Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual

Ce manuel convient également à

Explosionsgeschützte Klemmenkästen
aus Kunststoff GHG 72.
Explosion protected terminal boxes made
of plastic GHG 72.
Boites de jonction GHG 72. en plastique
pour atmospres explosives
GHG 720 7001 P0001 D/GB/F (o)
CROUSE-HINDS
SERIES
Betriebsanleitung
Operating instructions
Mode d’emploi
2
Explosionsgeschützte
Klemmenkästen, Typ GHG 72.
Explosion protected terminal
boxes type, GHG 72.
Boites de jonction type GHG 72.
pour atmosphères explosives
1 Technische Angaben ...........................3
2 Legende ..............................................4
2.1 Sicherheitshinweise ........................... 4
3 Normenkonformität .............................4
4 Verwendungsbereich ..........................4
5 Verwendung / Eigenschaften ...............4
6 Installation ...........................................5
7 Instandhaltung / Wartung ....................6
8 Reparatur / Instandsetzung /
Änderungen
......................................... 7
9 Entsorgung /
Wiederverwertung
..............................7
10 Strombelastungstabelle ....................18
11 Kunststoffleitungseinführungen ........20
1 Technical data ......................................8
2 Principles ............................................ 9
2.1 Safety instructions ...............................9
3 Conformity with standards .................. 9
4 Field of application ..............................9
5 Use / Properties ..................................9
6 Installation .........................................10
7 Maintenance / Servicing .................... 11
8 Repairs / Overhaul / .............................
Modifications .....................................12
9 Disposal /
Recycling ...........................................12
10 Current load values ...........................18
11 Plastic cable glands ...........................20
1 Caractéristiques techniques .............. 13
2 Légende ............................................14
2.1 Consignes de sécurité.......................14
3 Conformité avec les normes .............14
4 Domaine d’utilisation .........................14
5 Utilisation / Propriétés .......................14
6 Installation .........................................15
7 Maintenance / Entretien ....................16
8 Réparations / Remise en état /
Modification
......................................17
9 Évacuation des déchets /
Recyclage
.......................................... 17
10 Tableau de charge .............................18
11 Entrées de câble en plastique ..........20
Konformitätserklärung separat beigelegt. Declaration of conformity, enclosed separately. Déclaration de conformité, jointe séparément.
Inhalt: Contents: Contenu:
3
Klemmenkasten GHG 721 1...
Maßbilder in mm
X = Befestigungsmaße
1 Technische Angaben
1.1 Kunststoffklemmenkästen GHG 721 ...
EG-Baumusterprüfbescheinigung: BVS 13 ATEX E 013 X
Gerätekennzeichnung 2014/34/EU und Norm
EN 60079-0:
II 2G Ex e
1)
IIC T4
2)
/T5/T6 Gb
II 2D Ex tb IIIC T80°C / T95°C Db
1)
Wahlweise kann die Kennzeichnung um die Zündschutzart gesondert bescheinigter Komponenten ergänzt werden,
z.B. "d", "e", "mb" und/oder "ia/ib
2)
".
2)
T4: Nur bei Verwendung von Einbaukomponenten in der Zündschutzart Eigensicherheit "i".
IECEx Konformitätsbescheinigung: IECEx BVS 13.0031X
Gerätekennzeichnung
IEC 60079-0: Ex e
1)
IIC T4
2)
/T5/T6 Gb
Ex tb IIIC T80°C / T95°C Db
1)
Wahlweise kann die Kennzeichnung um die Zündschutzart gesondert bescheinigter Komponenten ergänzt werden,
z.B. "d", "e", "mb" und/oder "ia/ib
2)
".
2)
T4: Nur bei Verwendung von Einbaukomponenten in der Zündschutzart Eigensicherheit "i".
Max. Verlustleistung
Temperaturklasse / Max. Umgebungstemperatur T6 / 40 °C T6 / 50 °C T5 / 40 °C T5 / 55 °C
Kunststoffausführung GHG 721 0 16 W 10 W 22 W 16 W
Kunststoffausführung GHG 721 1 24 W 15 W 33 W 24 W
Bemessungsspannung: bis 690 V
Bemessungsstrom: siehe Tabelle im Gehäusedeckel
Zulässige Umgebungstemperatur /
Zul. Lagertemperatur in Originalverpackung:
-40 °C/-55°C bis +40°C/+55°C (Listenausführ
ung)
Gehäuse mit Kunststoffflansch -20 °C
-40 °C (geschützt montiert 4 J)
Gehäuse mit interner Erdungsplatte und
Aussenerdungsanschluss
-42 °C
Abw
eichende Temperaturen sind bei Sonderversionen möglich.
Schutzart nach EN/IEC 60529: IP 66 (Listenausführung)
IP 65 (Gehäuse mit Kunststoffflansch)
Schutzklasse nach EN/IEC 61140: I - mit Metallflansch
II - wird von den Kunststoffklemmenkästen erfüllt
Anschlussklemmen
Klemmenkasten GHG 721 0... max. 16 mm²
Klemmenkasten GHG 721 1... max. 35 mm²
Leitungseinführung laut Auftrag, im Rahmen der Bescheinigung
Leergewicht
Klemmenkasten GHG 721 0... ca. 1,1 kg
Klemmenkasten GHG 721 1... ca. 1,7 kg
Prüfdrehmomente
Prüfdrehmomente für Kabel- und Leitungseinführungen siehe Kapitel 11.
Deckelschrauben: 2,50 Nm
Explosionsgeschützte Klemmenkästen, Typ GHG 72.
D
GHG 721 0 GHG 721 1
4
2. Legende
Achtung
Dieses Symbol warnt vor einem möglichen
Ausfall. Wird diese Warnung nicht beobach-
tet kann der Gesamtausfall der Vorrichtung
oder des Systems oder des Betriebes
erfolgen, an die es angeschlossen wird.
Hinweis
Dieses Symbol hebt wichtige Informationen
hervor.
X
ATEX - IEC
Besondere Bedingungen
Dieses Symbol weißt auf Hinweise zum
sicheren Betrieb gemäß EU-Baumusterprüfbe-
scheinigung / IECEx-Konformitätsbescheini-
gung hin.
2.1 Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und geeignet
qualifizierte, unterwiesene Personen
gemäß den nationalen Rechtsvorschriften,
einschließlich der einschlägigen Normen für
elektrische Geräte in explosionsgefährdeten
Bereichen (EN/IEC 60079-14).
Die Klemmenkästen GHG 72. sind nicht für
Zone 0 und Zone 20 geeignet.
Die Anforderungen der EN/IEC 60079-31 u.a.
in Bezug auf übermäßige Staubablagerun-
gen und Temperatur, sind vom Anwender zu
beacht
en.
Die auf den Klemmenkästen angegebene
Temperaturklasse und Explosionsgruppe ist
zu beachten.
Umbauten oder Veränderungen an den
Klemmenkästen sind nicht gestattet.
Sie sind bestimmungsgemäß in unbeschä-
digtem und einwandfreiem Zustand zu
betr
eiben.
Vor Inbetriebnahme müssen die Klemmen-
kästen entsprechend der im Abschnitt 6
genannten Anweisung geprüft werden.
Beachten Sie die nationalen Sicherheits- und
Unfallverhütungsvorschriften und die
nachfolgenden Sicherheitshinweise in
dieser Betriebsanleitung, die wie dieser Text
in Kursivschrift gefasst sind!
3 Normenkonformität
Die Klemmenkästen entsprechen den aufge-
führten Normen, in der separat beigelegten
Konformitäts erklärung.
Verweise auf Normen und Richtlinien in dieser
Betriebsanleitung beziehen sich immer auf die
aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4 Verwendungsbereich
Die Kunststoffkästen sind zum Einsatz
in explosionsgefährdeten Bereichen der
Zonen 1, 2 und 21, 22 gemäß
EN/IEC 60079-10-1 und
EN/IEC 60079-10-2 geeignet.
Die eingesetzten Gehäusematerialien ein-
schließlich der außenliegenden Metallteile
bestehen aus hochwertigen Werkstoffen,
die einen anwendungsgerechten Korrosions-
schutz und Chemikalienresistenz in "normaler
Industrieatmosphäre" gewährleisten:
- glasfaserverstärktes Polyester
- Edelstahl V 4A AISI 316 L.
