Safety and regulatory compliance
The Model 16 and 16EU have passed extensive testing and comply with the following
specifications and uses:
263556_02
UL1480 listed:
• Fire Protective Signaling Use - UL Category UUMW, File Number S 3241
Control Number 42S9
• Suitable for use indoors in damp locations.
• Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in
accordance with NFPA 70, National Electric Code, 2002, Article 640.
• Suitable for use with fi re alarm circuit wiring methods in accordance with NFPA
70, National Electric Code, 2002, Article 760.
Suitable for use in air handling plenum spaces with a model PC-16 Plenum Cover
installed:
• UL-2043, Fire Test and Visible Smoke Release for Discrete Products and their
Accessories Installed in Air Handling Spaces
• NFPA-70, National Electrical Code, 2002, Article 300.22(C)
• NFPA 90A, 2002, Installation of Air Conditioning and Ventilation Systems,
Paragraph 4.3.10.2.6.5
EMC Directive 89/336/EEC and Article 10 (1) of the directive, EN50081-1 and
EN50082-1 as signifi ed by the CE mark.
The Model 16EU has also been designed to the requirements defi ned in the
following European regulatory specifi cations for combination systems:
• British Standard Code of Practice BS 5839, Part 8
• Netherlands Standard NEN 2575
UL Sensitivity per UL-1480/ ANSI-S12.31:
Wattage Tap Sound pressure level*
dBA at 3.1m (10 ft)
(70V)
Sound pressure level*
dBA at 3.1m (10 ft)
(100V)
1 Watt 74 dBA -
2 Watt 77 dBA 77 dBA
4 Watt 80 dBA 80 dBA
8 Watt 83 dBA 83 dBA
16 Watt 85 dBA 85 dBA
*SPLs given are per the UL1480 specifi ed reporting method
Frequency Response:
Fire alarm: 400 Hz to 4 kHz
General Signaling: 80 Hz to 16 kHz (+/- 3 dB)