Eaton Crouse-Hinds GHG 592 Mode d'emploi

Taper
Mode d'emploi
Explosionsgeschützte Steckvorrichtungen,
16A 7-polig, GHG 511 .7.. / GHG 592,
10A 21-polig, GHG 511 .9../ GHG 591
Explosion-protected plugs and sockets,
16A 7-pole, GHG 511 .7.. / GHG 592,
10A 21-pole, GHG 511 .9../ GHG 591
Fiches et prises
à 16A 7 pôles, GHG 511 .7../ GHG 592,
à 10A 21 pôles, GHG 511 .9.. / GHG 591,
pour atmosphères explosives
Betriebsanleitung
Operating instructions
Mode d’emploi
CROUSE-HI NDS
SERIES
GHG 510 7006 P0001 D/GB/F (i)
2
Explosionsgeschützte
Steckvorrichtungen,
7-polig GHG 511 .7.. / 592 und
21-polig GHG 511 .9.. / 591
Explosion-protected
plugs and sockets,
7-pole GHG 511 .7.. / 592 and
21-pole GHG 511 .9.. / 591
Fiches et prises à 7-pôles
GHG 511 .7.. / GHG 592 et à
21 pôles GHG 511 . 9.. / GHG 591,
pour atmosphères explosives
Inhalt
1 Technische Daten .................................... 3
2 Sicherheitshinweise ................................ 3
3 Normenkonformität ................................. 5
4 Verwendungsbereich .............................. 5
5 Verwendung / Eigenschaften .................. 5
6 Installation ............................................... 5
6.1 Montage .................................................. 5
6.1.1 Wandsteckdose ...................................... 5
6.1.2 Buchsen und Steckerstifte ...................... 5
6.2 Öffnen des Gerätes/ .................................
Elektrischer Anschluss ............................ 6
6.2.1 7-polige Stecker (siehe S.18; B.5 u. B.6) . 6
6.2.2 21-polige Stecker ..................................... 6
6.2.3 Anschluss der Steckerstifte und
der Buchsen ............................................ 6
6.3 Kabel-und Leitungseinführungen (KLE); ...
Verschlussstopfen ................................... 6
6.3.1 Steckdosen ............................................. 6
6.3.2 Stecker / Kupplung .................................. 6
6.4 Schließen des Gerätes ............................ 7
6.5 Inbetriebnahme ....................................... 7
7 Instandhaltung / Wartung ........................ 7
8 Reparatur / Instandsetzung / ....................
Änderungen ............................................ 7
9 Entsorgung / ..............................................
Wiederverwertung .................................. 7
Konformitätserklärung separat beigelegt.
Contents
1 Technical data .......................................... 8
2 Safety instructions .................................. 8
3 Conformity with standards .....................10
4 Field of application .................................10
5 Use / Properties .....................................10
6 Installation ..............................................10
6.1 Mounting ................................................ 10
6.1.1 Wall socket ............................................. 10
6.1.2 Socket contact pins and plug pins .........10
6.2 Opening the device/
Electrical connection ..............................11
6.2.1 Plug, 7-pole ............................................11
6.2.2 Plug, 21-pole ..........................................11
6.2.3 Connection of plug pins and
socket contact pins ................................11
6.3 Cable entries (KLE);
blanking plugs ........................................11
6.3.1 Socket ....................................................11
6.3.2 Plug / coupler .........................................11
6.4 Closing the device ..................................12
6.5 Putting into operation ............................. 12
7 Maintenance / Servicing ......................... 12
8 Repairs / Modifications ..........................12
9 Disposal / Recycling ...............................12
Declaration of conformity, enclosed separately.
Contenu
1 Caractéristiques techniques ..................13
2 Consignes de sécurité ...........................13
3 Conformité aux normes .........................15
4 Domaine d’utilisation .............................15
5 Utilisation / Propriétés ............................15
6 Installation ..............................................15
6.1 Montage .................................................15
6.1.1 Prises murale .........................................15
6.1.2 Douilles et chevilles d’enfichage ............15
6.2 Ouverture du dispositif /
Raccordement électrique .......................16
6.2.1 Fiche à 7 pôles .......................................16
6.2.2 Fiche à 21 pôles .....................................16
6.2.3 Connexion des douilles et des chevilles
d’enfichage ............................................16
6.3 Entrées de câble (KLE);
bouchons de fermeture .........................16
6.3.1 Prise .......................................................16
6.3.2 Fiche / Prolongateur ...............................16
6.4 Fermeture du dispositif ..........................17
6.5 Mise en service ...................................... 17
7 Maintien / Entretien ...............................17
8 Réparation / Remise en état ...................17
9 Évacuation des déchets /
Recyclage ...............................................17
Déclaration de conformité, jointe séparément.
3
D
Explosionsgeschützte Steckvorrichtungen,
7-polig GHG 511 .7.. / 592 und 21-polig GHG 511 .9.. / 591
1 Technische Daten
1.1 Steckvorrichtung 7-polig
EG-Baumusterprüfbescheinigung PTB 00 ATEX 1109
Gerätekennzeichnung nach 2014/34/EU
und der Normenreihe EN 60079:
II 2 G Ex e IIC T5 / T6
II 2 G Ex de [ia] IIC T5 / T6
Bemessungsspannung bis 500 V, 50/60 Hz
Max. Bemessungsstrom 16 A (T6) / 20 A (T5)
Max. Vorsicherung ohne therm. Schutz mit therm. Schutz
16 A / 20 A 25 A gG
Schaltvermögen AC 3 400 V /16 A
Schaltvermögen AC 15 400 V / 6 A 230 V / 8 A
Schaltvermögen DC 13 24 V / 6 A 230 V / 0,4 A
Zulässige Umgebungstemperatur -20° C bis +40° C (Listenausführung)
(Abweichende Temperaturen sind bei Sonderversionen möglich)
Zul. Lagertemperatur in Originalverpackung -20° C bis +40° C
Schutzart nach EN/IEC 60529 IP 66 (Listenausführung)
bei geschlossenem und gesichertem Klappdeckel sowie ordnungsgemäß gesteckten Kombinationen
Schutzklasse nach EN/IEC 61140 I - mit Metallflansch oder Metall KLEs
II - wird von den Geräten erfüllt
Leitungseinführung (Listenausführung)
Wandsteckdose (GHG 511 47) 2 x M40 1x M40 + 1x Schraubverschluss
geeignete Leitungen und Prüfdrehmomente
der Druckschraube
Ø Nm
Dicht
ung 1+2
1 2
3
min.
max.
(1)
19,0
22,0
3,3
5,5
Dichtung 1
1 2
3
min.
max.
(1)
22,0
28,0
3,3
6,7
Prüfdrehmomente Einschraubgewinde 7,5 Nm
(1)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann
der Klemmbereich v
ariieren. Bitte verwenden Sie im Zwischenbereich eine geeignete Kombination aus
Dichtungen, so dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
Stecker (GHG 592 2) Ø 9 - 17 mm
Anschlussklemme Querschnitt
Abisolierlänge der Adern
Schaltersockel der Wandsteckdose 2 x 1,5 - 4,0 mm² 6 mm
Stift für Stecker 1 x 1,0 - 2,5 mm² * 13 mm
* Quetsch- oder Lötverbindung
Prüfdrehmomente
Deckel- und Steckerschrauben 2,5 Nm
Anschlussklemmen 2,5 Nm
Gewicht (Listenausführung) Wandsteckdose
ca. 2,20 kg
Steck
er
ca. 0,30 kg
2 Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und geeignet
qualifizierte, unterwiesene Personen
gemäß den nationalen Rechtsvorschriften,
einschließlich der einschlägigen Normen für
elektrische Geräte in explosionsgefährdeten
Bereichen (EN/IEC 60079-14).
Die Vielpoligen Steckvorrichtungen 7-polig
(GHG 511 .7. / GHG 592)
und 21-polig (GHG 511 .9 /
GHG 591) sind nicht für Zone 0 geeignet.
Die auf den Geräten angegebene Tempera-
turklasse und Zündschutzart ist zu beachten.
Für die Einhaltung der auf dem Typschild
des Betriebsmittels angegebenen Tempera-
turklasse ist die zulässige Umgebungstem-
peratur, der Anschlussquerschnitt, sowie die,
maßgeblich durch die Verlustleistung
bedingte Eigenerwärmung des Betriebs-
mittels zu beachten (Prüfkriterium für
die Eigenerwärmung ist eine Überlastung
um 10%).
Umbauten oder Veränderungen an den
Steckvorrichtungen sind nicht gestattet.
Sie sind bestimmungsgemäß in unbeschä-
digtem und einwandfreiem Zustand zu
betreiben.
Vor Inbetriebnahme müssen die Steckvor-
richtungen entsprechend der im Abschnitt 6
genannten Anweisung geprüft werden.
Die Steckvorrichtungen nur mit den
zugehörigen unbeschädigten COOPER
CROUSE-HINDS Steckern betreiben.
Die 7-polige Wandsteckdose ist mit einem
Verriegelungsschalter gesichert und deshalb
ohne gesteckten Stecker nicht einschaltbar.
Der Stecker der 21-poligen Steckvorrichtung
darf nicht unter Spannung in die 21-poligen
Steckdosen und der Kupplung gesteckt oder aus
diesen gezogen werden (siehe auch Punkt 5).
Alle Fremdkörper müssen vor der ersten
Inbetriebnahme aus den Geräten entfernt
werden.
Beachten Sie die nationalen Sicherheits-
und Unfallverhütungsvorschriften und die
nachfolgenden Sicherheitshinweise in
dieser Betriebsanleitung, die wie dieser
Text in Kursivschrift gefasst sind!
