wattstopper Contact Input Station Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Vantage
®
Contact Input Station - DIN
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
IS-0584– rev. 2
CIS10-DIN / STIDER121 • Les Numéros de Catalogue • Los Números de Catálogo:
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
OVERVIEW
The DIN Contact Input Station WireLink™ model, CIS10-DIN, features 10 contact
input channels for receiving Dry-Contact Open/Close states from external devices.
Various types of external switches and sensors are available from Vantage and
other third party manufacturers. These include magnetic door contact switches,
momentary switches, motion detectors, stress sensors, humidity and temperature
sensors, smoke and carbon monoxide detectors, driveway probes, etc.
36V stations have a symbol on the
Serial Number sticker. Any station, not
displaying this symbol, , should not
be connected to a 36Volt Station Bus.
CAUTION
SPECIFICATIONS
Description Specication
Dimensions, HWD 3.38” x 6.19” x 2.44” (85.7mm x 157.2mm x 61.9mm)
Weight 7.09oz / 201g
Mounting 35 mm DIN Rail (EN 50 022: 1977)
Number of Contacts 10
Max. Current from +12V 50mA combined
Station Wiring Conguration Daisy-chain / Star / Branch
Station Bus Specication 2C, 16AWG / 1.31mm2, twisted, non-shielded, <30pF per foot. Separate
a minimum of 12” / 30.5cm from other parallel communication and/or
high-voltage runs
Station Equivalent 0.5W on IC-24 / 0.7W on IC-36
Station Bus Connections 24V / 36V Station Bus
LED Indicators Contact State, Program State and Status
Ambient Operating Temperature 32-95°F / 0-35°C
Ambient Operating Humidity 5-95% non-condensing
CE, UL and CUL Listed Yes
SOFTWARE/FIRMWARE
The WireLink and RadioLink models are compatible with InFusion Design Center software. For new projects it is recommended that
rmware and software be kept to the most current release.
Installation of Vantage products should be performed or supervised by a Certied Vantage Installer. There are two methods of
connecting the Station Bus to the Contact Input Relay Station:
1. Using the Station Bus connection on the removable screw terminal connectors.
2. The RadioLink model requires a 15-36VDC, 500mA power supply.
INSTALLATION
2
INSTALLATION (continued)
CONNECTING DEVICE REQUIREMENTS
All low-voltage connections to each Contact Input are wired to removable screw terminal connectors. All 10 Contact Inputs are
available on the bottom of the Station. Each Contact Input can be given custom names in software to facilitate their use in the
installation. Auxiliary 12VDC connections are also available on the DIN CIS screw terminal connectors. There are 4 screw terminal
connections available with a maximum, combined current of 50ma or any single connection with a maximum of 50ma. The ground for
the 12VDC connections is any one of the Contact Input ground connections.
The DIN CIS has two sets of removable screw terminal connectors on the bottom for wiring. Any device that connects to the CIS must
only use the CIS ground for the ground reference. This is often called a “oating” or “isolated” input to the DIN CIS. This isolation can
be provided from several different systems. The most common are door contacts and motion detectors, providing a dry contact relay
connection to the CIS. Battery powered devices that are not connected to other equipment can be used with the DIN CIS. Devices
that are powered from the +12Vdc and CIS ground connections can also be used.
The DIN CIS inputs can accept small voltage levels (0 to 12VDC) instead of dry contacts as long as the voltage is only referenced
to the CIS’s ground. The input will switch the CIS when the voltage reaches the required level. The logic may be reversed in the
software by changing the polarity from Normally Open to Normally Closed. A power level of 0.0VDC to 0.5VDC equals a PRESS,
3.0VDC to 12VDC equals a RELEASE. A 2.0VDC power range is insufcient to toggle an Open/Close state.
EXAMPLE:
NOTE: WIRE RECOMMENDATION-Contact wire runs should be limited to 250 feet / 76.2 meters for each wire run, using a
minimum of 20AWG gauge wire. All connections use 4.4 inch pound torque. Stranded wire recommended.
