Astria Fireplaces POLARIS Mode d'emploi

Catégorie
Poêles
Taper
Mode d'emploi

Ce manuel convient également à

INSTALLATION AND OPERATION MANUAL
WARNING
Hot! Do not touch! The glass and surfaces of this appliance will
be hot during operation and will retain heat for a while after
shutting off the appliance. Severe burns may result.
Carefully supervise children in the same room as appliance.
Save These Instructions
For Future Reference
A French manual is available upon request. Order P/N 900189-00.
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la
pièce 900189-00.
This appliance must be properly installed and operated in order to prevent the pos-
sibility of a house fire. Please read this entire installation and operation manual
before installing and using your wood stove. Failure to follow these instruc-
tions could result in property damage, bodily injury or even death. Contact
your local building or fire officials to obtain a permit and information
on any installation requirements and inspection requirements
in your area.
Wood-Burning Stove
Model Tahoma™ 2100
Free-Standing
EPA Certified
Wood-Burning Stoves
P/N 900109-00, Rev. C, 10/2018
P900109-00
CUS
Report # 14-193
2
USING THIS MANUAL
Please read and carefully follow all of the instructions found in this
manual. Please pay special attention to the safety instructions provided
in this manual.
PRODUCT IS SUBJECT TO CHANGE WITHOUT NOTICE
CONGRATULATIONS!
When you purchased your new wood stove, you joined the ranks of
thousands of individuals whose answer to their home heating needs
reflects their concern for aesthetics, efficiency and our environment. We
extend our continued support to help you achieve the maximum benefit
and enjoyment available from your new wood stove.
Thank you for selecting an Innovative Hearth Products, LLC (IHP) Stove
as the answer to your home supplemental heating needs.
TABLE OF CONTENTS
Using This Manual ......................................................................... 2
Important Safety Information ......................................................... 3
Testing Information ........................................................................ 4
Draft Requirements ........................................................................ 4
Selecting the Proper Venting System ............................................. 4
Negative Pressure Warning ........................................................... 5
Clearances to Combustibles ........................................................6-7
Floor Protection ............................................................................. 6
Chimney and Connector ................................................................. 6
Components .................................................................................. 6
Installation Clearances ................................................................... 7
Specifications ................................................................................ 8
Typical Installation Figures ............................................................. 9
Chimney Installation .................................................................... 10
Manufactured (mobile) Home Installations .................................. 10
Chimney - Wall Pass-Through Requirements .............................. 11
Outside Combustion Air Kit Installation ....................................... 12
Brick Installation .......................................................................... 13
Post Installation Checks ............................................................... 14
Paint Curing ................................................................................. 15
Burn-In Period ............................................................................. 15
Operating Hints ............................................................................ 15
Door Operation ........................................................................... 15
Starting and Maintaining a Fire .................................................... 16
Fuel ......................................................................................... 17
Getting the Most Out of Your Stove ............................................. 18
Maximizing Your Stove’s Overall Efficiency .................................. 18
Achieving Clean, Long Burns ....................................................... 18
Optional Blower Kit ..................................................................... 19
Do’s and Don’ts ........................................................................... 20
Smoke Detector Recommended ................................................... 20
Carbon Monoxide Monitor Recommended .................................. 20
Maintenance ................................................................................ 21
Creosote ....................................................................................... 22
Troubleshooting ........................................................................... 23
Replacement Parts Lists .............................................................. 24
Accessories .................................................................................. 25
Safety / Listing Label .................................................................... 26
Warranty ...................................................................................... 27
Product Reference Information .................................................... 28
3
IMPORTANT SAFETY AND WARNING
INFORMATION
READ THIS MANUAL IN ITS ENTIRETY AND UNDER-
STAND THESE RULES TO FOLLOW FOR SAFETY.
1. When this room heater is not properly installed, a house
fire may result. To reduce the risk of fire, follow the instal-
lation instructions. Contact local building or fire officials
about restrictions and installation inspection requirements
in your area.
2. Wear gloves during installation to avoid injury from sharp
edges on the stove and/or its parts.
3. This unit is designed and engineered to burn only dry, well-
seasoned wood. Burning wet wood will greatly reduce the
stove’s efficiency, produce excessive amounts of smoke
and can cause dangerous chimney fires due to creosote
build-up.
4. Before opening the door, the draft control must be fully open
to avoid possible combustion flash (ignition of hot volatile
gases as the door is opened).
5. Never use gasoline, gasoline-type lantern fuel, kerosene,
charcoal lighter fluid, or similar liquids to start or ’freshenup’
a fire in this heater. Keep all such liquids well away from
the heater while it is in use. DO NOT USE CHEMICALS OR
FLUIDS TO START THE FIRE.
6. While burning, fuel utilizes oxygen from the air in the room.
Be sure to allow an adequate amount of fresh air into the
room where the stove is burning.
7. The outside surface of the stove will be hot while burning
properly and can set items like clothing and curtains on
fire. Keep furnishings and other combustible materials
away from the stove. Using the heat from the stove to dry
wet clothing can be hazardous if clothes are placed too
near the surface of the stove.
8. HOT WHILE IN OPERATION. KEEP CHILDREN, CLOTHING
FURNISHINGS AND COMBUSTIBLE MATERIAL A CONSIDER-
ABLE DISTANCE AWAY. CONTACT MAY CAUSE SKIN BURNS.
Do not allow children to play near the stove without close
supervision. Do not touch the stove while it is burning.
Use extreme caution while the unit is in use. Surface tem-
peratures become dangerously hot and can cause serious
burns.
9. Do not allow anyone to operate the stove who is not familiar
with the operating instructions.
10. Attempts to achieve heat output rates that exceed stove
design specifications can result in permanent damage to
the stove. Never leave your stove unattended on high burn
rates. This may cause overfiring. Overfiring the stove may
cause a house fire. If the stove glows, you are overfiring.
11. Keep a water hose or hand-operated fire extinguisher close
for safety.
12. Smoke Detectors - Since there are always several poten-
tial sources of fire in any home, we recommend installing
smoke detectors. If possible, install the smoke detector in
a hallway adjacent to the room (to reduce the possibility
of occasional false activation from the heat produced by
the stove). If your local code requires a smoke detector
be installed within the same room, you must follow the
requirements of your local code. Check with your local
building department for requirements in your area.
13. Inspect your chimney at least once a month during the burn
-
ing season to check for soot and creosote accumulations.
Any accumulations over 1/8” thick should be removed by
a professional chimney sweep. Do not attempt to burn out
heavy creosote accumulations with a hot fire. If large ac
-
cumulations are occurring, review your burning procedures.
14. If a creosote fire should develop, the fire department should
be called immediately and then attempts should be made
to control the fire until assistance arrives. If a “runaway”
fire should develop causing over-heating of the stove, the
door and draft regulators should be closed immediately.
