Tripp Lite SMART750TSU & SMART1050TSU Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
UPS Systems
Models:
SMART750TSU, SMART1050TSU
(Series Numbers: AG-888F, AG-8890)
Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite. All rights reserved.
Español 13 • Français 25
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
18-12-064-933901.indb 1 1/9/2019 5:01:22 PM
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the
installation, operation, maintenance and storage of the UPS and batteries. Failure
to heed these warnings may affect the warranty.
UPS Location Warnings
Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust
or direct sunlight.
For best performance, keep the indoor temperature between 32º F and 104º F
(0º C and 40º C).
Leave adequate space around all sides of the UPS for proper ventilation.
Only set the UPS upright on a sturdy flat surface. Do not block fans or ventilation holes, as
this will seriously inhibit the unit's internal cooling and cause product damage not covered
under warranty.
UPS Connection Warnings
Connect your UPS directly to a properly-grounded AC power outlet. Do not plug the UPS into
itself; this will damage the UPS.
Do not modify the UPS plug, and do not use an adapter that would eliminate the UPS
ground connection.
Do not use extension cords to connect the UPS to an AC outlet.
If the UPS receives power from a motor-powered AC generator, the generator must provide
clean, filtered, computer-grade output.
The mains socket outlet that supplies the UPS should be easily accessible and located near
the UPS.
Equipment Connection Warnings
Install in accordance with National Electrical Code standards ANSI/NFPA
70 and Canadian Electrical Code, Part I, C22.1.
Short-circuit backup protection and overcurrent protection is provided by
the building installation.
To reduce the risk of fire, connect only to a circuit provided branch circuit
overcurrent protection in accordance with the National Electrical Code,
ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1. The plug on
the power supply cord is intended to serve as the disconnect device. Be
sure that the socket-outlet is installed near the equipment and is made
easily accessible.
Important Safety Instructions
18-12-064-933901.indb 2 1/9/2019 5:01:23 PM
3
Important Safety Instructions
Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to significantly
affect its safety or effectiveness is not recommended.
Do not connect surge protectors or extension cords to the output of your UPS. This might
damage the UPS and may affect the surge protector and UPS warranties.
Connect the UPS to an outlet that is adequately protected against excess currents, short
circuits and earth faults as part of the building installation.
Battery Warnings
Batteries can present a risk of electrical shock and burn from high short-circuit current.
Observe proper precautions. There are no user-serviceable parts inside the UPS. Do not
open the UPS except to perform battery replacement. Do not open batteries. Do not
short or bridge the battery terminals with any object. Do not dispose of batteries in a fire.
The batteries may explode. Released material is harmful to the skin and eyes. It may be
toxic. Unplug and turn off the UPS before performing battery replacement. Use tools with
insulated handles. Battery replacement should be performed only by authorized service
personnel using the same number and type of batteries (sealed lead-acid). Do not dispose
of the batteries in a fire. Tripp Lite offers a complete line of UPS System Replacement
Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/products/battery-
finder to locate the specific replacement battery for your UPS.
CAUTION: A battery can present a risk of electrical shock and high short-
circuit current. Contact with any part of a grounded battery can result in
electrical shock. The following precautions should be observed when working
on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source and load prior to installing or maintaining the battery.
Remove battery grounds during installation and maintenance to reduce likelihood
of shock.
Remove the connection from ground if any part of the battery is determined to be
grounded.
UPS and Battery Recycling
Tripp Lite products use sealed lead-acid batteries, which are highly recyclable.
Call Tripp Lite at 1.773.869.1234 or visit www.tripplite.com/support/recycling-
program for more information on recycling the batteries or any other Tripp Lite
product. Please refer to local codes for disposal requirements.
18-12-064-933901.indb 3 1/9/2019 5:01:23 PM
4
STEP 1: Plug the UPS into
a properly grounded outlet.
After plugging the UPS into a wall outlet, press
and hold the power button until the alarm starts to
sound, then release to turn on the UPS.
Note: The UPS will not turn on automatically in the
presence of live utility power.
STEP 2: Plug your equipment
into the UPS.
There are two sets of outlets on the back of your
UPS. Outlets marked SURGE PROTECTED do not
provide battery backup power during power outages.