Maßangaben in mm
X = Befestigungsmaße
Wandsteckdose 7polig
Anschlussbild Steckvorrichtung 7polig
Stecker 7polig
Codierung 7polig
6h 5h 7h
maisgelb braun orange
4
D
Explosionsgeschützte Steckvorrichtungen,
7-polig GHG 511 .7.. / 592 und 21-polig GHG 511 .9.. / 591
1.2 Steckvorrichtung 21-polig
EG-Baumusterprüfbescheinigung
Wandsteckdose, Kupplung und Stecker PTB 00 ATEX 1109
Flanschsteckdose PTB 00 ATEX 1108 U
Gerätekennzeichnung nach 2014/34/EU
und der Normenreihe EN 60079:
II 2 G Ex e IIC T5 / T6
II 2 G Ex e [ia] IIC T5 / T6
Bemessungsspannung bis 250 V, 50/60 Hz (max. bis 400 Hz)
Max. Bemessungsstrom 10 A
Max. Vorsicherung ohne therm. Schutz mit therm. Schutz
16 A 25 A gG
Zulässige Umgebungstemperatur -20° C bis +40° C (Listenausführung)
(Abweichende Temperaturen sind bei Sonderversionen möglich)
Zul. Lagertemperatur in Originalverpackung -20° C bis +40° C
Schutzart nach EN/IEC 60529 IP 65 (Listenausführung)
bei geschlossenem und gesichertem Klappdeckel sowie ordnungsgemäß gesteckten Kombinationen
Schutzklasse nach EN/IEC 61140 I - mit Metallflansch oder Metall KLEs
II - wird von den Geräten erfüllt
Leitungseinführung (Listenausführung)
Wandsteckdose 1 x M40
geeignete Leitungen und Prüfdrehmomente
der Druckschraube
Ø Nm
Dicht
ung 1+2
1 2
3
min.
max.
(1)
19,0
22,0
3,3
5,5
Dichtung 1
1 2
3
min.
max.
(1)
22,0
28,0
3,3
6,7
Prüfdrehmomente Einschraubgewinde 7,5 Nm
(1)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann
der Klemmbereich v
ariieren. Bitte verwenden Sie im Zwischenbereich eine geeignete Kombination aus
Dichtungen, so dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
Stecker Ø 19 - 28 mm
Kupplung Ø 9 - 27 mm
Anschlussklemme Querschnitt
Abisolierlänge der Adern
Buchse für Steckdosen und Kupplung 1 x 1,0 - 2,5 mm² * 13 mm
Stift für Stecker 1 x 1,0 - 2,5 mm² * 13 mm
* Quetsch- oder Lötverbindung
Prüfdrehmomente
Deckel- und Steckerschrauben 2,5 Nm
Gewicht (Listenausführung) (Listenausführung)
Wandsteckdose GHG 511 47 ca. 1,79 kg
Stecker GHG 591 2 ca. 0,70 kg
Flanschsteckdose GHG 591 4 ca. 0,43 kg
Kupplung GHG 591 3 ca. 0,77 kg
1.3 Eigensichere Schalterstromkreise
Sicherheitstechnische Maximalspannung U
m
690 V eff
Galvanisch sicher getrennt von allen
anderenStromkreisen und von Erde
Maßangaben in mm
X = Befestigungsmaße
Wandsteckdose 21polig
Stecker 21polig
Kupplung 21polig
Bohrbid für Flanschsteckdose 21polig
Codierung 21polig
6h 5h 7h
maisgelb braun orange
5
3 Normenkonformität
Das Betriebsmittel entspricht den aufgeführten
Normen, in der separat beigelegten Konformi-
tätserklärung.
Verweise auf Normen und Richtlinien in dieser
Betriebsanleitung beziehen sich immer auf die
aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4 Verwendungsbereich
Die Mehrfach-Steckvorrichtungen sind zum
Einsatz in explosionsgefährdeten Bereichen der
Zonen 1, 2 gemäß EN/IEC 60079-10-1
geeignet!
Die eingesetzten Gehäusematerialien ein-
schließlich der außenliegenden Metallteile
bestehen aus hochwertigen Werkstoffen, die
einen anwendungsgerechten Korrosionsschutz
und Chemikalienresistenz in "normaler
Industrieatmosphäre" gewährleisten:
– schlagfestes Polyamid
– glasfaserverstärktes Polyester
– Edelstahl AISI 316 L
Edelstahl A4-70.
Bei einem Einsatz in extrem aggressiver
Atmosphäre, können Sie zusätzliche Informatio-
nen über die Chemikalienbeständigkeit der
eingesetzten Kunststoffe, bei Ihrer zuständigen
Cooper Crouse-Hinds Niederlassung erfragen.
5 Verwendung / Eigenschaften
Die mehrpoligen Steckvorrichtungen dienen
zur Stromversorgung von standortvariablen
Vorortsteuerungen, elektrischen Anlagen sowie
von beweglichen Maschinen und Antrieben in
explosionsgefährdeten Bereichen.
Die für die "Eigensicherheit" maßgebenden
elektrischen Grenzwerte sind zu beachten.
Das am Stecker angeschlossene Betriebsmit-
tel muss für die anliegende Netzspannung
geeignet sein.
5.1 Die 7-polige Steckvorrichtung ist mit einem
Verriegelungsschalter ausgestattet und ist bis
max. 500V 16 A / 20 A einsetzbar.
Das Stecken und Ziehen des Steckers in bzw.
aus der Steckdose ist nur im ausgeschalteten
Zustand möglich.
Der Schalter Pos. 4, kann nur eingeschaltet
werden, wenn der Stecker Pos. 1 korrekt in
die Steckdose Pos. 2, eingesteckt ist.
(siehe S.18; B.1 und B 2)
Nach dem Einschalten des Verriegelungsschal-
ters Pos. 4, ist ein Ziehen des Steckers nicht
möglich (siehe S.18; B.2).
Um die Schutzart gem. Typenschild auch mit
gestecktem Stecker zu erreichen, muss der
Bajonettring Pos. 3, des Steckers Pos. 1, bis
zum Anschlag auf die Steckdose Pos. 2,
gedreht werden (siehe S.18; B.1 und B 2).
6 Installation
Für das Errichten / Betreiben sind die relevanten
nationalen Vorschriften (z.B. Betr.Si.V, Geräte-
sicherheitsgesetz in Deutschland) sowie die
allgemein anerkannten Regeln der Technik
maßgebend (EN/IEC 60079-14).
6.1 Montage
6.1.1 Wandsteckdose
Die Montage der Wandsteckdosen kann ohne
Öffnen des Gehäuses erfolgen.
Die Wandsteckdosen dürfen bei der Direkt-
montage an der Wand nur an den vorgesehe-
nen Befestigungspunkten eben aufliegen.
Die gewählte Schraube muss der Befestigungs-
öffnung angepasst sein (siehe Maßbild) und
sie darf die Öffnung nicht beschädigen
(z.B. Verwendung einer Unterlegscheibe).
Die Wandsteckdosen sind mit mindestens
2 Schrauben diagonal zu befestigen.
Die Wand- und Flanschsteckdosen sind so zu
montieren, dass die Stecköffnung nicht nach
oben zeigt (Bild 2).
Die Wandsteckdosen sind zur Schnappbefesti-
gung auf dem Cooper Crouse-Hinds - Geräte-
halter Größe 5 durch seitliches Einschieben
in die Führungsnut von der linken Seite des
Gerätehalters geeignet.
Die betreffende Montageanleitung ist zu
beachten.
Befestigungspunkt A
Wandsteckdose 7- und
21-polig
A A
A A
6.1.2 Buchsen und Steckerstifte
Die Montage der Steckbuchsen der 21-poligen
Wandsteckdose und der Steckerstifte der
7- und 21-poligen Stecker werden unter
Punkt 6.2 beschrieben.
Zum Ausschalten und Ziehen des Steckers ist in
umgekehrter Reihenfolge vorzugehen. Nach
dem Trennen des Steckers von der Steckdose
ist die Steckdose mit dem Klappdeckel Pos. 5,
zu schließen und mit dem Bajonettbügel Pos. 6,
zu sichern (siehe S.18; B. 2 und B. 3).
Nach einem Kurzschluss im Stromkreis ist
die Funktionsfähigkeit der Steckvorrichtung
und der Stecker zu überprüfen.
Da die Schaltkontakte wegen der druck-
festen Kapselung nicht mehr prüfbar sind,
muss nach mehrmaligen Kurzschlüssen
der komplette Schalteinsatz (Verriegelungs-
schalter) ausgetauscht werden.
5.2 Die 21-polige Steckvorrichtung hat keinen
Verriegelungsschalter und darf bis maximal
250V, 10A eingesetzt werden.
Bei der Benutzung (Stecken, Trennen, etc.)
dieser Steckvorrichtung ist auf folgendes zu
achten: (siehe S.18; B. 3)
Nach dem Einstecken des Steckers Pos. 1, ist
der Bajonettring Pos. 3, des Steckers auf der
Steckdose Pos. 2, zu verriegeln.
Danach wird die Einrastnase Pos. 8, am
Klappdeckel Pos. 5, der Dose in die dafür
vorgesehene Vertiefung mit Einrasthaken
Pos. 7, des Steckers eingerastet.
Zum Entriegeln muss der Einrasthaken des
Steckers mit einem spitzen Werkzeug
(z.B: Schraubendreher Größe 2) entriegelt
werden.
Dann kann der Bajonettring Pos. 3, gelöst
und der Stecker aus der Steck- bzw.
Flanschsteckdose oder der Kupplung
herausgezogen werden.
Nach dem Trennen des Steckers von der
Steckdose ist die Wand-, Flanschsteckdose
und Kupplung mit dem Klappdeckel Pos. 5,
zu schließen und mit dem Bajonettbügel
Pos. 6, zu sichern. (siehe S.18; B.3)
Achtung: Nur im spannungslosen Zustand
Stecker stecken und ziehen!
Die Verantwortung hinsichtlich bestim-
mungsgemäßer Verwendung dieser
Steckvorrichtungen unter Bezugnahme der
in dieser Anleitung vorhandenen Rahmen-
bedingungen (siehe technische Daten) liegt
allein beim Betreiber.
Die Stecker sind im Freien mit der Stecker-
öffnung (Stiftseite) nach unten aufzubewahren
bzw. mit optional erhältlichen Steckerschutz-
kappen (siehe Hauptkatalog) zu verschließen.
Angaben aus Punkt 3 und 4 sind bei der
Verwendung zu berücksichtigen.
Andere als die beschriebenen Anwendungen
sind ohne schriftliche Erklärung der
Fa. COOPER CROUSE-HINDS nicht zulässig.
Beim Betrieb sind die in der Betriebsanlei-
tung unter Punkt 7 genannten Anweisungen
zu beachten.
D
Explosionsgeschützte Steckvorrichtungen,
7-polig GHG 511 .7.. / 592 und 21-polig GHG 511 .9.. / 591
6
D
Explosionsgeschützte Steckvorrichtungen,
7-polig GHG 511 .7.. / 592 und 21-polig GHG 511 .9.. / 591
6.3 Kabel-und Leitungseinführungen
(KLE); Verschlussstopfen
6.3.1 Steckdosen
Es dürfen generell nur bescheinigte KLE
und Verschlussstopfen verwendet werden.
Für bewegliche Leitungen sind Trompeten-
verschraubungen oder andere geeignete
Einführungen mit zusätzlicher Zugent-
lastung zu verwenden.