Bei einem Einsatz in extrem aggressiver
Atmosphäre, können Sie zusätzliche Infor-
mationen über die Chemikalienbeständigkeit
der eingesetzten Kunststoffe, bei Ihrer
zuständigen Cooper Crouse-Hinds (CCH)/
EATON Niederlassung erfragen.
5 Verwendung/Eigenschaften
Die Klemmenkästen dienen zum Verteilen
von elektrischer Energie, z.B. Lichtstromkreise,
Heizstromkreise, Steuerstromkreise,
eigensichere Stromkreise usw..
Temperaturklasse, Explosionsgruppe, zulässige
Umgebungs temperatur siehe technische
Daten.
Angaben zum sicheren Benutzen von
Fremdprodukten, sofern nicht in dieser
Betriebsanleitung genannt, sind den
beiliegenden Anleitungen zu entnehmen
oder bei dem jeweiligen Hersteller des
Betriebsmittels anzufragen.
Angaben aus Punkt 3 u. 4 sind bei der
Verwendung zu berücksichtigen.
Andere als die beschriebenen Anwen-
dungen sind ohne schriftliche Erklärung der
Fa. Cooper Crouse-Hinds/EATON nicht
zulässig. Beim Betrieb sind die in der
Betriebsanleitung unter Punkt 7 genannten
Anweisungen zu beachten.
Die Verantwortung hinsichtlich Eignung
und bestimmungsgemäßer Verwendung
dieser Klemmenkästen unter Bezugnahme
der in der Anlage vorhandenen Rahmen-
bedingungen (s. technische Daten) liegt
allein beim Betreiber.
Explosionsgeschützte Klemmenkästen, Typ GHG 72.
D
5
6 Installation
Für das Errichten / Betreiben sind die
relevanten nationalen Vorschriften sowie die
allgemein anerkannten Regeln der Technik
maßgebend (EN/IEC 60079-14).
X
ATEX - IEC
Bei dem Einbau der separat bescheinig-
ten Klemmen müssen die Luft- und Kriech-
strecken der Tabelle 1 der EN/IEC 60079-7
entsprechen.
6.1 Montage
Die Montage der Klemmenkästen kann ohne
Öffnen der Gehäuse erfolgen.
Die Klemmenkästen dürfen bei der Direkt-
montage an der Wand nur an den vorgesehe-
nen Befestigungspunkten eben aufliegen. Die
ge
wählte Schraube muss der Befestigungsöff-
nung angepasst sein (siehe Maßbilder, Seite 3)
und sie darf die Öffnung nicht beschädigen
(z.B. Verwendung einer Unterlegscheibe).
Die Klemmenkästen sind mit mindestens 2
Schrauben diagonal zu befestigen.
a
Bei übermäßigem Anziehen können
die Kunststoffklemmenkästen beschädigt
werden.
Die Kunststoffklemmenkästen GHG 721 0 und
GHG 721 1 sind zur schraubenlosen Befesti-
gung auf den CCH/EATON - Gerätehaltern
geeignet (siehe Bild 4-7, Seite 6+7).
Die betreffende Montageanleitung ist
zu beachten.
6.2 Öffnen des Gerätes /
Elektrischer Anschluss
Der elektrische Anschluss des Betriebs-
mittels darf nur durch Fachpersonal
erfolgen (EN/IEC 60079-14).
Die Luft- und Kriechstrecken nach
EN/IEC 60079-7; Tabelle 1 einhalten.
Die im Deckel der Klemmenkästen angegebe-
ne Strombelastungstabelle ist zu beachten.
Zur
Aufrechterhaltung der Zündschutzart ist der
Leiteranschluss mit besonderer Sorgfalt
durchzuführen.
Die Isolation muss bis an die Klemme
heranreichen. Der Leiter selbst darf nicht
beschädigt sein.
Die minimal und maximal anschließbaren
Leiterquerschnitte sind zu beachten.
Alle Schrauben und/oder Muttern der An-
schlussklemmen, auch die der nicht benutzten,
sind f
est anzuziehen.
Die eingebaute Standardklemme ist zum Direktan-
schluss von Leitern mit Kupferadern ausgelegt.
B
ei eingebauten Bolzenklemmen sind
DIN -Kabelschuhe zu verwenden.
Das Aufpressen der Kabel schuhe auf
das Kabel ist fachgemäß durchzuführen. Es
ist sicherzustellen, dass die erforderlichen
Mindestluftstrecken eingehalten werden
(bei 690V -> 12mm).
Bei Mischbestückungen Ex-e / Ex-i sind die
erforderlichen Trennabstände, Luft- und
Kriechstrecken einzuhalten. Die Anschluss-
leitungen der Ex-i Stromkreise sind getrennt
von den Anschlussleitungen der Ex-e
Stromkreise zu verlegen
(siehe z.B. EN/IEC 60079-11).
Die Anschlussleitungen der Ex-i Stromkreise
sind zu kennzeichnen (z.B. farblich, hellblau).
Nach der Demontage der Klemmentragschiene
(zur leichteren Einführung der Kabel und
Leitungen), muss vor dem elektrischen
Anschluss die Klemmentragschiene wieder
ordnungsgemäß montiert werden.
Die Demontage und Montage erfolgt, wie
nachfolgend beschrieben:
Durch Auseinanderdrücken der seitlichen
Gehäusewände wird die Klemmentragschiene
aus dem Gehäuseunterteil gelöst.
Zur Montage ist die Klemmentragschiene in die
Rastnocke einer Gehäuseseitenwand einzuset
-
zen. Danach wird die Schiene auf der anderen
Gehäuseseite
eingeschnappt (Siehe Bild 3).
Die PE-Schiene ist in 4 Positionen variabel
einbaubar (siehe Bild 1):
A Gehäuseseite oben - PE-Anschluss unten
B Gehäuseseite oben - PE-Anschluss oben
C Gehäuseseite unten - PE-Anschluss unten
D Gehäuseseite unten - PE-Anschluss oben
Die Montage ist wie folgt durchzuführen:
In die Führungsleisten, die in die Gehäuse
-
seitenwände eingearbeitet sind, werden die
PE-Schienen bis zum Anschlag eingeschoben.
Die Schiene muss in die Aufnahme am
Gehäuseboden einrasten.
Es ist darauf zu achten, dass die Einbau-
lage der PE-Schiene einen korrekten
Leiter-Anschluss gewährleistet.
Wird das Betriebsmittel in der Ausführung
"Schutzisoliert" ausgeführt, kann das entspre-
chende Klebeschild GHG 905 1002 P0005
beim Hersteller angefordert werden.
Wird die eingebaute Klemmentragschiene
nicht komplett mit Reihenklemmen bestückt,
muss die Klemmentragschiene in den
Potentialausgleich mit einbezogen werden.
Explosionsgeschützte Klemmenkästen, Typ GHG 72.
D
Bild 1
Bild 2
Bild 3
A
B
C
D
12
6
6.3 Kabel- und Leitungseinführungen
(KLE); Verschlussstopfen
Es dürfen generell nur bescheinigte KLE
und Verschluss-Stopfen verwendet werden.
Für bewegliche Leitungen sind Trompeten-
verschraubungen oder andere geeignete
Einführungen mit zusätzlicher Zugentlas-
tung zu verwenden.
Eigensichere Stromkreise (Ex-i) sind über die
farblich (hellblau) gekennzeichneten KLE
einzuführen.
Die für die eingebauten KLE maßgebenden
Montagerichtlinien sind zu beachten.
Beim Einsatz von KLE mit einer niedrigeren
als der für das Gerät zutreffenden
IP-Schutzart (Siehe Technische Daten,
Seite 3) wird die IP-Schutzart des
gesamten Gerätes reduziert.
Nicht benutzte Einführungsöffnungen sind
mit einem bescheinigten Verschluss-Stopfen
zu verschließen, um die Mindestschutzart
herzustellen.
Es ist darauf zu achten, dass bei der Installation
der KLE die für den Leitungsdurchmesser
geeigneten Dichtungseinsätze verwendet
werden.
Bei ausschneidbaren Dichtungseinsätzen ist
sicherzustellen, dass der Einsatz ordnungs gemäß
dem Leitungsdurchmesser angepasst wird.
Alle nicht benutzten metrischen CCH/EATON
KLE sind mit dem bescheinigten Verschluss für
metrische KLE zu verschließen.
Zur Sicherstellung der erforderlichen Mindest
-
schutzart sind die KLE fest anzuziehen.
