Unitronics EX-RC1 Remote I/O Adapter Mode d'emploi

Taper
Mode d'emploi
Unitronics
1
EX-RC1 User Guide
Remote I/O Adapter
The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed
throughout your system.
The adapter is connected to a PLC via CANbus. Each adapter may be connected to up to 8 I/O Expansion
Modules. The network may comprise up to 60 nodes, including both PLCs and adapters; note that the PLC must
comprise a CANbus port. Communication is via UniCAN, Unitronics’ proprietary CANbus protocol.
The EX-RC1 is run by a factory-installed application. The adapter can auto-detect digital I/O Expansion
Modules. If the system includes analog modules, the application must be edited. For more information refer to
the Remote I/O topics in the VisiLogic Help system.
The EX-RC1 may either be snap-mounted
on a DIN rail, or screw-mounted onto a
mounting plate.
23
6
1
5
4
Component identification
1
Status indicators
2
PC to EX-RC1 connection port
3
Power supply connection points
4
EX-RC1 to expansion module
connection port
5
CANbus port
6
DIP Switches
Before using this product, it is the responsibility of the user to read and understand this document and
any accompanying documentation.
All examples and diagrams shown herein are intended to aid understanding, and do not guarantee
operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product in accordance with local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
User safety and equipment protection guidelines
This document is intended to aid trained and competent personnel in the installation of this equipment as
defined by the European directives for machinery, low voltage, and EMC. Only a technician or engineer trained
in the local and national electrical standards should perform tasks associated with the device’s electrical wiring.
Symbols are used to highlight
information relating to the user’s
personal safety and equipment
protection throughout this document.
When these symbols appear, the
associated information must be read
carefully and understood fully.
Symbol
Meaning
Description
Danger
The identified danger causes physical
and property damage.
Warning
The identified danger can cause
physical and property damage.
Caution
Caution
Use caution.
Failure to comply with appropriate safety guidelines can result in severe personal injury or
property damage. Always exercise proper caution when working with electrical equipment.
Check the user program before running it.
Do not attempt to use this device with parameters that exceed permissible levels.
Install an external circuit breaker and take appropriate safety measures against short-circuiting
in external wiring.
To avoid damaging the system, do not connect / disconnect the device when the power is on.
EX-RC1 Remote I/O Adapter
11/22
2
Unitronics
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Leave a minimum of 10mm space for ventilation between the top and bottom edges of the
device and the enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
11/22
EX-RC1 Remote I/O Adapter
Unitronics
3
UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: IO-AI4-AO2, IO-AO6X, IO-ATC8, IO-DI16, IO-DI16-L, IO-DI8-RO4, IO-DI8-RO4-L, IO-DI8-TO8,
IO-DI8-TO8-L, IO-RO16, IO-RO16-L, IO-RO8, IO-RO8L, IO-TO16, EX-A2X are UL listed for Hazardous Locations.
The following models: EX-D16A3-RO8, EX-D16A3-RO8L, EX-D16A3-TO16, EX-D16A3-TO16L, IO-AI1X-AO3X, IO-
AI4-AO2, IO-AI4-AO2-B, IO-AI8, IO-AI8Y, IO-AO6X, IO-ATC8, IO-D16A3-RO16, IO-D16A3-RO16L, IO-D16A3-TO16,
IO-D16A3-TO16L, IO-DI16, IO-DI16-L, IO-DI8-RO4,
IO-DI8-RO4-L, IO-DI8-RO8, IO-DI8-RO8-L, IO-DI8-TO8, IO-DI8-TO8-L, IO-DI8ACH, IO-LC1, IO-LC3, IO-PT4, IO-
PT400, IO-PT4K, IO-RO16, IO-RO16-L, IO-RO8, IO-RO8L, IO-TO16, EX-A2X, EX-RC1 are UL listed for Ordinary
Location.
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that have been
approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
WARNINGExplosion Hazardsubstitution of components may impair suitability for Class I, Division
2.
WARNING EXPLOSION HAZARD Do not connect or disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.
WARNING Exposure to some chemicals may degrade the sealing properties of material used in
Relays.
This equipment must be installed using wiring methods as required for Class I, Division 2 as per the
NEC and/or CEC.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Input/Output expansion modules, Models: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L
When these specific products are used in hazardous locations, they are rated at 3A res, when these specific products
are used in non-hazardous environmental conditions, they are rated at 5A res, as given in the product’s
specifications.
Certification UL des automates programmables, pour une utilisation en environnement à risques,
Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés pour une
utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C
et D, ou dans Non-dangereux endroits seulement.
Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue
pour être non dangereuse.
AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
Modules d’Extensions d'E/S, modèles: IO-DI8-RO4, IO-DI8-RO4-L, IO-RO8, IO-RO8L.
Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive, lorsque ces produits spécifiques sont utilisés dans un environnement non
dangereux, ils sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures.
EX-RC1 Remote I/O Adapter
11/22
4
Unitronics
Mounting the Module
DIN-rail mounting
Snap the device onto the DIN rail as shown below; the module will be squarely situated on the DIN rail.
60mm
(2.362")
3.5mm
(0.137")
14mm
(0.55")
80mm
(3.15")
93mm
(3.66")
44.5mm
(1.75")
POWER
EX-RC1
0VV
Remote I/O Adapter
PRG
Network ID CANbus
PWR I/O COMM.
Bus COMM.
Screw-Mounting
The figure below is not drawn to scale. It may be used as a guide for screw-mounting the module.
Mounting screw type: either M3 or NC6-32.