STATION SET UP IN SOFTWARE
InFusion: First select the room, then click on Vantage Objects in the Object Explorer and expand Stations, WireLink or
Stations, RadioLink. From the list of stations double-click on the DIN Contact Input Station to place it in the room. In the Object
Editor, name the station and make sure it is on the correct Station Bus port. Each contact is also listed in the Object Editor and may
be assigned to a task and given unique names, Polarity and Hold On Time settings.
QLink: In QLink Location view, select the oor and room where the Contact Input Station will be added. Right-click on the room
and select Add DIN Stations. Select Contact Input. The Contact Input Station Box will pop up. Input 10 may be programmed as
an auxiliary input or the Vantage LightPoint Sensor. Each of the buttons on the CIS are programmed identically as Keypad Station
buttons.
PROGRAMMING CONTACT INPUTS
When programming, each Contact Input can trigger any appropriate tasks or functions available in Design Center, and work like a
button press and release. Select switch polarity Normally Open or Normally Closed and set Switch Hold Time (Default hold time of
0.00s, is normally used).
CONFIGURATION WITH WIRELINK MODELS
When the DIN CIS is rst connected to the Station Bus, the Status LED will blink twice followed by a pause, meaning that the station
is connected correctly but not yet congured. From Design Center, click in the Serial Number section in the Object Editor and type in
the serial number. Once congured, the Status LED will blink evenly.
NOTE: The ability to congure a CIS station by pressing any button on the front of the CIS was removed because it was possible
for the station to send unwanted presses during the conguration stage causing a station to receive the wrong serial number. An
example of this happening is as follows: A CIS could have motion detectors connected to it and when walking through a project to
congure stations the person walking could inadvertently cause the motion detectors to send button presses telling the software to
congure the station that was currently highlighted in the Congure Stations window. This could happen on DIN CIS and Standard
CIS stations. Now Button presses received from dry-contacts are ignored when on-line conguration is selected.
CONFIGURATION WITH RADIOLINK MODELS
RadioLink DIN CIS stations need to be congured to associate which physical station goes with the station in software. When the
station is initially powered-up, the Status LED will blink three times followed by a pause - this means the station is powered correctly
but not yet on the network. Before uploading the le to the Vantage system, do the following: From Design Center, click in the Serial
Number section in the Object Editor and type in the serial number. The serial number of each station is located on the station. Record
the number for easy reference when programming. The Main Controller will add to its network and congure all the RadioLink
stations that it has serial numbers for. This may take several minutes depending on the number of RadioLink stations on the network.
The Status LED will blink steadily when a station has been added to the network and congured.
Current CIS State Input Voltage Resulting CIS State
Open < 0.5V Closed (PRESS)
Closed >3.0V Open (RELEASE)
3
DIAGNOSTIC AND TEST INFORMATION
FCC INFORMATION
Each contact input has an actuator button and 2 status LED’s. The actuator button shorts the input to ground. The Contact State LED
illuminates when the contact input is grounded. The Program State LED operates the same as switch LEDs on a keypad station.
When grounded, Contact States trigger the Program State ON or OFF depending on whether the contact’s polarity is set to Normally
Open or Normally Closed.
The Status LED blinks steady on and off for 1, 2, 3 or 4 blinks followed by a pause.
One Even Blink: CIS is operating correctly and is congured
Two Blinks: CIS is operating correctly but is not congured (wired model)
Three Blinks: CIS is not communicating with the Main Controller, verify Station Bus wiring or if it is not yet congured
Four Blinks: Factory problem, please contact the factory
Five Blinks: Conguration mode
*NOTE: A new feature with Design Center 2.3 and up is the ability to congure RadioLink stations the same way WireLink stations
are congured, e.g., 3-button press. When conguring stations, if the Exclude RadioLink Bus check box, under Settings | System
Preferences, is not checked, all RadioLink stations go back to nonprogrammed mode when the Congure Stations button on the tool
bar is clicked. The station’s LEDs will all blink while in congure station mode. After conguring stations and clicking the Congure
Stations button again to turn congure stations mode off, all RadioLink stations need to log back on to the system before working as
programmed. Allow time for this to occur.