Connect common desktop items like printers,
scanners and other accessories not requiring
battery support to these outlets. Outlets marked
BATTERY/SURGE PROTECTED offer UPS battery
backup support during power failures. Connect your
vital computer equipment into these outlets.
Your UPS is designed to support electronic
equipment only. You will overload the UPS
if the total volt-amp (VA) ratings for all the
equipment connected to the BATTERY/SURGE
PROTECTED outlets exceed the UPS output
capacity. To find your equipment’s VA ratings,
look on their nameplates. If the equipment is
listed in amps (A), multiply the number of amps
by 120 to determine VA. For example: 1A ×
120 = 120VA.
If the color LCD panel does not illuminate when the
UPS is turned ON, try the following:
1. Make sure that the UPS is plugged into a live AC
outlet.
2. Press the power button to turn on the UPS. A
beep should sound when the UPS starts.
3. If the UPS still does not start, contact Tripp Lite
Tech Support for assistance.
Quick Installation
18-12-064-933901.indb 4 1/9/2019 5:01:23 PM
5
Quick Installation
Optional Installation
All models include a USB communication port
and tel/DSL/Ethernet surge protection jacks (not
compatible with PoE applications). Select models
will also include an RS-232 serial port. These
connections are optional, as the UPS will work
properly without them.
Basic Operation
UPS ON/OFF
Plug the UPS into a live, grounded outlet.
The entire LCD screen will illuminate for 5 seconds, then the display will report output
voltage of “0V”. The BATTERY / SURGE PROTECTED outlets will be OFF and the SURGE
ONLY outlets will be ON. The battery charger will engage as necessary.
Plug equipment into the UPS: You will overload the UPS if the total volt-amp (VA) ratings
for all the equipment connected to the BATTERY/SURGE PROTECTED outlets exceed the
UPS output capacity. To find your equipment’s VA ratings, look on their nameplates. If the
equipment is listed in amps (A), multiply the number of amps by 120 to determine VA. For
example: 1A × 120 = 120VA.
Turn the UPS on: Press and hold the power button until the alarm begins to sound, then
release. The UPS alarm will beep once briefly. The BATTERY/SURGE PROTECTED outlets
will begin passing AC line power. The UPS will automatically recharge internal batteries
as needed. Once turned on, your UPS is ready to protect connected equipment from
blackouts, brownouts, overvoltages and transient surges.
Turn the UPS off: Press the power button.
Note: The UPS system will function properly upon initial startup; however, maximum runtime for the unit’s
battery will only be accessible after it has been charged for 24 hours.
18-12-064-933901.indb 5 1/9/2019 5:01:23 PM
6
Basic Operation
Display UPS/Power Conditions
On-Line AC Power Mode LCD Data
The LCD touchscreen offers 5 screens of UPS and site power information when the UPS
is operating in on-line power mode. Screens 1-4 (Output Voltage, Input Voltage, Load %,
Battery Charge Level) are available for viewing in on-line power mode. Press the front panel
LCD to advance to the next screen. Screen #5 (Overload) is displayed automatically only
when the UPS is loaded to levels greater than 100%.
The LCD screen reports that AVR (Auto Voltage Regulation) buck/boost circuits are active any
time the on-line power symbol is flashing.
1
4
2
5
3
1
Output Voltage
2
Input Voltage
3
Load %
4
Battery Charge Level
5
Overload
Operating Mode Alarm Description
Battery Mode Normal No Alarm
Battery Low Sounds Every Second
Overload Sounds Every 0.5 Second
On-Line Mode Normal No Alarm
Overload Sounds Every 0.5 Second
Battery Replace Sounds Every Minute
Fault Mode Sounds Continuously
Note: The LCD touchscreen automatically turns off in on-line power mode 20 seconds after it was last
touched. To re-activate the LCD for an additional 20 seconds, touch the screen.
18-12-064-933901.indb 6 1/9/2019 5:01:23 PM
7
Basic Operation
Battery Power Mode LCD Data
The LCD touchscreen offers 5 screens of UPS and site power information when the UPS
is operating in battery power mode. Screens 1-4 (Output Voltage, Input Voltage, Load %,
Battery Charge Level) are available for viewing in battery power mode. Press the front panel
LCD to advance to the next screen. Screen #5 (Overload) is displayed automatically only
when the BATTERY/SURGE PROTECTED outlets are loaded to levels greater than 100%.
