Tripp Lite AVRT450U, AVRT65OU & SMART550USB2 UPS Systems Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
UPS Systems
Models:
AVRT450U, AVRT65OU, SMART550USB2
(Series Numbers AG-0300, AG-0303, AG-888E)
Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
Español 11 • Français 21
18-04-268-933853.indb 1 8/8/2018 9:32:40 AM
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the
installation, operation and storage of this product. Failure to heed these warnings
may affect the warranty.
UPS Location Warnings
Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust
or direct sunlight.
For best performance, keep the indoor temperature between 32º F and 104º F
(0º C and 40º C).
Leave adequate space around all sides of the UPS for proper ventilation.
Only set the UPS upright on a sturdy flat surface. Do not block fans or ventilation holes, as
this will seriously inhibit the unit's internal cooling and cause product damage not covered
under warranty.
UPS Connection Warnings
Connect your UPS directly to a properly-grounded AC power outlet. Do not plug the UPS into
itself; this will damage the UPS.
Do not modify the UPS plug, and do not use an adapter that would eliminate the UPS
ground connection.
Do not use extension cords to connect the UPS to an AC outlet.
If the UPS receives power from a motor-powered AC generator, the generator must provide
clean, filtered, computer-grade output.
The mains socket outlet that supplies the UPS should be easily accessible and located near
the UPS.
Equipment Connection Warnings
Install in accordance with National Electrical Code standards ANSI/NFPA
70 and Canadian Electrical Code, Part I, C22.1.
Short circuit backup protection and overcurrent protection is provided by
the building installation.
To reduce the risk of fire, connect only to a circuit provided branch circuit
overcurrent protection in accordance with the National Electrical Code,
ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1. The plug on
the power supply cord is intended to serve as the disconnect device. Be
sure that the socket-outlet is installed near the equipment and is made
easily accessible.
Important Safety Instructions
18-04-268-933853.indb 2 8/8/2018 9:32:40 AM
3
Important Safety Instructions
Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to significantly
affect its safety or effectiveness is not recommended.
Do not connect surge protectors or extension cords to the output of your UPS. This might
damage the UPS and may affect the surge protector and UPS warranties.
Connect the UPS to an outlet that is adequately protected against excess currents, short
circuits and earth faults as part of the building installation.
Battery Warnings
Batteries can present a risk of electrical shock and burn from high short-circuit current.
Observe proper precautions. There are no user-serviceable parts inside the UPS. Do not
open the UPS except to perform battery replacement. Do not open batteries. Do not
short or bridge the battery terminals with any object. Do not dispose of batteries in a fire.
The batteries may explode. Released material is harmful to the skin and eyes. It may be
toxic. Unplug and turn off the UPS before performing battery replacement. Use tools with
insulated handles. Battery replacement should be performed only by authorized service
personnel using the same number and type of batteries (sealed lead-acid). Do not dispose
of the batteries in a fire. Tripp Lite offers a complete line of UPS System Replacement
Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/products/battery-
finder to locate the specific replacement battery for your UPS.
CAUTION: A battery can present a risk of electrical shock and high short-
circuit current. Contact with any part of a grounded battery can result in
electrical shock. The following precautions should be observed when working
on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear rubber gloves.
Do not lay tools or metal parts on top of batteries.
Unplug the UPS from the AC mains receptacle. Disconnect all cables, including the
equipment plugged into the UPS.
UPS and Battery Recycling
Tripp Lite products use sealed lead-acid batteries, which are highly recyclable.
Call Tripp Lite at 1.773.869.1234 or visit www.tripplite.com/support/recycling-
program for more information on recycling the batteries or any other Tripp Lite
product. Please refer to local codes for disposal requirements.
18-04-268-933853.indb 3 8/8/2018 9:32:40 AM
4
STEP 1: Plug the UPS into
a properly grounded outlet.
After plugging the UPS into a wall outlet, press the
power button to turn on the UPS
(See Basic Operation).
Note: The UPS will not turn on automatically in the
presence of live utility power.