Beim Einsatz von KLE mit einer niedrigeren als
der für das Gerät zutreffenden IP-Schutzart,
(siehe Seite 3, technische Daten) wird die
IP-Schutzart des gesamten Gerätes reduziert.
Die für die eingesetzten KLE maßgebenden
Montagerichtlinien sind zu beachten.
Um die Mindestschutzart herzustellen, sind
nicht benutzte Einführungsöffnungen mit
einem bescheinigten Verschlussstopfen zu
verschließen.
Es ist darauf zu achten, dass bei der Installation
der KLE die für den Leitungsdurchmesser
geeigneten Dichtungseinsätze verwendet
werden. Bei ausschneidbaren Dichtungs-
einsätzen ist sicherzustellen,dass der Einsatz
ordnungsgemäß dem Leitungsdurchmesser
angepasst wird.
Eigensichere Stromkreise sind über die farblich
(hellblau) gekennzeichneten KLE einzuführen.
Zur Sicherstellung der erforderlichen Mindest-
schutzart sind die KLE fest anzuziehen.
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
Alle nicht benutzten metrischen COOPER
CROUSE-HINDS KLE sind mit dem
bescheinigten Verschluss für metrische
KLE zu verschließen.
6.3.2 Stecker / Kupplung
Es dürfen generell nur die im Stecker oder der
Kupplung vorhandenen Dichteinsätze verwen-
det werden.
Bei der Installation der Leitung ist darauf zu
achten, dass die für den Leitungsdurchmesser
geeigneten Dichtungseinsätze verwendet
werden.
4. Das angeschlossene Kabel ist folgerichtig in
die Trompetenverschraubung Pos. 15, die
Dichtung Pos. 13, die Steckerhülse Pos. 5
einzuführen (siehe S.18; B. 7).
Danach kann der Stecker in umgekehrter
Reihenfolge zusammenmontiert werden
(siehe auch Punkt 6.4).
6.2.3 Anschluss der Steckerstifte und
der Buchsen
Die abisolierten Anschlussadern des Anschluss-
kabels werden in die Anschlussöffnung der
Steckerstifte Pos. 10, bzw. in die Anschluss-
öffnung der Buchsen Pos. 9, eingesteckt
und mit der Spezialquetschzange Pos. 11
(auf Anfrage bei COOPER CROUSE-HINDS
erhältlich), angequetscht (siehe S.18; B. 9).
Die Buchsen Pos. 9, der 7-poligen Steckdose
sind bereits Werkseitig auf dem Verriegelungs-
schalter angeschlossen.
Wahlweise können diese Stift- und Buchsenan-
schlüsse, unter Verwendung eines zusätzlichen
Schrumpfschlauches über der Lötstelle,
angelötet werden.
Die Steckbuchsen bzw. Steckerstifte sind nach
dem Anschließen von hinten in den Steckdose-
neinsatz bzw. Steckereinsatz bis zum Anschlag,
(mit normaler Handkraft möglich), einzudrücken
(siehe Bild 15).
Eine Demontage der Buchsen sowie der Stifte
wird unter Punkt 8, Reparatur / Instandsetzung
beschrieben (siehe auch S.18; B. 11, B. 12 und B. 13).
Nicht benutzte Buchsen- und Stiftöffnungen
werden mit den im Lieferumfang enthaltenen
Buchsen, Pos. 9 sowie den Stiften, Pos. 10
verschlossen.
Vor dem Schließen der Steckdosen, der
Kupplung und der Stecker ist der korrekte
Sitz aller Buchsen und Stifte zu überprüfen.
Die minimal und maximal anschließbaren
Leiterquerschnitte sind zu beachten
(siehe technische Daten).
Alle Schrauben der Anschluss klemmen, auch
die der nicht benutzten, sind fest anzuziehen.
Zur Aufrechterhaltung der Zündschutzart ist
der Leiteranschluss mit besonderer Sorgfalt
durchzuführen.
Die Anschlussklemmen sind für den Anschluss
von Kupferleitern ausgelegt.
Bei der Verwendung von mehr- oder fein-
drähtigen Anschlußkabel /-leitungen sind die
Aderenden entsprechend den geltenden
nationalen und internationalen Vorschriften
zu behandeln (z.B. Verwendung von Aderend-
hülsen).
Achtung: Bei Verlust der Befestigungsschrau-
ben, sind diese durch gleichartige Schrauben
zu ersetzen oder direkt vom Hersteller
anzufordern.
6.2 Öffnen des Gerätes/
Elektrischer Anschluss
Der elektrische Anschluss des Betriebsmit-
tels darf nur durch Fachpersonal erfolgen
(EN/IEC 60079-14).
Die Isolation der Anschlussleitungen muss
bis an die Klemme bzw. die Steckbuchsen/
Steckerstifte heranreichen. Der Leiter selbst
darf nicht beschädigt sein.
Bei Mischbestückungen Ex-e / Ex-i sind
die erforderlichen Mindestabstände
einzuhalten (siehe z.B. EN/IEC 60079-11).
Bei geöffneten Geräten ist sicherzustellen
(Spannungsfreiheit herstellen), dass keine
Spannungsverschleppung auf die ange-
schlossenen eigensicheren Stromkreise
übergreift.
Die ordnungsgemäß abisolierten Anschluss-
leitungen der Kabel sind unter Berücksichtigung
einschlägiger Vorschriften wie folgt anzuschlie-
ßen (Steckerstifte und Buchsen sind dem
Stecker bzw. Der 21-poligen Steckdose und
Kupplung lose beigepackt).
6.2.1 7-polige Stecker (siehe S.18; B.5 u. B.6)
1. Am Stecker wird zuerst das Druckstück
Pos. 3, des Steckers durch lösen der
Schrauben Pos. 2, entfernt.
2. Hierauf werden die 2 Befestigungsschrauben
der Steckerhülse Pos 5, gelöst und die Haube
vom Steckereinsatz getrennt (siehe S.18; B. 4).
3. Die Kabelzugentlastung Pos. 7, wird durch
lösen der Schrauben Pos. 8, geöffnet und
kann dann vom Steckereinsatz gelöst werden
(siehe S.18; B. 5 + B.6).
4. Nun können, wie unter Punkt 6.2.3 beschrie-
ben, die angeschlossenen Steckerstifte in
die Bohrung des Steckereinsatzes eingesetzt
werden.
5. Das angeschlossene Kabel ist mit der
Zugentlastung gegen das Herausziehen
aus dem Steckerensatz zu sichern.
Danach kann der Stecker in umgekehrter
Reihenfolge zusammenmontiert werden
(siehe auch Punkt 6.4).
6.2.2 21-polige Stecker
(siehe S.18; B. 7)
1. Zuerst wird die Trompetenverschraubung
Pos. 15, durch lösen der Zugentlastungsnase
Pos. 14, mit den 2 Zylinderschrauben aus der
Steckerhülse Pos. 5, herausgedreht.
2. Hierauf werden die 2 Befestigungsschrauben
Pos. 4 der Steckerhülse Pos 5, gelöst und die
Hülse vom Steckereinsatz Pos.6, getrennt.
3. Nun können, wie unter Punkt 6.2.3 beschrie-
ben, die angeschlossenen Steckerstifte in
die Bohrung des Steckereinsatzes eingesetzt
werden.
7
D
Explosionsgeschützte Steckvorrichtungen,
7-polig GHG 511 .7.. / 592 und 21-polig GHG 511 .9.. / 591
4. Die auf den Buchsen oder der Stifte sitzende
Abdeckscheibe Pos. 19, Bild 12, entfernen.
5. Stift bzw. Buchse vom Leiter lösen (ablöten/
abschneiden) und mit dem Demontagewerk-
zeug Pos. 12; B.13
(COOPER CROUSE-HINDS Bestellnummer
GHG 590 1903 R0001), durch lösen der
Verriegelungsfeder Pos. 20, den Stift bzw. die
Buchse entriegeln und nach hinten herauszie-
hen.
6. Der Zusammenbau erfolgt in umgekehrter
Reihenfolge wie die Demontage und ist auch
unter Punkt 6.2 beschrieben.
7. Das Schließen des Gerätes ist unter
Punkt 6.4 beschrieben.
Andere als die beschriebenen Umbauten
oder Änderungen am Betriebsmittel sind
nicht gestattet.
9 Entsorgung /
Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind die
jeweils geltenden nationalen Abfallbeseitigungs-
vorschriften zu beachten.
Zusätzliche Informationen zur Entsorgung des
Produktes können Sie bei Ihrer zuständigen
Cooper Crouse-Hinds Niederlassung erfragen.
Zur Erleichterung der Wiederverwertbarkeit von
Einzelteilen sind Kunststoffteile mit dem
Kennzeichen des verwendeten Kunststoffes
versehen.
Programmänderungen und -ergänzungen sind
vorbehalten.
7 Instandhaltung / Wartung
Die für die Wartung / Instandhaltung von
elektrischen Betriebsmitteln in explosions-
gefährdeten Bereichen geltenden nationalen
Bestimmungen sind einzuhalten
(z.B. EN/IEC 60079-17).
Vor Öffnen des Gehäuses Spannungsfreiheit
sicherstellen oder geeignete Schutzmaßnah-
men ergreifen.
Die erforderlichen Wartungsintervalle sind
anwendungsspezifisch und daher in Abhängig-
keit von den Einsatzbedingungen vom Betreiber
festzulegen.
Im Rahmen der Wartung sind vor allem die Teile,
von denen die Zündschutzart abhängt, zu
prüfen (z.B. Unversehrtheit der druckfesten
Komponenten, des Gehäuses, der Dichtungen
und der Kabel- und Leitungseinführung).
Sollte bei einer Wartung festgestellt werden,
dass Instandsetzungsarbeiten erforderlich sind,
ist Abschnitt 8 dieser Betriebsanleitung zu
beachten.
8 Reparatur / Instandsetzung /
Änderungen
Instandsetzungsarbeiten / Reparaturen dürfen
nur mit COOPER CROUSE-HINDS Original-
ersatzteilen vorgenommen werden.
Bei Schäden an der druckfesten Kapselung
ist das betroffene Betriebsmittel an
COOPER CROUSE-HINDS zur Reparatur
zurückzugeben.
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von COOPER CROUSE-
HINDS oder einer qualifizierten Elektrofach-
kraft in Übereinstimmung mit national
geltenden Regeln durchgeführt werden
(z.B. EN/IEC 60079-19).