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
Beim Anziehen der Hutmutter der
Metall-KLE ist die Verschraubung mit einem
geeigneten Werkzeug gegen Verdrehen zu
sichern.
6.4 Flansche und Metallplatten
Müssen Flanschplatten demontiert werden
(z.B. zum Bohren von Einführungsöffnungen),
ist bei der Montage zur Aufrechterhaltung der
Mindestschutzart auf den korrekten Sitz der
Flanschplatte und den Sitz des Befestigungs-
bügels zu achten.
Die Flanschplatten sind so zu montieren, dass
die IP-Schutzart gewährleistet bleibt. Dabei ist
auf den exakten Sitz und die Unversehrtheit der
Dichtung zu achten.
Von außen herangeführte PE-Leitungen
sind auf die dafür vorgesehene PE-Klemme
am Flansch anzuschließen. Der maximale
Anschlussquerschnitt beträgt 50 mm².
Achtung: Metallflansche, Metallplatten
und Metallverschraubungen müssen in den
Potentialausgleich miteinbezogen werden.
Werden Klemmenkästen mit Kunst-
stoffflansche, im Rahmen der Baumuster-
prüfbescheinigung, bei Umgebungstempera-
turen unter -40°C eingesetzt, müssen diese
bauseits vor unzulässigen mechanischen
Belastungen geschützt werden.
6.5 Schließen des Gerätes /
Deckelverschluss
Alle Fremdkörper sind aus dem Gerät zu
entfernen.
Zur Sicherstellung der erforderlichen
Mindestschutzart sind die Deckelschrauben
fest anzuziehen.
Bei übermäßigem Anziehen kann die
Schutzart beeinträchtigt werden.
6.6 Inbetriebnahme
Vor Inbetriebnahme des Betriebsmittels sind
die in den einzelnen nationalen Bestimmungen
genannten Prüfungen durchzuführen. Außer
-
dem ist vor der Inbetriebnahme die korrekte
Instal
lation des Betriebsmittels in Übereinstim-
mung mit dieser Betriebsanleitung und anderen
anwendbaren Bestimmungen zu überprüfen.
Unsachgemäße Installation und Betrieb
der Klemmenkästen kann zum Verlust der
Garantie führen.
7 Instandhaltung / Wartung
Die für die Wartung / Instandhaltung von
elektrischen Betriebsmitteln in explo-
sionsgefährdeten Bereichen geltenden
nationalen Bestimmungen sind einzu halten
(EN/IEC 60079-17).
Vor Öffnen des Gehäuses Spannungsfreiheit
sicherstellen bzw. geeignete Schutzmaßnah-
men ergreifen.
Bei eigensicheren Stromkreisen ist das
Arbeiten unter Spannung zulässig.
Die erforderlichen Wartungsintervalle sind
anwendungsspezifisch und daher in Abhän-
gigkeit von den Einsatzbedingungen vom
Betreiber festzulegen.
Explosionsgeschützte Klemmenkästen, Typ GHG 72.
D
Bild 4
Gerätehalter Größe 2A für Rohrbefestigung
Bild 5
Gerätehalter Größe 2A für Gitterrinnen- und Wandbefestigung
C
C
Steckbefestigungslöcher für
Klemmenkasten GHG 721 0...
Steckbefestigungslöcher für
Klemmenkasten GHG 721 0...
7
Im Rahmen der Wartung sind vor allem die
Teile, von denen die Zündschutzart abhängt,
zu prüfen (z.B. Unversehrtheit und Dichtheit
des Gehäuses, Unversehrtheit der Dichtun-
gen und der Kabel- und Leitungseinführungen).
Es ist vor dem Schließen des Gehäuse-
deckels auf den korrekten Sitz des Nieder-
halters im Deckel und die Unversehrtheit des
Niederhalters zu achten (siehe Bild 2, Seite 5).
X
ATEX - IEC
Zur Vermeidung elektrostatischer
Aufladung ist das Betriebsmittel und der
Aufkleber nur mit einem feuchten Tuch oder
Schwamm zu reinigen!
Sollte bei einer Wartung festgestellt werden,
dass Instandsetzungsarbeiten erforderlich
sind, ist Abschnitt 8 dieser Betriebsanleitung
zu beachten.
8 Reparatur / Instandsetzung /
Änderungen
Instandsetzungsarbeiten / Reparaturen dürfen
nur unter Verwendung von CCH/EATON
Originalersatzteilen vorgenommen werden.
Reparaturen, die den Explosionsschutz
betreffen, dürfen nur von CCH/EATON oder
einer qualifizierten Elektrofachkraft in
Übereinstimmung mit national geltenden
Regeln durchgeführt werden
(EN/IEC 60079-19).
Umbauten oder Änderungen am Betriebs-
mittel sind nicht gestattet; ausgenommen
ist das Anbringen von zusätzlichen KLE und
das Montieren von Anschlussklemmen im
Rahmen der Zulassung des Betriebsmittels.
9 Entsorgung /
Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind die
jeweils geltenden nationalen Abfallbeseitigungs-
vorschriften zu beachten.
Zusätzliche Informationen zur Entsorgung des
Produktes können Sie bei Ihrer zuständigen
Cooper Crouse-Hinds/EATON Niederlassung
erfragen.
Zur Erleichterung der Wiederverwertbarkeit
von Einzelteilen sind Kunststoffteile mit dem
Kennzeichen des verwendeten Kunststoffes
versehen.
Programmänderungen und -ergänzungen sind
vorbehalten.
Explosionsgeschützte Klemmenkästen, Typ GHG 72.
D
Bild 6
Gerätehalter Grösse 3, horizontale Rohrbefestigung
Bild 7
Gerätehalter Grösse 3, horizontale Gitterrinnen- und Wandbefestigung
C
C
Schraubbefestigungslöcher für Klemmenkasten GHG 721 1....
Steckbefestigungslöcher für Klemmenkasten GHG 721 1....
8
Explosion protected terminal boxes type, GHG 72.
GB
Terminal box GHG 721 1...
Dimensions, plastic terminal boxes
X = fixing dimensions
1 Technical data
GHG 721 0 GHG 721 1
1.1 Plastic terminal boxes GHG 721 ...
ATEX type examination certificate: BVS 13 ATEX E 013 X
Marking acc. to 2014/34/EU and standard
EN 60079-0:
II 2G Ex e
1)
IIC T4
2)
/T5/T6 Gb
II 2D Ex tb IIIC T80°C / T95°C Db
1)
Optional the marking can be amplified with the tyres of protection of the separately certified components,
for example "d", "e", "mb" and/or "ia/ib
2)
".
2)
T4: Only for use of terminals in type of protection Intrinsic Safety "i".
IECEx certificate: IECEx BVS 13.0031X
Category of application:
IEC 60079-0: Ex e
1)
IIC T4
2)
/T5/T6 Gb
Ex tb IIIC T80°C / T95°C Db
1)
Optional the marking can be amplified with the tyres of protection of the separately certified components,
for example "d", "e", "mb" and/or "ia/ib
2)
".
2)
T4: Only for use of terminals in type of protection Intrinsic Safety "i".
Max. Power dissipation
Temperature class / Max. ambient temperature T6 / 40 °C T6 / 50 °C T5 / 40 °C T5 / 55 °C
Plastic version GHG 721 0 16 W 10 W 22 W 16 W
Plastic version GHG 721 1 24 W 15 W 33 W 24 W
Rated voltage: up to 690 V
Rated current: acc. to table on the inside of the enclosure cover
Permissible ambient temperature /
Perm. storage temperature in original packing
-40 °C/-55°C to +40°C/+55°C (c
atalogue version)
Enclosure with plastic flange -20 °C
-40 °C (protected mounting 4 J)
Enclosure with internal earth plate
and external earthing
-42 °C
De
viating temperatures possible with special versions.
Protection category acc. to IEC/EN 60529: IP 66 (catalogue version)
IP 65 (enclosure with plastic flange)
Insulation class acc. to IEC/EN 61140: I - with metal flange
II - plastic terminal boxes fulfil this requirement
Terminals
Terminal box GHG 721 0... max. 16 mm²
Terminal box GHG 721 1... max. 35 mm²
Test torques acc. to customer´s specification and as certified
Empty weights
Terminal box GHG 721 0... approx. 1.1 kg
Terminal box GHG 721 1... approx. 1.7 kg
Test torques
Test torques for cable glands see cap. 11.