STEP 2: Plug your equipment
into the UPS.
There are two sets of outlets on the back of your
UPS. Outlets marked SURGE PROTECTED do not
provide battery backup power during power outages.
Connect common desktop items like printers,
scanners and other accessories not requiring
battery support to these outlets. Outlets marked
BATTERY/SURGE PROTECTED offer UPS battery
backup support during power failures. Connect your
vital computer equipment into these outlets.
Your UPS is designed to support electronic
equipment only. You will overload the UPS if the
total volt-amp (VA) ratings for all the equipment
connected to the BATTERY/SURGE PROTECTED
outlets exceed the UPS output capacity. To find your
equipment’s VA ratings, look on their nameplates.
If the equipment is listed in amps (A), multiply
the number of amps by 120 to determine VA. For
example: 1A × 120 = 120VA. If you suspect you
have overloaded the outlets, check Load Meter
screens (see Display UPS/Power Conditions in
Basic Operation).
If the on-line AC power icon does not illuminate
when the UPS is turned ON, try the following:
1. Make sure that the UPS is plugged into a live AC
outlet.
2. Press the power button to turn on the UPS.
A beep should sound when the UPS starts.
3. If the UPS still does not start, contact Tripp Lite
Tech Support for assistance.
IN OUT
Quick Installation
18-04-268-933853.indb 4 8/8/2018 9:32:41 AM
5
IN OUT
Quick Installation
Optional Installation
Select models (AVRT450U and AVRT650U) include
a USB communication port. The SMART550USB2
model includes tel/DSL/Ethernet surge protection
jacks (not compatible with PoE applications). These
connections are optional, as the UPS will work
properly without these connections.
Basic Operation
UPS ON/OFF
Plug the UPS into a live, grounded outlet.
The green LED will illuminate, the battery charger will engage as necessary and the
SURGE PROTECTED outlets will begin passing power.
Plug equipment into the UPS: You will overload the UPS if the total volt-amp (VA) ratings
for all the equipment connected to the BATTERY/SURGE PROTECTED outlets exceed the
UPS output capacity. To find your equipment’s VA ratings, look on their nameplates. If the
equipment is listed in amps (A), multiply the number of amps by 120 to determine VA. For
example: 1A × 120 = 120VA.
Turn the UPS on: Press the power button . The UPS alarm will beep once briefly.
The BATTERY/SURGE PROTECTED outlets will begin passing AC line power. The UPS will
automatically recharge internal batteries as needed. Once turned on, your UPS is ready
to protect connected equipment from blackouts, brownouts, overvoltages and transient
surges.
Turn the UPS off: Press the power button .
Note: UPS system will function properly upon initial startup; however, maximum runtime for the
unit’s battery will only be accessible after it has been charged for 24 hours.
18-04-268-933853.indb 5 8/8/2018 9:32:41 AM
6
Basic Operation
LED Indicators
Description
Fault
LED (Red)
Battery
LED (Amber)
Online
LED (Green) Alarm
Line Mode Off Off On Off
Battery Mode Off
Flashes Every
10 Seconds
Off Off
Battery Low On
Flashes Every
1 Second
Off
Sounds Every
1 Second
Line Mode
Overload Alert *
Off Off On
Sounds Every
0.5 Second
Battery Mode
Overload Alert **
Off
Flashes Every
1 Second
Off
Sounds Every
0.5 Second
Line Mode
Overload Fault *
On Off Off
Sounds
Continuously
Battery Mode
Overload Fault **
Off Off Off Off
Replace Battery
Flashes Every
Minute
Off On
Sounds Every
Minute
Fault Condition On Off Off
Sounds
Continuously
*Line Mode Overload Alert Condition - 110%±10%, goes to fault after 5 minutes; Overload Fault
Condition - 120%±10%, goes to fault immediately.
**Battery Mode Overload Alert Condition - 110%±10%, shuts down in 5 seconds; Battery Mode Overload
Fault Condition - 120%±10%, shuts down immediately.
