QOLSYS QS5110-840 Le manuel du propriétaire

Taper
Le manuel du propriétaire

Ce manuel convient également à

ATTENTION: This manual should be read prior to use and retained for
further information.
GENERAL INFORMATION
The Wireless Smoke Heat Alarm is a 3xAAA battery powered wireless
detector intended for use with a compatible wireless alarm system. The
detector has a built-in wireless transmitter, which communicates with
the control panel. When smoke is detected, the alarm sounds a loud
local alarm and the built-in transmitter sends a signal to the control
panel. The Wireless Smoke Heat Alarm contains an integrated xed
41°F temperature freeze sensor that will send a warning signal based on
temperature detected. This detector is designed to provide protection
with 70-foot spacing capability.
The detector can send alarm, tamper and battery condition messages to
the system’s receiver. Refer to the wireless system’s instruction for the
maximum number of transmitters that can be supported.
CONTENTS OF BOX:
Wireless Smoke Heat Alarm with base
Installation guide (APD0595)
Pack of screws and anchors
Labels or decals as appropriate
3 AAA PC2400 Duracell Procell batteries (1.5V 1100mAh) or 3 AAA
Energizer E92 batteries (1.5V 1100mAh)
IQSmoke (QS5110-840)
Wireless Smoke Heat Alarm
Installation Guide
2
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
Status LEDs
Sounder
(do not pulse the sounder
and LED concurrently)
Normal Green ash every 12 seconds Off
Heat Alarm Red ash every 1 second ANSI S3.41 temporal 3
Heat Test Red ash every 1 second ANSI S3.41 temporal 3
Smoke Alarm Red ash every 1 second ANSI S3.41 temporal 3
(press button to hush
for 5-10 minutes)
Smoke Test Red ash every 1 second ANSI S3.41 temporal 3
(press button to hush
for 5-10 minutes)
Test Alarm Red ash every 1 second ANSI S3.41 temporal 3
Freeze Warning 3 yellow ashes
every 4 seconds
Off
Detector Trouble Yellow ash every 4 seconds One chirp every 48 seconds
Low Battery Yellow ash every 12 seconds One chirp every 48
seconds (press button
to hush for 12 hours)
Detector Dirty Yellow ash every 8 seconds One chirp every 48 seconds
Power-up Red, yellow, green
ash sequence
One chirp at the end
of power-up sequence
Tamper Red, yellow, green ash
sequence every 12 seconds
Off
The Wireless Smoke Heat Alarm contains a sounder which generates the
ANSI S3.41 temporal 3 pattern in an alarm condition. In alarm, a message
is also sent to the control panel and the detector’s ID is displayed at
the console. During an alarm condition, pressing the detector’s hush
button will silence the sounder (see table below). The mounting base
installation is simpli ed by the incorporation of features compatible
for both drywall fasteners (not supplied) and other methods.
Tricolored LED (red, yellow, green) and a sounder on the detector
provide local visual and audible indication of the detector’s status as
listed in Table 1.
During initial power-up the LED blinks alternately red, yellow then
green. It takes about 8 seconds for the detector to stabilize.
After power-up has completed and the detector is functioning normally,
the green LED blinks once every 12 seconds.
Detector Trouble: When the detector has a general fault, the yellow LED
blinks once every four seconds and there is a chirp every 48 seconds.
After 12 hours the panel will display a loss of supervision message.
Table 1. Detector status and indication
Qolsys
1900 The Alameda, Suite 420
San Jose, CA 95126
www.qolsys.com
Tech Support: 1-855-476-5797
22
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
Cette réimpression n’exprime pas la position complète et of cielle de la National
Fire Protection Association sur le sujet ci qui est représenté uniquement par la
norme dans son intégralité.)
(Code national d’alarme incendie® et NFPA 72
®
sont des marques poes de la
National Fire Protection Association, Inc., Quincy, MA 02269.)
Dans les maisons d'habitation à niveau unique et à plusieurs niveaux ainsi que
dans les immeubles d'habitation équipés de systèmes de détecteurs de fumée
similaires, il est possible que les signaux envoyés par des capteurs sans l soient
bloqués ou ré échis par le métal avant d'atteindre le panneau de commande du
détecteur et ce, même si le parcours du signal a été récemment véri é au cours
d'un test hebdomadaire. Un blocage peut se produire si un objet métallique a été
déplacé dans le parcours du signal du capteur.
3
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
Detector Dirty Feature: When the detector has been contaminated, the
yellow LED blinks once every 8 seconds and there is a chirp every 48
seconds. Refer to MAINTENANCE section for cleaning your alarm. After
12 hours the panel will display a loss of supervision message.
Low Battery Detection: The Wireless Smoke Heat Alarm is powered by
3 AAA Duracell Procell or 3 AAA Energizer E92 batteries (included). The
detector regularly checks for a low battery. If a low battery is detected,
the transmitter sends a low battery message to the control panel, which
displays the detector’s ID at low battery. In addition, the yellow LED
of the detector will blink every 12 seconds. The detector’s sounder
will chirp every 48 seconds (yellow LED continues to blink) until the
batteries are replaced. Pressing the hush button will silence the chirps
for 12 hours, if no other trouble conditions exist. The batteries should
be replaced WHEN the chirps begin. Be sure to replace the batteries
with fresh ones.
BATTERY INSTALLATION AND REPLACEMENT
To replace the batteries:
1. Remove the detector from its mounting base by twisting the
detector counterclockwise. Remove and dispose of the batteries
according to your local regulations.
2. To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new batteries.
3. Install 3 new AAA batteries (available from your local Duracell or
Energizer dealer) in the battery compartment. Follow the polarity
diagram inside the compartment. If the batteries are incorrectly
inserted please remove gently with a non-conductive tool and
correctly reinsert.