Cover screws: 2.50 Nm
9
2 Principles
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result in
the total failure of the device or the system
or plant to which it is connected.
Note
This symbol highlights important information.
X
ATEX - IEC
Special conditions
This symbol shows Highlights for safe use in
accordance to EU-Type-Examination Certificate/
IEC Ex-Certificate of Conformity.
2.1 Safety instructions
Target group:
For skilled electricians and suitable
qualified, instructed personnel in
accordance with national legislation,
including the relevant standards and, where
applicable, in acc. with IEC/EN 60079-14 on
electrical apparatus for explosive atmospheres.
The terminal boxes GHG 72. are not suitable
for Zone 0 and Zone 20 hazardous areas.
The requirements of the IEC/EN 60079-31
regarding excessive dust deposits and
temperature to be considered from the user.
The t
emperature class and explosion group
marked on the terminal boxes have to be
observed.
Modifications to the terminal boxes or
changes of their design are not permitted.
They shall to be used for their intended
purpose and in perfect and clean condition.
Prior to taking the terminal boxes into
operation, they shall be checked in accord-
ance with the instruction as per section 6.
Observ
e the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
3 Conformity with standards
The apparatus is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
References to standards and directives in these
operating instructions always relate to the latest
version. Other additions (e.g. details relating to
the year) shall be observed.
4 Field of application
The plastic terminal boxes are suitable for use
in Zone 1, 2 and 21, 22 hazardous areas acc.
to IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion pro-
tection and resistance to chemical sub-stanc-
es corresponding to the requirements
in a "normal industrial atmosphere":
- glass-fibre reinforced polyester
- special stainless steel V4 A AISI 316 L.
In case of use in an extremely aggressive
atmosphere, you can obtain information
concerning the chemical resistance of the
materials used from your
Cooper Crouse-Hinds branch.
5 Use / Properties
The terminal boxes are intended for the
distribution of electrical energy, e.g. light
circuits, heating circuits, control circuits,
intrinsically safe circuits etc..
As to temperature class, explosion group,
permissible ambient temperature, see
technical data.
Information on the safe use of third-party
products, unless non specified in these
operating instructions, have to be requested
from the respective manufacturer of the
equipment.
The data as per point 3 and 4 shall
be taken into account with the use.
Applications other than described are
not permitted without Cooper Crouse-Hinds
(CCH)/EATON's prior written consent. For
the operation, the instructions stated in
section 7 of the operating instructions shall
be observed.
The user alone is responsible for the
appropriate use of this installation switch in
consideration of the basic conditions
existing at the plant (see technical data).
Explosion protected terminal boxes type, GHG 72.
GB
10
6 Installation
For the mounting and operation, the
respective national regulations as well as
the general rules of engineering shall be
observed (IEC/EN 60079-14).
X
ATEX - IEC
When mounting the separately certified
terminals, the clearance an creepage distance
must be observed in accordance to table 1 of
IEC/EN 60079-7.
6.1 Mounting
The plastic boxes can be mounted without
opening their enclosure.
When mounting the terminal boxes directly
onto the wall, they shall rest evenly only on the
fastening points provided for them. The chosen
screw must match the fastening hole (see
dimensional drawings page 8) and they shall
not damage the hole (e.g. use of a washer).
The terminal boxes must be fastened diagonally
by means of at least 2 screws.
If the screws are overtightened, the
plastic terminal boxes may be damaged.
The plastic terminal boxes GHG 721 0 and
GHG 721 0 are suitable for fastening onto CCH/
EATON apparatus holders by means
of self-cutting screws and clip-on mounting
(see fig. 4 - 7, page 11 + 12).
The respective mounting instructions
will have to be observed.
6.2 Opening the apparatus/
Electrical connection
a
The electrical connection of the
apparatus may only be carried out by
skilled staff (IEC/EN 60079-14).
The minimum clearances and creepage
distances in accordance with IEC/EN 60079-7,
Table 1, shall be observed.
The table indicating the current load values
which is provided on the cover inside of the
terminal boxes is to be observed.
In order to maintain the mode of protection, the
conductors will have to be connected with
special care.
The insulation shall reach up to the
terminal. The conductor itself shall not
be damaged.
The connectable min. and max. conductor
cross-sections will have to be observed.
All screws and/or nuts of the supply terminals,
and unused terminals, shall be tightened down.
The fitted standard terminals are designed for
direct connection of conductors with copper
cores.
If stud terminals are fitted, DIN cable lugs shall
be used.
The cable lugs should be crimped onto
the cable in a workmanlike manner. It is to
be ensured that the required min. air gaps
are kept (at 690V ->12mm).
When combining Ex-e/Ex-i it is essential to
maintain the separation, air and creepage
distances. The Ex-i circuit wires are to be laid
separately from the Ex-e circuit wires
(see e.g. EN/IEC 60079-11).
The connection wires of the Ex-i circuits are
to be marked (e.g. by colour, light blue).
After removing the terminal rail (in order to
facilitate the entry of cables), the terminal rail
shall again be properly put in place before
establishing the electrical connection.
Removal and mounting of the terminal rail are
performed as follows:
By pressing apart the enclosure sides, the
terminal rail can be detached from the bottom
part of the enclosure.
In order to install the terminal rail, it is fitted
onto the catch on one side of the enclosure wall
and then snapped in on the opposite enclosure
wall (see fig. 3).
The PE rail can optionally be fitted in 4 positions
(see fig.1):
A Enclosure top side - PE-connection bottom
B Enclosure top side - PE-connection top
C Enclosure bottom side - PE-connection bottom
D Enclosure bottom side - PE-connection top
The PE rail is fitted as follows: It has to be
pushed home in the respective guide rails that
are integrated into the lateral enclosure walls.
The rail must engage into the receptacle
on the bottom of the housing. Care has to
be taken that the PE rail has such a position
that a proper conductor connection is
ensured.
In the case of building up the electrical
equipment in the "protective insulation" version,
appropriate sticker GHG 905 1002 P0005 can
be requested by the manufacturer.
If the inserted terminal rail is not equipped
completely with line-up terminals, the terminal
rail must be included in the equipotential earth
connection also.
Fig. 1
Fig. 2
Fig. 3
A
B
C
D
12
Explosion protected terminal boxes type, GHG 72.
GB
11
6.3 Cable entries (KLE)/
Blanking plugs
Generally, only certified cable entries
and blanking plugs may be used. Flexible
cables are to be used with trumpet-shaped
cable glands or other suitable entries with
additional pull-relief.
Intrinsically safe circuits (Ex-i) are to be
connected through the coloured (light blue)
cable entries.
The mounting directives applicable to the
fitted cable entries are to be observed.
When using cable entries with a lower IP
protection than that which applies to the
device (see technical data) the IP protection
of the whole device will be reduced.
In order to establish the minimum protection
category, unused holes have to be closed with
a certified blanking plug.
Care has to be taken that when fitting the cable
entries, sealing inserts appropriate to the cable
diameter are used.
In case of sealing inserts that are cut out, it will
have to be ensured that the insert is properly
adapted to the cable diameter.
All vacant metric CCH/EATON cable entries are
to be closed with the certified blanking plug for
metric cable entries.
In order to ensure the required minimum
protection category, the cable glands shall
be tightened down.
Overtightening might impair the
protection category.
Attention: When tightening the cap
nut of the type ADE 1F metal cable entry, the
screwing is to be protected against
twisting by means of a suitable tool.
6.4 Flange and metal plates
If flange plates have to be removed in case of
plastic terminal boxes (e.g. for drilling entry
holes), attention will have to be paid to the
proper fit of the flange plate and of the clamp
clip when mounting them in order to maintain
the minimum protection category.
Flange plates for stainless steel terminal
boxes shall be fitted so that the IP protection
in maintained. Pay attention to the proper
seat of the sealing element.
PE conductors fed from outside are to be
connected to the PE terminal provided on
the flange. The maximum cross-section is
50mm².
Attention: Metal flanges, metal plates
and metal cable glands shall be included in
the equip potential earth connection.
If terminal boxes with plastic flanges are
used within the scope of the type examina-
tion certificate in ambient temperatures
below -40°C, they shall be installed in such a
way that they are protected against
inadmissible mechanical loads.
6.5 Closing the device/
cover closure
Any foreign matter is to be removed
from the apparatus.