The fire should die down once deprived of oxygen. After a
severe chimney fire, the complete chimney system should
be checked before further use.
15. Do Not Use Grate Or Elevate Fire - Build Wood Fire Directly
On Hearth (firebrick). Do not use andirons or other methods
of supporting the fuel.
16. Please read this entire manual before you install and use
your new room heater. Failure to follow instructions may
result in property damage, bodily injury, or even death.
17. Check all local building and safety codes before installation.
The installation instructions and appropriate code require
-
ments must be followed exactly and without compromise.
In the absence of local codes the following standards and
codes must be followed.
18. In the U.S.A, install in accordance with the National Fire
Protection Association’s Code, NFPA 211, Standards for
Chimneys, Fireplaces, Vents and Solid-Fuel-Burning Appli
-
ances, or similar regulations, may apply to the installation
of a Solid-Fuel-Burning appliance in your area. In Canada,
the guideline is established by the CSA Standard, CAN/
CSA-B365-M93, Installation Code for Solid-Fuel-Burning
Appliances and Equipment.
19. DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY
AIR DISTRIBUTION DUCTWORK UNLESS SPECIFICALLY
APPROVED FOR SUCH INSTALLATIONS.
20. WARNING: BURNING IMPROPER FUEL (I.E. CHARCOAL)
CAN RESULT IN CARBON MONOXIDE POISONING, WHICH
MAY LEAD TO DEATH!
21. Carbon Monoxide Poisoning – Early signs of carbon monox
-
ide poisoning resemble the flu with headaches, dizziness,
or nausea. If you have these signs, get fresh air at once!
Have the heater inspected by a qualified service technician.
Some people are more affected by carbon monoxide than
others. These include pregnant women, people with heart
or lung disease or anemia, those under the influence of
alcohol, and those at high altitudes.
22. Failure to use manufacturer provided parts, variations in
techniques and construction materials or practices other
than those described in this manual may create a fire hazard
and void the limited warranty.
23. Do not make any make-shift compromises during installa
-
tion. Any modification or alteration may result in damage
to the appliance or dwelling and will void the warranty,
certification and listings of this unit.
24. These appliances are designed as supplemental heaters.
Therefore, it is advisable to have an alternate heat source
when installed in a dwelling.
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TESTING INFORMATION
This manual describes the installation and operation of these non-catalytic
wood heaters. These heaters meet the U.S. Environmental Protection
Agency’s emissions limits, and are compliant with 2015 EPA Phase III
particulate emission standards. These heaters have been developed,
tested and constructed in accordance with the requirements of UL 1482,
ULC S627 and HUD standards and are listed by PFS Corporation. These
heaters have been approved for residential and mobile home installations.
Model Emission
Rate
EPA Test Range
BTU/hr
Max. Output
BTU/hr
EPA Default
Efficiency
T2100 3.05 g/hr 10,491 - 30,387 76,000 63% *
DRAFT REQUIREMENTS
This appliance is dependent upon a properly functioning chimney for
optimum performance. It is a high efficiency appliance that loses much
less heat up the chimney than older appliances and fireplaces. For this
reason it is important to match the stove to the chimney. The chimney
has two functions:
1. It draws combustion air into the appliance (without air, no fuel will
burn) and
2. It exhausts combustion by-products. Your new appliance is what is
known as a “natural draft” appliance.
The appliance depends solely on the natural draft of the chimney system
to draw combustion air into the unit. Draft is the force that moves air
from the appliance up into the chimney. The amount of draft in your
chimney depends on the length of the chimney, local geography, nearby
obstructions and other factors. Too much draft may cause excessive
temperatures in the appliance (overfiring). Slow or inadequate draft equals
poor combustion and possible smoking problems.
* Default - Category rating as assigned by the EPA. The estimated efficiency is
as follows: 63% (non-catalyst equipped), 72% (catalyst-equipped), and 78%
(wood pellets). See § 60.536(i)(3) at www.epa.gov.
WARNING
This product can expose you to chemicals includ-
ing Carbon Black, which is known to the State of
California to cause cancer, and Carbon Monoxide,
which is known to the State of California to cause
birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
The following are some conditions that may contribute to poor chimney
draft:
1. A chimney too large for your appliance.
2. A chimney with not enough height to produce adequate draft.
3. A chimney with excessive height (this may allow exhaust to cool too
much before exiting, which will stall the rate the exhaust exits).
4. Offsets in the venting system are too restrictive (see Chimney Guide-
lines).
Inadequate draft will cause the appliance to leak smoke into the room
through the stove and the chimney connector joints.
Excessive draft may cause an uncontrollable burn or a glowing red stove
or chimney part.
Overfiring Damage - If the heater or chimney connector glows, you are
overfiring. Other symptoms may include: Cracking, warping or burning
out of components, stove glass may develop a haze, which will not come
off with cleaning.
Overfiring of a stove is a condition where excessive temperatures are
reached, beyond the design capabilities of the appliance. The damage
that occurs from overfiring is not covered under the manufacturer’s
limited warranty.
Also see Troubleshooting on Page 23.
SELECTING THE PROPER VENTING SYSTEM
The appliance is merely one component of a larger system. The other
equally important component is the venting system. This is necessary for
achieving the required flow of combustion air to the fire chamber and for
safely removing unwanted combustion by-products from the appliance.
If the venting system’s design does not promote these ends, the system
may not function properly. Poorly functioning venting systems may create
performance problems as well as be a safety hazard. A draft test should
read greater than .04’ W.C. (inches water column) and less than .08”
W.C. As per NFPA-211 standard (see paragraph below), the installer
must take into account all variables within the installation and install the
appliance in such a manner that satisfies the draft requirements of the
appliance. See Chimney Guidelines below to assist you in selecting the
proper venting system for your installation.
American National Standards Institute ANSI/NFPA 211, Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances - See
Draft Section: A chimney or vent shall be so designed and constructed
to develop a flow sufficient to completely remove all flue and vent gases
to the outside atmosphere. The venting system shall satisfy the draft
requirements of the connected appliance in accordance with the manu-
facturer’s instructions.
Chimney Guidelines:
This appliance requires approximately 12 feet minimum of “effective
draw” provided by the venting system. As a rule of thumb, every 90
degree total direction change in the venting will result in a loss of
approximately 5 feet of “effective draw.” Example: If two 45 degree
offsets are used, subtract 5 feet from the actual vertical vent height
to determine your “effective draw.” In this case if you had 14 feet of
vertical vent, the effective draw would only be approximately 9 feet
(14 ft. - 5 ft. = 9 ft.), therefore it may be necessary to add additional
height to the venting system.
Do not install an offset within the first two feet above the flue outlet
on the appliance.
In well insulated and weather tight homes, it may be difficult to es-
tablish a good draft up your chimney. The poor draft is caused by a
shortage of air in the house. In this situation an Outside Air Kit may
need to be installed (See Negative Pressure Warning on Page 5 and
Outside Combustion Air on Page 12).