%$77(5<&203$570(17
HUSH/TEST BUTTON
Fig 1. Wireless Smoke Heat Alarm
4
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
4. Reinstall the detector onto the mounting base by turning the
detector clockwise until the mating marks align.
5. After the power-up sequence the green LED should blink about
once every 12 seconds to indicate normal operation. If the batteries
are not installed correctly, the detector will not operate and the
batteries may be damaged. If the detector does not power-up, check
for correct batteries installation and for a fully charged batteries.
6. Test the detector (as described later).
CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH
HUMIDITY MAY REDUCE BATTERY LIFE.
PROGRAMMING
Refer to the appropiate compatible control panel programming guide
for the proper procedure required to enroll the wireless smoke/heat
into the system.
RECOMMENDED LOCATIONS FOR SMOKE HEAT ALARM
According to National Fire Protection Association (NFPA) the major
threat from re in a dwelling unit occurs at night when everyone is
asleep. The principal threat to persons in sleeping areas comes from
res in the remainder of the unit; therefore, a smoke detector(s) is best
located between the bedroom areas and the rest of the unit. In units
with only one bedroom area on one oor, the smoke detector(s) should
be located as shown in Figure 2. In dwelling units with more than one
bedroom area or with bedrooms on more than one oor, more than
one smoke detector is required, as shown in Figure 3.
In addition to smoke detectors outside of the sleeping areas, the
device should be installed on each additional story of the dwelling
unit, including the basement. These installations are shown in Figure
4. The living area smoke detector should be installed in the living
room or near the stairway to the upper level, or in both locations. The
basement smoke detector should be installed in close proximity to the
stairway leading to the oor above. Where installed on an open-joisted
ceiling, the detector should be placed on the bottom of the joists. The
detector should be positioned relative to the stairway so as to intercept
smoke coming from a re in the basement before the smoke enters the
stairway.
Smoke detectors are optional where a door is not provided between
living room and recreation room (Figure 5). The smoke from a re
generally rises to the ceiling, spreads out across the ceiling surface, and
begins to bank down from the ceiling. The corner where the ceiling
and wall meet is an air space into which the smoke could have dif culty
21
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
Des changements ou modi cations non autoris pourraient entraîner l’annulation
de l’autorisation d’exploiter l’équipement.
Cet appareil est conforme à la partie 15 de la glementation de la FCC et aux normes
RSS sur les appareils exempts de licence d'Industrie Canada. Son fonctionnement
est soumis aux deux conditions suivantes : (1) Ce dispositif ne doit pas causer
d’interférences nuisibles, et (2) cet appareil doit accepter toute interférence reçue, y
compris les interférences pouvant causer un fonctionnement inopiné de l’appareil.
Cet équipement a é tes et décla conforme aux limites applicables aux
péripriques nuriques de classe B, selon la partie 15 de la glementation de
la FCC. Ces limites ont é conçues pour fournir une protection raisonnable contre
les interférences nuisibles en milieu résidentiel. Cet équipement produit, utilise et
peut émettre de l’énergie de fréquence radio. Si léquipement nest pas instal et
utili conforment aux instructions fournies, il peut provoquer des interférences
néfastes aux communications radio. Cependant, la possibilité qu'une interférence
se produise dans une installation particulière n’est pas totalement exclue. Si cet
équipement ne produit pas d'interférences nuisibles à la ception radio ou
télévision, ce qui peut être terminé en éteignant et en rallumant l’équipement,
il est recomman à l’utilisateur d'essayer de remédier aux interférences en
appliquant l’une ou plusieurs des mesures suivantes:
Réorientez ou déplacez l’antenne de réception.
Augmentez la distance qui sépare l’équipement du récepteur
Branchez l’équipement à une prise située sur un circuit différent de celui
auquel le récepteur est connecté.
Consultez le revendeur ou un technicien radio/TV expérimenté pour obtenir
de l’aide
«Pour votre information, la norme NFPA 72 du code national d’alarme incendie
stipule que:
«Détection requise 11.5.1»
«Lorsque cela est requis par les lois, des codes ou normes applicables pour un type
spéci que d’habitation, les détecteurs de fue simples et multipostes approuvés
seront installés de la manière suivante:
1. Dans les chambres à coucher et chambres d'amis
2. À l’exrieur de chaque chambre à coucher d'une maison d'habitation, à 6,4m
(21pieds) de toute porte donnant sur une chambre à coucher, la distance
étant mesurée le long d’un chemin de circulation
3. À chaque niveau d’une maison d’habitation, y compris les sous-sols
4. À chaque niveau d’un foyer résidentiel et d'un établissement de soins (petit
établissement), y compris les sous-sols et excep les vides sanitaires et les
combles inachevés
5. Dans la salle de séjour d'une suite d'amis
6. Dans la salle de séjour d’un foyer résidentiel et d'un établissement de soins.
(Réimpri avec la permission de la norme NFPA 72®, du code national d’alarme
incendie Copyright © 2007 National Fire Protection Association, Quincy, MA 02269.
20
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
Faites un plan d’évacuation de la maison. Dessinez un plan de votre maison qui
indique toutes les portes et fetres. Discutez du plan avec tout le monde dans
votre maison.
Retenez au moins deux sorties de chaque pièce, si possible. Assurez-vous que
toutes les portes et fenêtres qui mènent dehors s’ouvrent facilement.
Ayez un point de rencontre à l’extérieur (comme un arbre, un lampadaire ou
une boîte aux lettres) à distance sûre de la maison, tout le monde devrait se
rencontrer.
Pratiquez votre exercice d’incendie familial pendant la nuit et pendant le jour
avec tout le monde dans votre maison, deux fois par an.