Müssen Steckerstifte oder Steckbuchsen
ausgewechselt werden, ist wie folgt vorzuge-
hen (siehe dazu S.18; B. 11, B. 12 u. B. 13):
1. Das Öffnen der Steckdose oder des Steckers
ist unter Punkt 6.2 beschrieben.
2. Nach dem Öffnen ist die Schlitz mutter
Pos. 17, der Stecker- bzw. Buchseneinsätze,
mit einem geeig neten Werkzeug
(z.B. Schlitzmutter-Steck schlüssel) zu lösen.
Ein Durchdrehen der Durchgangsschraube ist
durch ein entsprechendes Gegenhalten zu
verhindern.
3. Die mit den Stift- bzw. Buchsenbezeichnun-
gen versehene vordere Abdeckung
abnehmen.
Achtung:
Stift- und Buchsenabdeckscheiben können
herausfallen, darum ist der Dosen- bzw. der
Steckereinsatz nach oben zu halten.
6.4 Schließen des Gerätes
Beim Schließen der Wandsteckdosen ist auf
die korrekte Montage der KLE zu achten.
Beim Aufsetzen des Deckels der 7-poligen
Wandsteckdose ist darauf zu achten, dass der
Schaltgriff in der "0"- Stellung steht und die
Achse des Schalters in die Mitnehmeröffnung
des Schaltgriffes eingreift.
Zur Sicherstellung der erforderlichen Mindest-
schutzart sind die Deckelschrauben, die
Schrauben der Stecker sowie der Kupplung
fest anzuziehen.
Nach dem Anschluss der Leitung ist der
Trompetenstutzen Pos. 15, des 21-poligen
Steckers und der Kupplung handfest bis zur
Erzielung der Dichtwirkung in den Einschraub-
stutzen der Stecker- bzw. der Kupplungshülse
einzudrehen.
Danach sind die Schrauben Pos. 16, der
Zugentlastung Pos. 14, fest anzuziehen. Sie sind
so fest anzuziehen, dass eine ausreichende
Zugenlastung gewährleistet, eine Beschädigung
der Leitung ausgeschlossen und die Verdrehungs-
sicherung erreicht wird (siehe S.18; B. 10).
Achtung! Übermäßiges Anziehen kann die
Zugentlastungswirkung negativ beeinträchtigen.
Nach dem korrekten Anschluss der Leitung und
Sicherstellung der Zugentlastung des 7-poligen
Steckers, wird mit den Schrauben Pos. 4, die
Druckschraube Pos. 3, so fest angezogen,
dass die Dichtigkeit erreicht wird
(siehe S.18; B. 4).
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
Alle Fremdkörper sind aus den Geräten zu
entfernen.
6.5 Inbetriebnahme
Vor Inbetriebnahme des Betriebsmittels sind
die in den einzelnen nationalen Bestimmungen
genannten Prüfungen durchzuführen.
Außerdem ist vor der Inbetriebnahme die
korrekte Funktion und Installation des Betriebs-
mittels in Übereinstimmung mit dieser
Betriebsanleitung und anderen anwendbaren
Bestimmungen zu überprüfen.
Vor jedem Stecken des Steckers in die
Steckdose ist dieser auf Beschädigungen
zu überprüfen.
Der Betreiber muss dafür sorgen, dass
beim Betrieb der Steckvorrichtung überall
ein gleiches Erdpotential anliegt.
Unsachgemäße Installation und Betrieb der
Steckvorrichtungen kann zum Verlust der
Garantie führen.
8
GB
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7.. / 592 and 21-pole GHG 511 .9.. / 591
1 Technical data
1.1 Plugs and sockets, 7-pole
EC type examination certificate PTB 00 ATEX 1109
Marking acc. to 2014/34/EU
and standard of series EN 60079:
II 2 G Ex e IIC T5 / T6
II 2 G Ex de [ia] IIC T5 / T6
Rated voltage up to 400 V, 50/60 Hz
Max. rated current 16 A (T6) / 20 A (T5)
Perm. short-circuit back-up fuse without therm. protect. with therm. protect.
max. 16 A max. 25 A gG
Switching capacity AC 3 400 V /16 A
Switching capacity AC 15 400 V / 6 A 230 V / 8 A
Switching capacity DC 13 24 V / 6 A 230 V / 0.4 A
Permissible ambient temperature -20° C up to +40° C (standard version)
(Other temperatures possible with special versions.)
Perm.storage temperature in original packing -20° C up to +40° C
Degree of protection to IEC/EN 60529 IP 66 (standard version)
with closed and secured hinged cover as well as combinations properly plugged together
Insulation class acc. to IEC/EN 61140
I – with metal flange or metal cable entries
II - is complied with by devices
Cable entries (standard version)
Wall socket (GHG 511 47) 2 x M40 1x M40 + 1x screwed plug
suitable cables and test torques of the
pressure screw
Ø Nm
Seal 1+2
1 2
3
min.
max.
(1)
19.0
22.0
3.3
5.5
Seal 1
1 2
3
min.
max.
(1)
22.0
28.0
3.3
6.7
Test torque for screw in thread cable entry 7.5 Nm
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
Plug (GHG 592 2) Ø 9 - 17 mm
Supply terminal Cross section Stripped wire length
Switch contact block of wall socket 2 x 1.5 - 4.0 mm² 6 mm
Pin for plug 1 x 1.0 - 2.5 mm² * 13 mm
* crimp or soldered connections
Test torques
Cover- and plug screws 2.5 Nm
Terminals 2.5 Nm
Weight (standard version) Wall socket
approx. 2.20 kg
Plug
approx. 0.30 kg
2 Safety instructions
Target group:
For skilled electricians and suitable
qualified, instructed personnel in
accordance with national legislation,
including the relevant standards and, where
applicable, in acc. with IEC/EN 60079-14 on
electrical apparatus for explosive atmospheres.
The multiple plug and socket systems 7-pole
(GHG 511 .7. / GHG 592) and 21-pole (GHG
511 .9 / GHG 591) are not suited for use in
Zone 0.
The operations must be carried out by
electrical suitably trained in hazardous area
with knowledge of increased safety
explosion protection IEC/EN 60079-14.
The temperature class and type of
protection stated on the apparatus shall
be observed.
To ensure adherence to the temperature
class stated on the type label of the
apparatus, the permissible ambient
temperature, the rated terminal cross
section and the self-heating of the appara-
tus, that
is mainly due to the power dissipation, shall
be taken into account (test criterion for the
self-heating is an overload of 10%).
Modifications or changes to the plug and
socket systems are not permitted.
They shall be used for their intended
purpose and in a perfect and clean state.
Prior to being put into operation, the plug
and socket systems shall be checked in
accordance with the instructions as per
section 6.
The sockets may only be used with the
associated COOPER CROUSE-HINDS plugs
in undamaged condition.
The 7-pole wall socket is safeguarded by an
interlocking switch and can, therefore, not
be switched on if the plug is not inserted.
The plug of the 21-pole plug and socket may
not be inserted into the 21-pole sockets and
coupler or withdrawn from them while they
are live (see also section 5).
Before initial operation, any foreign matter
shall be removed from the apparatus.
The national safety rules and regulations
for the prevention of accidents, as well as
the safety instructions included in these
operating instructions, that, like this text,
are set in italics, shall be observed!
Dimensions in mm
X = fixing dimensions
Wall socket 7pole
Contact ararangement 7pole
Plug 7pole
Code 7pole
6h 5h 7h
maize yel. brown orange
9
GB
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7.. / 592 and 21-pole GHG 511 .9.. / 591
1.2 Plugs and sockets, 21-pole
EC Type Examination Certificate:
Wall socket, coupler, plug PTB 00 ATEX 1109
Flange socket PTB 00 ATEX 1108 U
Marking acc. to 2014/34/EU
II 2 G Ex e IIC T5 / T6
and standard of series EN 60079:
II 2 G Ex e [ia] IIC T5 / T6
Rated voltage up to 250 V, 50/60 Hz (max. up to 400 Hz)
Max. rated current 10 A
Perm. short-circuit back-up fuse without therm. protect. with therm. protect.
max. 16 A max. 25 A gG
Permissible ambient temperature -20° C up to +40° C (standard version)
(Other temperatures possible with special versions.)
Perm.storage temperature in original packing -20° C up to +40° C
Degree of protection to IEC/EN 60529 IP 65 (standard version)
with closed and secured hinged cover as well as combinations properly plugged together
Insulation class acc. to IEC/EN 61140
I – with metal flange or metal cable entries
II - is complied with by devices
Cable entries (standard version)
Wall socket 1 x M40
suitable cables and test torques of the
pressure screw
Ø Nm
Seal 1+2
1 2
3
min.
max.
(1)
19.0
22.0
3.3
5.5
Seal 1
1 2
3
min.
max.
(1)
22.0
28.0
3.3
6.7
Test torque for screw in thread cable entry 7.5 Nm
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
Plug Ø 19 - 28 mm
Coupler Ø 9 - 27 mm
Supply terminal Cross section Stripped wire length
Contact pin for sockets and coupler 1 x 1.0 - 2.5 mm² * 13 mm
Pin for plug 1 x 1.0 - 2.5 mm² * 13 mm
* crimp or soldered connections
Test torques
Cover and plug screws 2.5 Nm
Weight (standard version) (standard version)
Wall socket GHG 511 47 approx. 1.79 kg
Plug GHG 591 2 approx. 0.70 kg
Flange socket GHG 591 4 approx. 0.43 kg
Coupler GHG 591 3 approx. 0.77 kg
1.3 Intrinsically safe switch circuits
Max. safe voltage U
m
690 V eff
Safe galvanic isolation from all other circuits
and earth
Dimensions in mm
X = fixing dimensions
Wall socket 21pole
Plug 21pole
Coupler 21pole
Flange socket 21pole
Code 21pole
6h 5h 7h
maize yel. brown orange
10
GB
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7.. / 592 and 21-pole GHG 511 .9.. / 591
3 Conformity with standards
The apparatus are conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4 Field of application
The multiple plug and socket systems are
suitable for use in Zone 1 and 2 hazardous
areas acc. to IEC60079-10-1 !
The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion
protection and resistance to chemical
substances corresponding to the requirements
for use in a “normal industrial atmosphere”:
– impact resistant polyamide
– glass-fibre reinforced polyester
– special steel AISI 316 L
– special steel A4-70.
In case of use in an extremely aggressive
atmosphere, please refer to manufacturer.
5 Use / Properties
The multiple plugs and sockets are used for
the power supply of local controls with varying
locations, as well as of electrical installations,
mobile machinery and drives in hazardous
areas.