25. Do Not Overfire – If Heater or Chimney Connector Glows,
You Are Overfiring.
26. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
27. DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH
AS GASOLINE, NAPHTHA OR ENGINE OIL.
28. This wood heater has a manufacturer-set minimum low
burn rate that must not be altered. It is against federal
regulations to alter this setting or otherwise operate this
wood heater in a manner inconsistent with operating
instructions in this manual.
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NEGATIVE PRESSURE WARNING
This appliance is not designed to be operated in a negative pressure.
In very airtight homes with large kitchen exhaust fans, furnace cold air
returns, fresh air exchange systems and any other air system in close
proximity to the heating appliance may create a negative pressure in the
same room as the heating appliance. This can create dangerous back
drafting of the stove and chimney joints, drawing combustion by-products
into the home. Be sure your home has adequate makeup air to eliminate
negative pressures caused by the above-mentioned sources. Outside
air connected to the appliance probably will not resolve such a problem
as the appliance is not the source of negative pressure. IHP accepts no
liability for damages resulting from negative pressures described here.
Ventilation Requirements - Provide adequate air for combustion. The
fresh air requirements of this appliance must be met within the space
where it will be installed. Ventilation is essential when using a Solid-Fuel-
Burning heater. In well insulated and weather tight homes, it may be
difficult to establish a good draft up the chimney (caused by a shortage
of air in the home). The lack of air is caused by many common household
appliances which exhaust air from the home (such as a furnace, heat
pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other
fuel burning appliances). Also, the combustion process of this heater
uses oxygen from inside the dwelling. If the available fresh air delivery
in the dwelling is insufficient to support the demands of these appliances,
problems can result (i.e. excessive negative pressure can develop in the
dwelling which will affect the rate at which this appliance can draft thus
resulting in performance problems. To correct this problem it may help
to open a window (preferably on the windward side of the house) or
install an optional outside air kit.
Figure 1 - Chimney Height Requirements
Less than
10' (3 m)
10'
(3 m)
3' (914 mm)
Min.
2’ (610 mm) Min.
(914 mm)
Min.
3'
To pass inspection in nearly any jurisdiction, the chimney must meet both
safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies
to both masonry and factory-built chimneys.
* Ref. USA - National Standard, NFPA 211-latest edition and Canada
National Standard CSA B365-01-latest edition. Vents installed with a
listed cap shall terminate in accordance with the terms of the cap’s
listings.
Chimney Height Requirements
The chimney must extend 3’ (.92m) above the level of roof penetration
and a minimum of 2’ (.61m) higher than any roof surface within 10’ (3m)
(see Figure 1). Check with your local building officials for additional
requirements for your area.
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
CLEARANCES TO COMBUSTIBLES
WARNING: BE ABSOLUTELY SURE THE DISTANCE BETWEEN THE
HEATER AND THE SURFACE OF ANY COMBUSTIBLE CONSTRUC-
TION IS NOT LESS THAN SHOWN IN THE FIGURES ON PAGE 7.
Floor Protection
USA - The floor in front and under the heater must be protected with
noncombustible material. The covering must extend 16” in front of the
door opening of the heater and 8” to either side of the door opening.
Canada - The floor in front and under the heater must be protected with
noncombustible material. The covering must extend 450 mm in front of
the door opening of the heater and 200 mm to either side of the stove
body and 200 mm to the rear or to the wall, whichever is smaller.
USA and Canada - A chimney connector / venting extends horizontally
over the floor, protection must also cover the floor under the connector
/ venting and at least 2” (51 mm) to either side.
CHIMNEY AND CONNECTOR
Minimum 6" diameter, minimum 24 MSG black steel connector pipe with
UL103HT listed factory-built chimney suitable for use with solid fuels
or masonry chimney. Horizontal connection not tested, refer to local
building codes for installation. See installation instructions for details.
Restrictions apply! Read instructions before installing.
Residential chimney systems must be from the same brands as listed
for mobile homes but connector pipe may be double wall, single wall or
single wall with shield as listed above.
This appliance may be vented into a code-approved masonry chimney
with flue liner.
WARNING: CHIMNEY CONNECTOR MUST BE IN GOOD CONDITION AND
KEPT CLEAN. DO NOT INSTALL DAMAGED PARTS.
All of the stove connector pipe used must be of the same brand. The
chimney that the stove pipe transitions into may be a different brand.
Other than the transition of the stove pipe into the chimney, do Not mix
different brand vent components. Install all vent components per vent
manufacturer’s instructions.
The chimney connector shall not pass through an attic or roof space,
closet or similar concealed space, or a floor, or ceiling. Where passage
through a wall, or partition of combustible construction is desired, the
installation shall conform to CAN/CSA-B365, Installation Code for Solid-
Fuel-Burning Appliances and Equipment.
There must be an effective vapor barrier at the location where the chimney
or other component penetrates to the exterior of the structure. Follow the
vent manufacturer's detailed instructions.
IMPORTANT NOTE: See Draft Requirements and Selecting a Proper
Venting System on Page 4 to assist you in choosing the proper venting
system for your installation.
Clearance dimensions are to flue collar. If a single wall connector pipe
with shield is used, a 1 inch air space is needed between pipe and shield.
Shield attaches to rear of stove pipe and must run from stove top to ceil-
ing. Pipe shield shall be UL listed.
7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 4
Figure 3
Footnotes:
1- These dimensions to the stove body are for reference
only. Actual distances should be measured from the
stove’s flue collar.
2- Minimum noncombustible hearth pad dimensions.
3- Clearances to connector pipe shall be measured from
the flue collar of the stove.
Stove
Stove
Stove
Floor
Protection
Floor
Protection
Floor
Protection
Combustible Wall
Combustible Wall
Combustible
Wall
E
USA
E
USA
K
K
J
D
C
B
AL
H
I
TFF
GG
6” Ø Flue
Collar
M
I
Corner Installation
Parallel Installation
Parallel Installation
Figure 2
Top View
Side View Top View
E
Canada
See note 8
USA - inches (millimeters)
PIPE INSTALLATION A (3) B (1) C (3) D (1) E (8) F (1) G (3) H (2)
I
(6) J (2) K (7) L (5) M T (6)
Single Wall Residential 14-1/4 11-1/2 23
13-3/8
8 9 18 37-5/8 49 34-7/8 16 0 84 61-1/2
(362) (292) (584) (340) (200) (229) (457) (956) (1245) (886) (406) (0) (2134) (1562)
Double Wall Residential or Mobile Home 12 9-1/8 19-1/2
9-5/8
8 6 15 37-5/8 46-3/4 34-7/8 16 0 84 57-1/2
(305) (232) (495) (245) (200) (152) (381) (956) (1188) (886) (406) (0) (2134) (1461)
CANADA
- inches (millimeters)
PIPE INSTALLATION A (3) B (1) C (3) D (1) E (8) F (1) G (3) H (2) I (6) J (2) K (7) L (5) M T (6)
Single Wall Residential 14-1/4 11-1/2 23
13-3/8
8 9 18 47-5/8 51 40-7/8 18 8 84 63-1/2
(362) (292) (584) (
340)
(200) (229) (457) (1210) (1295) (1038) (450) (200) (2134) (1613)
Double Wall Residential or Mobile Home 12 9-1/8 19-1/2
9-5/8
8 6 15 47-5/8 48-3/4 40-7/8 18 8 84 59-1/2
(305) (232) (495) (
245
) (200) (152) (381) (1210) (1238) (1038) (450) (200) (2134) (1511)
5- In corner applications, when installed at minimum
back wall clearances, the required floor protection
is dimensioned off the back plane of the stove,
therefore the floor protection required off the
back corners (at a 45 degree angle) only needs
to extend to the wall. This situation will only occur
in CANADA installations.
