bulkhead size requires at least longer 20cm than the product each side.
Wall Mount
Ceiling Mount
Step 2
Use the screws to mount the product under the Drip Shield.
Please make sure the height from the ground to product
at least 70 cm.
Drip shield
Step 1
Use the screws to mount the Drip Shield on the wall.
Step 1
Use the screws to mount the product on the wall, and the product mounng required as follow:
a. The mounng height from the ground to product requires at least 70 cm.
b. The bulkhead size requires at least longer 20cm than the product each side.
Wall Mount
Ceiling Mount
Step 2
Use the screws to mount the product under the Drip Shield.
Please make sure the height from the ground to product
at least 70 cm.
Drip shield
28”
Bulkheads
28”
1. Use the
screws to
mount the
drip shield
1. Use the screws
to mount the
drip shield and
the Inverter/
Charger
together to the
ceiling.
2. Use the screws to
mount the GP-
IC-2000 under the
drip shield. Please
make sure the
height from the
ground to the GP-
IC-2000 is at least
2. Ensure the
Inverter/Charger is
centered and that
there is at least
8” (20cm)of space
Step 1
Use the screws to mount the Drip Shield on the wall.
Step 1
Use the screws to mount the product on the wall, and the product mounng required as follow:
a. The mounng height from the ground to product requires at least 70 cm.
b. The bulkhead size requires at least longer 20cm than the product each side.
Wall Mount
Ceiling Mount
Step 2
Use the screws to mount the product under the Drip Shield.
Please make sure the height from the ground to product
at least 70 cm.
Drip shield
28”
(304mm)
12”
(51mm)
2”
(124mm)
4.9” (124mm)
4.9”
(346mm)
13.6”
(7mm) (13mm)
.28”
(321mm)
12.6”
.51”
(205mm)
8.1”
(349mm)
13.7”
(378mm)
14.9”
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
BATTERY
TEMP
REMOTE
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
Temperature Sensor
®
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds)● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
(304mm)
12”
(51mm)
2”
(124mm)
4.9” (124mm)
4.9”
(346mm)
13.6”
(7mm) (13mm)
.28”
(321mm)
12.6”
.51”
(205mm)
8.1”
(349mm)
13.7”
(378mm)
14.9”
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
BATTERY
TEMP
REMOTE
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG -
POS +
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
Temperature Sensor
®
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds)● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
®MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA ● DC Input: 12.6V
● Maximum Continuous Input Current: 267ADC ● Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
● Maximum Continuous Output Current: 16.7AAC ● Surge Power: 3400 Real Watts (5 seconds) ● THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100
[email protected] VDC nominal with 120
VAC / 60Hz (15 AAC) input
●Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC●
Input Voltage: 120 VAC●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000VA
● DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz●
Generator Input Frequency Range: 50 to 70Hz●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER E483757
INSTALLATION