The electrical limiting values that are
decisive for the intrinsic safety shall be
observed.
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
5.1 The 7-pole plug and socket is fitted with
an interlocking switch and can be used up to
max.500 V, 20 A.
The plug can only be inserted into the socket
and withdrawn when no voltage is applied.
The switch, item 4, can only be switched on,
if the plug, item 1, has been inserted properly
into the socket, item 2 (see p.18; fig.1 and 2).
After switching on the interlocking switch,
item 4, the plug cannot be withdrawn.
(see p.18; fig.2).
In order to guarantee the type of protection,
also when the plug has been inserted, the bayo-
net ring, item 3, of the plug, item 1, has to be
turned until it reaches the stop on the socket,
item 2 (see p.18; fig.1 and 2).
6 Installation
The relevant national regulations(e.g. Betr.Si.V
the equipment safety law for Germany) and
the generally recognized rules of engineering
apply for the installation and operation
(IEC/EN 60079-14).
6.1 Mounting
6.1.1 Wall socket
The wall sockets can be mounted without
opening the enclosure.
When wall sockets are mounted directly onto
the wall, they shall rest evenly only at the
respective fastening points. The chosen screw
shall match the fastening hole (see dimensional
drawing) and it must not damage the hole (e. g.
use of a washer). The device shall be fastened
diagonally with at least 2 screws.
The wall-mounting and flange sockets shall
be mounted in such a way that the plug
opening does not face upwards (fig. 2).
The wall sockets can be clipped onto the
COOPER CROUSE-HINDS mounting plate size
5. They are pushed laterally into the guiding
groove on the left-hand side of the mounting
plate.
See the respective mounting instructions.
Fastening point A
wall socket 7- and 21-pole
A A
A A
6.1.2 Socket contact pins and plug pins
See section 6.2. for details of how to assemble
the contact pins of the 21-pole wall socket and
the plug pins of the 7-pole and 21-pole plugs.
To switch off and withdraw the plug, proceed in
the reverse order. After withdrawing the plug
from the socket, seal the socket with the hinged
cover, item 5, and secured with the bayonet
catch, item 6 (see p.18; fig.1 and 2).
After a short in the circuit, the functioning
of the plug and socket shall be checked.
As, due to the flameproof encapsulation, it
is not possible to check the switch contacts,
the complete switch insert (interlocking
switch) has to be replaced after several
short circuits.
5.2 The 21-pole plug and socket does not
feature an interlocking switch. It can be
operated up to max. 250 V, 10 A.
When using plugs and sockets (inserting or
withdrawing plugs, etc.), the following shall be
observed: (see p.18; fig.3)
After inserting the plug, item 1, the bayonet
ring, item 3, of the plug has to be interlocked
with the socket, item 2.
After this, the engaging nose, item 8, on the
hinged cover, Item 5, of the socket engages
in the recess with locking hook of the plug,
item 7, that is provided for this purpose.
To disengage, the locking hook of the plug
has to be disengaged with a pointed tool
(e.g. size 2 screwdriver).
The bayonet ring, item 3, can then be released
and the plug can be withdrawn
from the socket.
After withdrawing the plug from the socket,
seal the socket with the hinged cover, Item 5,
and secure it with the bayonet catch, item 6
(see p.18; fig.3).
Warning:
The plug may only be inserted or withdrawn
when no voltage is being applied!
The sole responsibility with respect to the
suitability and proper use of the plugs and
sockets with regard to the basic require-
ments of these instructions (see technical
data) lies with the operator.
When used in open air installations, the plugs
must be kept with the plug opening (pin end)
facing downwards or be sealed with protective
plug caps that are available as an optional extra
(see main catalogue).
The data according to sections 3 and 4 shall
be taken into account during use.
Applications other than those described are
not permitted without Cooper Crouse-Hinds´
prior written consent.
During operation the instructions stated in
section 7 of the operating instructions shall
be observed.
11
GB
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7.. / 592 and 21-pole GHG 511 .9.. / 591
6.2 Opening the device/
Electrical connection
The electrical connection of the device may
only be carried out by skilled staff
(IEC/EN 60079-14).
The insulation of the conductors must reach
up to the terminal or the socket contact pins
and plug pins. The conductor itself must not
be damaged.
In the case of mixed Ex-e / Ex-i installations,
the required minimum clearances shall be
maintained (see, for example,
IEC/EN 60079-11).
When apparatus is open, it is necessary to
ensure (disconnect voltage supply) that no
voltage is carried over into any connected
intrinsically safe circuits.
The correctly stripped wires of the cable shall
be connected according to the relevant
regulations as follows (plug pins and socket
contact pins are included loose with the plugs
or the 21-pole socket and coupler).
6.2.1 Plug, 7-pole (see p.18; fig.5 and fig.6)
1. First remove the pressure piece, item 3,
of the plug by undoing the screws, item 2
(see p.18; fig.5).
2. Then undo the 2 fixing screws of the plug
sleeve, item 5, and separate the sleeve from
the plug insert (see p.18; fig. 4).
3. To open the pull relief of the cable, item 7,
undo the screws, Item 8. It can then be
removed from the plug insert
(see p.18; fig. 5 and 6).
4. Now, as described in Section 6.2.3, the
connected plug pins can be inserted into the
drilled holes of the plug insert.
5. The connected cable shall be safe-guarded
against being pulled out of the plug insert by
means of the pull relief.
Then, to assemble the plug, proceed in the
reverse order (see also section 6.4).
6.2.2 Plug, 21-pole (see p.18; fig 7)
1. First, unscrew the trumpet-shaped gland,
Item 15, from the plug sleeve, Item 5, by
undoing the pull relief lug, item 14, with the
2 cylinder head screws.
2. Then undo the 2 fixing screws, item 4, of the
plug sleeve, item 5, and separate the sleeve
from the plug insert, item 6.
3. Now, as described in Section 6.2.3, the
connected plug pins can be inserted into
the drilled holes of the plug insert.
4. The connected cable shall be fed into the
trumpet-shaped gland, item 15, the seal,
item 13, and the plug sleeve, Item 5, in the
given order (see p.18; fig. 7).
Then, to assemble the plug, proceed in the
reverse order (see also section 6.4).
6.3 Cable entries (KLE);
blanking plugs
6.3.1 Socket
Generally, only certified cable entries and
blanking plugs are permitted for use.
Flexible cables shall be used with trumpet-
shaped cable glands or other suitable
entries with additional pull-relief.
When using cable entries with a lower IP
protection than that which applies to the device
(see page 9, technical data), the IP protection of
the whole device will be reduced.
The mounting directives applicable to the cable
entries used shall be observed.
Unused holes shall be closed with a certified
blanking plug in order to establish the minimum
protection category.
In case of sealing inserts that are cut to size, it
shall be ensured that the insert is properly
adapted to the cable diameter.
Care has to be taken that, when fitting the
cable entries, sealing inserts appropriate to the
cable diameter are used.
Intrinsically safe circuits shall be fed through
cable entries that are colour-coded (light blue).
In order to ensure the required minimum
protection category, the cable glands are to be
tightened down.
Overtightening might impair the protection
category.
All unused metric COOPER CROUSE-HINDS
cable entries shall be closed with the
certified blanking plug for metric cable
entries.
6.3.2 Plug / coupler
In general, only the sealing inserts fitted in the
plug or in the coupler may be used.
When mounting the cable, ensure that the
sealing inserts match the cable diameter used.
6.2.3 Connection of plug pins and
socket contact pins
The stripped wires of the connection cable
are pushed into the connection opening of the
plug pins, Item 10, or the connection opening
of the socket contact pins, item 9, and crimped
on using a special crimping tool, item 11
(available from the manufacturer, Messrs.
COOPER CROUSE-HINDS, on request)
(see p.18; fig. 9).
The socket contact pins, item 9, of the 7-pole
socket are connected to the interlocking switch
in our factory.
Optionally, the pin and socket pin connections
can be soldered on, whereby an additional
shrink-on sleeve is fitted over the solder
connection.
After connection, the socket contact pins or
plug pins are pushed into the socket or plug
insert from the rear until they reach the stop
(can be done using normal hand pressure)
(see p.18; fig. 8).
A description of how to dismantle the contact
pins or plug pins can be found in Section 8,
Repair / Overhaul / Modifications
(see also p.18; fig. 11, 12 and 13).
Unused socket pin and plug pin openings are to
be sealed with the socket pins, item 9, and plug
pins, item 10, that are included in the scope of
delivery.
Before closing the sockets, couplers or
plugs, check to ensure that all the contact
pins or plug pins fit correctly.
The min. and max. connectible cable cross
sections shall be observed
(see technical data).
All the screws of the connection terminals,
including the unused ones, shall be tightened
down.
To maintain the type of protection,
all conductors shall be connected with
special care.
The supply terminals are designed for the
connection of copper conductors.
If multi- or fine-wire connecting cables are
used, the wire ends will have to be handled in
acc. with the applicable national and interna-
tional rules (e.g. use of sleeves for strands).
Warning:
If any fixing screws are missing, they shall
be replaced by screws of the same type or
ordered directly from the manufacturer.
12
GB
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7.. / 592 and 21-pole GHG 511 .9.. / 591
6.4 Closing the device
Before closing the wall sockets, check that
the cable entries are fitted correctly.
When placing the cover of the 7-pole wall
socket, pay attention that the switch handle
is in “0” position and the shaft of the switch
engages into the tappet hole on the switch
handle.
In order to ensure the required minimum
protection category, the cover screws must be
tightened down.
The screws on the plug and on the coupler
must be tightened down.
After connecting the cable, screw the
trumpet-shaped gland, Item 15, of the 21-pole
plug and coupler into the screw-in insert of the
plug or coupler sleeve by hand so that it seals. )
After this, tighten down the screws, item 16,
of the pull relief, Item 14. They shall be screwed
down tight enough to ensure sufficient pull
relief, to exclude any possible damage to the
cable and to safeguard it from twisting
(see p.18; fig.10).
Warning! Excessive tightening might impair
the pull relief.
After having connected the cable correctly
and checked the pull relief of the 7-pole plug,
screw down the pressure piece, Item 3, with
the screws, Item 4, tight enough to ensure
that it is sealed (see p.18; fig. 4).
Overtightening might impair the protection
category.
Any foreign matter shall be removed from
the device.
6.5 Putting into operation
Before putting the apparatus into operation,
the tests specified in the relevant national
regulations shall be carried out.
In addition to this, the correct functioning and
installation of the apparatus in accordance with
these operating instructions and other
applicable regulations shall be checked.
Check the plug for any damage before inserting
it into the socket.