Critical Fault Screens
Error Code Critical Fault Solution
F01 OUTPUT SHORT Disconnect load(s) from UPS outlets. Power off UPS and
contact Tripp Lite Technical Support for assistance.
F02 OVERLOAD Remove excess load, check load meter on LCD for load
status.
F03 OVERCHARGE Turn unit off, unplug UPS and contact Tripp Lite
Technical Support for assistance.
F04 BATTERY LOW
VOLTAGE
Charge UPS for 24 hours. If problem persists, replace
battery and contact Tripp Lite Technical Support if
problem persists.
F05 BATTERY MODE
HIGH OUTPUT
Turn off power to the UPS and contact Tripp Lite
Technical Support for assistance.
1
4
2
5
3
1
Output Voltage
2
Input Voltage
3
Load %
4
Battery Charge Level
5
Overload
Note: The LCD touchscreen will remain ON continuously during battery mode operation.
18-12-064-933901.indb 7 1/9/2019 5:01:24 PM
8
Features
UPS Features
12
All Models
5
3
4
8
7
6
18-12-064-933901.indb 8 1/9/2019 5:01:24 PM
9
Features
1
ON/OFF Button: When the UPS is OFF, press and hold the ON/OFF button until a beep
is heard to turn the UPS ON. When the UPS is ON, press and hold the ON/OFF button to
turn the UPS OFF.
2
LCD Touchscreen Panel: Provides current status of the UPS. For a detailed description,
refer to “Display UPS/Power Conditions” in the Basic Operation section.
3
Battery Backup/Surge Protected Outlets: These outlets offer battery backup support
and premium surge suppression for critical devices requiring battery backup support.
4
Surge Protected Outlets: These outlets offer premium surge suppression for critical
devices.
5
USB and RS-232* Communication Ports: These port can connect your UPS to
any computer for automatic saves and unattended shutdown in the event of a power
failure. Use with Tripp Lite’s PowerAlert
®
Software (available as a FREE download at
www.tripplite.com) and the USB cable included with your UPS. These connections are
optional, your UPS will work properly without this connection.
*All models include a USB communication port. Select models also include an RS-232 serial port.
Note: This UPS System provides basic communication compatibility with most integrated Windows
®
,
Macintosh
®
and Linux
®
power management applications.
6
Tel/DSL/Ethernet Line Protection Jacks: These jacks protect equipment against surges
over a single phone line or network connection. Connecting your equipment to these
jacks is optional; your UPS will work properly without this connection.
Note: Not compatible with PoE (Power over Ethernet) applications.
7
Resettable Input Circuit Breaker: Protects your electrical circuit from overcurrent draw
from the UPS load. If this breaker trips, remove some of the load, then reset by pressing
it in.
8
Fan: Provides cooling during AVR mode or when the UPS is operating in battery mode.
18-12-064-933901.indb 9 1/9/2019 5:01:24 PM
10
Storage
To avoid battery drain, all connected equipment should be turned off and disconnected from
the UPS. Press the power button and disconnect the unit from AC power. Your UPS will be
completely turned off (deactivated), and will be ready for storage. If you plan on storing your
UPS for an extended period, fully recharge the UPS batteries every three months. Plug the
UPS into a live AC outlet and allow the batteries to recharge for 4 to 6 hours. If you leave
your UPS batteries discharged for a long period of time, they will suffer a permanent loss of
capacity.
Storage and Service
Battery Replacement
Under normal conditions, the original battery in your UPS will last several years. Battery
replacement should only be performed by qualified personnel. Refer to “Battery Warnings” in
the Important Safety Instructions section for more information.
All models require two 12V DC, 9Ah replacement batteries (Tripp Lite model: RBC51).
For further information about replacement compatibility and ordering, visit
www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and
quantity: 12V DC sealed lead-acid, 6-cell and in compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove
conductive jewelry such as chains, wristwatches and rings. High energy
passing through conductive materials may cause severe burns.