18-04-268-933853.indb 6 8/8/2018 9:32:41 AM
7
IN OUT
Features
1
ON/OFF Button: When the UPS is on, press this button to turn the UPS off.
2
LED Indicators: Provide current status of the UPS. For a detailed description, refer to
”LED Indicators” in the Basic Operation section.
3
Battery Backup/Surge Protected Outlets: These outlets offer battery backup support
and premium surge suppression for critical devices requiring battery backup support.
4
Surge Protected Outlets: These outlets offer premium surge suppression for critical
devices.
5
USB Communication Port: This port can connect your UPS to any computer for
automatic saves and unattended shutdown in the event of a power failure. Use with Tripp
Lite’s PowerAlert
®
Software (available as a FREE download at www.tripplite.com) and
the USB cable included with your UPS. This connection is optional; your UPS will work
properly without this connection.
Note: This UPS System provides basic communication compatibility with most integrated Windows
®
,
Macintosh
®
and Linux
®
power management applications.
6
Tel/DSL/Ethernet Line Protection Jacks (SMART550USB2 Model): These jacks
protect equipment against surges over a single phone line or network connection.
Connecting your equipment to these jacks is optional; your UPS will work properly without
this connection.
Note: Not compatible with PoE (Power over Ethernet) applications.
7
Resettable Input Circuit Breaker: Protects your electrical circuit from overcurrent draw
from the UPS load. If this breaker trips, remove some of the load, then reset by pressing
it in.
UPS Features
1 5 6
7
2
4
3
18-04-268-933853.indb 7 8/8/2018 9:32:42 AM
8
Storage
To avoid battery drain, all connected equipment should be turned off and disconnected from
the UPS. Press the power button and disconnect the unit from AC power. Your UPS will be
completely turned off (deactivated), and will be ready for storage. If you plan on storing your
UPS for an extended period, fully recharge the UPS batteries every three months. Plug the
UPS into a live AC outlet, turn it on by pressing the power button and allow the batteries
to recharge for 4 to 6 hours. If you leave your UPS batteries discharged for a long period of
time, they will suffer a permanent loss of capacity.
Storage and Service
Battery Replacement
Under normal conditions, the original battery in your UPS will last several years. Battery
replacement should only be performed by qualified personnel. Refer to “Battery Warnings” in
the Important Safety Instructions section for more information.
Model AVRT450U requires one 12V DC, 7AH replacement battery.
Models AVRT650U and SMART550USB2 require one 12V DC, 9AH replacement battery.
For further information about replacement compatibility and ordering, visit
www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and
quantity: 12V DC sealed lead-acid, 6-cell and in compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove
conductive jewelry such as chains, wristwatches and rings. High energy
passing through conductive materials may cause severe burns.
18-04-268-933853.indb 8 8/8/2018 9:32:42 AM
9
Storage and Service
Product Registration
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You’ll be automatically entered into a
drawing for a chance to win a FREE Tripp Lite product! *
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
Service
A variety of Extended Warranty and On-Site Service Programs are available from Tripp Lite. For
more information on service, visit www.tripplite.com/support.
Before returning your product for service, follow these steps:
1. Review the installation and operation procedures in this manual to ensure that the service
problem does not originate from a misreading of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit
www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Product
Returns link. From here you can request a Returned Material Authorization (RMA) number,
which is required for service. This simple on-line form will ask for your unit’s model and
serial numbers, along with other general purchaser information. The RMA number, along
with shipping instructions, will be emailed to you. Any damages (direct, indirect, special
or consequential) to the product incurred during shipment to Tripp Lite or an authorized
Tripp Lite service center is not covered under warranty. Products shipped to Tripp Lite or an
authorized Tripp Lite service center must have transportation charges prepaid. Mark the
RMA number on the outside of the package. If the product is within its warranty period,
enclose a copy of your sales receipt. Return the product for service using an insured
carrier to the address given to you when you request the RMA.
