MGE UPS Systems Evolution S EXB 3000 RT 2U Manuel utilisateur

Taper
Manuel utilisateur
www.mgeops.com
Evolution
S 1250 RT 2U
S 1750 RT 2U
2000 RT 2U
S 2500 RT 2U
S 3000 RT 2U
S 3000 RT 3U
S EXB 1250/1750 RT 2U
S EXB 2500/3000 RT 2U
S EXB 2500/3000 RT 3U
Installation and User Manual
Manuel d’installation et d’utilisation
Manual de instalación y uso
Instalação e manual do usuário
ENGLISH
FRANÇAIS
ESPAÑOL
PORTUGUESE
ENGLISH
ENGLISH Installation and User Manual
86-81710-00 A01
Evolution
Installation and User Manual
Revision History
Evolution Installation and User Manual, 86-81710-00
Revision: A01 ECN#: 005225 03/2007
Copyright © 2007 MGE Office Protection Systems
All rights reserved. Printed in U.S.A.
MGE Office Protection Systems
13 Whatney, Suite #101
Irvine, CA 92618
(949) 268-2800
For Technical Support, Customer Care Center, or Customer FAQ,
please visit our website: www.mgeops.com or call (800) 279-7776
ENGLISH
Evolution
86-81710-00 A01
Contents
Contents
c i
86-81710-00 A01
ENGLISH
Introduction
IMPORTANT SAFETY INSTRUCTIONS ............................................................................................2
Certification Standards ........................................................................................................................2
Safety of Persons ..........................................................................................................................2
Product Safety ..........................................................................................................................2
Special Precautions ..........................................................................................................................2
Environment ..........................................................................................................................2
Symbol Usage ..........................................................................................................................3
Presentation
1.1 Standard Positions..........................................................................................................1 — 1
1.2 Rear Panels ..................................................................................................................1 — 2
1.3 Control Panel..................................................................................................................1 — 2
2.1 Unpacking and Contents Check ....................................................................................2 — 1
2.2 Installation of Tower Model ............................................................................................2 — 2
2.3 Installation of Rack Model ..............................................................................................2 — 2
2.4 Communication Ports ....................................................................................................2 — 3
2.5 Equipment Connections..................................................................................................2 — 4
2.6 Connection with a FlexPDU (Power Distribution Unit) Module (optional) ......................2 — 4
2.7 Connection with a HotSwap MBP Module (optional) ....................................................2 — 5
Operation
3.1 Start-Up and Normal Operation......................................................................................3 — 1
3.2 Operation on Battery Power ..........................................................................................3 — 1
3.3 Return of AC Input Power ..............................................................................................3 — 2
3.4 UPS Shutdown ..............................................................................................................3 — 2
3.5 UPS Remote Control Functions ....................................................................................3 — 2
Access to Measurements and Personalization Data
Main-Output Personalization ..........................................................................................4 — 1
Voltage-Threshold Personalization ................................................................................4 — 1
UPS-Sensitivity Personalization ....................................................................................4 — 1
UPS ON/OFF Personalization ........................................................................................4 — 2
Battery Personalization ..................................................................................................4 — 2
Maintenance
5.1 Troubleshooting ............................................................................................................5 — 1
5.2 Battery Module Replacement ........................................................................................5 — 2
5.3 Training Center ..............................................................................................................5 — 3
Appendices
6.1 Technical Specifications..................................................................................................6 — 1
6.2 Programming the Programmable Outlets ......................................................................6 — 2
6.3 Glossary..........................................................................................................................6 — 4
ENGLISH
Evolution
c ii 86-81710-00 A01
Introduction
ENGLISH
Introduction
Thank you for selecting an MGE Office Protection Systems product to protect your electrical equipment.
The Evolution range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible
Power System).
Warning: This is a class A UPS product. In a domestic environment, this product may cause radio interference, in which case, the
user may be required to take additional measures.
If the device must be installed in overvoltage category III or IV environments, additional upstream overvoltage protection must be
provided for.
Before installing Evolution, please read the booklet on the required safety instructions. Then follow the indications in this manual.
To discover the entire range of MGE Office Protection Systems products and the options available for the Evolution range, we invite
you to visit our web site at www.mgeops.com or contact your MGE Office Protection Systems representative at (800) 279-7776..
Environmental Protection
MGE Office Protection Systems has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
The cardboard we use comprises over 50% of recycled cardboard.
Sacks and bags are made of polyethylene.
Packing materials are recyclable and bear the appropriate identification symbol.
Follow all local regulations for the disposal of packing materials.
End of life
MGE Office Protection Systems will process products at the end of their service life in compliance with local regulations.