Exercez-vous en utilisant différentes sorties.
Enseignez à vos enfants comment s’échapper seuls au cas vous ne pourriez
pas les aider.
Fermez les portes derrière vous lorsque vous partez.
SI L’ALARME RETENTIT
Si l’alarme du détecteur de fumée retentit, sortez et restez dehors. Ne retournez
jamais à l’intérieur pour chercher des personnes ou des animaux.
Si vous devez évacuer à travers la fumée, baissez-vous et marchez sous la fumée
pour sortir.
Appelez le service des pompiers de l’exrieur de votre maison. POUR
PLUS DE RENSEIGNEMENTS SUR LA SÉCURITÉ, CONSULTEZ LE SITE WEB :
www.nfpa.org/education
SPÉCIFICATIONS
Fréquence de l’émetteur: 345 000MHz (piloté par quartz)
Dimensions: Ø 125mm x hauteur 63mm (Ø 5po x hauteur 2,5po)
Poids (piles incluses): 243g oz (8,57)
Couleur: blanc
Capacité du rayon: 70pi
Signal sonore (ANSI Temporel 3) : 85 dBA min. en cas de déclenchement de
l'alarme
Sensibilité: 1,5 - 3,5 %/pied
Température de fonctionnement: 4,4°-37,8°C (40°-100°F)
Valeur thermique supplémentaire: 135°F
Humidité relative: 15-90 % sans condensation
Piles (incluses): trois (3) piles AAA PC2400 Duracell Procell ou trois (3) piles AAA
Energizer E92
Liste de matériels homologués réglementaires: UL 217
Garantie: deux (2) ans
Accessoires inclus: Trousse de matériel de montage
INFORMATIONS RÉGLEMENTAIRES:
5
penetrating. In most res, this dead air space measures about 0.1m
(4in.) along the ceiling from the corner and about 0.1m (4in.) down the
wall. Detectors should not be placed in this dead air space, see Figure
6, 7 and 8.
Where NOT to install the alarm:
Directly above a sink, cooker, stove or oven
Do not locate detector within 5 feet (1.5 m) of any cooking appliance
Next to a door or window that would be affected by drafts i.e
extractor fan or air vent
Outside
Do not install in any environment that does not comply with the
detector’s environmental speci cations
Dining
room
Kitchen
Bedroom
Bedroom
Bedroom
Living room
TV
room
Dining
room
Kitchen
Living room
Bedroom
Bedroom
Bedroom
Fig 2./RFDWLRQRIWKHGHWHFWRUV
LQXQLWVZLWKRQO\RQHEHGURRP
DUHDRQRQHÀRRU
Fig 3./RFDWLRQRIWKHGHWHFWRUVLQ
GZHOOLQJXQLWVZLWKPRUHWKDQRQH
EHGURRPDUHDRUZLWKEHGURRPVRQ
PRUHWKDQRQHÀRRU
Q
o
m
o
m
Ceiling
Acceptable here
Never here
Top of detector
acceptable here
Sidewall
100 mm (4 in.)
100-mm
(4-in.)
minimum
300-mm
(12-in.)
maximum
Note: Measurements shown are to
the closest edge of the detector.
Anywhere in
this area
Not in this area
900 mm
(36 in.)
900 mm
(36 in.)
102 mm
(4 in.)
900 mm (3 ft)
102 mm (4 in.)
Not in this area
Anywhere in
this area
Fig 6.([DPSOHRISURSHUPRXQWLQJIRUGHWHFWRUV
Fig 8.([DPSOHRISURSHUPRXQWLQJIRU
GHWHFWRUVZLWKSHDNHGFHLOLQJV
Fig 7.([DPSOHRISURSHUPRXQWLQJIRUGHWHFWRUVZLWKVORSHGFHLOLQJV
Bedroom
Living room
Recreation room
Bedroom
Basement
Indicates optional smoke alarm where a door
is not provided between living room and recreation room
Indicates required smoke detector
Hall
Bedroom
Living
room
Dining
room
Basement
Hall
Bedroom
Fig 5.6SOLWOHYHODUUDQJHPHQW
Fig 4.'HWHFWRUORFDWHGRQHDFKVWRU\
6
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
In or below a cupboard
Where air ow would be obstructed by curtains or furniture
Where dirt or dust could collect and block the sensor
Where it could be knocked, damaged, or inadvertently removed
This detector shall not be installed in location where the normal ambient
temperature is below 40°F (4.4°C) or where it exceeds 100°F (37.8°C).
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH
NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE.
MOUNTING THE DETECTOR
Note: These alarm devices should only be installed by a competent
engineer/technician.
This device should not be used with a guard.
Once a suitable location is found, mount the detector as follows:
1. Refer to the diagram below and install the mounting base on the
ceiling or on the wall (if local ordinances permit) using screw
locations as required. Use the two screws and anchors provided.
Maneuver the base so the screws are at the elbow of the screw
slots and secure.
2. Fit the detector inside the base by aligning it over the base as
shown (detector’s alignment notch should be slightly offset from
mounting base tamper release tab), then turn the detector in a
clockwise direction until it clicks into place.
3. Test the detector after completing the installation (as described
in the TESTING THE DETECTOR section of this manual) and refer
to the control system’s instructions for additional information
concerning the use of wireless devices.