FCC Part 68 Notice (United States Only)
If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily
discontinue your service. If possible, they will notify you in advance. If advance notice isn’t practical, you will be
notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone
company may make changes in its facilities, equipment, operations or procedures that could affect the proper
operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain
uninterrupted service. If you experience trouble with this equipment’s Modem/Fax Protection, please visit www.
tripplite.com/support for repair/warranty information. The telephone company may ask you to disconnect
this equipment from the network until the problem has been corrected or you are sure the equipment is not
malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This
equipment may not be used on coin service provided by the telephone company. Connection to party lines is
subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)
Regulatory Compliance
18-04-268-933853.indb 9 8/8/2018 9:32:42 AM
10
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V : DC Voltage
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Regulatory Compliance
FCC Notice, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
WARNING: Changes or modifications not expressly approved by the party responsible for compliance could void the
user’s authority to operate the equipment.
Equipment Attachment Limitations (models with the Industry Canada label in Canada only)
NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment
meets the telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements Document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction. Before installing this equipment, users should ensure that it is
permissible to be connected to the facilities of the local telecommunications company. The equipment must also
be installed using an acceptable method of connection. The customer should be aware that the compliance with
the above conditions might not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs
or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications
company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be
particularly important in rural areas. Caution: Users should not attempt to make connections themselves, but
should contact the appropriate electric inspection authority, or electrician, as appropriate.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been
assigned a unique series number. The series number can be found on the product nameplate label, along with
all required approval markings and information. When requesting compliance information for this product, always
refer to the series number. The series number should not be confused with the marking name or model number of
the product.
Tripp Lite has a policy of continuous improvement. Product specifications are subject to change without notice.
18-04-268-933853.indb 10 8/8/2018 9:32:42 AM
11
Sistemas UPS
Modelos:
AVRT450U, AVRT65OU, SMART550USB2
(Números de Serie AG-0300, AG-0303, AG-888E)
Manual del Propietario
1111 W. 35th Street, Chicago, IL 60609 EE. UU. • www.tripplite.com/support
Copyright © 2018 Tripp Lite. Todos los derechos reservados.
English 1 • Français 21
18-04-268-933853.indb 11 8/8/2018 9:32:42 AM
12
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse durante
la instalación, operación y almacenamiento de este producto. La omisión en la
observancia de estas advertencias puede afectar la garantía.
Advertencias para la Ubicación del UPS
Instale su UPS en interiores, alejado de humedad o calor excesivos, contaminantes
conductores, polvo o luz solar directa.
Para mejor desempeño, mantenga la temperatura interior entre 0 ºC y 40 ºC [32 ºF y 104 ºF].
Deje espacio adecuado alrededor de todos los lados del UPS para una ventilación apropiada.
Sólo ponga el UPS en posición vertical sobre una superficie plana sólida. No bloquee los
ventiladores o los orificios de ventilación, ya que inhibirá seriamente el enfriamiento interno
de la unidad y causará daños no cubiertos por la garantía.
Advertencias para la Conexión del UPS
Conecte su UPS directamente a un tomacorrientes de CA conectado correctamente a
tierra. No enchufe el UPS en sí mismo; esto dañará al UPS.
No modifique la clavija del UPS y no use un adaptador que pueda eliminar la conexión a
tierra del UPS.
No use cables de extensión para conectar el UPS a un tomacorrientes de CA.
Si el UPS recibe alimentación de un generador de CA activado por motor, debe probarse
que el generador proporciona una salida de grado computadora, limpia y filtrada.
El tomacorrientes que alimenta al UPS debe ser fácilmente accesible y estar cerca del UPS.
Advertencias para la Conexión del Equipo
Instale de acuerdo con los estándares del Código Eléctrico Nacional ANSI /
NFPA 70 y Código Eléctrico Canadiense, Parte I, C22.1.
La protección de respaldo por corto circuito y la protección contra
sobrecorriente es proporcionada por la instalación del edificio.