The user shall ensure that an equipotential earth
is applied throughout when the plug and socket
is in operation.
The improper installation and operation of
the plugs and sockets may result in the
invalidation of the guarantee.
4. Remove the cover disc, item 19 fig.12,
on the contact pins or pins.
5. Remove pin or contact pin from conductor
(unsolder / cut off) and disengage the pin or
contact pin by taking off the interlocking
spring, item 20, using the dismantling tool,
item 12; fig.13 (COOPER CROUSE-HINDS
Order No. GHG 590 1903R0001). Pull the pin
out backwards.
6. To reassemble the plug / socket, proceed in
the reverse order or refer to Section 6.2 for
assembly details.
7. How to close the apparatus is described in
Section 6.4.
Apparatus modifications other than those
described or changes to apparatus are not
permitted.
9 Disposal / Recycling
When the apparatus is disposed of, the respec-
tive national regulations on waste disposal will
have to be observed.
In case of disposal you can obtain additional
information from your Cooper Crouse-Hinds
branch.
In order to facilitate the recycling of individual
components, plastic parts are provided with the
identification mark of the plastic material used.
Subject to modifications or supplement of the
product range.
7 Maintenance / Servicing
The valid national regulations for the
servicing / maintenance of electrical
apparatus for use in potentially explosive
atmospheres shall be observed
(IEC/EN 60079-17).
Prior to opening the enclosure, it is
necessary to ensure that the voltage
supply has been isolated or to take suitable
protective measures.
The necessary intervals between servicing
depend upon the specific application and shall
be stipulated by the operator according to the
respective operating conditions.
During servicing, above all, the parts on which
the explosion protection depends,
(e.g. intactness of the flameproof components,
the enclosure, the seals and cable entries),
shall be checked.
If, in the course of servicing, it is ascertained,
that repairs are necessary, section 8 of these
operating instructions shall be observed.
8 Repairs / Modifications
Only original COOPER CROUSE-HINDS parts
shall be used for carrying out repairs.
In the event of damage to the flameproof
encapsulation, replacement of these
components is mandatory. In case of doubt,
the respective apparatus shall be sent to
Cooper Crouse-Hinds for repair.
Repairs that affect the explosion protection
may only be carried out by Cooper Crouse-
Hinds or by a qualified electrician in
compliance with the respective national
regulations (IEC/EN 60079-19).
If it is necessary to replace plug pins or socket
contact pins, proceed as follows
(see p.18; fig. 11, 12 and 13):
1. Open socket or plug as described in
section 6.2.
2. After opening, undo the slotted nut, Item 17,
of the plug or socket inserts using a suitable
tool (e.g. slotted nut spanner). To prevent
the through-screw from turning, hold screw
accordingly. (see p.18; fig.11)
3. Remove the front cover that bears the
designations of the plug or socket pins.
Warning:
The cover discs for the plug or socket pins
can fall out. To avoid this, hold the socket or
plug insert facing upwards.
13
F
Fiches et prises à 7-pôles GHG 511 .7.. / GHG 592 et à 21 pôles
GHG 511 . 9.. / GHG 591, pour atmosphères explosives
1 Caractéristiques techniques
1.1 Fiche et prise à 7 pôles
Attestation d’examen CE de type: PTB 00 ATEX 1109
Marquage selon 2014/34/UE
et normes de la série EN 60079:
II 2 G Ex e IIC T5 / T6
II 2 G Ex de [ia] IIC T5 / T6
Tension nominale jusqu’à 500 V, 50/60 Hz
Courant nominal au maxi 16 A (T6) / 20 A (T5)
Fusible placé en amont
sans protection thermique avec protection thermique
16 A au maxi 25 A gG au maxi
Puissance de coupure AC 3 400 V /16 A
Puissance de coupure AC 15 400 V / 6 A 230 V / 8 A
Puissance de coupure DC 13 24 V / 6 A 230 V / 0,4 A
Température ambiante admissible -20° C à +40° C (modèle de liste)
(En cas de modèles spéciaux d’autres températures possibles)
Température de stockage dans l’emballage original
-20° C à +40° C
Indice de protection selon EN/CEI 60529 IP 66 (modèle de liste)
avec le couvercle rabattant fermé et arrêté et les dispositifs dûment enfichés
Classe d’isolation selon EN/CEI 61140
I – version avec plaque laiton pour câbles armés ou
Entrées de câble de metal
II - est remplie par les dispositifs
Entrée de câble (modèle de liste)
Prise murale (GHG 511 47) 2 x M40 1x M40 + 1x bouchon de fermeture
câbles appropriés et couples d’essai de la vis
de pression
Ø Nm
Garnit
ure 1+2
1 2
3
min.
max.
(1)
19,0
22,0
3,3
5,5
Garniture 1
1 2
3
min.
max.
(1)
22,0
28,0
3,3
6,7
Couple d' essai pour l’entrée de câble 7,5 Nm
(1)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la
possibilité de resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
Fiche (GHG 592 2) Ø 9 - 17 mm
Borne de connexion Section transv.
Longueur dénudée des fils
Socle du commutateur de la prise murale 2 x 1,5 - 4,0 mm² 6 mm
Cheville pour fiche 1 x 1,0 - 2,5 mm² * 13 mm
* Raccordement serti ou soudé
Torques d’essai
Vis de couvercle et de fiche 2,5 Nm
Bornes de connexion 2,5 Nm
Poids (modèle de liste) Prise murale
env. 2,20 kg
Fiche
env. 0,30 kg
2 Consignes de sécurité
Groupe cible:
Pour les électriciens qualifiés et les
personnels ayant reçu les formations
adéquates, conformément à la législation
nationale en vigueur et, si applicable, à la
norme CEI/EN 60079-14 sur les installations
électriques pour les atmosphères explosives.
Les fiches et prises mul tiples à
7 pôles (GHG 511 .7. / GHG 592) et
à 21 pôles (GHG 511 .9 / GHG 591) ne
conviennent pas à un emploi en zone 0.
Le groupe d’explosion et la classe de
température marqués sur les appareils
devront être respectés. (CEI/IEC 60079-14)
Afin de respecter la classe de température
indiquée sur l’étiquette du type de l’appareil,
on prendra en compte la température
ambiante, le diamètre de connexion ainsi
que les pertes d’énergie occasionnées par
l’échauffement propre de l’appareil (le critère
de contrôle limite pour l’échauffement est
une surcharge de 10%).
Il n’est pas admis de transformer ou de
modifier les fiches et prises. Elles ne doivent
être employées que pour la fonction qui leur
est dévolue, et ce, en parfait état de propreté
et de fonctionnement.
Avant leur mise en service, les fiches
et prises doivent être vérifiées selon
l’instruction donnée dans la section 6.
Les prises ne doivent être utilisées qu’avec
les fiches COOPER CROUSE-HINDS, et ce, en
parfait état.
La prise murale à 7 pôles est assurée par un
interrupteur de verrouillage. De ce fait, une
commutation sans fiche est impossible.
La fiche de la prise à 21 pôles ne doit pas
être connectée à de la prise à 21 pôles ou
au coupleur sous tension. De même, une
déconnexion sous tension est à proscrire
(voir aussi Point 5).
Avant la première mise en service, tout
corps étranger doit être ôté des appareils.
Respectez les prescriptions nationales
de sécurité et de prévoyance contre les
accidents ainsi que les consignes de sécurité
qui suivent dans ce mode d’emploi en
italique!
Dimensions en mm
X = dimensions de fixation
Prise murale à 7pôles
Schémas de connexion à 7pôles
Fiche à 7pôles
Code 7pôles
6h 5h 7h
J. mais marron orange
14
F
Fiches et prises à 7-pôles GHG 511 .7.. / GHG 592 et à 21 pôles
GHG 511 . 9.. / GHG 591, pour atmosphères explosives
1.2 Fiche et prise à 21 pôles
Attestation d’examen CE de type:
Prise murale, Fiche, Prolongateur PTB 00 ATEX 1109
Prise à bride PTB 00 ATEX 1108 U
Marquage selon 2014/34/UE
et normes de la série EN 60079:
II 2 G Ex e IIC T5 / T6
II 2 G Ex e [ia] IIC T5 / T6
Tension nominale jusqu’à 250 V, 50/60 Hz (jusqu’à 400Hz au maxi)
Courant nominal 10 A au maxi
Fusible placé en amont
sans protection thermique avec protection
thermique
16 A au maxi 25 A gG au
maxi
Température ambiante admissible -20° C à +40° C (modèle de liste)
(En cas de modèles spéciaux d’autres températures possibles)
Température de stockage dans l’emballage original
-20° C à +40° C
Indice de protection selon CEI/EN 60529 IP 65 (modèle de liste)
avec le couvercle rabattant fermé et arrêté et les dispositifs dûment enfichés
Classe d’isolation selon CEI/EN 61140
I – version avec plaque laiton pour câbles armés ou
Entrées de câble de metal
II - est remplie par les dispositifs
Entrée de câble (modèle de liste)
Prise murale 1 x M40
câbles appropriés et couples d’essai de la vis
de pression
Ø Nm
Garnit
ure 1+2
1 2
3
min.
max.
(1)
19,0
22,0
3,3
5,5
Garniture 1
1 2
3
min.
max.
(1)
22,0
28,0
3,3
6,7
Couple d' essai pour l’entrée de câble 7,5 Nm
(1)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin
métallique. La plage de serrage peut varier légèrement selon le type de câble et les propriétés des matériaux
utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la
possibilité de resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
Fiche Ø 19 - 28 mm
Prolongateur Ø 9 - 27 mm
Borne de connexion Section transv.
Longueur
dénudée des fils
Douille pour prise et coupleur 1 x 1,0 - 2,5 mm² * 13 mm
Cheville pour fiche 1 x 1,0 - 2,5 mm² * 13 mm
* Raccordement serti ou soudé
Torques d’essai
Vis de couvercle et de fiche 2,5 Nm
Poids (modèle de liste) (modèle de liste)
Prise murale GHG 511 47 env. 1,79 kg
Fiche GHG 591 2 env. 0,70 kg
Prise à bride GHG 591 4 env. 0,43 kg
Prolongateur GHG 591 3 env. 0,77 kg
1.3 Circuit à sécurité intrinsèque
Tension maximale pour sécurité technique Um: 690 V eff
isolation galvanique de tous les autres circuits à
sécurité intrinsèque et de la terre
Dimensions en mm
X = dimensions de fixation
Prise murale à 21pôles
Fiche à 21pôles
Prolongateur à 21pôles
Prise à bride à 21pôles
Code 21pôles
6h 5h 7h
J. mais mar. orange
15
F
Fiches et prises à 7-pôles GHG 511 .7.. / GHG 592 et à 21 pôles
GHG 511 . 9.. / GHG 591, pour atmosphères explosives
3 Conformité aux normes
Les Appareils sont conformes aux normes
reprises dans la déclaration de conformité.