'2127DWWDFKWKHGHWHFWRUWRUHPRYDEOHFHLOLQJSDQHOV
100 mm (4 in.) minimum
100 mm (4 in.)
minimum
Fig 9.0RXQWLQJWKHGHWHFWRU
19
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
AVERTISSEMENT: LIRE ATTENTIVEMENT ET MINUTIEUSEMENT
La norme NFPA 72 stipule : Un équipement d’alerte incendie pour locaux
d'habitation est capable de protéger environ la moitié des occupants des incendies
potentiellement mortels. Les victimes sont souvent proches de l’incendie, trop
âgées ou trop jeunes, présentent des ciences physiques ou mentales, de telle
façon qu’elles ne peuvent pas s’échapper, même si elles sont averties suf samment
tôt pour qu’une évacuation soit possible. Pour ces personnes, d’autres stratégies
telles que des mesures de protection, une évacuation ou un secours assisté seraient
nécessaires.
Un détecteur alimenté par piles doit avoir des piles du type spéci é, en bon
état et convenablement installées.
Les détecteurs de fumée doivent être régulièrement testés pour s’assurer que
les piles et les circuits du détecteur sont en bon état de fonctionnement.
Les détecteurs de fumée ne peuvent pas produire une alarme si la fumée
n’atteint pas le détecteur. Par conséquent, les détecteurs de fumée ne peuvent
pas détecter les incendies commençant dans les cheminées, sur les murs, les
toits, de l’autre côté d’une porte fermée ou sur un autre étage.
Si le détecteur est situé hors de la chambre à coucher ou sur un autre étage, il
peut ne pas réveiller une personne profondément endormie.
Les études ont montré que les détecteurs de fumée et de chaleur peuvent ne
pas veiller toutes les personnes endormies, et qu’il incombe aux habitants
de la maison qui sont en mesure d’aider les autres de porter assistance à ceux
qui pourraient ne pas être réveillés par le son de l’alarme ou ceux qui seraient
incapables d’évacuer le site en toute sécurité de manière autonome.
La consommation d’alcool ou de drogues peut également diminuer la capacité
à entendre lalarme de fumée. Pour une protection maximale, installez un
détecteur de fumée dans chaque chambre à coucher à chaque étage d’une
habitation.
Bien que les détecteurs de fumée puissent aider à sauver des vies en donnant
une alerte incendie précoce, ils ne se substituent pas à une police d’assurance.
Les propriétaires et les locataires doivent avoir une assurance adaptée à la
protection de leurs biens.
PLAN D’ÉVACUATION FAMILIALE
Selon la National Fire Protection Association (NFPA), il s'écoule souvent très peu
de temps entre la détection d’un incendie et le momentil devient mortel. Cet
intervalle peut être de seulement 1 ou 2 minutes. La plani cation et la pratique
des conditions d’incendie avec un accent sur l’évacuation rapide de l’habitation
sont importantes. Il faut organiser des exercices a n que tous les membres de la
famille sachent quelle action entreprendre.
CONSIGNES DE SÉCURITÉ
18
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
TESTER LE DÉTECTEUR
REMARQUE: Avant le test, informez le poste central que le système du détecteur est
en maintenance a n dempêcher des alarmes super ues. Le test du tecteur active
une alarme et envoie un signal au panneau. Par ailleurs, la fonction de test ne peut
pas être utilisée si le détecteur est en panne.
Les tecteurs doivent être testés après installation et en fonction de l’entretien
périodique.
Tester le fonctionnement du détecteur
Ce test véri e la sonde du détecteur, les DEL et lémetteur.
1. Le bouton de test est situé sur le boîtier du détecteur.
2. Appuyez et maintenez le bouton de test pendant au moins 5 secondes. Le
panneau d’alarme se clenche puis le tecteur se met en alerte. La sonde
émet la quence temporelle 3 et la DEL rouge clignote. La console du panneau
d’alarme doit en principe af cher le nom du détecteur ayant déclenché l'alarme.
Test de fumée
Tenez un bâtonnet fu mant ou un e mèche de coton à cô té du dé tecteur et so uf ez
doucement la fumée sur le tecteur jusqu’à ce que l’appareilclenche l’alarme.
La fumée en rosol est également une thode acceptable. Le test de tection de
fumée est recommandé pour véri er la capacité de protection du système.
Méthode de chauffage direct (sèche-cheveux de 1 000·1 500 watts)
Dirigez la chaleur vers le thermistor. Assurez-vous de tenir la source de chaleur
à environ 12 pouces du détecteur pour éviter d'endommager le plastique. Le
détecteur se réinitialise uniquement après avoir eu le temps de refroidir.
Un détecteur qui ne s’active pas au cours d'un de ces tests doit d’abord être nettoyé
comme le décrit la section MAINTENANCE de ce manuel. Si le détecteur ne s’active
toujours pas, retournez-le pour réparation.
MAINTENANCE
EFFECTUEZ LE TEST UNE FOIS PAR SEMAINE.
AVERTISSEMENT! UTILISEZ UNIQUEMENT LES PILES SCIFIÉES. L’USAGE DE PILES
DIFFÉRENTES PEUT AVOIR UN EFFET NUISIBLE SUR LE DÉTECTEUR DE FUMÉE.
VOTRE DÉTECTEUR DOIT ÊTRE NETTOYÉ AU MOINS UNE FOIS UN AN.
Pour nettoyer votre détecteur, ôtez-le du socle de xation. Vous pouvez nettoyer
l’intérieur de votretecteur à l’aide dun tuyau dair comprimé ou dun aspirateur
en souf ant ou en aspirant les ori ces situés autour du péritre du tecteur.
L’extérieur du détecteur peut être essuyé avec un chiffon humide.
Après nettoyage, réinstallez et testez votre détecteur à l’aide du bouton de test. Si le
nettoyage ne restaure pas le fonctionnement normal de l’alarme, le détecteur doit
être remplacé.
7
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
TESTING THE DETECTOR
NOTE: Before testing, notify the central station that the detector system
is undergoing maintenance in order to prevent unwanted alarms. Testing
the detector will activate an alarm and send a signal to the panel. Also,
the test function cannot be used if the detector has a trouble condition.