6- Reference dimension only, to assist in planning
the installation.
7- Measured from front of floor protection to the
front of firebox.
8- USA=8” (200mm) from door opening, Canada=8”
(200mm) from sides and back of unit.
INSTALLATION CLEARANCES - REFER TO FIGURES 2, 3 AND 4
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
SPECIFICATIONS - Tahoma™ 2100 Stove Pipe Diameter
Single Wall or Double Wall 6” (152 mm)
Log Length 20” Max. (508 mm Max.)
Firebox Volume = 2.1 cu. ft.
Cord Wood: u 76,000 BTUs/hr.
Maximum Burn Times u 7-9 hours
Heating Capacity u 1,200 to 2,000 sq. ft.
EPA Grams Per Hour 3.0 gr/hr
EPA Phase II and Washington State Approved
Product Reference Information
Cat. No. Description Ship.
Weight
Ship.
Volume
F2629 Tahoma™ 2100 Wood-Burning Stove 310 lb. 23 cu. ft.
Specifications
The Tahoma™ 2100 woodstove is safety
listed with the following agency:
PFS Corporation, Tested to UL 1482,
ULC S627
Listing
Dimensions
NOTES:
Dimensions shown are approximations only (+/- 1/4”)
Diagrams, illustrations and photographs are not to scale – consult installa-
tion instructions. Product designs, materials, dimensions, specifications,
colors and prices are subject to change or discontinuance without notice.
Approved for residential and manufactured home installations.
Optional Kits Available:
Blower
Outside Air Kit
u Square-foot heating capacities and burn times are approximations only.
Actual performance may vary depending upon home design and insula-
tion, ceiling heights, climate, condition and type of wood used, appliance
location, burn rate, accessories chosen, chimney installation and how the
appliance is operated.
Figure 5
25-7/8”
(657mm)
23-3/8”
(594mm)
26-1/4”
(667mm)
3-3/4” (96mm)
5-3/4” (146mm)
Optional Blower
TOP VIEW
FRONT VIEW
RIGHT SIDE VIEW
1-5/8” (41mm)
9” (229mm)
22-1/4”
(565mm)
25-7/8”
(657mm)
20”
(508mm)
18-3/4”
(476mm)
30-3/8”
(772mm)
21”
(533mm)
23-3/8”
(584mm)
5-3/4”
(146mm)
CUS
Report # 14-193
9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Chimney
Termination
Cap
Storm
Collar
Roof
Flashing
Ceiling Support
Assembly
Slip
Adaptor
Chimney
Connector
6” x 24” 24-gage
black steel or 26
gage blued steel
single wall pipe
Single Wall Pipe
Using 6” Diameter Single Wall Connector Pipe
Figure 6 - Typical Installation
Floor
Protector
Fasten each stove pipe
connection with at least
3 sheet metal screws.
Single wall stove pipe
must not pass through
attics, closets, walls or
ceilings. It is used to
connect this appliance
to a factory built or
masonry chimney.
INSTALL VENTING SYSTEM PER VENT MANUFACTURERS
INSTRUCTIONS!
Fasten stove pipe to
flue collar with 3 sheet
metal screws.
Stove
Side View
TYPICAL INSTALLATIONS YOUR CHIMNEY INSTALLATION MUST COMPLY WITH LOCAL
BUILDING AND FIRE CODES.
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Termination Cap
with Spark Arrestor Remove, if mobile
home is transported
Storm
Collar
Flashing
Support
Box
DVL Close
Clearance
Connector Pipe
Floor
Protector
3 Feet
Minimum
7 Feet
Minimum
Double Wall Pipe
Using 6” Diameter Type L-Vent Connector Pipe
Manufactured (Mobile) Home Installation Shown
Figure 8 - Typical Installation
Minimum of
12-15’ of Flue
to achieve a
stable draft.
Fasten each stove pipe
connection with at least
3 sheet metal screws.
Mobile home installations
require a spark arrestor at the
chimney termination.
All mobile home installa-
tions require an outside
air kit (see Page 24 for
ordering information)
and the stove must be
secured to the floor and
grounded to the mobile
home chassis.
Install Outside
Air Kits per
instructions on
Page 12
INSTALL VENTING SYSTEM PER VENT MANUFACTURERS
INSTRUCTIONS!
Fasten stove pipe to
flue collar using 3
sheet metal screws.
Secure Stove
to floor (2 places)*
Grounded to Steel Chassis using a #8
AGW copper wire or equivalent.
Chassis
Floor
CHIMNEY INSTALLATION
Install chimney as per manufacturer’s instructions. Some brands of
pipe may require removal of the spacer ring in the flue collar.
All horizontal runs of pipe should be as short as possible and are
required by NFPA No. 211 to have an upward pitch or rise in the same
direction the smoke travels of no less than 1/4” to the linear foot. The
connector pipe must meet minimum clearances in any direction to
walls or other combustible materials. It must attach to a listed double
wall metal chimney at least 6” in diameter or to a masonry chimney
with a flue passage of at least 48 square inches.
It is required that a chimney connector pipe not extend further than
the inner wall of the flue when it is connected to a masonry chimney
and that it either be cemented to the masonry or be installed without
cement in a thimble connected to the masonry wall. When the
connector is inserted into a thimble, the joint must be tight enough
so that it will not be dislodged in normal use.
Chimney connector pipes should never pass through a floor, ceiling,
fire wall, partition, or combustible construction of any type unless
certain precautions are taken. The best method is to use a listed
thimble and a listed chimney in accordance with the manufacturer’s
directions. NFPA No. 211 gives approved methods for passing a flue
pipe through combustible constructions (see Page 11).
Manufactured Home Installations (ref. Figure 8)
This appliance is approved for installation into a manufactured
(mobile) home.