Para reducir el riesgo de incendio, conecte solamente a un circuito
provisto de una protección contra sobrecorrientes del circuito derivado
según el Código Eléctrico Nacional, ANSI / NFPA 70 y el Código Eléctrico
Canadiense, parte I, C22.1. La clavija en el cable de alimentación está
diseñada para servir como dispositivo de desconexión. Asegúrese que
el tomacorrientes esté instalado cerca del equipo y sea fácilmente
accesible.
Instrucciones de Seguridad Importantes
18-04-268-933853.indb 12 8/8/2018 9:32:42 AM
13
Instrucciones de Seguridad Importantes
No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde
razonablemente se pueda esperar que la falla de este equipo cause la falla del equipo de
soporte de vida o afectar significativamente su seguridad o efectividad.
No conecte supresores de sobretensiones o cables de extensión a la salida de su UPS.
Esto puede dañar al UPS y afectar las garantías del supresor de sobretensiones y del UPS.
Conecte el UPS a un tomacorrientes que esté adecuadamente protegido contra corrientes
excesivas, cortocircuitos, y fallas de conexión a tierra como parte de la instalación del
edificio.
Advertencias de la Batería
Las baterías pueden presentar un riesgo de descarga eléctrica y quemaduras por la alta
corriente de corto circuito. Observe las precauciones apropiadas. No hay partes dentro
del UPS a las que el usuario pueda dar servicio. No abra el UPS, excepto para realizar el
reemplazo de la batería. No abra las baterías. No ponga en corto o puentee las terminales
de la batería con ningún objeto. No deseche las baterías en el fuego. Las baterías pueden
explotar. El material liberado es dañino a la piel y ojos. Puede ser tóxico. Desenchufe y
apague el UPS antes de reemplazar la batería. Use herramientas con mangos aislados. El
reemplazo de la batería debe realizarlo solo el personal de servicio autorizado usando el
mismo número y tipo de baterías (Plomo-Ácido Selladas). No deseche las baterías en el
fuego. Tripp Lite ofrece una línea completa de Cartuchos de Batería de Repuesto (R.B.C.)
para Sistemas UPS. Para localizar la batería de repuesto específica para su UPS, visite Tripp
Lite en el sitio www.tripplite.com/products/battery-finder.
PRECAUCIÓN: Una batería puede presentar un riesgo de descarga eléctrica
y alta corriente de cortocircuito. Hacer contacto con cualquier parte de una
batería conectada a tierra puede causar una descarga eléctrica. Al trabajar
con baterías deben observarse las siguientes precauciones:
Retire relojes, anillos u otros objetos metálicos.
Use herramientas con mangos aislados.
Use guantes de hule.
No coloque herramientas o partes metálicas sobre la parte superior de las
baterías.
Desconecte el UPS del tomacorrientes de CA de la red pública. Desconecte todos
los cables, incluido el equipo conectado al UPS.
Reciclado de la Batería y el UPS
Los productos de Tripp Lite usan baterías selladas de Plomo-Ácido, que son
altamente reciclables.
Llame a Tripp Lite al 1.773.869.1234 o visite www.tripplite.com/support/recycling-
program para obtener información adicional sobre el reciclado de baterías u otro
producto de Tripp Lite. Para los requisitos de desecho, por favor consulte sus
códigos locales.
18-04-268-933853.indb 13 8/8/2018 9:32:42 AM
14
Enchufe el UPS en
un tomacorrientes activo
conectado a tierra.
Después de enchufar el UPS en un tomacorrientes
en la pared, presione y sostenga el botón de
encendido por un segundo para encender el
UPS (Vea Operación Básica).
Nota: El UPS no encenderá automáticamente en
presencia de energía activa de la red pública.
PASO 2: Enchufe su equipo en
el UPS.
Hay dos juegos de tomacorrientes en la parte
posterior de su UPS. Los tomacorrientes marcados
SURGE PROTECTED no proporcionan respaldo de
energía por batería durante apagones. Conecte
en estos tomacorrientes los equipos de escritorio
comunes como impresoras, escáneres y otros
accesorios que no requieran respaldo por batería.