Detectors must be tested after installation and following periodic
maintenance.
Testing Detector Operation
This test checks the detector’s sounder, LEDs, and transmitter.
1. The test button is located on the detector housing.
2. Push and hold the test button for a minimum of 5 seconds. The
alarm panel will trigger and then the detector will go into alarm. The
sounder begins the temporal 3 pattern and the red LED blinks. The
alarm panel’s console should display the detector’s name in alarm.
Smoke Test
Hold a smoldering punk stick or cotton wick at the side of the detector
and gently blow smoke through the detector until the unit alarms.
Canned smoke aerosol is also an acceptable method. Smoke detection
testing is recommended for verifying system protection capability.
Direct Heat Method (Hair dryer of 1000-1500 watts)
Direct the heat toward the thermistor. Be sure to hold the heat source
about 12 inches from the detector to avoid damage to the plastic. The
detector will reset only after it has time to cool.
A detector that fails to activate with any of these tests should rst be
cleaned as outlined in this manual’s MAINTENANCE section. If the
detector still fails to activate, return for repair.
MAINTENANCE
TEST ONCE A WEEK.
WARNING! USE ONLY BATTERIES SPECIFIED. USE OF DIFFERENT
BATTERIES MAY HAVE A DETRIMENTAL EFFECT ON THE SMOKE ALARM.
YOUR ALARM SHOULD BE CLEANED AT LEAST ONCE A YEAR.
To clean your alarm, remove it from the mounting base. You can clean
the interior of your alarm by using compressed air or vacuum cleaner
hose and blowing or vacuuming through the openings around the
perimeter of the alarm. The outside of the alarm can be wiped with a
damp cloth.
After cleaning, reinstall and test your alarm by using the test button.
If cleaning does not restore the alarm to normal operation the alarm
should be replaced.
8
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY
NFPA 72 states: Fire-warning equipment for residential occupancies
are capable of protecting about half of the occupants in potentially
fatal res. Victims are often intimate with the re, too old or too
young, or physically or mentally impaired such that they cannot
escape even when warned early enough that escape should be
possible. For these people, other strategies such as protection-in-
place or assisted escape or rescue would be necessary.
A battery powered alarm must have a battery of the speci ed type,
in good condition and installed properly.
Smoke alarms must be tested regularly to make sure the batteries
and the alarm circuits are in good operating condition.
Smoke alarms cannot provide an alarm if smoke does not reach the
detector. Therefore, smoke alarms may not sense res starting in
chimneys, walls, on roofs, on the other side of a closed door or on a
different oor.
If the alarm is located outside the sleeping room or on a different
oor, it may not wake up a sound sleeper.
Studies have shown that smoke and heat alarms may not awaken all
sleeping individuals, and that it is the responsibility of individuals
in the household that are capable of assisting others to provide
assistance to those who may not be awakened by the alarm sound or
those who may be incapable of safely evacuating the area unassisted.
The use of alcohol or drugs may also impair one’s ability to hear the
smoke alarm. For maximum protection, a smoke alarm should be
installed in each sleeping area on every level of a home.
Although smoke alarms can help save lives by providing an early
warning of a re, they are not a substitute for an insurance policy.
Home owners and renters should have adequate insurance to
protect their properties.
FAMILY ESCAPE PLAN
According to National Fire Protection Association (NFPA) there often
is very little time between the detection of a re and the time it
becomes deadly. This interval can be as little as 1 or 2 minutes. Planning
and practicing for re conditions with a focus on rapid exit from the
residence are important. Drills should be held so that all family members
know the action to be taken.
SAFETY TIPS
Make a home escape plan. Draw a map of your home showing all
doors and windows. Discuss the plan with everyone in your home.
17
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
À l'intérieur ou sous un placard
Dans des endroits où la circulation d'air serait obstruée par des rideaux ou
des meubles
Dans un endroit de la sale ou de la poussre pourrait s'accumuler et bloquer
le détecteur
Dans un endroit où il pourrait être cogné, endommagé ou ôté par inadvertance
Cetecteur ne doit pas être installé dans un endroit la température ambiante
normale est inférieure à 4,4°C (40°F) ou là où elle est supérieure à 37,8°C (100°F).
CET ÉQUIPEMENT DOIT ÊTRE INSTAL CONFORMÉMENT À LA NORME 72 DE
LA NATIONAL FIRE PROTECTION ASSOCIATION: CODE NATIONAL D'ALARME
INCENDIE ET DE SIGNALISATION.
MONTAGE DU DÉTECTEUR
Remarque : Ces dispositifs d’alarme doivent être installés uniquement par un
ingénieur/technicien compétent.
Cet appareil ne doit pas être utilisé avec une grille de protection.
Une fois que vous avez trouvé un emplacement convenable, montez le détecteur
comme suit:
1. Consultez le schéma ci-dessous et installez le socle de xation au plafond ou sur
le mur (si les crets locaux le permettent) à l’aide des positions de vis indiquées.
Utilisez les deux vis et les pièces d'ancrage fournies. Manipulez le socle pour que
les vis s’emboîtent correctement dans les fentes prévues à cet effet.
2. Ajustez le détecteur sur son socle en l’alignant dessus comme l'indique
l'illustration (l’encoche d’alignement du tecteur devrait être rement
décalée de la languette de sécurité du socle de xation), puis tournez le
détecteur dans le sens horaire jusqu’à ce qu’il s'emboîte dans un déclic.
3. Testez le détecteur à la n de l’installation (comme le décrit la section TESTER
LE DÉTECTEUR de ce manuel) et consultez les instructions du système de
commande pour plus de renseignements sur l’utilisation des appareils sans l.