Installation should be in accordance with the Mobile Home
Construction and Safety Standard, Title 24 CFR, Part 3280 (in
Canada CAN/CSA Z240 MH), or, when such a standard is not
applicable, the Standard for Mobile Home Installations, ANSI
A225.1.
All mobile home installations require an outside air kit (see Page 24
for ordering information). The stove must be secured to the floor and
grounded to the chassis of the mobile home.
WARNING: DO NOT INSTALL IN SLEEPING ROOM OF A MOBILE
HOME.
CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED.
Approved Chimney - Your stove is approved for use with Class A, UL
103 HT (U.S.) / ULC-S629 (Canada) Listed Residential Type and Building
Heating Appliance Chimney (HT chimney - 2100° Fahrenheit) and double
wall connector pipe. Approved chimney brands are Security Chimneys™,
Jakes Evans/GSW, Dura-vent, Metal Fab, Ameri-Tec, Metalbestos and
Industrial Chimney (ICC).
Clearances to connector shall be measured from 6” flue collar. Restric-
tions apply! Read instructions before installing.
YOUR CHIMNEY INSTALLATION MUST COMPLY WITH LOCAL
BUILDING AND FIRE CODES.
Stove
Side View
Rear Pedestal
Panel
* Remove rear pedestal panel to access
holes (indicated by arrows) for securing
stove to floor.
11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Chimney Connector Systems and Clearances
from Combustible Walls for Residential Heat-
ing Appliances (NFPA 211) - Refer to Figure 9
System A. Minimum 3.5 in. (90 mm) thick brick masonry wall framed
into combustible wall with a minimum of 12 in. (305 mm) brick sepa-
ration from clay liner to combustibles. Fireclay liner (ASTM C 315,
Standard Specification for Clay Flue Linings, or equivalent), minimum
5/8 in. (16 mm) wall thickness, shall run from outer surface of brick
wall to, but not beyond, the inner surface of chimney flue liner and
shall be firmly cemented in place.
Clearance: 12 in. (305 mm)
System B. Solid-insulated, listed factory-built chimney length of the
same inside diameter as the chimney connector and having 1 in. (25.4
mm) or more of insulation with a minimum 9 in. (229 mm) air space
between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of
the masonry chimney flue and shall be sealed to the flue and to the
brick masonry penetration with non-water-soluble refractory cement.
Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not penetrate
the chimney liner.
Clearance: 9 in. (229 mm)
System C. Sheet steel chimney connector, minimum 24 gage [0.024
in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24
gage [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 mm)
air channels, separated from combustibles by a minimum of 6 in. (152
mm) of glass fiber insulation. Opening shall be covered, and thimble
supported with a sheet steel support, minimum 24 gage [0.024 in.
(0.61 mm)] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and
shall be sized to fit and hold chimney section. Fasteners used to secure
chimney section shall not penetrate chimney flue liner.
Clearance: 6 in. (152 mm)
System D. Solid-insulated, listed factory-built chimney length with an
inside diameter 2 in. (51 mm) larger than the chimney connector and
having 1 in. (25.4 mm) or more of insulation, serving as a pass-through
for a single wall sheet steel chimney connector of minimum 24 gage
[0.024 in. (0.61 mm)] thickness, with a minimum 2 in. (51 mm) air
space between the outer wall of chimney section and combustibles.
Minimum length of chimney section shall be 12 in. (305 mm). Chimney
section concentric with and spaced 1 in. (25.4 mm) away from con-
nector by means of sheet steel support plates on both ends of chimney
section. Opening shall be covered, and chimney section supported on
both sides with sheet steel supports of minimum 24 gage [0.024 in.
(0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and
shall be sized to fit and hold chimney section. Fasteners used to secure
chimney section shall not penetrate chimney flue liner.
Clearance: 2 in. (51 mm)
Additional requirements:
1. Insulation material used as part of wall pass-through system shall be of
noncombustible material and shall have a thermal conductivity of 1.0
Btu-in./hr-ft2 - ºF (4.88 kg-cal/hr-m2 - ºC) or less.
2. All clearances and thicknesses are minimums; larger clearances and
thicknesses shall be permitted.
3. Any material used to close up an opening for the connector shall be of
noncombustible material.
4. A connector to a masonry chimney, except for System B, shall extend
in one continuous piece through the wall pass-through system and the
chimney wall to the inner face of the flue liner, but not beyond.
Factory Built
Chimney Length
Air Space – 9 in.
(228.6mm) Min.
Chimney Length
Flush with
Inside of Flue
Min. Clearance
9 in. (229mm)
Chimney
Connector
Use Chimney
Mfrs. Parts to
Attach
Connector
Solid-Insulated
Listed Factory-
Built Chimney
Length
Sheet Steel Supports
Sheet Steel Supports
Sheet Steel Supports
Minimum Chimney Clearance from Masonry to Sheet Steel
Supports & Combustibles – 2 in. (51mm)
Nonsoluble
Refractory
Cement
Minimum chimney clearance to sheet
steel supportrs and combustibles
2 in. (51mm)
Chimney
Connector
2 Air Channels, Each 1
in. (25.4 mm)
2 Ventilated Air
Channels, Each
1 in. (25.4 mm)
Construction of
Sheet Steel
Minimum chimney clearance to sheet steel
supports and combustibles 2 in. (51mm)
Sheet Steel
Supports
Chimney
Connector
Chimney
Section
Air Space – 2 in.
(51mm) Min.
Chimney connector
Chimney length
1 in. (25.4 mm)
air space to
chimney length
Min. Clearance
2 in. (51 mm)
Minimum
12 in.(305mm)
to combustibles
Masonrychimney
constructed to NFPA 211
Masonrychimney
constructed to NFPA 211
Masonry chimney
constructed to NFPA 211
Masonrychimney
constructed to NFPA 211
Minimum chimneyclearancetobrick
andcombustibles2in. (51mm)
Minimum clearance
12 in. (305mm)
of brick
Chimney
Chimney
flue
Chimney
flue
Chimney
flue
connector
Fireclay
liner
Figure 9 - Chimney Connector Systems and Clearances from Combustible Walls
System A
System B
System C
System D
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 12A - Outside Air Connection, Through the Floor
Figure 12B - Outside Air Connection, Through the Wall
OUTSIDE COMBUSTION AIR KIT INSTALLATION
Outside Air Kits
Order:
1 ea. P/N UZIAD Outside Air Coupler Kit (connects outside air ducting, UZI, to
stove)
AND
1 ea. P/N UZI Outside Air Ducting Kit (includes 4” insulated flex x 10’ long)
AND
1 ea. P/N H8874 Outside Air Panel and Air Channel Kit (includes rear pedestal
panel and side and front air channels)
An outside air kit is required in Manufactured (mobile) Home installa-
tions. For residential installations, check with local authorities having
jurisdiction in your area, it may be mandatory.