MGE Office Protection Systems works with companies in charge of collecting and eliminating our products at the end of their
service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning
batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
The "Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*.
(*) For more information or to contact the Product Environmental manager, please visit our website: www.mgeops.com.
Material Abbreviation Symbol
number
Polyethylene terephthalate PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
1
86-81710-00 A01
01
PET
01
PET
Installation and User Manual
ENGLISH
Evolution
286-81710-00 A01
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The Evolution models that are covered in this manual are intended for installation in an environment
within 0 to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commer-
cial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Certification Standards
IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability
FCC rules and regulations of Part 15, Subpart B, Class A
UL listed under 1778, Standards for Uninterruptible Power Supply Equipment
IEC 61000-4-2 (ESD): level 4
IEC 61000-4-3 (Radiated field): level 3
IEC 61000-4-4 (EFT): level 4
IEC 61000-4-5 (surge): level 4
IEC 61000-4-6 (electromagnetic conducted field): level 3
IEC 61000-4-8 (radiated magnetic field): level 4
Safety of Persons
The system has its own power source (the battery). Consequently, the power outlets may be energized even if the systems is disconnected
from the AC power source.
Dangerous voltage levels are present within the system. It should be opened exclusively by qualified service personnel.
The system must be properly grounded.
The battery supplied with the system contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed:
-Never burn the battery (risk of explosion).
-Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
-Comply with all applicable regulations for the disposal of the battery.
-Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling:
remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.
-Do not lay tools or metal parts on top of batteries.
Product Safety
The UPS connection instructions and operation described in the manual must be followed in the indicated order.
A protection circuit breaker must be installed upstream and be easily accessible. The system can be disconnected from the AC power source
by opening this circuit breaker.
Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the
equipment to be connected to the system.
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -20ºC to +50ºC.
Special Precautions
All handling operations will require at least two people (unpacking, installation in rack system).
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least
once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided
with the UPS to maintain an identical level of performance and safety. In case of doubt, don’t hesitate to contact your MGE Office Protection
Systems representative.
Environment
This product has been designed to respect the environment:
It does not contain any Chlorofluorocarbon (CFC) or Hydrochlorofluorocarbon (HCFC).
UPS recycling at the end of service life:
MGE Office Protection Systems undertakes to recycle, by certified companies and in compliance with all applicable
regulations, all UPS products recovered at the end of their service life (contact your MGE Office Protection Systems
branch office).
Packing: UPS packing materials must be recycled in compliance with all applicable regulations.
WARNING: This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not
properly recycled by specialized companies.
Introduction
Symbol Usage
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audible signal.
LED off.
LED on
LED flashing
ENGLISH Installation and User Manual
3
86-81710-00 A01 Introduction
ENGLISH
(This page left blank intentionally)
Evolution
486-81710-00 A01
ENGLISH
Presentation
1.1 Standard Positions
Tower Models
Rack Models
D
H
W
1 — 1
86-81710-00 A01 Presentation
Weights in lbs
S 1250 RT 2U 54.3
S 1750 RT 2U 58
2000 RT 2U 56.2
S 2500 RT 2U 76.4
S 3000 RT 2U 77.9
S 3000 RT 3U 75.5
S EXB 1250/1750 RT 2U 64.2
S EXB 2500/3000 RT 2U 92.7
S EXB 2500/3000 RT 3U 88
Dimensions (W x H x D) in inches
S 1250 RT 2U
S 1750 RT 2U
2000 RT 2U
17.3 x 3.38 x 20
S 2500 RT 2U
S 3000 RT 2U 17.3 x 3.38 x 25
S 3000 RT 3U 17.3 x 5.16 x 19
S EXB 1250/1750 RT 2U 17.3 x 3.38 x 20
S EXB 2500/3000 RT 2U 17.3 x 3.38 x 25
S EXB 2500/3000 RT 3U 17.3 x 5.16 x 19
1.2 Rear Panels
Evolution S 2500 / S 3000
Evolution S 1250 / S 1750 / 2000
Evolution S EXB (optional battery module)
1.3 Control Panel
(20) Bargraph indicating the percent load
(21) Bargraph indicating battery charge level
(22) Programmable outlet 1 is supplied with power
(23) Programmable outlet 2 is supplied with power
(24) Lighted ON/OFF button for outlets
(25) Load protected LED
(26) Downgraded operation LED
(27) Load not protected LED
(12) Connectors for battery modules (to the UPS or to
the other battery modules)
(13) Connectors for automatic recognition of battery
modules
(1) USB communication port
(2) RS232 communication port
(3) Connector for automatic recognition of an additional
battery module
(4) Slot for optional communication card
(5) Connector for ROO (remote ON/OFF) or RPO (Remote
Power OFF) control
(6) Connector for additional battery module
(7) 30A outlet for connection of equipment (for Evolution
S 2500 and S 3000 only)
(8) A group of 2 programmable outlets for connection of
equipment
(9) Group of 4 outlets for connection of equipment
(10) Attached 6 ft. input power cord for AC-power source
L5-30P for S 2500/S 3000
L5-15P for S 1250
L5-20P for S 17500/2000
(a) LED indicating site wiring fault (SWF) alarm with reset button
a
ENGLISH
Evolution
Presentation
1 — 2 86-81710-00 A01
Installation
2.1 Unpacking and Contents Check
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
(38) Mounting kit for 19-inch bays
(39) 2 supports for the upright position (RT 2U
version only)
(42) NMC communication card (optional)
(30) Evolution UPS
(33) RS232 communication cable
(34) USB communication cable
(36) Solution-Pac CD-ROM
(37) Documentation
Installation 2 — 1
ENGLISH
86-81710-00 A01
ENGLISH
2.2 Installation of Tower Model
Note. The two supports for the upright position are used on the RT 2U version only.