1HSDVIL[HUOHGpWHFWHXUVXUGHVSDQQHDX[GHSODIRQGDPRELEOHV
100 mm (4 in.) minimum
100 mm (4 in.)
minimum
Fig 9.,QVWDOODWLRQGXGpWHFWHXU
d’air la fumée peut dif cilement nétrer. Dans la plupart des incendies, cet
espace sans courant d’air mesure environ 0,1m (4po) le long du plafond depuis
l’angle et environ 0,1m (4po) le long du mur. Les tecteurs ne doivent pas être
placés dans cet espace sans courant d’air. Voir les gures 6, 7 et 8.
Endroits déconseillés pour l'installation d'un détecteur:
Directement au-dessus d'un évier, d'une cuisinière, d'un poêle ou d'un four
Ne placez pas le détecteur à 1,5m (5pi) d’un appareil de cuisson
Près d'une porte ou d'une fetre où il peut y avoir des courants d'air, à l'instar
d'un ventilateur d'extraction ou d'une bouche d'aération
À l'extérieur
Ne l'installez pas dans un environnement qui n'est pas conforme aux
spéci cations environnementales du détecteur.
3ALLEË
MANGER
#UISINE
#HAMBRE#HAMBRE
#HAMBRE
3ALON
TV
room
#UISINE
3ALON
#HAMBRE
#HAMBRE
#HAMBRE
Fig 2.(PSODFHPHQWGHVGpWHFWHXUV
GDQVGHVPDLVRQVD\DQWXQHVHXOH
FKDPEUHjFRXFKHUVXUXQpWDJH
Fig 3.(PSODFHPHQWGHVGpWHFWHXUV
GDQVGHVPDLVRQVGHSOXVGXQH
FKDPEUHjFRXFKHURXD\DQWGHV
FKDPEUHVVXUSOXVGXQpWDJH
3ALLEË
MANGER
Q
B
RE
B
RE
0LAFOND
)NSTALLATIONACCEPTABLEICI
.EJAMAISLINSTALLERICI
)NSTALLATIONDELAPARTIE
SUP RIEUREDUD TECTEUR
ACCEPTABLEICI
0AROILAT RALE
100 mm (4 in.)
100-mm
(4-in.)
minimum
300-mm
(12-in.)
maximum
2EMARQUELESMESURES
INDIQU ESSONTËLANGLE
LEPLUSPROCHEDUD TECTEUR
)NSTALLATION
RECOMMAND E
PARTOUTDANS
CETTEZONE
)NSTALLATIONINTERDITE
DANSCETTEZONE
900 mm
(36 in.)
900 mm
(36 in.)
102 mm
(4 in.)
900 mm (3 ft)
102 mm (4 in.)
0ASDANSCETTEZONE
.IMPORTEO
DANSCETTEZONE
U
V
Fig 6.([HPSOHG¶LQVWDOODWLRQDSSURSULpHGHVGpWHFWHXUV
Fig 8.([HPSOHG¶LQVWDOODWLRQDSSURSULpH
GHGpWHFWHXUVVXUGHVSODIRQGVHQUHOLHI
Fig 7.([HPSOHG¶LQVWDOODWLRQDSSURSULpHGHVGpWHFWHXUVVXUXQSODIRQGLQFOLQp
#HAMBRE
3ALON
3ALLEDEJEUX
#HAMBRE
#AVE
I)NSTALLATIONOPTIONNELLEDUND TECTEURDEFUM ESgIL
NgYAPASDEPORTEENTRELESALONETLASALLEDEJEUX
)NSTALLATIONDUND TECTEURDEFUM EREQUISE
%NTR E
#HAMBRE
3ALON
3ALLEË
MANGER
#AVE
%NTR E
#HAMBRE
100 (4 i )
Fig 5.,QVWDOODWLRQGDQVXQHPDLVRQ
jGHPLQLYHDX[
Fig 4.8QGpWHFWHXULQVWDOOpjFKDTXHpWDJH
9
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
Know at least two ways out of every room, if possible. Make sure all
doors and windows leading outside open easily.
Have an outside meeting place (like a tree, light pole or mailbox) a
safe distance from the home where everyone should meet.
Practice your home re drill at night and during the day with everyone
in your home, twice a year.
Practice using different ways out.
Teach children how to escape on their own in case you can’t help
them.
Close doors behind you as you leave.
IF THE ALARM SOUNDS
if the smoke alarm sounds, get out and stay out. Never go back inside
for people or pets.
if you have to escape through smoke, get low and go under the
smoke to your way out.
Call the re department from outside your home. FOR MORE SAFETY
INFORMATION SEE THE WEBSITE: www.nfpa.org/education
SPECIFICATIONS
T
ransmitter Frequency: 319.5 MHz (crystal controlled)
Dimensions: Ø 5’x 2.5’high (Ø 125mm x 63mm high)
Weight (including battery): 8.57 oz (243 g)
Color: White
Spacing rating: 70ft
Audible Signal (ANSI Temporal 3): 85dBA min. in alarm
Sensitivity: 1.5 - 3.5%/foot
Operating Temperature: 40°-100°F (4.4°-37.8°C)
Supplementary heat rating: 135°F
Relative Humidity: 15-90% Non-Condensing
Battery (included): Three (3) AAA PC2400 Duracell Procell or three
(3) AAA Energizer E92 batteries
Regulatory Listing: UL 217
Warranty: Two (2) years
Included Accessories: Mounting Hardware Package
REGULATORY INFORMATION NOTICE:
Unauthorized changes or modi cations could void the user’s authority
to operate the equipment.
This device complies with Part 15 of the FCC Rules and Industry Canada
licence-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including
10
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
interference that may cause undesired operation of the device.