18-12-064-933901.indb 10 1/9/2019 5:01:24 PM
11
Storage and Service
Product Registration
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You’ll be automatically entered into a
drawing for a chance to win a FREE Tripp Lite product! *
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
Service
A variety of Extended Warranty and On-Site Service Programs are available from Tripp Lite. For
more information on service, visit www.tripplite.com/support.
Before returning your product for service, follow these steps:
1. Review the installation and operation procedures in this manual to ensure that the service
problem does not originate from a misreading of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit
www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Product
Returns link. From here you can request a Returned Material Authorization (RMA) number,
which is required for service. This simple on-line form will ask for your unit’s model and
serial numbers, along with other general purchaser information. The RMA number, along
with shipping instructions, will be emailed to you. Any damages (direct, indirect, special
or consequential) to the product incurred during shipment to Tripp Lite or an authorized
Tripp Lite service center is not covered under warranty. Products shipped to Tripp Lite or an
authorized Tripp Lite service center must have transportation charges prepaid. Mark the
RMA number on the outside of the package. If the product is within its warranty period,
enclose a copy of your sales receipt. Return the product for service using an insured
carrier to the address given to you when you request the RMA.
FCC Part 68 Notice (United States Only)
If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily
discontinue your service. If possible, they will notify you in advance. If advance notice isn’t practical, you will be
notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone
company may make changes in its facilities, equipment, operations or procedures that could affect the proper
operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain
uninterrupted service. If you experience trouble with this equipment’s Modem/Fax Protection, please visit www.
tripplite.com/support for repair/warranty information. The telephone company may ask you to disconnect
this equipment from the network until the problem has been corrected or you are sure the equipment is not
malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This
equipment may not be used on coin service provided by the telephone company. Connection to party lines is
subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)
Regulatory Compliance
18-12-064-933901.indb 11 1/9/2019 5:01:24 PM
12
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V : DC Voltage
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Regulatory Compliance
FCC Notice, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
WARNING: Changes or modifications not expressly approved by the party responsible for compliance could void the
user’s authority to operate the equipment.
Equipment Attachment Limitations (models with the Industry Canada label in Canada only)
NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment
meets the telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements Document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction. Before installing this equipment, users should ensure that it is
permissible to be connected to the facilities of the local telecommunications company. The equipment must also
be installed using an acceptable method of connection. The customer should be aware that the compliance with
the above conditions might not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs
or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications
company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be
particularly important in rural areas. Caution: Users should not attempt to make connections themselves, but
should contact the appropriate electric inspection authority, or electrician, as appropriate.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been
assigned a unique series number. The series number can be found on the product nameplate label, along with
all required approval markings and information. When requesting compliance information for this product, always
refer to the series number. The series number should not be confused with the marking name or model number of
the product.
Tripp Lite has a policy of continuous improvement. Product specifications are subject to change without notice.
18-12-064-933901.indb 12 1/9/2019 5:01:24 PM
13
Sistemas UPS
Modelos:
SMART750TSU, SMART1050TSU
(Números de Serie: AG-888F, AG-8890)
Manual del Propietario
1111 W. 35th Street, Chicago, IL 60609 EE UU • www.tripplite.com/support
Copyright © 2019 Tripp Lite. Todos los derechos reservados.
English 1 • Français 25
18-12-064-933901.indb 13 1/9/2019 5:01:24 PM
14
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse durante
la instalación, operación, mantenimiento y almacenamiento del UPS y baterías. El
incumplimiento de estas advertencias puede afectar la garantía.
Advertencias para la Ubicación del UPS
Instale su UPS en interiores, alejado de humedad o calor excesivos, contaminantes
conductores, polvo o luz solar directa.
Para mejor desempeño, mantenga la temperatura interior entre 0 ºC y 40 ºC
[32 ºF y 104 ºF].
Deje espacio adecuado alrededor de todos los lados del UPS para una ventilación
apropiada.
Sólo ponga el UPS en posición vertical sobre una superficie plana sólida. No bloquee los
ventiladores o los orificios de ventilación, ya que inhibirá seriamente el enfriamiento interno
de la unidad y causará daños no cubiertos por la garantía.
Advertencias para la Conexión del UPS
Conecte su UPS directamente a un tomacorrientes de CA conectado correctamente a
tierra. No enchufe el UPS en sí mismo; esto dañará al UPS.