2.3 Installation of Rack Model
It is advised to first install the battery module, then the power module above.
Follow steps 1 to 4 for module mounting on the rails.
The rails and necessary hardware are supplied by MGE Office Protection Systems.
Evolution
Installation
2 — 2 86-81710-00 A01
2.4 Communication Ports
Connection of RS232 or USB communication port
The RS232 and USB communication ports cannot operate simultaneously.
Installation of the communication cards (optional)
Characteristics of the contact communication port (optional)
When a signal is activated, the contact is closed between the common (pin 2) and the pin for the corresponding signal.
Contact characteristics (optocoupler)
Voltage: 48 V DC max
Current: 25 mA max
Power: 1.2 W
Pins 1, 3, 4, 5, 6, 10: not used
Pin 2: common (user)
Pin 7: low battery
Pin 8: operation on battery power
Pin 9: UPS ON, equipment supplied
n.o.: normally open contact
n.o. n.o. n.o.
common
It is not necessary to shutdown the UPS before
installing a communication card.
1. Remove the slot cover (4) secured by screws.
2. Insert the communication card in the slot.
3. Secure the card cover with the 2 screws.
Limited-access slot for the
communication card
1. Connect the RS232 (33) or USB (34) communica-
tion cable to the serial or USB port on the
computer equipment.
2. Connect the other end of the communication
cable (33) or (34) to the USB (1) or RS232 (2)
communication port on the UPS.
The UPS can now communicate with MGE Office
Protection Systems power management software.
Installation
ENGLISH Installation and User Manual
2 — 3
86-81710-00 A01
ENGLISH
2.5 Equipment Connections
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and the
true electrical consumption of the total load
Evolution S 2500 / S 3000 Evolution S 1250 / S 1750 / 2000*
1. Input cable power source.
2. Connect the loads to the UPS. It is preferable to connect the priority loads to the four outlets marked (7) or (9) and the
nonpriority loads to the programmable outlet marked (8).
To program shutdown of outlets (8) during operation on battery power and thus optimize the available backup time.
Fit the connection securing system (rack model only).
*Note: Input cord
NEMA 5-15P for S1250
NEMA 5-20P for S1750/2000
2.6 Connection with a FlexPDU (Power Distribution Unit) Module (optional)
1. Evolution S 2500 / S 3000: Connect the UPS input
socket (10) to the AC-power source using the cable
(31) supplied.
Evolution S 1250 / S 1750 / 2000: Use the power
cable of the protected equipment.
2. Evolution S 2500 / S 3000: Connect the input socket
on the FlexPDU module (48) to the UPS outlet (9).
Evolution S 1250 / S 1750 / 2000: Connect the input
socket on the FlexPDU module (48) to one of the
outlets (9).
The cable and the connectors are marked in red.
3. Connect the equipment to the outlets (45) and (46) on
the FlexPDU module. These outlets differ, depending
on the version of the FlexPDU module.
4. Fit the connection securing system that prevents the
plugs from being pulled out accidentally.
45 46 48
Evolution S 2500 / S 3000
FlexPDU
a
Evolution
Installation
2 — 4 86-81710-00 A01
ENGLISH
2.7 Connection with a HotSwap MBP Module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads
(HotSwap function).