This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and if not installed and used
in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the
following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver
Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
Consult the dealer or an experienced radio/television technician
for help
“For your information, The National Fire Alarm Code, NFPA 72, reads as
follows:
“11.5.1 Required Detection.
“Where required by applicable laws, codes, or standards for a speci c
type of occupancy, approved single- and multiple-station smoke alarms
shall be installed as follows:
1. In a sleeping rooms and guest rooms
2. Outside of each separate dwelling unit sleeping area, within 6.4 m
(21 ft) of any door to a sleeping room, the distance measured along
a path of travel
3. On every level of a dwelling unit, including basements
4. On every level of a residential board and care occupancy (small
facility), including basements and excluding crawl spaces and un
nished attics
5. In the living area(s) of a guest suite
6. In the living area(s) of a residential board and care occupancy.
(Reprinted with permission from NFPA 72®, National Fire Alarm Code
Copyright © 2007 National Fire Protection Association, Quincy, MA
02269. This reprinted material is not the complete and of cial position
of the National Fire Protection Association, on the referenced subject
which is represented only by the standard in its entirety.)
(National Fire Alarm Code® and NFPA 72
®
are registered trademarks of
the National Fire Protection Association, Inc., Quincy, MA 02269.)
15
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
4. installez le tecteur sur la base de montage en tournant le détecteur
dans le sens horaire jusqu’à ce que les repères soient alignés.
5. Après la mise sous tension, la DEL verte devrait clignoter une fois toutes
les 12 secondes environ, pour indiquer un fonctionnement normal. Si les
piles ne sont pas correctement installées, le détecteur ne fonctionnera pas
et les piles risquent d'être endommagées. Si vous ne parvenez pas à mettre
le détecteur sous tension, véri ez que les piles sont correctement instales
et qu'elles sont bien chargées.
6. Testez le détecteur (comme décrit plus loin).
DES EXPOSITIONS CONSTANTES À DES TEMPÉRATURES ÉLEVÉES OU BASSES
OU À UNE HUMIDITÉ ÉLEVÉE PEUVENT RÉDUIRE LA DURÉE DE VIE DES PILES.
PROGRAMMATION
Reportez-vous au guide de programmation appropr du panneau de commande
compatible pour connaître la procédure adéquate et requise pour enregistrer le
détecteur de fumée/chaleur sans l dans le système.
EMPLACEMENTS RECOMMANDÉS POUR LE DÉTECTEUR DE CHALEUR ET DE
FUMÉE
Selon la National Fire Protection Association (NFPA), la principale menace
d’incendie dans une maison d'habitation survient la nuit, quand tout le monde
est endormi. La menace principale pour les personnes se trouvant dans les
chambres à coucher vient des incendies survenant dans le reste de l’habitation.
Le meilleur emplacement pour un détecteur de fumée se situe donc entre
les chambres à coucher et le reste de l’habitation. Dans les habitations avec
seulement une chambre à coucher sur un étage, le détecteur doit être installé
tel que l'indique la Figure 2. Dans les maisons d'habitations ayant plus d’une
chambre à coucher ou des chambres sur plus d’un étage, il est nécessaire
d'installer plus d’un détecteur de fumée, comme le démontre la Figure 3.
En plus des détecteurs de fumée installés hors des chambres à coucher, l’appareil
doit être installé à chaque étage supplémentaire de la maison, y compris au sous-
sol. Ces installations sont illustrées dans la Figure 4. Le détecteur de fumée de
la salle de séjour doit être installé dans le salon ou près de l’escalier menant au
niveau supérieur, ou aux deux endroits. Le détecteur de fumée du sous-sol doit
être installé tout près de l’escalier qui mène à l'étage supérieur. S’il est installé sur
un plafond à solives apparentes, le détecteur devrait être placé sous les solives.
Le détecteur doit être placé par rapport à l’escalier de manière à intercepter la
fumée provenant d’un incendie au sous-sol avant que la fue n’entre dans
l’escalier.
Les détecteurs de fumée sont optionnels s’il n’y a pas de porte entre la salle de
séjour et la salle de jeux (Figure 5). La fumée d’un incendie s’élève généralement
au plafond, se pand sur toute la surface du plafond et commence à s'amonceler
à partir du plafond. L’angle le plafond et le mur se rejoignent est un espace
14
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
Fonction détecteur sale: Lorsque le tecteur est contami, la DEL jaune clignote
une fois toutes les 8 secondes et un bip sonore retentit toutes les 48 secondes.
Reportez-vous à la section MAINTENANCE pour le nettoyage de votre détecteur.
Au bout de 12 heures le panneau de contrôle af che un message de perte de
contrôle.
Détection d'un signal de piles faibles: Le détecteur de chaleur et de fumée sans l est
alimen par 3 piles AAA Duracell Procell ou 3 piles AAA Energizer E92 (incluses).
Il véri e régulièrement le niveau des piles. Si des piles faibles sont détectées,
l’émetteur envoie un message de piles faibles au panneau de commande qui
af che lidenti ant du détecteur ayant un faible niveau. Par ailleurs, la DEL jaune
du détecteur va clignoter toutes les 12 secondes. La sonde du détecteur émet un
signal sonore toutes les 48 secondes (la DEL jaune continue à clignoter) jusqu’à
ce que les piles soient remplacées. Appuyez sur le bouton silence pour arrêter
les bips sonores pendant 12 heures, s'il n'existe aucun autrefaut. Remplacez
les piles dès que les bips sonores recommencent. Assurez-vous de remplacer
les anciennes piles par des neuves.
INSTALLATION ET REMPLACEMENT DES PILES
Pour remplacer les piles:
1. Déposez le détecteur de son socle de xation en le tournant dans le sens
antihoraire. Enlevez les piles et mettez-les au rebut selon les réglementations
locales.