INSTALLATION (continued)
RadioLink Model FCC Information
This device contains transmitter module:
FCC ID: PII-VSUB075-1 or PII-VSUB235
IC ID: 3505A-VSUB0751 or 3505A-VSUB235
This device complies with Part 15 of the FFC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
800.879.8585
www.legrand.us/wattstopper
IS-0584 – rev. 2
© Copyright 2020 Legrand All Rights Reserved.
© Copyright 2020 Tous droits réservés Legrand.
© Copyright 2020 Legrand Todos los derechos reservados.
Vantage warranties its products to be free of
defects in materials and workmanship for a period
of five (5) years. There are no obligations or
liabilities on the part of Vantage for consequential
damages arising out of, or in connection with,
the use or performance of this product or other
indirect damages with respect to loss of property,
revenue or profit, or cost of removal, installation or
reinstallation.
Vantage garantit que ses produits sont exempts
de défauts de matériaux et de fabrication pour une
période de cinq (5) ans. Vantage ne peut être tenu
responsable de tout dommage consécutif causé
par ou lié à l’utilisation ou à la performance de
ce produit ou tout autre dommage indirect lié à
la perte de propriété, de revenus, ou de profits,
ou aux coûts d’enlèvement, d’installation ou de
réinstallation.
Vantage garantiza que sus productos están libres
de defectos en materiales y mano de obra por un
período de cinco (5) años. No existen obligaciones
ni responsabilidades por parte de Vantage por
daños consecuentes que se deriven o estén
relacionados con el uso o el rendimiento de este
producto u otros daños indirectos con respecto a
la pérdida de propiedad, renta o ganancias, o al
costo de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
MULTI-VIEW LINE DRAWINGS AND CONNECTION DIAGRAMS
STIDER121
SERIAL NUMBER
3.38”
85.7mm
6.19”/157.2mm
SIDE VIEW
SIDE LABEL ENLARGED
FRONT VIEW
RADIOLINK MODEL TOP LABEL
NOTE: RadioLink Model - Top Label; Power input connection
is 15-36VDC or 12-28VAC, 250mA IN
IN
GND
6
IN
GND
7
IN
GND
8
IN
GND
9
IN
GND
10
+12VDC
OUTPUTS
50mA Max Total
IN
GND
5
IN
GND
4
IN
GND
3
IN
GND
2
IN
GND
1
IN GND
SENSOR
+12V
IR
SENSOR
STATUS
CONTACT INPUT STATION 10 - DIN
CONTACT
STATE
PROGRAM
STATE
1 2 3 4 5 6 7 8 9 10
CIS10-DIN
STATION
BUS
CLASS 2
OPEN ENERGY MANAGEMENT EQUIPMENT
51XT
SERIAL NUMBER
2.44”
61.9mm
CIS10-DIN
Wire Gauge Max.
Screw Torque Max.
Enclosure
Ambient Temperature Max.
DC Input Max.
12 AWG
4.4 in/lb.
Type 1
I
IP20
95°F
I
35°C
12V
For Use With Copper Wire Only
Strip Back Insulation
0.25” / 6.5mm
LOADS:
Stranded - 0.75 - 3.31mm
2
/ 20-14 AWG,
copper wire
STATION BUS:
Vantage Station Bus - (See specifications table)
RECOMMENDED WIRE TYPE
FOR CIS10-DIN SCREW TERMINALS
CIS10-DIN
Wire Gauge Max.
Screw Torque Max.
Enclosure
Ambient Temperature Max.
DC Input Max.
12 AWG
4.4 in/lb.
Type 1
I
IP20
95°F
I
35°C
12V
For Use With Copper Wire Only