INSTALLATION INSTRUCTIONS
1. (Manufactured Home Installations Only) Secure stove to floor per
instructions in Figure 8 on Page 10.
2. Install rear pedestal panel as shown in Figure 11.
3. Install Outside Air Coupler - Line up the “V” notch in the coupler with
the “V” notch in the opening on the back of the pedestal (see Figure
11). Push and twist so the rolled edge catches and continue turning
a full 360° to lock the coupler in place.
4. Install Ducting and Air Register (refer to Figures 11 through 13) -
The outside air assembly may be installed according to the following
requirements:
a) Duct length should be kept to a minimum.
b) The air intake register must not be installed more than ten (10)
feet (3050 mm) above the base of the stove.
c) The fresh air must come from outside the house. The air intake
must not draw air from the attic, from the basement or garage.
d) The air intake should be installed where it is not likely to be blocked
by snow or exposed to extreme wind and away from automobile
exhaust fumes, gas meters and other vents.
e) The duct and register may be installed above or below floor level.
- Make a 4-1/4” (110 mm) hole in the outside wall of the house at
the chosen location. From outside, place the outside air register
in the hole (open side down) and fasten the register to the wall,
with screws as shown (see Figures 12B and 13).
- Install the coupler onto the existing collar on stove (see Figure
11).
- Attach the duct to the coupler on stove (see Figures 12A and 12B).
Using the aluminium tape provided, wrap the tape around the joint
between the flexible duct and the air inlet.
5. Install Front and Side Air Channels - Install the front and side air
channels per the instructions in Figure 14 on Page 13.
Figure 13 - Through the Wall, Outside Air Termination
Outside
Intake
OUTDOORS
INDOORS
Screw
Opening
Facing
Down
Wall
Aluminum Tape
Duct
Outside Air Coupler
Outside Air Coupler
Duct
Duct
See Figure 8 on Page 10 for additional Manufactured Home re-
quirements.
Aluminum
Tape
Aluminum
Tape
UZIAD Outside Air Coupler
Rear Pedestal Panel
Figure 11
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 14 - Install Front and Side Air Channels
BRICK INSTALLATION
CAUTION: Wear gloves during brick installation in case of
sharp edges inside the stove.
Measure bricks before installing, as per list of dimensions in Figure 15.
1. Install the brick as shown in Figure 15.
2. The baffle boards are pre-installed. Ensure that they have not moved
during shipping. Make sure all three baffle boards are resting on top
of the secondary tubes, placed edge to edge, and positioned fully
against the rear of the unit.
CAUTION: It is critical that baffle boards are fully against
the rear of the unit.
These brick sizes may be slightly smaller to adjust for steel and
firebrick tolerances beyond our control. Be sure to measure and
mark bricks with their numbers when removing.
WARNING: IF THE BRICKS ARE NOT INSTALLED EXACTLY AS
SHOWN, THEY COULD FALL OUT OF PLACE DURING REFUEL-
ING OR BURNING OF THE STOVE CAUSING SERIOUS INJURY.
Firebox Brick Layout as Viewed from the Front
Figure 15
Brick Sizes
A = 4-1/2”x 9” C = 2-1/8”x 9”
B = 1-1/2”x 9” D = 1-1/2”x 6-3/4”
* Bricks 6 and
10 fit up against
the back of the
firebox.
Figure 16
Firebox
Brick
Baffle Boards
Side Cut-A-Way View of Firebox
1
A
2
A
4
A
5
A10
A
18
B
19
D
11
A12
A13
C
6
A
7
A
8
A
9
C
14 A
15 A
16 A
17 C
20 A
21 A
22 A
23 C
3
B
Side Air Channel
(1 on each side)
Side Air Channel
(1 on each side)
Using the existing screws on the stove, install the front and side air
channels as shown here.
Front Air Channel
Front Air Channel
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Check that all chimney pipe joints are
secured and installed according to the
manufacturers instruction.
If used, make sure the outside air kit is
properly installed and unobstructed.
Double check all stove clearances.
Be sure bricks and baffle boards are
properly installed.
FOR YOUR OWN PROTECTION AND INSURANCE PURPOSES,
HAVE YOUR CHIMNEY AND CONNECTOR PIPE INSTALLATION
INSPECTED BY YOUR LOCAL BUILDING CODE AUTHORITY OR
FIRE MARSHAL BEFORE STARTING A FIRE IN YOUR STOVE.
NOTIFY YOUR INSURANCE COMPANY.
Be sure the stove is properly grounded
Be sure the stove is properly securely
fastened to the floor
Be sure the outside air vent is free of
obstructions and has a mesh screen in place
FOR MOBILE HOME INSTALLS: POST INSTALLATION CHECKS
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
PAINT CURING
Do not close the door tightly during the “Burn-In Period.” Also, open
the door frequently (every 5-10 minutes) to keep the gasket from
adhering to the curing paint. Ventilate the house well during these first
firings as the paint gives off carbon dioxide and unpleasant odors. It is
recommended that persons sensitive to an imbalance in the indoor air
quality avoid the appliance during the curing process.
Your new appliance is painted with a high temperature paint that cures
during the first few firings. We recommend that you put your stove or
fireplace insert through a regimen of three burns. The first two should
last for 20 minutes each at 250 degrees (the appliance should be allowed
to cool completely between each burn). The third should be a burn of
at least 450 degrees F. for 45-60 minutes. The paint will become soft,
gummy and emit non-toxic smoke during these burns. After the appliance
cools down for the third time, the paint will harden. DO NOT BUILD A
LARGE ROARING FIRE UNTIL THIS CURING EFFECT IS COMPLETE
OR YOU MAY DAMAGE THE FINISH OF YOUR STOVE. Spray can
touch-ups should be done only with a high temperature stove paint (cat.
no. H8159), available from all IHP dealers.
OPERATING HINTS
1. Burn only dry, well-seasoned cord wood. In some states it is illegal
to burn wet wood or anything other than clean, dry wood products.
2. Your stove or fireplace insert is designed to operate with the door
closed! Operate only with the door shut tightly at all times except
when loading wood and possibly on start up to establish a draft.
Never leave the unit unattended while the front door is opened.
3. DO NOT contact or move the baffle boards while loading wood. Oc-
casionally check the baffle to assure that the boards are in there correct
location.
4. CAUTION: THE DRAFT CONTROL MUST BE FULLY OPEN BE-
FORE OPENING THE DOOR TO AVOID POSSIBLE COMBUSTION
FLASH!! (Ignition of hot volatile gases as the door is opened).
5. Feeding excessive amounts of fuel to the appliance should be avoided.
It is important to supply it with sufficient draft and fuel to maintain
a moderately hot fire. If, during overnight burns, heavy creosote
deposits develop inside your stove and on the door, the draft is set
too low - review your burning habits!