In order to ensure the required minimum
protection category, the cover screws are to
be tightened down.
Overtightening might impair the
protection category.
6.6 Taking into operation
Prior to taking the apparatus into operation,
the tests specified in the relevant national
regulat
ions will have to be carried out. Apart
from that, the correct functioning and installa-
tion of the apparatus in accordance with these
operating instructions and other applicable
regulations will have to be checked.
Incorrect installation and use of
the terminal boxes can invalidate the
guarantee.
7 Maintenance / Servicing
The relevant national regulations which
apply to the maintenance/repair of electrical
apparatus in explosive atmospheres, will
have to be observed (IEC/EN 60079-17).
Before opening the enclosure make sure
that the terminal box is disconnected from
the voltage, or take the appropriate
protective measures.
In case of intrinsically safe circuits, working is
permitted while voltage applies.
The required maintenance intervals depend
on the specific application and will therefore
have to be determined by the user dependent
on the conditions of use.
Fig. 4
Apparatus holder size 2A for pipe mounting
Fig. 5
Apparatus holder size 2A for channel- and wall mounting
C
C
Clamp fastening holes for
termional box GHG 721 0...
Clamp fastening holes for
terminal box GHG 721 0...
Explosion protected terminal boxes type, GHG 72.
GB
12
When servicing the apparatus, particularly
those parts that are decisive for the type of
protection against explosion, will have to be
checked (e.g. intactness and tightness of the
enclosure, efficacy of the gaskets and the
cable entries).
Before closing the enclosure cover, pay
attention to the correct position and intact-
ness of the holding-down clamps
(see fig. 2, page 10).
X
ATEX - IEC
To avoid a build-up of electrostatic charge,
only use a damp cloth or sponge to clean the
adhesive sticker and equipment.
If during servicing, repairs prove to be
necessary, section 8 of these operating
instructions will have to be observed.
8 Repairs / Overhaul /
Modifications
Overhaul and repairs may only be carried out
with genuine CCH/EATON spare parts.
Repairs that affect the explosion
protection, may only be carried out by CCH/
EATON or a qualified electrician in compli-
ance with the applicable national rules
(IEC/EN 60079-19).
Modifications to the apparatus or changes of
its design are not permitted, except for the
mounting of additional cable entries and the
installation of supply terminals in accordance
with the approval of the apparatus.
9 Disposal/Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed.
In case of disposal you can obtain additional
information from your Cooper Crouse-Hinds/
EATON branch.
In order to facilitate the recycling of individual
components, plastic parts are provided
with the identification mark of the plastic
material used.
Subject to modifications or supplement of the
product range.
Fig. 6
Apparatus holder, size 3 for pipe mounting, horizontally
Fig. 7
Apparatus holder, size 3 for channel- and wall mounting, horizontally
C
C
Screwed fastening holes for terminal boxes GHG 721 1....
Clamp fastening holes for terminal boxes GHG 721 1....
Explosion protected terminal boxes type, GHG 72.
GB
13
Boites de jonction type GHG 72. pour atmosphères explosives
F
Boite de jonction GHG 721 1...
Dimensions boites de jonction en plastique
X = dimensions de fixation
1 Caractéristiques techniques
GHG 721 0 GHG 721 1
1.1 Boites de jonction en plastique GHG 721 ...
ATEX Certificat de Conformité: BVS 13 ATEX E 013 X
Marquage selon 2014/34/UE et directive
EN 60079-0:
II 2G Ex e
1)
IIC T4
2)
/T5/T6 Gb
II 2D Ex tb IIIC T80°C / T95°C Db
1)
En option, le marquage pourra être complété avec les modes de protection des composants internes additionnels,
par exemple « d », « e », « mb » et/ou « ia/ib
2)
».
2)
T4 : Uniquement dans le cas où des bornes à sécuritée intrinsèque « Ex i » sont utilisées.
IECEx Certificat: IECEx BVS 13.0031X
Marquage selon
IEC 60079-0: Ex e
1)
IIC T4
2)
/T5/T6 Gb
Ex tb IIIC T80°C / T95°C Db
1)
En option, le marquage pourra être complété avec les modes de protection des composants internes additionnels,
par exemple « d », « e », « mb » et/ou « ia/ib 2)».
2)
T4 : Uniquement dans le cas où des bornes à sécuritée intrinsèque « Ex i » sont utilisées.
Dissipation thermique max.
Classe de température / max. température
ambiante admissible
T6 / 40 °C T6 / 50 °C T5 / 40 °C T5 / 55 °C
Version GRP GHG 721 0 16 W 10 W 22 W 16 W
Version GRP GHG 721 1 24 W 15 W 33 W 24 W
Tension nominale: jusqu’à 690 V
Courant nominal: voir tableau à l’intérieur du couvercle
Température ambiante admissible /
Temp. de stockage dans l’emballage original
-40 °C/-55°C à +40°C/+55°C (m
odèles de liste)
Boitier avec plaque plastique amovible -20 °C
-40 °C
pour un montage avec protection contre les chocs (4J)
B
oitier avec plaque métallique interne
et borne de terre traversante
-42 °C
D’autres températ
ures possibles avec des modèles spéciaux.
Indice de protection selon CEI/EN 60529: IP 66 (catalogue version)
IP 65 (enclosure with plastic flange)
Classe d’isolation selon CEI/EN 61140: Class I pour les BJ avec plaque laiton
Class II pour les BJ avec PE polyamide
Bornes de raccordement
Boite de jonction GHG 721 0... max. 16 mm²
Boite de jonction GHG 721 1... max. 35 mm²
Test torques selon spécification du client et certificat
Empty weights
Boite de jonction GHG 721 0... env. 1,1 kg
Boite de jonction GHG 721 1... env. 1,7 kg
Couples de serrage testés
Ecrou borgne d’entrée de câble voir le Chapitre 11.
Vis du couvercle: 2,50 Nm
14
Boites de jonction type GHG 72. pour atmosphères explosives
F
2 Légende
Attention
Ce symbole met en garde contre un éventuel
défaut. Le non-respect de cette consigne
peut entrainer une panne totale de l’appareil
ou du système ou de l’installation à laquelle
il est connecté.
Remarque
Ce symbole indique la présence d’informations
importantes.
X
ATEX - IEC
Conditions particulières:
Ce symbole indique la présence de conditions
particulières d’utilisation à respecter, en lien
avec l’attestation d’examen UE de type et le
certificat IEC Ex.
2.1 Consignes de sécurité
Groupe cible:
Pour les électriciens qualifiés et les
personnels ayant reçu les formations
adéquates, conformément à la législation
nationale en vigueur et, si applicable, à la
norme CEI/EN 60079-14 sur les installations
électriques pour les atmosphères explosives.
Les boites de jonction GHG 72. ne
conviennent pas pour une utilisation en
zones 0 et 20.
Les exigences des CEI/EN 60079-31 en ce qui
concerne les dépôts de poussière excessifs
et la température doivent être considérées
par I’utilisateur.
Respecter la classe de températures et le
type de protection contre l'inflammation
indiqués sur les appareils.
Il n’est pas permis de transformer ou de
modifier les boites de jonction.
Seules des boîtes de jonction intactes
devront être employées pour la fonction qui
leur est dév
olue.
Avant la mise en service, les boites de
jonction doivent être vérifiées selon
l’instruction donnée dans la section 6.
Respectez les prescriptions nationales de
sécurité et de prévoyance contre les
accidents ainsi que les consignes de sécurité
de ce mode d’emploi en italique comme ce
texte.
3 Conformité avec les normes
Les boîtes à jonction sont conformes aux
normes reprises dans la déclaration de
conformité, jointe séparément.
Les références aux normes et directives dans
cette notice se réfèrent toujours à la dernière
version. Les suppléments éventuels doivent
également être respectés.
4 Domaine d’utilisation
Les boites de jonction en plastique on en
acier inoxydable conviennent à l’emploi en les
zones 1, 2 et zones 21, 22 d’une atmosphère
explosive selon CEI/EN 60079-10-1 et
CEI/EN 60079-10-2!
Pour l’enveloppe et les pièces métalliques
extérieures, des matières de qualité supé-
rieure ont été employées qui assurent une
protection appropriée contre la corrosion et
une résistance contre des agents chimiques
en “atmosphère industrielle normale”:
- polyester renforcé en fibres de verre
- acier inoxydable V 4A AISI 316 L.