Les références aux normes et directives dans
cette notice se réfèrent toujours à la dernière
version. Les suppléments éventuels doivent
également être respectés.
4 Domaine d’utilisation
Les fiches et prises multiples conviennent à
l’emploi en les zones 1, 2 d’une atmosphère
explosive selon CEI/EN60079-10-1 !
Pour l’enveloppe et les pièces métalliques
extérieures, des matières de qualité supérieure
assurant une protection appropriée contre la
corrosion et une résistance aux agents
chimiques en “atmosphère industrielle
normale” ont été employées:
– polyamide résistant au choc
– polyester renforcé par fibre de verre
– acier spécial AISI 316 L
– acier spécial A4 - 70.
En cas d’utilisation dans une atmosphère
extrêmement agressive, des informations
supplémentaires au sujet de la résistance
contre des agents chimiques des matières
plastiques employées se trouvent dans la
fiche technique GHG 902 4001 P0001.
5 Utilisation / Propriétés
Les prises et fiches multiples servent à
l’alimentation en courant d’installations
électriques, machines et commandes mobiles
en atmosphère explosible.
Dans ce cas, les valeurs électriques limites
de la sécurité intrinsèque sont à respecter.
L’ appareil connecté à la fiche doit être
adapté à la tension du réseau correspondant.
5.1 La prise à 7 pôles est équipée d’un
interrupteur de verrouillage. Avec la prise,
elle peut être exploitée jusqu’à 500 V, 20 A.
La fiche ne peut être enfichée dans la prise ou
retirée de celle-ci qu’en état mis hors circuit.
L’interrupteur, Pos. 4, ne peut être mis en circuit
que si la fiche, Pos. 1, a été enfichée correcte-
ment dans la prise, Pos. 2 (voir p.18; fig. 1 et 2).
Après avoir mis en circuit l’interrupteur, Pos 4,
de verrouillage, la fiche ne peut plus être retirée
(voir p.18; fig. 2).
Afin d’assurer le mode de protection selon la
plaque signalétique après la mise en circuit de
la prise avec la fiche mise en place, l’anneau
en baïonnette, Pos. 3, de la fiche, Pos. 1, est
tourné jusqu’à sa butée sur la prise, Pos. 2,
(voir p.18; fig. 1 et 2).
6 Installation
Pour l’installation et l’exploitation d’appareils
électriques pour atmosphère explosive, la
règlementation nationale en vigueur (en
Allemagne par ex. Betr.Si.V, loi sur la sécurité
des appareils) ainsi que les règles de la
technique générale-ment reconnues devront
être respectées (CEI/EN 60079-14).
6.1 Montage
6.1.1 Prises murale
Le montage des prises murales peut se faire
sans ouvrir l’enveloppe.
En cas de montage directement au mur, les
prises murales ne doivent reposer au niveau
du mur que sur les points de fixation prévus.
La vis choisie doit correspondre au trou de
fixation (voir plan coté) et elle ne doit pas avarier
l’ouverture (par ex. emploi d’une rondelle).
Le dispositif doit être fixé en diagonale avec au
moins deux vis.
Les prises murales et à bride doivent être
montées de telle sorte que l’ouverture
d’enfichage ne soit pas orientée vers le
haut (fig. 2).
Les prises murales peuvent être verrouillées par
ressort sur le porte-appareil COOPER CROUSE-
HINDS, taille 5, en les poussant latéralement
dans la rainure de guidage du côté gauche du
porte-appareil.
Les instructions respectives pour le montage
devront être respectées.
Point de fixation A
prises murale à 7 et 21 pôles
A A
A A
6.1.2 Douilles et chevilles d’enfichage
Le montage des douilles de la prise à 21 pôles
et des chevilles d’enfichage de la fiche à
7 ou 21 pôles est décrit sous le point 6.2.
Pour la mise hors circuit de la prise et pour
retirer la fiche, procédez dans l’ordre inverse.
Après avoir séparé la fiche de la prise, celle-ci
est fermée avec le couvercle, Pos. 5, à
charnière et bloquée avec l’anneau en
baïonnette, Pos. 6, (voir p.18; fig. 1 et 2).
Après un court-circuit dans le circuit, le
fonctionnement de la prise et de la fiche
doit être vérifié.
Etant donné que les contacts de commuta-
tion ne peuvent plus être vérifiés en raison
de l’enveloppe antidéflagrante, l’insert de
commutation complet (prise à bride) devra
être remplacé après des courts-circuits
répétés.
5.2 La fiche et prise à 21 pôles n’a pas
d’interrupteur de verrouillage. Elle peut être
employée jusqu’à 250 V 10 A maxi. Pour
l’emploi de cette fiche et prise (enficher,
séparer etc.) il faudra faire attention aux
points suivants: (voir p.18; fig.3)
Après connexion de la fiche (Pos. 1), l’anneau
en baïonnette de la fiche (Pos. 3) doit être
verrouillé sur la prise (Pos. 2).
Le crochet (Pos. 8) du capot (Pos. 5) sera
alors enclenché dans l’espace prévu à cet
effet (Pos. 7).
Pour dégager le crochet de la prise,
on utilisera un outil pointu (par ex. tournevis
taille 2).
Cela étant fait, la bague-baïonnette (Pos. 3)
peut alors être dégagée et la prise retirée de
la fiche.
Après avoir séparé la fiche de la prise, celle-ci
est fermée avec le couvercle, Pos. 5, à
charnière et bloquée avec l’anneau en
baïonnette, Pos. 6, (voir p.18; fig. 3).
Attention: La prise ne doit pas être enfichée
ou retirée de la fiche sous tension.
Seul l’utilisateur est responsable de l’emploi
conforme de cette fiche et prise, en tenant
compte des conditions générales figurant
dans cette notice (voir Caractéristiques
techniques).
En plein air, les fiches doivent être gardées avec
leur ouverture (côté des broches) vers le bas.
A l’option, elles peuvent être fermées avec les
capuchons protecteurs pour la fiche qui sont
disponibles sur demande (voir catalogue général).
Pour l’emploi, les consignes des sections 3
et 4 devront être respectées.
Des emplois autres que ceux décrits ne sont
admis qu’avec le consentement par écrit de
COOPER CROUSE-HINDS.
Lors de l’exploitation, les instructions
selon point 7 de ce mode d’emploi doivent
être respectées.
16
F
Fiches et prises à 7-pôles GHG 511 .7.. / GHG 592 et à 21 pôles
GHG 511 . 9.. / GHG 591, pour atmosphères explosives
6.3 Entrées de câble (KLE);
bouchons de fermeture
6.3.1 Prise
Généralement, seuls des bouchons de
fermeture et des entrées de câble certifiés
peuvent être utilisés. Pour des câbles
flexibles il faudra utiliser des presses-
étoupes à trompette ou d’autres entrées
convenables avec décharge de traction
supplémentaire.
Lorsque des entrées de câble avec un indice de
protection IP inférieur à celui du dispositif sont
employées (voir page 13), l’indice de protection
IP de l’ensemble sera réduit.
Les directives pour le montage applicables
aux entrées de câble montées doivent être
respectées.
Des ouvertures d’entrée non utilisées doivent
être fermées avec un bouchon de fermeture
certifié pour établir l’indice de protection
minimum.
Lors du montage des entrées de câble il faudra
veiller à ce que des garnitures d’étanchéité
correspondant au diamètre du câble soient
utilisées.
En cas de garnitures qui doivent être coupées
sur mesure, il faudra faire attention à ce que la
garniture soit adaptée au diamètre du câble.
Pour les circuits à sécurité intrinsèque, seules
les entrées de câble EX-i (reconnaissables à leur
couleur bleu clair) devront être utilisées.
Les entrées de câble doivent être serrées à
fond pour maintenir l’indice de protection
minimum.
Au cas où elles seraient forcées, cela pourrait
être nuisible à l’indice de protection.
Toutes les entrées de câble métriques
COOPER CROUSE-HINDS non utilisées
doivent être fermées avec un bouchon de
fermeture certifié pour des entrées de câble
métriques.
6.3.2 Fiche / Prolongateur
Généralement, les garnitures pourvues dans
la fiche ou dans le prolongateur doivent être
utilisées.
Lors du montage du câble, il faut faire attention
à ce que des garnitures convenables pour le
diamètre du câble soient employées.
6.2.3 Connexion des douilles et des
chevilles d’enfichage
Les fils conducteurs isolés du câble de
connexion seront introduits dans l’ouverture
prévue à cet effet (Pos. 10 et 9) à l’aide de la
pince spéciale (Pos. 11 – disponible chez
COOPER CROUSE-HINDS sur demande).
Voir p.18; fig. 9.
Les douilles (Pos. 9) de la fiche à 7 pôles sont
déjà connectées à l’interrupteur de verrouillage.
Ces connexions des douilles et chevilles
peuvent être soudées en employant un boyau
spécial. Après connexion, les douilles et
chevilles doivent être enfoncées jusqu’à la
butée (une pression manuelle suffit) dans la
pièce d’espacement (voir p.18; fig. 8).
Un démontage des douilles et des chevilles est
décrit sous le point 8 (Réparation / Remise en
état) – Voir aussi p.18; fig. 11, 12 et 13.
Les ouvertures des douilles et chevilles non
utilisées seront bouchées avec les douilles et
chevilles supplémentaires (Pos. 9 et 10).
Avant de fermer les fiches, coupleurs et
prises, le bon positionnement des chevilles
et douilles est à vérifier.
Les sections minimales et maximales de
conducteurs devront être respectées (voir
Caractéristiques techniques).
Toutes les vis des bornes de connexion, aussi
celles des bornes non utilisées, doivent être
serrées à fond.
Afin de maintenir le mode de protection
contre l’explosion, le raccordement des
conducteurs doit se faire très soigneusement.
Les bornes sont prévues pour le raccordement
de conducteurs en cuivre.
En cas d’utilisation des câbles de connexion
multifilaires ou à fils de faible diamètre, les
bouts de fils doivent être traités selon la
règlementation nationale et internationale
applicable (par ex. emploi des embouts).
Attention: En cas de perte des vis de
fixation, celles ci devront être remplacées
par des vis semblables ou commandées
chez le constructeur.