2. A n de garantir une mise hors tension appropriée, attendez 20 secondes au
moins avant d'installer les piles neuves.
3. Installez 3 nouvelles piles AAA (disponibles auprès votre détaillant Duracell
ou Energizer local) dans le compartiment à piles. Suivez le schéma de
polarité présenté dans le compartiment. Si les piles sont insérées de façon
incorrecte, veuillez les enlever doucement avec un outil isolant et réinsérez-
les correctement.
&203$57,0(17'(/$%$77(5,(
#0650/4*-&/$&5&45
Fig 1. Détecteur de chaleur et de fumée sans l
11
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
In typical single level and multilevel dwelling units and apartment
buildings having similar smoke alarm systems there is a possibility that
signals sent by wireless sensors may be blocked or re ected by metal
before they reach the alarm Control Panel, even if the signal path has
been recently checked during a weekly test. Blockage can occur if a
metal object has been moved into the sensor’s signal path.
ATTENTION: Vous devez lire ce manuel avant de l'utiliser et le
conserver pour les références futures.
RENSEIGNEMENTS GÉNÉRAUX
Le détecteur de chaleur et de fumée sans l est un détecteur sans l
alimenté par 3 piles AAA conçu pour être utilisé avec des systèmes
d'alarme sans l compatibles. Le détecteur est doté d'un émetteur sans
l intégré qui communique avec le panneau de commande. Lorsque
de la fumée est détectée, l'alarme retentit comme une sonnerie
locale bruyante et l'émetteur intégré envoie un signal au panneau de
commande. Le détecteur de chaleur et de fumée sans l contient un
capteur de gel intégré à une température de 5 °C qui envoie un
signal d'alarme en fonction de la température détectée. Ce détecteur a
été conçu pour fournir une protection dans un rayon de 70pieds.
Il peut envoyer des messages concernant le statut de l’alarme, du
dispositif de sécurité et des messages sur l'état des piles au récepteur
du système. Reportez-vous aux instructions du système sans l pour
connaître le nombre maximum d'émetteurs pouvant être pris en charge.
CONTENU DE LA BOÎTE:
Détecteur de chaleur et de fumée sans l avec base
Guide d'installation (APD0595)
Paquet de vis et de pièces d'ancrage
Étiquettes ou décalcomanies au besoin
3 piles Duracell Procell AAA PC2400 (1,5V 1 100mAh) ou 3 piles
Energizer E92 AAA (1,5V 1 100mAh)
IQSmoke (QS5110-840)
Détecteur de chaleur et de fumée sans
l Guide d'installation
13
Guide d'installation du détecteur de chaleur et de fumée sans l INST APD0595 A140618
État DEL
Sonde
(n'appuyez pas simultanément sur
la sonde et la DEL)
Normal
Clignote en vert toutes les 12 secondes
Désactivé
Détecteur de chaleur
Clignote en rouge chaque seconde ANSI S3.41 temporel 3
Épreuve de résis-
tance à la chaleur
Clignote en rouge
chaque seconde
ANSI S3.41 temporel 3
Détecteur de
fumée
Clignote en rouge
chaque seconde
ANSI S3.41 temporel 3
(appuyez sur le bouton pour
l'arrêter pendant
5 à 10 minutes)
Test de fumée Clignote en rouge
chaque seconde
ANSI S3.41 temporel 3
(appuyez sur le bouton pour
l'arrêter pendant
5 à 10 minutes)
Tester le détecteur Clignote en rouge chaque seconde ANSI S3.41 temporel 3
Alarme de gel Clignote en jaune 3 fois
toutes les 4 secondes
Désactivé
Défaut du détecteur
Clignote en jaune toutes les 4 secondes Un bip sonore toutes les 48 secondes
Piles faibles Clignote en jaune toutes les
12 secondes
Un bip sonore toutes les 48
secondes (appuyez sur le bouton
pour l'arrêter pendant 12 heures)
Détecteur sale
Clignote en jaune toutes les 8 secondes Un bip sonore toutes les 48 secondes
Activation Rouge, jaune, vert
séquence de clignotement
Un bip sonore à la n
de la séquence d'activation
Languette de
sécurité
Rouge, jaune, vert
quence de clignotement toutes les
12 secondes
Désactivé
Le détecteur de fumée et de chaleur sans l contient une sonde qui émet une
quence temporelle 3 ANSI S3.41 dans des conditions d'alarme. En état d'alerte, un
message est envoyé aussi au panneau de commande et l'ID du détecteur s'af che sur
la console. En cas de déclenchement d'une alarme, appuyez sur le bouton de silence
du tecteur pour arrêter la sonde (voir le tableau ci-dessous). L'installation du socle
de xation est simpli ée grâce à l'intégration de caractéristiques compatibles avec
les attaches pour cloisons sèches (non fournies) et d'autres méthodes.
La DEL tricolore (rouge, jaune, vert) et la sonde du détecteur émettent des signaux
visuels et sonores locaux relatifs au statut du détecteur tel que l'indique le Tableau 1.
Lors de la première mise sous tension, la DEL clignote alternativement entre le
rouge, le jaune et le vert. Il faut environ 8 secondes pour que le détecteur se stabilise.
À la n de la mise sous tension, si le tecteur fonctionne normalement, la DEL verte
clignote une fois toutes les 12 secondes.
Défaut du détecteur: Lorsque le détecteur est en panne, la DEL jaune clignote une
fois toutes les quatre secondes et un bip sonore retentit toutes les 48 secondes.
Après 12 heures, le panneau af che un message de perte de supervision.
Tableau 1. Statut et indications du détecteur
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

QOLSYS QS5110-840 Le manuel du propriétaire

Taper
Le manuel du propriétaire
Ce manuel convient également à

dans d''autres langues