No modifique la clavija del UPS y no use un adaptador que pueda eliminar la conexión a
tierra del UPS.
No use cables de extensión para conectar el UPS a un tomacorrientes de CA.
Si el UPS recibe alimentación de un generador de CA activado por motor, debe probarse
que el generador proporciona una salida de grado computadora, limpia y filtrada.
El tomacorrientes que alimenta al UPS debe ser fácilmente accesible y estar cerca del UPS.
Advertencias para la Conexión del Equipo
Instale de acuerdo con los estándares del Código Eléctrico Nacional ANSI /
NFPA 70 y Código Eléctrico Canadiense, Parte I, C22.1.
La protección de respaldo por corto circuito y la protección contra
sobrecorriente es proporcionada por la instalación del edificio.
Para reducir el riesgo de incendio, conecte solamente a un circuito
provisto de una protección contra sobrecorrientes del circuito derivado
según el Código Eléctrico Nacional, ANSI/NFPA 70 y el Código Eléctrico
Canadiense, Parte I, C22.1. La clavija en el cable de alimentación está
diseñada para servir como dispositivo de desconexión. Asegúrese que
el tomacorrientes esté instalado cerca del equipo y sea fácilmente
accesible.
Instrucciones de Seguridad Importantes
18-12-064-933901.indb 14 1/9/2019 5:01:24 PM
15
Instrucciones de Seguridad
Importantes
No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde
razonablemente se pueda esperar que la falla de este equipo cause la falla del equipo de
soporte de vida o afectar significativamente su seguridad o efectividad.
No conecte supresores de sobretensiones o cables de extensión a la salida de su UPS.
Esto puede dañar al UPS y afectar las garantías del supresor de sobretensiones y del UPS.
Conecte el UPS a un tomacorrientes que esté adecuadamente protegido contra corrientes
excesivas, cortocircuitos, y fallas de conexión a tierra como parte de la instalación del
edificio.
Advertencias de la Batería
Las baterías pueden presentar un riesgo de descarga eléctrica y quemaduras por la alta
corriente de corto circuito. Observe las precauciones apropiadas. No hay partes dentro
del UPS a las que el usuario pueda dar servicio. No abra el UPS, excepto para realizar el
reemplazo de la batería. No abra las baterías. No ponga en corto o puentee las terminales
de la batería con ningún objeto. No deseche las baterías en el fuego. Las baterías pueden
explotar. El material liberado es dañino a la piel y ojos. Puede ser tóxico. Desenchufe y
apague el UPS antes de reemplazar la batería. Use herramientas con mangos aislados. El
reemplazo de la batería debe realizarlo solo el personal de servicio autorizado usando el
mismo número y tipo de baterías (Plomo-Ácido Selladas). No deseche las baterías en el
fuego. Tripp Lite ofrece una línea completa de Cartuchos de Batería de Repuesto (R.B.C.)
para Sistemas UPS. Para localizar la batería de repuesto específica para su UPS, visite
Tripp Lite en el sitio www.tripplite.com/products/battery-finder.
PRECAUCIÓN: Una batería puede presentar un riesgo de descarga eléctrica
y alta corriente de cortocircuito. Hacer contacto con cualquier parte de una
batería conectada a tierra puede causar una descarga eléctrica. Al trabajar
con baterías deben observarse las siguientes precauciones:
Retire relojes, anillos u otros objetos metálicos.
Use herramientas con mangos aislados.
Use botas y guantes de hule.
No coloque herramientas o partes metálicas sobre la parte superior de las
baterías.
Desconecte la fuente de carga y la carga antes de la instalación o el
mantenimiento de la batería.
Elimine las conexiones a tierra de la batería durante la instalación y mantenimiento
para reducir la probabilidad de descarga.
Quite la conexión a tierra si se determina que cualquier parte de la batería debe
estar conectada a tierra.
Reciclado de la batería y el UPS
Los productos de Tripp Lite usan baterías selladas de plomo-ácido, que son
altamente reciclables.
Llame a Tripp Lite al 1.773.869.1234 o visite www.tripplite.com/support/recycling-
program para obtener información adicional sobre el reciclado de baterías u otro
producto de Tripp Lite. Para los requisitos de desecho, por favor consulte sus
códigos locales.