6.2 Ouverture du dispositif /
Raccordement électrique
Le raccordement électrique du dispositif ne
doit se faire que par un personnel qualifié
(CEI/EN 60079-14).
L’isolation doit couvrir le conducteur jusqu’à
la borne, au contact mâle ou femelle. Le
conducteur lui-même ne doit pas être
endommagé.
Les sections minimales et maximales
admissibles des conducteurs doivent être
respectées (voir caractéristiques techniques).
Si l’appareil comporte des composants Ex-i
et Ex-e, les distances minimales requises
sont à respecter (voir par ex. CEI/EN 60079-11).
Les conducteurs correctement isolés doivent
être connectés en respect des prescriptions
suivantes (les chevilles et les douilles sont
livrées avec les prises et coupleurs à 21 pôles).
6.2.1 Fiche à 7 pôles (voir p.18; fig. 5 et 6)
1. Dans un premier temps, la pièce de pression
(Pos. 3) de la fiche doit être retirée après
enlèvement des vis (Pos. 2) (voir p.18; fig. 5).
2. Ensuite, les 2 vis de fixation (Pos. 4) de la
douille (Pos. 5) de la fiche seront retirées et
le capot séparé de la pièce d’espacement
(voir p.18; fig 4).
3. La décharge de traction (Pos. 7), ouverte
par enlèvement des vis (Pos. 8), peut alors
être séparée de la pièce d’espacement
(voir p.18; fig. 5 et 6).
4. Les chevilles d’enfichage peuvent alors être
introduites dans les perçages de la pièce
d’espacement.
5. A l‘aide de la décharge de traction, le câble
doit être assuré contre tout risque de
glissement hors de la pièce d’espacement.
La fiche sera montée dans l’ordre inverse
(voir aussi Point 6.4).
6.2.2 Fiche à 21 pôles (voir p.18; fig. 7)
1. Le presse-étoupe trompette (Pos. 15) doit
être retiré de la douille de la fiche (Pos. 5),
après enlèvement du nez de la décharge de
traction (Pos. 14) et des 2 vis cylindriques.
2. Ensuite, les 2 vis de fixation (Pos. 4) de la
douille (Pos. 5) de la fiche seront retirées et
le capot séparé de la pièce d’espacement
3. Les chevilles d’enfichage peuvent alors être
introduites dans les perçages de la pièce
d’espacement.
4. Le câble doit être introduit consécutivement
dans le presse-étoupe (Pos. 15), le joint
d’étanchéité (Pos. 13) et la douille de la fiche
(Pos. 5) (voir p.18; fig. 7).
La fiche sera montée dans l’ordre inverse
(voir aussi Point 6.4).
17
F
Fiches et prises à 7-pôles GHG 511 .7.. / GHG 592 et à 21 pôles
GHG 511 . 9.. / GHG 591, pour atmosphères explosives
4. Retirer les caches (Pos. 19; fig. 12) des
douilles et des chevilles.
5. Séparer (couper / déssouder) la cheville et
les douilles du conducteur avec un outil
de démontage (Pos. 12; fig. 13 de référence
COOPER CROUSE-HINDS GHG590
1903R0001) en libérant le ressort de
verrouillage (Pos. 20), dégager la cheville
et la douille et tirer par l’arrière.
6. Le montage se déroule dans le sens inverse.
Il est également décrit sous le point 6.2.
7. La fermeture du dispositif est décrite sous
le point 6.4.
Toute transformation ou modification de
l’appareil autre que celles décrites ici est
interdite.
Toute transformation ou modification de
l’appareil est interdite.
9 Évacuation des déchets /
Recyclage
Lors de l’évacuation de ce matériel électrique,
la règlementation nationale respective en
vigueur devra être respectée.
En cas d'élimination, vous pouvez obtenir des
informations supplémentaires auprès de votre
branche Cooper Crouse-Hinds.
Pour faciliter la réutilisation des composants
individuels, des pièces en matière plastique
sont repérées de la marque distinctive de la
matière plastique employée.
Sous réserve de modification ou de supplément
de cette série de produits.
7 Maintien / Entretien
La règlementation nationale en vigueur
pour le maintien et l’entretien du matériel
électrique pour atmosphère explosive devra
être respectée (CEI/EN 60079-17).
Avant d’ouvrir l’enveloppe, mettre le
dispositif hors tension ou prendre des
mesures préventives appropriées.
Les intervalles de service requis dépendent de
l’emploi spécifique et devront donc être fixés
par l’utilisateur en tenant compte des condi-
tions d’exploitation.
Lors de l’entretien des appareils, les compo-
sants qui sont essentiels à leur mode de protec-
tion contre l’explosion, devront être vérifiés (par
ex. intégrité des composants antidéflagrants,
de l’enveloppe, des joints d’étanchéité et des
entrées de câble).
Si, lors d’un entretien, on constate que des
travaux d’entretien sont nécessaires, il faudra
suivre le point 8 de ce mode d’emploi.
8 Réparation / Remise en état
Des réparations ne doivent être exécutées
qu’à l’aide de pièces de rechange d’origine
COOPER CROUSE-HINDS.
Si l’enveloppe antidéflagrante est avariée,
seul un remplacement sera admis. En cas de
doute, le dispositif en question devra être
renvoyé à COOPER CROUSE-HINDS pour
être réparé.
Des réparations qui portent sur la protection
contre l’explosion, ne devront être exécutées
que par COOPER CROUSE-HINDS ou par
un électricien qualifié en conformité avec
la règlementation nationale en vigueur
(CEI/EN 60079-19).
Si des chevilles d’enfichage ou des douilles
doivent être changées, on procèdera de la
manière suivante (voir p.18; fig. 11, 12 et 13):
1. L’ouverture de la prise ou de la fiche
est décrite sous le point 6.2.
2. Après ouverture, l’écrou (Pos. 17) de la fiche
est à retirer à l’aide d’un tournevis. Une
torsion de la vis traversante doit être évité.
3. Retirer le cache des chevilles et douilles.
Attention: les caches des douilles peuvent
tomber, c’est pourquoi il est recommandé de
tenir la pièce d’espacement tournée vers le haut.
6.4 Fermeture du dispositif
Lorsque les prises murales sont fermées, il
faut faire attention au montage correct des
entrées de câble.
Lors la pose le couvercle de la prise murale à
7 pôles, veiller à ce que le garrot de l’interrup-
teur soit en position “0” et que l’arbre de
l’interrupteur s’engage dans le trou d’entraîne-
ment du garrot.
Les vis de couvercle doivent être serrées à fond
afin d’assurer l’indice de protection minimum
requis.
Les vis de la fiche et du prolongateur doivent
être serrées à fond.
Après connexion du conducteur, la tubulure en
trompette (Pos. 15) de la prise à 21 pôles et du
coupleur doit être serrée dans la pièce d’espace-
ment de la fiche / douille du coupleur jusqu’à
ce que l’étanchéité soit assurée.
Ensuite, on serrera les vis (Pos. 16) de la
décharge de traction (Pos. 14). Elles sont à
serrer de telle sorte qu’une décharge de
traction suffisante garantisse l’improbabilité
d’un endommagement ou d’une torsion du
câble (voir p.18; fig. 10).
Attention: Un serrage excessif peut
endommager la décharge de traction.
Après avoir effectué correctement la connexion
du câble et vérifié la décharge de traction de la
fiche à 7 pôles, la pièce de pression (Pos. 3)
sera serrée á l’aide des vis (Pos. 4) de manière
à ce que l’étanchéité soit assurée
(voir p.18; fig. 4).
Au cas où elles seraient forcées, cela pourrait
être nuisible à l’indice de protection.
Tout corps étranger doit être ôte du
dispositif.
6.5 Mise en service
Avant la mise en service du matériel, les
vérifications spécifiées dans les règlements
nationaux individuels devront être exécutées.
De plus, il faudra vérifier son fonctionnement et
installation corrects en conformité avec ce
mode d’emploi et avec d’autres règlements
applicables.
Chaque fois que la fiche est enfichée dans la
prise, elle devra d’abord être vérifiée pour des
avaries.
L’utilisateur doit veiller à ce que le même
potentiel terrestre soit appliqué en tout lieu.
L’installation et l’exploitation inadéquates
des fiches et prises peuvent entraîner la
perte de la garantie.
18
Steckerstift /
Pos. 17
Pos. 18
Bild 11 / fig. 11 / fig. 11
Steckereinsatz /
Plug insert /
Insert enfichable Pos. 6
Pos. 2
Pos. 4
Pos. 5
Pos. 6
Bild 1 / fig. 1 / fig. 1
Pos. 5 Pos. 13 Pos. 15
Pos. 4 Pos. 14 Pos. 16
Bild 10 / fig. 10 / fig. 10
Pos.19 Pos.18 Pos.20 Pos.10
Bild 12 / fig. 12 / fig. 12
Pos. 3
Pos. 1
Pos. 2
Pos. 4
Pos. 5
Pos. 6
Bild 2 / fig. 2 / fig. 2
Pos. 2
Pos. 5
Pos. 6
Pos. 8
Pos. 3
Pos. 1
Pos. 7
Pos. 9
Bild 3 / fig. 3 / fig. 3
Pos. 12
Pos. 18
Pos. 20
Pos. 10
Pos. 9
Pos. 10
Bild 13 / fig. 13 / fig. 13
Pos. 6 Pos. 5
Pos. 7 Pos. 8 Pos. 2 Pos. 3
Bild 5 / fig. 5 / fig. 5
Pos. 8 Pos. 7
Pos. 5 Pos. 13 Pos. 2 Pos. 3
Bild 6 / fig. 6 / fig. 6
Pos. 6 Pos. 5 Pos. 4 Pos. 13 Pos. 15
Pos. 10 Pos. 4 Pos. 14
Bild 7 / fig. 7 / fig. 7
Pos. 10 Pos. 11
Pos. 9
Bild 9 / fig. 9 / fig. 9
Bild 8 / fig. 8 / fig. 8
Steckerstift Pos. 10
Bohrung
Steckereinsatz Pos. 6
Pos. 2 Pos. 3
Pos. 6 Pos. 5
Bild 4 / fig. 4 / fig. 4
Pos. 4
Plug pin / Chevilles
d’enfichage /
Pos. 10
19
Notizen / Notes / Remarques
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2018 Eaton
All Rights Reserved
Printed in Germany
dd
Publication No.
GHG 510 7006 P0001 D/GB/F (i)
Auflage / 27.2017 / CS
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Eaton Crouse-Hinds GHG 592 Mode d'emploi

Taper
Mode d'emploi