4mm
5.8mm
(0.228")
85mm
(3.346")
80mm
(3.15")
68.4mm
(2.693")
93mm
(3.66")
4mm (x2)
(0.16")
(0.16")
11/22
EX-RC1 Remote I/O Adapter
Unitronics
5
Setting the Unit ID Number
The ID number range is from 1 to 60.
The DIP switch settings represent the ID number as a binary value as shown in the following figures.
Unit ID
1 (Default)
2
59
60
Settings
Connecting Expansion Modules
An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to
the adapter or to another module:
1. Push the module-to-module connector into the port located on the right side of the device.
Note that there is a protective cap provided with the adapter. This cap covers the port of the final
I/O module in the system.
To avoid damaging the system, do not connect or disconnect the device when the
power is on.
1 2
Component identification
1
Module-to-module
connector
2
Protective cap
Wiring
Do not touch live wires.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
Do not connect the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s 0V pin.
In the event of voltage fluctuations or non-conformity to voltage power supply specifications,
connect the device to a regulated power supply.
Double-check all the wiring before turning on the power supply.
Wiring Procedures
Use crimp terminals for wiring; use 26-14 AWG wire (0.13 mm 23.31 mm2) for all wiring purposes.
1. Strip the wire to a length of 7±0.5mm (0.2500.2.08 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure that a proper connection can be made.
4. Tighten enough to keep the wire from pulling free.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break.
Install at maximum distance from high-voltage cables and power equipment.
EX-RC1 Remote I/O Adapter
11/22
6
Unitronics
Wiring Power Supply
Connect the "positive" cable to the "+V" terminal, and the “negative” to the "0V" terminal.
Earthing the Power Supply
To maximize system performance, avoid electromagnetic interference by:
Mounting the module on a metal panel.
Earthing the modules power supply: connect one end of a 14 AWG wire to the chassis signal;
connect the other end to the panel.
Note: If possible, the wire used to earth the power supply should not exceed 10 cm in length. However, it is
recommended to earth the module in all cases.
Circuit protection
device
0V
+V
12VDC or
24VDC
Power supply
POWER
0V
V
11/22
EX-RC1 Remote I/O Adapter
Unitronics
7
Communication
Connecting the EX-RC1 to a PC
Connect the PC to the adapter via the programming cable. The pinout below shows the RS232 port signals.
Pin #
Description
Pin #1
1
2
0V reference
3
TXD signal
4
RXD signal
5
0V reference
6
Connecting the EX-RC1 to the CANbus network
Connect the EX-RC1 adapter to an OPLC as shown below. The module communicates via Unitronics’
proprietary UniCAN protocol. UniCAN can comprise up to 60 nodes, including PLCs and EX-RC1
remote I/O adapters.
The CANbus port is galvanically isolated.
CANbus Wiring
121
terminating
resistor
121
terminating
resistor
Circuit
protection
device
+
-
24V Power
Supply
-V
L
H
+V
PE
-V
L
H
+V
PE
-V
L
H
+V
PE
Network terminators: Place terminators
at each end of the CANbus network.
Resistance must be set to 1%, 121Ω,
1/4W.
Connect ground signal to the earth at
only one point, near the power supply.
The network power supply need not be
at the end of the network.
CANbus Connector
Network Layout
The EX-RC1 enables you to remotely locate I/Os up to 1 kilometer from a PLC. You can include both PLCs and
adapters on the UniCAN network, up to a total of 60 nodes.
EX-RC1 Remote I/O Adapter
11/22
8
Unitronics
EX-RC1 Technical Specifications
I/O module capacity
Up to 8 I/O modules can be connected to a single adapter. The number of I/Os
may vary according to module.
Power supply
12VDC or 24VDC
Permissible range
10.2 to 28.8VDC
Quiescent current
90mA@12VDC; 50mA@24VDC
Max. current consumption
650mA @ 12VDC; 350mA @ 24VDC
Current supply for
I/O modules
800mA maximum from 5V. See Note 1
Status indicators
(PWR)
Green LED
Lit when power is supplied.
(I/O COMM.)
Green LED
Lit when communication is established between the adapter to
the other units.
Blinks 0.5sec ON 0.5sec OFF when adapter is in Stop mode.
(Bus COMM.)
Green LED
Lit when communication is established between the adapter and
the OPLC.
Notes
1. Example: 2 IO-DI8-TO8 units consume a maximum of 140mA of the 5VDC supplied by the adapter.
Communication
RS232 port
1
Galvanic isolation
No
Voltage limits
20V
Cable length
Up to 15m (50‘)
CANbus port
1
Nodes
60
Power requirements
24VDC (±4%), 40mA max. per unit
Galvanic isolation
Yes, between CANbus and adapter
Cable type
Twisted-pair; DeviceNet® thick shielded twisted pair cable is recommended.
Cable length/baud rate
25 m
100 m
250 m
500 m
500 m
1000 m*
1000 m*
1 Mbit/s
500 Kbit/s
250 Kbit/s
125 Kbit/s
100 Kbit/s
50 Kbit/s
20 Kbit/s
* If you require cable lengths over 500 meters, contact
technical support.
Environmental
IP20/NEMA1
Operating temperature
0 to 50C (32 to 122F)
Storage temperature
-20 to 60C (-4 to 140F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Dimensions (WxHxD)
80mm x 93mm x 60mm (3.15” x 3.66” x 2.36”)
Weight
135g (4.76 oz.)
Mounting
Either onto a 35mm DIN-rail or screw-mounted.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice,
to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness
for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be
liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this
information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you