Los tomacorrientes marcados BATTERY / SURGE
PROTECTED ofrecen respaldo por batería del
UPS durante fallas de energía. Conecte en estos
tomacorrientes su equipo de cómputo vital.
IN OUT
Instalación Rápida
Su UPS está diseñado para soportar solamente equipo electrónico. Usted sobrecargará el
UPS si el valor total en volt-amperes (VA) para todo el equipo conectado a los tomacorrientes
BATTERY / SURGE PROTECTED excede la capacidad de salida del UPS. Para localizar
los valores de VA de su equipo, consulte las placas de identificación. Si el equipo está
especificado en amperes (A), multiplique el número de amperes por 120 para determinar
VA. Por ejemplo: 1A × 120 = 120VA. Si sospecha que ha sobrecargado los tomacorrientes,
vea las pantallas del Medidor de Carga (vea Mostrar Condiciones de UPS / Energía en
Operación Básica).
Si el ícono de alimentación de CA en línea no se enciende cuando el UPS es encendido,
intente lo siguiente:
1. Asegúrese de que el UPS esté conectado a un tomacorrientes de CA.
2. Oprima el botón de encendido para encender el UPS. Sonará un bip cuando el UPS
arranque.
3. Si el UPS aún no arranca, póngase en contacto con Soporte Técnico de Tripp Lite para
solicitar apoyo.
18-04-268-933853.indb 14 8/8/2018 9:32:43 AM
15
IN OUT
Instalación Rápida
Instalación Opcional
Modelos selectos (AVRT450U y AVRT650U)
incluyen un puerto de comunicación USB. El
modelo SMART550USB2 incluye conectores de
supresión de sobretensiones Tel / DSL / Ethernet
(no compatible con aplicaciones PoE). Estas
conexiones son opcionales, el UPS funcionará
adecuadamente sin estas conexiones.
Operación Básica
ENCENDIDO Y APAGADO DEL UPS
Enchufe el UPS en un tomacorrientes activo conectado a tierra.
El LED verde se encenderá, el cargador de la batería se activará según sea necesario y
los tomacorrientes con SUPRESIÓN DE SOBRETENSIONES empezarán a pasar energía.
Enchufe el equipo en el UPS: Usted sobrecargará el UPS si el valor total en volt-amperes
(VA) para todo el equipo conectado a los tomacorrientes BATTERY / SURGE PROTECTED
excede la capacidad de salida del UPS. Para localizar los valores de VA de su equipo,
consulte las placas de identificación. Si el equipo está especificado en amperes (A),
multiplique el número de amperes por 120 para determinar VA.
Por ejemplo: 1A × 120 = 120VA.
Presione el botón de alimentación para encender el UPS . La alarma del UPS emitirá
un bip brevemente. Los tomacorrientes BATTERY / SURGE PROTECTED empezarán a pasar
energía de la línea de CA. El UPS recargará automáticamente las baterías internas según
sea necesario. Una vez encendido, su UPS está listo para proteger los equipos conectados
contra apagones, caídas de voltaje, sobrevoltajes y sobretensiones transientes.
Apague el UPS: Presione el botón de alimentación .
Nota: El sistema UPS funcionará correctamente en el arranque inicial; no obstante, la autonomía
máxima para la batería de la unidad sólo será accesible después de haberse cargado por 24 horas.
18-04-268-933853.indb 15 8/8/2018 9:32:43 AM
16
Operación Básica
Indicadores LED
Descripción
LED
de Falla (Rojo)
LED
de Batería
(Ámbar)
LED
de En Línea
(Verde) Alarma
Modo en Línea Apagado Apagado Encendido Apagado
Modo de
Respaldo por
Batería
Apagado
Destella Cada
10 Segundos
Apagado Apagado
Batería Baja Encendido
Destella Cada
1 Segundo
Apagado
Suena Cada
1 Segundo
Alerta por
Sobrecarga en el
Modo En Línea *
Apagado Apagado Encendido
Suena Cada 0.5
Segundos
Alerta por
Sobrecarga
en el Modo de
Respaldo por
Batería **
Apagado
Destella Cada
1 Segundo
Apagado
Suena Cada 0.5
Segundos
Falla por
Sobrecarga en el
Modo En Línea *
Encendido Apagado Apagado
Suena
Continuamente.
Falla por
Sobrecarga
en el Modo de
Respaldo por
Batería **
Apagado Apagado Apagado Apagado
Reemplace su
Batería
Destella Cada
Minuto
Apagado Encendido
Suena Cada
Minuto
Condición de
Falla
Encendido Apagado Apagado
Suena
Continuamente.
*Condición de Alerta por Sobrecarga en el Modo en Línea - 110% ±10%, se va a falla después de
5 minutos; Condición de Falla por Sobrecarga - 120% ±10%, se va a falla inmediatamente.
**Condición de Alerta por Sobrecarga en el Modo de Respaldo por Batería - 110% ±10%, se apaga en
5 segundos; Condición de Falla por Sobrecarga en el Modo de Respaldo por Batería - 120% ±10%, se
apaga inmediatamente.
18-04-268-933853.indb 16 8/8/2018 9:32:44 AM
17
IN OUT
Características
1
Botón ON/OFF [Encendido / Apagado] : Cuando el UPS está encendido, presione este
botón para apagar el UPS.
2
Indicadores LED: Proporcionan el estado de la corriente del UPS. Para una descripción
detallada, consulte "Indicadores LED" en la sección de Operación Básica.
3
Tomacorrientes con Respaldo por Batería / Con Supresión de Sobretensiones: Estos
tomacorrientes ofrecen soporte de respaldo por batería y supresión de sobretensiones
premium para dispositivos críticos que requieran soporte de respaldo por batería.
4
Tomacorrientes con Supresión de Sobretensiones: Estos tomacorrientes ofrecen
supresión de sobretensiones premium para dispositivos críticos.
5
Puerto de Comunicación USB: Este puerto puede conectar su UPS a cualquier
computadora para guardar los archivos automáticamente y apagar el equipo sin
supervisión en el caso de una falla de energía. Úselo con el Software PowerAlert
®
de Tripp Lite (disponible como descarga gratuita en www.tripplite.com) y el cable
USB incluido con su UPS. Esta conexión es opcional, el sistema UPS funcionará
correctamente sin esta conexión.
Nota: Este Sistema UPS provee compatibilidad de comunicación básica con la mayoría de las
aplicaciones integradas de administración de energía de Windows
®
, Macintosh
®
y Linux
®
.
6
Conectores con Protección de Línea Tel / DSL / Ethernet (Modelo
SMART550USB2): Estos conectores protegen al equipo contra sobretensiones en
una sola línea telefónica o conexión de red. Conectar su equipo a estos conectores es
opcional, el sistema UPS funcionará correctamente sin esta conexión.
Nota: No es compatible con aplicaciones de PoE [Power over Ethernet].
7
Breaker Restaurable del Circuito de Entrada: Protege su circuito eléctrico de un
consumo de corriente superior a la carga del UPS. Si se dispara este breaker, retire algo
de la carga y entonces restablézcalo oprimiéndolo.
Características del UPS
1 5 6
7
2
4
3
18-04-268-933853.indb 17 8/8/2018 9:32:44 AM
18
Almacenamiento
Para evitar la descarga de la batería, todo el equipo conectado debe ser apagado y
desconectado del UPS. Presione el botón de encendido y desconecte la unidad de
la alimentación de CA. Su UPS se apagará totalmente (desactivado) y estará listo para
almacenamiento. Si planea guardar el sistema UPS por un período prolongado, recargue
completamente las baterías del UPS cada tres meses. Enchufe el UPS en una salida de CA
activa, enciéndalo presionado el botón de alimentación y permita que las baterías se
recarguen de 4 a 6 horas. Si usted deja sus baterías del UPS descargadas por un período
prolongado, sufrirán una pérdida permanente de capacidad.