En cas d‘utilisation en atmosphère extrè-
mement corrosive, vous pouvez obtenir des
informations complémentaires sur la résis-
tance chimique des plastiques utilisés chez
la succursale Cooper Crouse-Hinds (CCH)/
EATON de votre région.
5 Utilisation / Propriétés
Les boites de jonction servent à la distribution
de l’énergie électrique, p.e. des circuits
d’éclairage, des circuits de chauffage, des
circuits de commande, des circuits à
sécurité intrinsèque etc..
Quant à la classe de température, le groupe
d’explosion et la température ambiante
admissible, voir les caractéristiques techniques.
Si elles ne sont pas mentionnées dans cette
notice, les informations d’utilisation et de
sécurité qui concernent des composants
provenant de fournisseurs extérieurs,
devront être demandées auprès du fabricant
de ces composants.
Pour l’utilisation, les consignes des
sections 3 et 4 devront être respectées.
Les utilisations autres que celles décrites
ne sont admises qu’avec le consentement
écrit de CCH/EATON. Lors de l’utilisation, les
instructions selon point 7 de ce mode
d’emploi doivent être respectées.
La responsabilité de qualification et la
bonne utilisation de ces boites à jonction
incombe à l’utilisateur seul.
15
Boites de jonction type GHG 72. pour atmosphères explosives
F
6 Installation
Pour l’installation et l’exploitation de ces
appareils, la règlementation nationale en
vigueur ainsi que les règles de la technique
généralement reconnues devront être
respectées (CEI/EN 60079-14).
X
ATEX - IEC
Pour l’installation de bornes d’alimentation
supplémentaires certifiées séparément,
respecter les distances de fuites et d’isolement
de la norme CEI/EN 60079-7 tableau 1.
6.1 Montage
Le montage de boites de jonction peut se faire
sans ouvrir l’enveloppe.
En cas de jonction ne doivent reposer que sur
les points de fixation prévus. La vis choisie doit
être en rapport avec le trou de fixation (voir plan
coté page 13) et elle ne doit pas endommager
le trou (par ex. emploi d’une rondelle).
Les boites de jonction doivent être fixées en
diagonale avec au moins 2 vis.
Si les vis sont forcées, l’appareil peut
être endommagé.
Les boites de jonction en plastique GHG 721 0
et GHG 721 1 sont conçues pour le montage
sans vis sur des plaques de montage sur tube,
voir fig. 4 à 7, page 16-17).
Les instructions respectives pour le
montage devront être respectées.
6.2 Ouverture de l’appareil /
Raccordement électrique
Le raccordement électrique de
l’appareil ne doit se faire que par une
personne qualifiée (CEI/EN 60079-14).
Les distances minimales d’isolement
préconisées dans la norme CEI/EN 60079-7,
tableau 1, doivent être respectées.
Les valeurs de charge électrique du tableau
qui se trouve sur la face interne du couvercle,
doiv
ent être respectées.
Afin de maintenir le mode de protection,
la connexion des conducteurs doit se faire
très soigneusement.
L’isolation doit couvrir le conducteur
jusqu’à la borne. Le conducteur lui-même
ne doit pas être endommagé.
Les sections minimales et maximales
admissibles des conducteurs doivent être
respectées (voir caractéristiques techniques).
Toutes les vis et/ou écrous des bornes de
connexion, aussi celles des bornes non
utilisées, doivent être serrées à fond.
La borne standard installée est prévue pour le
raccordement direct des conducteurs au cuivre.
En cas de bornes à tige, il faut utiliser des
cosses de câble selon DIN.
Les cosses de câble doivent être
emmanchées par pression sur le câble de
manière appropriée. Il faut veiller à ce que
les entrefers minimaux requis soient
respectés (à 690V -> 12mm).
Dans le cas d’une combinaison Ex-e/Ex-i, il
est essentiel de maintenir la séparation des
circuits et les distances d’isolement.
Les conducteurs du circuit Ex-i doivent être
clair
ement séparés des conducteurs du
circuit Ex-e (voir EN/IEC 60079-11), et ils
doivent être repérés distinctement
(par exemple avec une couleur bleue claire).
Après avoir enlevé le rail DIN (afin de faciliter
l’introduction des câbles), celui-ci devra être
remis en place avant le raccordement
électrique.
Le démontage et le montage se font comme suit:
En écartant les parois láterales du boitier, le
rail DIN peut être détaché de la partie inférieure
du boit
ier.
Pour monter le profilé support, il est mis sur la
came d’arrêt sur l’un côté de la paroi du boitier.
Puis, on le fait encliqueter sur l’autre côté du
boitier (voir fig. 3).
La barrette de terre peut être montée
facultativement en 4 positions (voir fig. 1).
A Face supérieure - PE connexion en bas
B Face supérieure - PE connexion en haut
C Face inférieure - PE connexion en bas
D Face inférieure - PE connexion en haut
La barrette de terre est montée comme suit:
La barrette doit être poussée jusqu’à la butée
dans les règlet
tes de guidage intégrées dans
les parois latérales du boitier.
La barrette doit s'encliqueter dans le
logement au fond du boitier. Il faut faire
attention à ce que la barrette de terre soit
placée de telle manière qu’un raccordement
correct des conducteurs soit assuré.
Si la classe d'isolation est type II (double
isolation), l'autocollant avec le symbole
GHG 905 1002 P0005 pourra être obtenu
auprès du fabricant.
Si le rail DIN n'est pas totalement équipé
de bornes, alors il doit être raccordé au circuit
équipotentiel de mise à la terre.
Fig. 1
Fig. 2
Fig. 3
A
B
C
D
12
16
Boites de jonction type GHG 72. pour atmosphères explosives
F
6.3 Entrées de câble (KLE) /
Bouchons de fermeture
Généralement, seuls des bouchons de
fermeture et des entrées de câble certifiés
doivent être utilisés. Pour des câbles
flexibles il faudra utiliser des presse-étoupes
en forme de trompette ou d’autres entrées
appropriées avec amarrage supplémentaire.
Les câbles des circuits intrinsèques (Ex-i)
doivent être raccordés via les presse étoupe
bleus.
Les directives pour le montage qui s’ap-
pliquent aux entrées de câble utilisées,
doiv
ent être respectées.
Lorsque des entrées de câble avec un indice
de protection IP inférieur à celui de la boite
de jonction sont employées (voir Caractéris-
tiques techniques, page 13), l’indice de
protection IP de l’ensemble sera réduit.
Les entrées de câble non utilisées doivent être
fermées avec un bouchon de fermeture certifié
pour établir l’indice de protection minimum.
Lors du montage des entrées de câble il faudra
veiller à ce que des garnitures d’étanchéité
correspondant au diamètre du câble soient
utilisées.
En cas de garnitures qui doivent être coupées
sur mesure, il faudra faire attention à ce que la
garniture soit adaptée au diamètre du câble.
Toutes les entrées de câble métriques CCH/
EATON non utilisées doivent être fermées avec
un bouchon de fermeture certifié pour des
entrées de câble métriques.
Les entrées de câble doivent être serrées à
fond pour maintenir l’indice de protection
minimum.
Au cas où elles seraient forcées,
cela pourrait être nuisible à l’indice de
protection.
Lors du serrage du chapeau de l'entrée
de câble métallique du, il faudra maintenir le
corps du presse étoupe à l'aide d'une clé
adaptée.
6.4 Plaques amovibles
Si les plaques amovibles doivent être démon
-
tées (pour le percage d’entrées de câble, par
e
xemple) il faudra veiller lors du montage au
maintien de l’indice de protection en replacant
correctement la plaque ainsi que la pièce rouge
de maintien.
Les plaques amovibles des boites en acier
inoxydable sont montées de telle facon que
l’indice de protection IP soit respecté. Il faut
également veiller au bon logement du joint
d’étanchéité.
Les conducteurs de terre amenés de
l’extérieur doivent être connectés à la borne
PE prévue à cet effet sur la bride. La section
maximale est de 50 mm².
Les plaques amovibles en laiton, les
plaques métalliques internes, et les
presse-étoupe métalliques doivent être
reliés au même potentiel.
Si les boîtes de jonction avec plaques
plastiques amovibles sont utilisées dans le
cadre de la certification avec des tempéra-
tures ambiantes inférieures à -40°C, elles
devront être installées de manière à être
protégées contre tout effort mécanique.
6.5 Fermeture du couvercle
Tout corps étranger doit être ôté de
l’appareil.
Pour garantir le type de protection minimale
nécessaire, les KLE doivent être serrées à fond.
Si les vis sont forcées, cela peut être
nuisible à l’indice de protection.
6.6 Mise en service
Avant la mise en service de l’appareil, les
vérifications spécifiées dans les règlements
nationaux individuels devront être exécutées.
De plus, il faudra vérifier la conformité du
montage avec ce mode d'emploi et avec les
autres réglementations en vigueur.
L’installation ou l’utilisation incorrecte
de ces boites à jonction peut entraîner la
perte de la garantie.
7 Maintenance/Entretien
La règlementation nationale en vigueur
pour la maintenance et l’entretien du
matériel électrique pour atmosphère
explosive doit être respectée
(CEI/EN 60079-17).
Avant d’ouvrir l’enveloppe, mettre le boitier
hors tension ou prendre des mesures
préventives appropriées.
En cas de circuits à sécurité intrinsèque, des
travaux sont permis sous tension.
Les intervalles de service requis dépendent
de l’emploi spécifique et devront donc être
fixés par l’utilisateur en tenant compte des
conditions d’utilisation.
Fig. 4
Plaque de montage taille 2A pour fixation sur tube
Fig. 5
Plaque de montage taille 2A pour fixation au mur et sur chemin de câble
C
C
Trous de fixation pour boite de
jonction GHG 721 0
Trous de fixation pour boite de
jonction GHG 721 0
17
Boites de jonction type GHG 72. pour atmosphères explosives
F
Lors de l’entretien des boîtes, surtout les
composants qui sont essentiels à leur mode
de protection contre l’explosion, doivent être
vérifiés (par ex. intégrité des composants anti-
déflagrants et du boîtier, efficacité des joints
de couvercle et serrage des entrées
de câble).
Avant de fermer le couvercle, veillez à ce
que les 2 pattes de maintien du rail DIN
soient bien en place et en bon état
(voir Fig. 2, Page 15).
X
ATEX - IEC
Afin d'éviter toute charge électrostatique,
utiliser uniquement un chiffon humide pour
nettoyer l'étiquette et l'appareil!
Si, lors d’un entretien, on constate que des
travaux d’entretien sont nécessaires, il faudra
suivre le point 8 de ce mode d’emploi.
8 Réparations/Remise en état/
Modification
Les réparations ne doivent être exécutées
qu’à l’aide des pièces de rechange d’origine
CCH/EATON.
Les réparations qui portent sur la
protection contre l’explosion, ne devront
être exécutées que par CCH/EATON ou par
un électricien qualifié en conformité avec la
règlementation nationale en vigueur
(CEI/EN 60079-19).
Il n’est pas permis de transformer ou de
modifier ces appareils, sauf pour le montage
d'entrées de câbles supplémentaires ou de
bornes de raccordement en conformité avec
le certificat ATEX.
9 Évacuation des déchets/
Recyclage
Lors de l’évacuation de ce matériel électrique,
la règlementation nationale respective en
vigueur devra être respectée.
En cas d'élimination, vous pouvez obtenir des
informations supplémentaires auprès de votre
branche Cooper Crouse-Hinds/EATON.
Pour faciliter la réutilisation des composants
individuels, des pièces en matière plastique
ont été repérées de la marque distinctive de
la matière plastique employée.
Sous réserve de modification ou de supplément
de cette série de produits.
Fig. 6
Plaque de montage, taille 3 pour fixation sur tubes, horizontalement
Fig. 7
Plaque de montage taille 3 pour fixation au mur et sur chemin de câble, horizontalement
C
C
Trous de fixation pour boite de jonction GHG 721 1...
Trous de fixation pour boite de jonction GHG 721 1...
18
10 Strombelastungstabelle 10 Current load values 10 Tableau de charge
19
10 Strombelastungstabelle
Anmerkungen:
1) max. Anzahl der Leiter in Abhängigkeit
vom Querschnitt und dem zulässigen
Dauerstrom für vorgenannte Gehäusetype.
Als Leiter zählt jeder eingeführte Leiter
und jeder interne Verbindungsleiter.
Brücken und Schutzleiter werden nicht
gezählt.
2) max. Klemmenzahl in Abhängigkeit
von obengenannter Gehäusetype und der
max. Anzahl der Leiter.
3) max. Klemmenzahl in Abhängigkeit von
obengenannter Gehäusetype und der
eingebauten 2-Leiter-Klemme.
Bei der Auswahl der zulässigen Dauerströme
für die Querschnitte sind die max. Belas-
tungsströme, der verwendeten Klemmen und
der angeschlossenen Kabel- und Leitungen zu
beachten. Leitungen, im Inneren der nach
obiger Tabelle bestückten Gehäuse, müssen
für eine Temperatur von 70 - 80 °C geeignet
sein. Mischbestückungen von Stromkreisen
unterschiedlicher Querschnitte und Ströme
sind durch anteilige Ausnutzung der Tabellen-
werte möglich.
Beispiel:
Bei der Anwendung dieser Tabellenwerte,
dürfen Gleichzeitigkeitsfaktoren oder Be-
messungsbelastungsfaktoren entsprechend
der EN/IEC 60439 berücksichtigt werden.
Der Tabellenwert ist für eine Umgebungs-
temperatur von 40 °C bemessen. Reduktion
bei höheren Temperaturen siehe Betriebs-
vorschrift.
4) In diesem Bereich kann unter Beachtung
der Hinweise und der festgelegten
Einbaumaße im Gehäuse beliebig
zusätzlich bestückt werden.
5) Bestückungen in diesem Bereich erfordern
einen gesonderten Erwärmungsnachweis.
Bestückungsvarianten mit kleineren oder
größeren Querschnitten als in diesen Tabellen
aufgeführt, wurden nicht gemessen. Sie
sind in Verbindung mit den zulässigen Dauer-
strömen gesondert zu betrachten und
erfordern in vielen Fällen eine Messung
(Erwärmungsnachweis).
10 Current load values
Note:
1) max. number of conductors depending on
the cross-section and allowed continuous
current for the mentioned apparatus type.
The number of conductors is the sum of
all incoming conductors and internal wire
connections. Bridge links and earth
conductors do not count.
2) max. number of terminals depending on
the above mentioned apparatus type and
the amx. number of conductors.
3) max. number of terminals depending on
the above mentioned apparatus type and
the built-in 2 wire terminals.
To determine the permissible continuous
current for the selected conductor cross-sec-
tion, the max. rated current for the terminal
used and the connected conductors must be
observed. Conductors used within the
enclosure must be suitable for a temperature
of 70 – 80°C. Mixed circuits of different
cross-sections and currents are possible by
using the table values in the respective
proportions.
Example:
When using this table the simultaneous factor
or the rated load factor in accordance with
IEC/EN 60439 may be taken into considera-
tion. The table values are given for an
ambient temperature of 40°C. Reductions for
higher temperatures see operating instruc-
tions.
4) In this range as many terminals can be
added as physically fit the available
mounting dimension and according to
the instructions.
5) The terminal content in this range requires
a power dissipation test report from the
manufacturer.
Smaller or larger cross sections not given in
the table have not been measured. These are
to observer with respect to their permissible
continuous currents and require in many
cases a power dissipation test.
10 Tableau de charge
Remarques:
1) nombre max. de conducteurs en fonction
de la section et du courant permanent
admissible pour le type de boîtier précité.
Est compté comme conducteur tout
conducteur introduit et tout conducteur
de liaison interne. Les ponts et conduc-
teurs de protection ne sont pas comptés.
2) nombre max. de bornes en fonction du
type de boîtier mentionné ci-dessus et
du nombre max. de conducteurs.
3) nombre max. de bornes en fonction du
type de boîtier mentionné ci-dessus et de
la borne 2 fils intégrée.
Lors de la sélection des courants permanents
admissibles pour les sections, on doit tenir
compte des courants de charge max., des
bornes utilisées et des câbles et lignes
raccordés. Les lignes à l’intérieur des boîtiers
équipés selon le tableau ci-dessus doivent
convenir pour une température de 70 - 80 °C.
Les équipements mixtes de circuits élec-
triques de sections et courants différents sont
possibles moyennant l’application correspon-
dante des valeurs du tableau.
Exemple:
Lors de l’application de ces valeurs de
tableau, les facteurs de simultanéité ou les
facteurs d’utilisation de dimensionnement
suivant CEI/EN 60439 peuvent être pris en
compte. La valeur du tableau est prévue
pour une température ambiante de 40 °C.
Réduction en cas de température plus
élevée, voir instructions de service.
4) Dans cette zone, on peut prévoir un
équipement supplémentaire à volonté à
condition de tenir compte des indications
et des dimensions de montage définies
dans le boîtier.
5) Les équipements dans cette zone
nécessitent un test de dissipation
thermique spécifique par le fabricant.
Les variantes d’équipement avec des
sections plus petites ou plus grandes que
mentionnées dans ces tableaux n’ont pas
été mesurées. En liaison avec les courants
permanents admissibles, elles doivent être
considérées séparément et exigent dans
de nombreux cas une mesure (preuve
d’échauffement).
Querschnitt / mm² Strom / A Anzahl Auslastung
Cross section / mm² Current / A Quantity Quantity Utilisation
Section / mm² Courant / A Nombre Charge
2,5 10 28 (von 40) = 70,0 %
16 35 6 (von 40) = 15,0 %
Summe = 85,0 % <100%
Total
Somme
Publication No.
GHG 720 7001 P0001 D/GB/F (o)
Auflage / 14.2017 / CS
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2017 Eaton
All Rights Reserved
Printed in Germany
dd
11 Kunststoffleitungseinführungen 11 Entrées de câble en plastique 11 Plastic cable glands
Typ Gewicht ca.
Type SW L1 L2 E Weight approx.
Type Poids env.
M12x1,5 15 mm 19,3 mm 12 / 8 mm 16,2 mm 3,4 g
M16x1,5 20 mm 23,0 mm 12 / 8 mm 22,0 mm 6,5 g
M20x1,5 24 mm 25,0 mm 13 / 8 mm 26,5 mm 10,1 g
M25x1,5 29 mm 29,5 mm 13 / 8 mm 32,0 mm 16,9 g
M32x1,5 36 mm 35,5 mm 15 / 10 mm 40,0 mm 27,6 g
M40x1,5 46 mm 39,5 mm 15 / 10 mm 50,5 mm 50,3 g
M50x1,5 55 mm 44,0 mm 16 / 12 mm 60,0 mm 75,9 g
M63x1,5 68 mm 47,0 mm 16 / 12 mm 75,0 mm 11 7, 6 g
Typ
Einsatz-
temperatur-
bereich
Schlag-
energie
Klemmbereich für Leitungen
Einschraub-
gewinde
Farbe Staubschutz-
kappe
Type
operating
temperature
impact
resistance
Cable diameter
Screw-in thread
in enclosure
Colour of dust
protection cover
Type
d'exploitation
température
Pouvoir d´
impact
Diamétre par câble
Partie fi letée
dans l’enveloppe
Cache-poussière
couleur
Dichtung 1+2+3/ Dichtung 1+2/ Dichtung 1/
gasket 1+2+3/ gasket 1+2/ gasket 1/
Garniture d’étanchéité
1+2+3
Garniture d’étanchéité
1+2
Garniture d’étanchéité 1
min. max. min. max. min. max.
°C Joule Ø Nm** Ø
(1)
Nm** Ø Nm** Ø
(1)
Nm** Ø Nm** Ø
(1)
Nm** Nm**
M12x1,5 -20 - 70 4 5,0 0,8 7, 0 1,0 1,2
weiß/ white/ blanc
M16x1,5 -20 - 70 4 5,5 1,0 7, 0 1,0 7, 0 1,0 10,0 1,4 3,3
weiß/ white/ blanc
M20x1,5 -20 - 70 7 5,5 1,5 7, 0 1,0 7, 0 1,5 9,0 1,4 9,5 1,0 13,0 1,7 2,7
weiß/ white/ blanc
M20x1,5 -40 - 70 4 5,5 1,5 7, 0 1,0 7, 0 1,5 9,0 1,4 9,5 1,0 11,0 1,7 2,7
grün/ green/ vert
M25x1,5 -20 - 70 7 8,0 1,5 10,0 2,0 10,0 2,3 13,0 2,6 13,5 1,3 17, 5 2,3 3,0
weiß/ white/ blanc
M25x1,5 -55 - 70 7 8,0 1,5 10,0 2,0 10,0 2,3 13,0 2,6 13,5 1,5 15,0 2,3 3,0
grün/ green/ vert
M32x1,5 -20 - 70 7 14,0 3,0 1 7, 0 4,0 1 7, 5 1,5 21,0 1,3 5,0
weiß/ white/ blanc
M32x1,5 -55 - 70 7 14,0 3,0 1 7, 0 4,0 1 7, 5 1,5 21,0 1,3 5,0
grün/ green/ vert
M40x1,5 -55 - 70 7 19,0 3,3 22,0 5,5 22,0 3,3 28,0 6,7 7, 5
grün/ green/ vert
M50x1,5 -55 - 70 7 24,0 6,0 28,0 7, 0 28,0 5,0 35,0 7, 0 7, 5
grün/ green/ vert
M63x1,5* -55 - 70 7 29,0 12,0 35,0 12,0 36,0 12,0 41,0 13,0 7, 5
grün/ green/ vert
41,0 13,0 48,0 7, 8
* mit M63 zusätzlich mitgelieferter Dichtungseinsatz/
*
M63 with additional seal
* M63 avec joint supplémentaire
** Prüfdrehmomente bei 20°C/
**
Test torques at 20°C
** Couples de serrage testés à 20°C
(1)
Die Prüfungen der Klemmbereiche und Prüfdrehmomente wurden mit Metalldornen durchgeführt.
Bei der Verwendung von Leitungen mit unterschiedlichen Fertigungstoleranzen und Materialeigenschaften kann der Klemmbereich variieren. Bitte verwenden Sie im Zwischenbe-
reich eine geeignete Kombination aus Dichtungen, so dass bei zukünftigen Wartungsarbeiten an der KLE die Hutmutter nachgezogen werden kann.
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can vary by using cables with different manufacturing tolerances
and material properties. Please use a suitable combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work on the cable
entry.
(1)
Les tests des plages de serrage et les valeurs de couple de serrage ont été réalisés avec un mandrin métallique. La plage de serrage peut varier légèrement selon le type
de câble et les propriétés des matériaux utilisés. Pour les plages de serrage intermédiaires, veuillez utiliser des garnitures d’étanchéité qui laisseront la possiblité de
resserrer le chapeau du presse étoupe lors de futures opérations de maintenance.
1
23
1+2+31+21
1
23
1+2+31+21
1
2
3
1+2+31+21
Dichtung 2
seal 2
Garniture
d’étanchéité 2
Dichtung 1
seal 1
Garniture
d’étanchéité 1
Ø 9 mm
Dichtung 1 + 2 + 3 verwenden.
use seal 1 + 2 + 3.
Utilisez garniture d’étanchéité
1 + 2 + 3 garniture d’étanchéité.
Dichtung 3
seal 3
Garniture
d’étanchéité 3
Dichtung 2
seal 2
Garniture
d’étanchéité 2
Dichtung 1
seal 1
Garniture
d’étanchéité 1
Dichtung 3
seal 3
Garniture
d’étanchéité 3
Ø 12 mm
Dichtung 1 + 2 verwenden.
Dichtung 3 entfernen.
Use seal 1 + 2. Remove seal 3.
Utilisez garniture d’étanchéité 1 + 2
garniture d’étanchéité.
Ø 16 mm
Dichtung 1 verwenden.
Dichtung 2 + 3 entfernen.
Use seal 1. Remove seal 2 + 3.
Utilisez garniture d’étanchéité 1
garniture d’étanchéité.
Dichtung 2
seal 2
Garniture
d’étanchéité 2
Dichtung 1
seal 1
Garniture
d’étanchéité 1
Dichtung 3
seal 3
Garniture
d’étanchéité 3
Fig. B Kabeldurchmesser z.B.:
Cable diameter e.g.:
Cable diameter e.g.:
9 mm; M25x1,5
Fig. C Kabeldurchmesser z.B.:
Cable diameter e.g.:
Cable diameter e.g.:
12 mm; M25x1,5
Fig. D Kabeldurchmesser z.B.:
Cable diameter e.g.:
Cable diameter e.g.:
16 mm; M25x1,5
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual
Ce manuel convient également à

dans d''autres langues