Opening Door - Lift
handle and pull to
open door
Closing Door - Hold
handle lifted, swing door
closed then push handle
down to engage latch
Handle
Door
DOOR OPERATION
Do not operate the appliance with the door open or ajar other
than possibly during start up to create a draft (Do not leave the
unit unattended while the front door is slightly open during start
up). Operating the appliance with the door open other than in
initial start up if needed will produce extreme temperatures
within the appliance. Damage caused from over-firing is not
covered under the manufacturers limited warranty.
Figure 18
WARNING
Be careful not to abuse door assembly by striking or
slamming it. If the door assembly or glass is broken or
damaged, they must be replaced with factory original
parts before heater can be safely operated. Use only
components provided by the manufacturer as replace-
ment parts.
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Place a small
amount of
crumpled paper
in the front of the
firebox
Cover paper with
a few pieces of
kindling
Light paper
Figure 19
Figure 20
DO NOT LEAVE THE STOVE UNATTENDED WHILE THE FRONT
DOOR IS SLIGHTLY OPEN.
CAUTION: Do Not alter the adjustment range of the draft control
for increased firing for any reason.
Operate only with fuel door closed. Maintain all seals in good
condition. Do not operate with broken glass.
STARTING AND MAINTAINING A FIRE
1. NEVER USE FLAMMABLE LIQUIDS TO START OR REKINDLE
A SOLID FUEL FIRE!!
2. Fully open the primary draft control by placing draft control (wood
handle located on left side of the stove) in the highest position. This
control determines the amount of air entering the stove. Lowering
this control reduces the burn rate of the stove.
3. Place a small amount of crumpled paper in the front of the firebox
and cover it with a few pieces of kindling.
4. Light the paper and allow sufficient time for the kindling to become
fully engulfed in flames. You will now close the wood units front door.
Your wood units front door may or may not need to be left slightly
open during this start up process, this depends on the stove model
and the amount of draft present.
5. When operating any wood burning appliance, it is important to
become familiar with how the damper control affects heat output
and the overall temperature of the appliance. A stove thermom-
eter can be a helpful tool to help ensure you are not over-firing
your appliance and it will also ensure you are burning fuel at a
rate that is most efficient. Place a stove thermometer on the top
of the appliance as shown in Figure 19. Monitor the temperature
every 15 minutes or so until you become more familiar with your
appliance. Close the damper all the way down if you begin to
reach 600 degrees, as this is a sign that you are operating your
appliance at too high a temperature.
SEE MAINTENANCE SECTION FOR GLASS CLEANING GUIDELINES AND
TIPS FOR KEEPING THE GLASS CLEAN (Page 22).
High
Low
Figure 21
6. Once kindling is burning well, larger pieces of wood may be added,
then the door should be fully closed if there was the need to keep it
slightly open during start up.
7. For best results, use smaller pieces of wood to get the appliance
temperature very high before loading larger wood for sustained
burns. If necessary, crack the door to allow ignition of the fuel charge.
Now you can add larger pieces of wood and after several minutes of
high burn, set the left control for the desired heat output. Check the
exhaust in about 15 to 20 minutes (see Figure 22). Large amounts
of smoke indicate an improper burn setting (either too high or too
low). Adjust and recheck in 5 to 10 minutes.
Magnetic Thermometer
(recommended)
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
FUEL
This appliance is designed to burn dry seasoned natural wood only (see
Page 20 for a list of prohibited fuels). Failure to burn proper fuels only
will void the certification and the warranty of the appliance.
Dry, seasoned wood is that which has been cut, split and allowed to dry
under a covered area where air is free to flow and circulate under and
around the wood (not under a tarp or plastic). Make sure wood is not
stacked directly on the ground, it may absorb moisture from the ground.
It should be allowed to dry in these conditions for a minimum of six
months, preferably one year or more. IT MUST BE UNDERSTOOD
THAT WOOD CANNOT BE LEFT IN ANY KIND OF WET OR DAMP
AREA OR IT WILL NEVER BECOME COMPLETELY SEASONED.
Do Not store fuel within space heater installation clearances or within
the space required for refueling and ash removal.
DO NOT OVERFIRE THIS HEATER
Attempts to achieve heat output rates that exceed heater design specifica-
tions can result in permanent damage to the heater.
Figure 22
Figure 23
OK
4'
4'
8'
Standard
Cord of
Wood
What does “Well-Seasoned” mean?
When a tree is cut down, the wood is green, full of sap and moisture.
This moisture content can exceed 80%, which must be reduced to less
than 20%. Wood properly seasoned is then capable of generating the
heat the stove was designed to provide.
Green wood does not burn easily. Attempting to burn green wood often
results in a lot of smoke and very little fire. Time is the most important
factor in seasoning wood. Ideally the moisture content should be reduced
to 11-20%. NOTE: The use of a firewood moisture meter is recommended
to ensure the firewood contains less than 20% moisture.
Seasoning Guide
Softwoods – 6 months to 18 months
Hardwoods – 12 months to 24 months
Logs that are 5” diameter across or larger should be split in half, three
pieces if over 8 inches, and four pieces when over a foot across. If a tree
has been dead for 2 – 4 years it still needs to be cut, split, and seasoned
for 6 to 24 months depending on the wood.
8 Ft.
(2.4M)
4 Ft.
(1.2M)
4 Ft. (1.2M)
18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
ACHIEVING CLEAN, LONG BURNS
To achieve long burn times, after having thoroughly preheated the
stove, load the firebox without blocking the small air opening found
in the center front of the firebox. At this point, you may need to burn
the stove with the draft open for a few minutes to ignite the wood. All
IHP stoves are EPA tested for emissions at low burn with the air control
completely closed. Whether or not you should burn your stove with the
air control completely closed will depend on the following factors:
How you load your wood
Your chimney type, height and draft
Your wood type and its moisture content
The temperature of the appliance
Which model stove or insert you have
In order to maximize the burn time of your stove you may need to experi-
ment to get the right balance of starting temperature, wood type, and
draft control setting for your particular venting configuration. Do not
reload the stove for long burns when the stainless secondary tubes or
baffles are glowing red, or when the stove is uncomfortably hot to load.
This indicates the stove is too hot to load for a long burn.
GETTING THE MOST OUT OF YOUR STOVE
Recent developments in wood-burning technology have made wood-
burning a cleaner and more convenient way to heat your home. Overall
efficiency in a wood-burning appliance is a combination of combustion
efficiency and heat transfer efficiency. Whether heating your entire home or
just a room or two, your understanding of how to best operate your stove
or insert will enhance its overall efficiency and performance. What this
can mean to you is longer, cleaner burns, less wood use and more heat.
The following sections will outline techniques you can use to “get the
most out of your stove.” Please read them carefully.