18-12-064-933901.indb 15 1/9/2019 5:01:25 PM
16
PASO 1: Enchufe el UPS en un
tomacorriente correctamente
aterrizado.
Después de enchufar el UPS en un tomacorriente
de pared, presione y sostenga el botón de
encendido durante un segundo hasta que la alarma
empiece a sonar y suéltelo para encender el UPS.
Nota: El UPS no encenderá automáticamente en
presencia de energía activa de la red pública.
PASO 2: Enchufe su equipo en
el UPS.
Hay dos juegos de tomacorrientes en la parte
posterior de su UPS. Los tomacorrientes marcados
SURGE PROTECTED no proporcionan respaldo de
energía por batería durante apagones. Conecte
en estos tomacorrientes los equipos de escritorio
comunes como impresoras, escáneres y otros
accesorios que no requieran respaldo por batería.
Los tomacorrientes marcados BATTERY / SURGE
PROTECTED ofrecen respaldo por batería del
UPS durante fallas de energía. Conecte en estos
tomacorrientes sus equipos de cómputo vitales.
Su UPS está diseñado para soportar solamente
equipo electrónico. Usted sobrecargará el
UPS si el valor total en volt-amperes (VA) para
todo el equipo conectado a los tomacorrientes
BATTERY / SURGE PROTECTED excede la
capacidad de salida del UPS. Para localizar
los valores de VA de su equipo, consulte las
placas de identificación. Si el equipo está
especificado en amperes (A), multiplique el
número de amperes por 120 para determinar
VA. Por ejemplo: 1A × 120 = 120VA.
Si el panel LCD de color no se ilumina cuando se
enciende el UPS, intente lo siguiente:
1. Asegúrese de que el UPS esté conectado a un
tomacorrientes de CA.
2. Presione el botón de encendido para encender
el UPS. Sonará un bip cuando el UPS arranque.
3. Si el UPS aún no arranca, póngase en contacto
con Soporte Técnico de Tripp Lite para solicitar
apoyo.
Instalación Rápida
18-12-064-933901.indb 16 1/9/2019 5:01:25 PM
17
Instalación Rápida
Instalación Opcional
Todos los modelos incluyen un puerto de
comunicación USB y conectores de supresión de
sobretensiones Tel / DSL / Ethernet (no compatible
con aplicaciones PoE). Modelos selectos también
incluirán un puerto serial RS-232. Estas conexiones
son opcionales, el UPS funcionará adecuadamente
sin ellas.
Operación Básica
ENCENDIDO Y APAGADO DEL UPS
Enchufe el UPS en un tomacorrientes activo conectado a tierra.
Toda la pantalla LCD se iluminará durante 5 segundos, después la pantalla informará el
voltaje de salida de “0V”. Los tomacorrientes marcados BATTERY / SURGE PROTECTED se
apagarán y los tomacorrientes SURGE ONLY se encenderán. El cargador de la batería se
activará según sea necesario.
Enchufe el equipo en el UPS: Usted sobrecargará el UPS si el valor total en Volts
Amperes (VA) para todo el equipo conectado a los tomacorrientes BATTERY / SURGE
PROTECTED excede la capacidad de salida del UPS. Para localizar los valores de VA de su
equipo, consulte las placas de identificación. Si el equipo está especificado en amperes
(A), multiplique el número de amperes por 120 para determinar VA. Por ejemplo:
1A × 120 = 120VA.
Encienda el UPS: Oprima y sostenga el botón de encendido hasta que la alarma empiece
a sonar, luego suéltelo. La alarma del UPS emitirá un bip brevemente. Los tomacorrientes
BATTERY/SURGE PROTECTED empezarán a pasar energía de la línea de CA. El UPS
recargará automáticamente las baterías internas según sea necesario. Una vez encendido,
su UPS está listo para proteger los equipos conectados contra apagones, caídas de voltaje,
sobrevoltajes y sobretensiones transientes.
Apague el UPS: Presione el botón de alimentación.
Nota: El sistema UPS funcionará correctamente en el arranque inicial; sin embargo, la autonomía máxima
para la batería de la unidad sólo será accesible después de haberse cargado por 24 horas.