54
55
53
49
Evolution S 1750 / 2000
HotSwap MBP
54 55
Evolution 2500 / 3000
HotSwap MBP
Installation and User Manual
Installation 2 — 5
86-81710-00 A01
1. Connect the input socket (56) on the HotSwap
MBP module to the AC-power source using the
cable (31) supplied.
2. Connect the UPS input socket (10) to the "UPS
Input" (55) on the HotSwap MBP module.
3. Evolution S 2500 / S 3000: Connect the UPS
outlet (7) to the "UPS Output" (54) on the
HotSwap MBP module.
Evolution S 1250 / S 1750 / 2000: Connect one
of the UPS outlets (9) to the "UPS Output" (54) on
the HotSwap MBP module.
4. Connect the equipment to the outlets (49) on the
HotSwap MBP module.
These outlets differ, depending on the version of the
HotSwap MBP module.
Caution: Do not use UPS outlets (8) and (9) to
supply equipment because use of switch (53) on
the HotSwap MBP module would cut supply to the
equipment.
ENGLISH
HotSwap MBP module operation
UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2. Set switch (53) to Normal position.
3. Start the UPS by pressing the ON/OFF button (24) on the UPS control panel.
The load is supplied by the UPS.
LED (51) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP module test
1. Set switch (53) to Bypass position and check that the load is still supplied.
2. Set switch (53) back to Normal position.
The HotSwap MBP module has a rotary switch (53)
with two positions:
Normal the load is supplied by the UPS,
Bypass – the load is supplied directly by the AC-power
source.
5351
51
Evolution
Installation
2 — 6 86-81710-00 A01
ENGLISH
Operation
3.1 Start-Up and Normal Operation
3.2 Operation on Battery Power
Transfer to battery power
Low-battery warning
End of battery backup time
All the LEDs go OFF.
The audio alarms stops.
The UPS is completely shut down.
Button (24) and LEDs (25) and (26) are ON.
The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all
applications on the connected equipment because
automatic UPS shutdown is imminent.
2624
25
The connected devices continue to be supplied by
the UPS when AC input power is no longer
available. The necessary energy is provided by
the battery.
Button (24) and LEDs (25) and (26) are ON.
The audio alarm beeps every ten seconds.
The connected devices are supplied by the battery.
Press button (24) for approximately 2 seconds.
The buzzer beeps once and all the LEDs go ON
simultaneously.
If AC input power is available, button (24) and
LED (25) are ON. The load is supplied by the AC-
power source. Conditions permitting, the UPS
runs a battery test, indicated by LEDs (21) and
the buzzer.
If AC input power is not available, button (24) and
LEDs (25) and (26) are ON. The load is supplied
by the UPS on battery power.
The connected devices are protected by the UPS.
If LED (27) is ON, a fault has occurred (see the
"Troubleshooting" section).
26
27
21 24
25
3 — 1
86-81710-00 A01 Operation
ENGLISH
Evolution
3 — 2 86-81710-00 A01
3.3 Return of AC Input Power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart function has been
disabled via UPS personalization) and the load is again supplied.
3.4 UPS Shutdown
3.5 UPS Remote Control Functions
Remote control connection and test
4. Plug connector (5) into the back of the UPS.
5. Connect and restart the UPS following the previously described procedures.
6. Activate the external remote shutdown contact to test the function.
Warning: This connector must only be connected to SELV (Safety Extra-Low Voltage) circuits.
Contact open: UPS shutdown
Contact closed: UPS start-up (UPS connected to AC
power and AC power is available).
Note: The local ON/OFF control using button (24)
overrides the remote-control function.
Contact open: UPS shutdown, LED (26) goes ON.
To return to normal operation, deactivate the remote
external contact and restart the UPS by pressing but-
ton (24).
ROO
RPO
1. Check that the UPS is OFF and disconnected from the AC input source.
2. Remove connector (5) after unscrewing the screws.
3. Connect a normally closed volt-free contact (60 V DC / 30 V AC max., 20 mA max., 0.75 mm2cable
cross-section) between the two pins of connector (5) (see diagram).
Evolution offers a choice between two remote control
functions.
RPO: Remote Power OFF allows a remote
contact to be used to disconnect all the
equipment connected to the UPS. Restarting the
UPS requires manual intervention.
ROO: Remote ON/OFF allows remote action of
button (24) to shut down the UPS.
These functions are obtained by opening of the contact
connected between the appropriate pins of connector
(5) on the rear panel of the UPS (see figures below).
Press button (24) for approximately 2 seconds.
The devices connected to the UPS are no longer
supplied.
24
Operation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104

MGE UPS Systems Evolution S EXB 3000 RT 2U Manuel utilisateur

Taper
Manuel utilisateur