MAXIMIZING YOUR STOVE’S OVERALL
EFFICIENCY
It is important to know that for clean highly efficient burns you will
need to have sufficient temperatures inside the firebox for thorough
combustion. The best method for determining if you have sufficient
temperatures is to watch the brick lining in your firebox. When you first
light your stove or fireplace insert, the firebrick will turn a dark brown or
black. After 20 to 30 minutes of a hot fire, most of the bricks should return
to near their original beige color. This means the firebrick have reached
a high enough temperature for your stove to achieve high combustion
efficiency and you are ready to adjust the draft control to a lower setting.
Second and just as important, is achieving a high level of heat transfer
efficiency. Slowing the rate of flow through the stove or insert enhances
heat transfer, thus allowing more time for heat to be transferred into your
home. To do this, be sure to thoroughly preheat your stove and then
reduce the amount of primary air by closing the draft control down to a
lower setting. (More air may produce a slightly greater amount of heat,
but will greatly increase wood consumption).
To get the most out of your appliance, you will need to combine good
combustion efficiency with good heat transfer practices. The following
are some tips on how to operate your stove to achieve the highest overall
efficiency.
1. Thoroughly preheat your stove before slowing the burn rate by closing
the draft control.
2. When loading wood into a preheated stove or fireplace insert, allow
a vigorous fire to build before lowering the draft control.
3. Operate your stove as much as possible in the low to medium burn
ranges.
4. Do not lower the draft setting so low as to completely extinguish the
flames in the firebox. Check for at least some small flames twenty
minutes after setting the draft control.
5. Do not continually operate your stove or fireplace insert in the high
(wide open) setting. This wastes wood by carrying a great deal of
heat up the chimney and can damage your stove or fireplace insert
and chimney.
6. Go outside and check your chimney. More than a very small amount
of smoke indicates wasted heat, creosote build up and pollution (see
Figure 22).
19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
WARNING
The blower must be plugged directly into a properly
grounded three-prong receptacle, 120 VAC, 60 Hz, single
phase. Do not cut or remove the grounding prong from
this plug. Do not route power cord under or in front of
appliance.
Installation must be in accordance with National Elec-
trical Code, ANSI/NFPA 70 - latest edition. In Canada,
the current CSA C22.1 Canadian Electrical Code - latest
edition.
DANGER: Disconnect power before servicing blower.
WARNING
In the event that you remove the blower for any reason, the rear heatshield must be returned to its original condi-
tion or replaced before using the heater. Excessive rear wall temperatures will result if the stove is burned with the
blower opening unobstructed.
Figure 24
The optional blower is controlled by a Dial-a-Temp (see Figure 24). It
contains an On/Off line switch with variable speed control from low to
high.
1) Install the optional blower kit per the instructions provided in the
blower kit.
2) Plug the blower power cord into the receptacle on the bottom of the
Dial-A-Temp.
3) Plug the connected Dial-A-Temp into a properly grounded, 120 VAC
wall outlet.
4) To operate, rotate the dial on the Dial-A-Temp clockwise until it clicks
on. Rotate the dial further clockwise for a lower speed, then counter-
clockwise for a higher speed.
NOTE: Turn blower off before opening the door to load the fuel.
OPTIONAL BLOWER KIT
HIGH
LOW
OFF
Blower Assembly
OPTIONAL BLOWER KIT
Dial-A-Temp
(on/off and blower
speed control)
Wall Outlet
1) Plug power cord
into the bottom of
Dial-A-Temp.
2) Plug Dial-A-Temp
into wall outlet.
20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
DO’S AND DON’TS
DO NOT: Install or operate the appliance before reading this manual.
DO NOT: Close the draft beyond the point at which the flames are
completely extinguished.
DO NOT: Open the appliance door without fully opening the draft
first.
DO NOT: Burn driftwood or wood that has been in salt water. This
includes some mill ends and scrap lumber that has been
floated in salt water on the way to the mill. (This will void
your warranty).
DO NOT: Force oversized logs into the firebox as this may dislodge
the baffle assembly.
DO NOT: Close the door tightly during Burn-In Period.
DO: Consult local building department if other than recom-
mended clearances are desired.
DO: Read instructions for the baffle boards occasionally to
ensure you have not bumped or moved them out of place
when loading wood.
DO: Check the chimney and baffle monthly to make sure they are
clean.
DO: Burn seasoned, dry wood only! (RAIN = WET WOOD)
DO: Open the door frequently during Burn-In Period to keep
gasket from adhering to the curing paint.
DO: Enjoy the warm feeling of your new IHP appliance.
Smoke Detector Recommended
Since there are always several potential sources of fire in any home, we
recommend installing smoke detectors. If possible, install the smoke
detector in a hallway adjacent to the room (to reduce the possibility of
occasional false activation from the heat produced by these appliances).
If your local code requires a smoke detector be installed within the same
room, you must follow the requirements of your local code. Check with
your local building department for requirements in your area.
Carbon Monoxide Monitor Recommended
Carbon Monoxide Poisoning: Early signs of carbon monoxide poison-
ing are similar to the flu with headaches, dizziness and/or nausea. If you
have these signs, obtain fresh air immediately. Some people are more
affected by carbon monoxide than others, including pregnant women,
people with heart or lung disease or anemia, those under the influence
of alcohol, and those at high altitudes.
It is against federal regulations to operate wood heaters in a man-
ner inconsistent with operating instructions in the manual.
PROHIBITED FUELS
This heater is designed to burn natural wood only. Higher efficiencies
and lower emissions generally result when burning air dried seasoned
hardwoods, as compared to softwoods or to green or freshly cut hard-
woods. DO NOT BURN:
• Garbage;
Lawn clippings or yard waste;
Materials containing rubber, including tires;
Materials containing plastic;
Waste petroleum products, paints or paint thinners, or asphalt
products;
Materials containing asbestos;
Construction or demolition debris;
Railroad ties or pressure-treated wood;
Manure or animal remains;
Salt water driftwood or other previously salt water saturated mate-
rials;
Unseasoned wood;
Christmas tree branches;
Paper products, colored paper, cardboard, plywood, or particle-
board;
• gasoline;
• naphtha;
engine oil;
flammable liquids;
• solvents;
grease; or
• coal
The prohibition against burning these materials does not prohibit the use
of fire starters made from paper, cardboard, saw dust, wax and similar
substances for the purpose of starting a fire in an affected wood heater.
Burning these materials may result in release of toxic fumes or render the
heater ineffective and cause smoke. Intense firing with these materials
may overheat the fireplace, causing damage to the unit, a fire or even
possibly igniting a chimney fire if the chimney is creosoted. Burning
unapproved fuel, resulting in excessive pollutants being emitted, may be
prohibited and subject to a fine or other penalty by the authority having
jurisdiction in your area.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Astria Fireplaces POLARIS Mode d'emploi

Catégorie
Poêles
Taper
Mode d'emploi
Ce manuel convient également à

dans d''autres langues