18-12-064-933901.indb 17 1/9/2019 5:01:25 PM
18
Operación Básica
Muestra las Condiciones del UPS / Energía
Datos del LCD de Modo de Alimentación de CA En Línea
La pantalla LCD táctil ofrece 5 pantallas de información de la energía del UPS y el sitio
cuando el UPS esté operando en modo de alimentación en línea. Pantallas 1 ~ 4 (Voltaje de
Salida, Voltaje de Entrada, % de Carga, Nivel de Carga de la Batería) están disponibles para
visualización en modo de alimentación de línea. Para avanzar a la siguiente pantalla, toque
el LCD de la pantalla frontal. La pantalla #5 (Sobrecarga) se muestra automáticamente solo
cuando el UPS esté cargado a niveles superiores al 100%.
La pantalla del LCD informa que circuitos de reducción y elevación de la AVR (Regulación
Automática de Voltaje) están activos en cualquier momento que el ícono de la alimentación
en línea esté destellando.
1
4
2
5
3
1
Voltaje de Salida
2
Voltaje de Entrada
3
% de Carga
4
Nivel de Carga de la Batería*
5
Sobrecarga
Modo de Operación Descripción de la Alarma
Modo de en
Respaldo por
Batería
Normal Sin Alarma
Batería Baja Suena Cada Segundo
Sobrecarga Suena Cada 0.5 Segundos
Modo En Línea Normal Sin Alarma
Sobrecarga Suena Cada 0.5 Segundos
Reemplazo de la Batería Suena Cada Minuto
Modo de Falla Suena Continuamente.
Nota: La pantalla LCD táctil se apaga automáticamente en el modo de alimentación en línea 20 segundos
después de la última vez que se tocó. Para volver a activar el LCD por 20 segundos adicionales, toque la pantalla.
18-12-064-933901.indb 18 1/9/2019 5:01:26 PM
19
Operación Básica
Datos del LCD del Modo de Alimentación por Batería
La pantalla LCD táctil ofrece 5 pantallas de información de la energía del UPS y el sitio
cuando el UPS esté operando en modo de alimentación por batería. Las pantallas 1 ~
4 (voltaje de salida, voltaje de entrada, % de carga, nivel de carga de la batería) están
disponibles para visualización en modo de respaldo por batería. Para avanzar a la siguiente
pantalla, toque el LCD de la pantalla frontal. La pantalla #5 (Sobrecarga) se muestra
automáticamente solo cuando los tomacorrientes BATTERY/SURGE PROTECTED se cargan a
niveles de más de 100%.
Pantallas de Fallas Críticas
Código de
Error Falla Crítica Solución:
F01 CORTO EN LA
SALIDA
Desconecte carga(s) de los tomacorrientes del UPS.
Apague el UPS y póngase en contacto con Soporte
Técnico de Tripp Lite para obtener apoyo.
F02 SOBRECARGA Elimine el exceso de carga, revise el medidor de carga
en el LCD para ver el estado de la carga.
F03 SOBRECARGA Apague la unidad, desenchufe el UPS y póngase en
contacto con el Soporte Técnico de Tripp Lite para
obtener apoyo
F04 VOLTAJE BAJO DE
LA BATERÍA
Cargue el UPS durante 24 horas. Si el problema
persiste, reemplace la batería y póngase en contacto
con el Soporte Técnico de Tripp Lite.
F05 SALIDA ALTA EN
MODO DE BATERÍA
Apague el UPS y póngase en contacto con el Soporte
Técnico de Tripp Lite para obtener apoyo.
1
4
2
5
3
1
Voltaje de Salida
2
Voltaje de Entrada
3
% de Carga
4
Nivel de Carga de la Batería*
5
Sobrecarga
Nota: La pantalla LCD táctil permanecerá encendida continuamente durante la operación en el modo de
respaldo por batería.
18-12-064-933901.indb 19 1/9/2019 5:01:26 PM
20
Características
Características del UPS
12
Todos los Modelos
5
3
4
8
7
6
18-12-064-933901.indb 20 1/9/2019 5:01:26 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Tripp Lite SMART750TSU & SMART1050TSU Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire