IS-0509 – Rev. 2
SOFTWARE/FIRMWARE
This station is compatible with InFusion Design Center software. For new projects it is recommended that rmware and software be
kept to the most current release.
INSTALLATION AND STATION SETUP IN SOFTWARE
Installation of Vantage products should be performed or supervised by a Certied Vantage Installer. Do not use this Relay Station to
control an outlet/plug. High-voltage DIN products must be installed inside of a properly vented and covered DIN enclosure. There are
two methods of connecting the Station Bus to this station:
1. Use the 2 wire pigtail connection located on the top of the DIN relay station, and
2. Use the pins on the side of the Station, to pass Station Bus between DIN stations, part #VDC-0197, (note: the VDC-0197 Station
Bus connector is not supported on all DIN products).
Mount DIN relay station on a standard 35 mm DIN Rail (EN 50022: 1977).
All voltage connections to the RS8-L-DIN relays are wired to removable screw terminal connectors. These relays may be given
custom names in software to facilitate their use in Design Center programming.
INFUSION
First select the room, then click on Vantage Objects in the Object Explorer and expand Stations, WireLink. From the list of stations
double-click on the DIN Relay Station Lighting-DIN to place it in the room. In the Object Editor name the station and make sure it is
assigned to the correct Station Bus.
PROGRAMMING THE RELAY STATION
Because they are relays the eight buttons on the RS8-L-DIN cannot be programmed directly. Programmed Tasks, Time Controls or
Host Commands are used to control the relays. The relays are accessed by selecting them in programmed tasks.
CONFIGURATION
When the station is rst connected to the Station Bus, the diagnostic LED will blink twice followed by a pause, meaning that the
station is connected correctly but not yet congured. From Design Center, click on the Congure Stations button on the toolbar.
Highlight the RS8-L-DIN station. The Status LED will blink 5 times followed by a pause and the button LEDs will blink rapidly
indicating that the station is in conguration mode. To nish conguring press any button on the Station 3 times. The station may also
be congured by typing the serial number in the project le, using this method the station will automatically be congured when the
system is programmed. Once congured the Status LED will blink evenly and the buttons stop blinking.
DIAGNOSTIC LED (STATUS)
The LED blinks steady on and off or 2, 3, 4, or 5 blinks followed by a pause:
One Even Blink: The Station is operating correctly and is congured
Two Blinks: The Station is operating correctly but is not congured
Three Blinks: The Station is not communicating with the Controller. Check Station Bus Wire connections
Four Blinks: Factory problem. Please contact the factory
Five Blinks: The Station is in conguration mode
WIRING DIAGRAM
Strip back insulation
0.25” (6.5mm) RECOMMENDED WIRE TYPE FOR SCREW TERMINALS
LOADS:
Stranded - 0.75 - 3.31mm2 / 18-12 AWG,
copper wire; must match breaker wire gauge
STATION BUS:
Vantage Station Bus (see specications table)