Almacenamiento y Servicio
Reemplazo de la Batería
Bajo condiciones normales, la batería original de su UPS durará varios años. El reemplazo
de la batería debe llevarse a cabo únicamente por personal calificado. Para información
adicional, refiérase a “Advertencias para la Batería” en las Advertencias de Seguridad
Importantes.
El modelo AVRT450U requiere una batería de repuesto de 12V CD, 7Ah.
Los modelos AVRT650U y SMART550USB2 requieren una batería de repuesto de 12V CD, 9Ah.
Para más información sobre compatibilidad de reemplazo y pedidos, visite
www.tripplite.com/products/battery-finder.
El reemplazo de la batería debe hacerse usando el mismo tipo y
cantidad de baterías: 12V CD selladas de plomo ácido, 6 celdas y en
conformidad con UL 1989.
PRECAUCIÓN: Riesgo de energía. Antes de reemplazar las baterías, retírese
toda la joyería conductora tal como cadenas, relojes de pulsera y anillos.
La alta energía pasando a través de materiales conductores puede causar
quemaduras graves.
18-04-268-933853.indb 18 8/8/2018 9:32:44 AM
19
Almacenamiento y Servicio
Servicio
Están disponibles una gran variedad de Programas de Garantía Extendida y Servicio En Sitio por
parte de Tripp Lite. Para información adicional acerca del servicio, visite www.tripplite.com/support.
Antes de regresar su producto para servicio, siga estos pasos:
1. Revise los procedimientos de instalación y operación en este manual para asegurar que el
problema de servicio no se origina por una mala lectura de las instrucciones.
2. Si el problema persiste, no se ponga en contacto ni regrese el producto al distribuidor. En
vez de ello, visite www.tripplite.com/support.
3. Si el problema requiere servicio, visite www.tripplite.com/support y haga click en la
liga Product Returns. Desde aquí usted puede solicitar un número de Autorización de
Devolución de Mercancía (RMA) que se requiere para servicio. Esta sencilla forma en
línea le solicitará los números de modelo y serie de su unidad junto con otra información
general del comprador. El número de RMA junto con las instrucciones de embarque
le serán enviadas por correo electrónico. Cualquier daño (directo, indirecto, especial
o consecuente) al producto incurrido durante el embarque a Tripp Lite o un Centro
de Servicio Autorizado de Tripp Lite no está cubierto bajo la garantía. Los productos
embarcados a Tripp Lite o un Centro de Servicio Autorizado de Tripp Lite deben tener
cargos de transporte prepagados. Marque el número de RMA en el exterior del empaque.
Si el producto está dentro del período de garantía, adjunte una copia de su recibo de
venta. Regrese el producto para servicio usando un transportista asegurado a la dirección
proporcionada a usted cuando requirió la RMA.
18-04-268-933853.indb 19 8/8/2018 9:32:44 AM
20
Notas sobre la etiqueta
Dos símbolos se usan en la etiqueta:
V~ : Voltaje de CA
V : Voltaje de CD
1111 W. 35th Street, Chicago, IL 60609 EE. UU. • www.tripplite.com/support
Cumplimiento de las Regulaciones
Números de Identificación de Conformidad Regulatoria
Para el propósito de certificaciones e identificación de conformidad con las normas, su producto Tripp Lite
ha recibido un número de serie exclusivo. El número de serie se puede encontrar en la etiqueta de placa de
identificación, junto con todas las marcas e información requeridas de aprobación. Al solicitar información de
conformidad para este producto, refiérase siempre al número de serie. El número de serie no debe confundirse
con el nombre de la marca o el número de modelo del producto.
Tripp Lite tiene una política de mejora continua. Las especificaciones del producto están sujetas a cambios sin
previo aviso.
18-04-268-933853.indb 20 8/8/2018 9:32:44 AM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Tripp Lite AVRT450U, AVRT65OU & SMART550USB2 UPS Systems Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire