Allen-Bradley MicroLogix 1200 Installation Instructions Manual

Taper
Installation Instructions Manual
Publication 1762-IN017B-EN-P - March 2004
Installation Instructions
MicroLogix™ 1200 Isolated Relay Output Module
(Catalog Number 1762-OX6I)
Inside
For More Information................................................................................2
Description................................................................................................3
Installation ................................................................................................3
Mounting...................................................................................................5
System Assembly......................................................................................7
Field Wiring Connections..........................................................................7
I/O Memory Mapping .............................................................................10
Specifications .........................................................................................11
Hazardous Location Considerations .......................................................15
Environnements dangereux ....................................................................16
AB Drives
2 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
For More Information
If you would like a manual, you can:
download a free electronic version from the internet:
www.ab.com/micrologix or www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representative
visiting www.theautomationbookstore.com and placing your order
calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
For Refer to this Document Pub. No.
Information on installing, wiring, and operating a
MicroLogix 1200 Programmable Controller
MicroLogix 1200 Programmable
Controllers User Manual
1762-UM001
Installation guide for the MicroLogix 1200
Programmable Controller.
MicroLogix 1200 Programmable
Controllers Installation Instructions
1762-IN006
Installation guide for the MicroLogix 1200 Memory
Module and Real Time clock.
MicroLogix 1200 Memory Module and/or
Real Time Clock Installation Instructions
1762-IN001
In-depth information on the MicroLogix 1200
controllers instruction set
MicroLogix 1200 and MicroLogix 1500
Programmable Controllers Instruction Set
Reference Manual
1762-RM001
More information on proper wiring and grounding
techniques.
Industrial Automation Wiring and
Grounding Guidelines
1770-4.1
MicroLogix™ 1200 Isolated Relay Output Module 3
Publication 1762-IN017B-EN-P - March 2004
Description
Installation
1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding
Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Item Description Item Description
1a upper panel mounting tab 5 bus connector cover
1b lower panel mounting tab 6 flat ribbon cable with bus connector (female)
2 power diagnostic LED 7 terminal block
3 module door with terminal identification label 8 DIN rail latch
4 bus connector
with male pins
9 pull loop
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
9
3
5
2
1b
1a
7
6
4
8
6
1a
1b
2
AB Drives
4 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
Prevent Electrostatic Discharge
Remove Power
ATTENTION
!
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow these
guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
ATTENTION
!
Remove power before removing or installing this module. When
you remove or install a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
causing permanent damage to the module’s circuitry
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
MicroLogix™ 1200 Isolated Relay Output Module 5
Publication 1762-IN017B-EN-P - March 2004
Mounting
Minimum Spacing
Maintain spacing from
enclosure walls, wireways,
adjacent equipment, etc.
Allow 50.8 mm (2 in.) of
space on all sides for
adequate ventilation, as
shown:
.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN
rail mounting area of the module against the DIN rail. The latch will momentarily
open and lock into place.
ATTENTION
!
Do not remove protective debris strip until after the module and
all other equipment near the module is mounted and wiring is
complete. Once wiring is complete and the module is free of
debris, carefully remove protective debris strip. Failure to remove
strip before operating can cause overheating.
TIP
1762 expansion I/O may be mounted horizontally only.
ATTENTION
!
During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into the
module. Debris that falls into the module could cause damage
when power is applied to the module.
Side
Side
Top
Bottom
MicroLogix
1200
1762 I/O
1762 I/O
1762 I/O
AB Drives
6 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35)
for environments with vibration or shock concerns.
Panel Mounting
Use the dimensional template shown below to mount the module. The preferred
mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6
panhead screws may also be used, but a washer may be needed to ensure a good
ground contact. Mounting screws are required on every module.
TIP
For environments with extreme vibration and shock concerns,
use the panel mounting method described below, instead of DIN
rail mounting.
End Anchor
End Anchor
90
(3.54)
100
(3.94)
40.4
(1.59)
40.4
(1.59)
14.5
(0.57)
For more than 2 modules: (number of modules - 1) x 40.4 mm (1.59 in.)
NOTE:
Hole spacing tolerance:
±0.4 mm (0.016 in.).
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
MicroLogix™ 1200 Isolated Relay Output Module 7
Publication 1762-IN017B-EN-P - March 2004
System Assembly
The expansion I/O module is attached to the controller or another I/O module by
means of a ribbon cable after mounting as shown below.
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the module’s mounting
tabs or DIN rail (if used) are not required unless the mounting surface cannot be
grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.
TIP
Use the pull loop on the connector to disconnect modules. Do
not pull on the ribbon cable.
!
WARNING
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must
be fully seated and the bus connector cover must be
snapped in place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
page 5. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762
I/O module.
AB Drives
8 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
Output Wiring
Basic wiring
(1)
of the 1762-OX6I is shown below.
Labeling the Terminals
A write-on label is provided with the module. Mark the identification of each
terminal with permanent ink, and slide the label back into the door.
(1) Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
OUT0 N.C.
OUT0 N.O.
OUT1 N.C.
OUT1 N.O.
OUT2 N.C.
OUT2 N.O.
OUT3 N.O.
OUT3 N.C.
OUT4 N.C.
OUT4 N.O.
OUT5 N.C.
OUT5 N.O.
CR
CR
CR
CR
CR
CR
L1 OR +DC
L1 OR +DC
L1 OR +DC
L1 OR +DC
L1 OR +DC
L1 OR +DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
MicroLogix™ 1200 Isolated Relay Output Module 9
Publication 1762-IN017B-EN-P - March 2004
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped
end of the wire or a spade lug. The terminals will accept a 6.35 mm
(0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.904 Nm (8
in-lbs).
3. After wiring is complete, remove the debris shield.
ATTENTION
!
Be careful when stripping wires. Wire fragments that fall into a
module could cause damage when power is applied. Once
wiring is complete, ensure the module is free of all metal
fragments.
TIP
If you need to remove the finger-safe cover, insert a screw driver
into one of the square wiring holes and gently pry the cover off.
If you wire the terminal block with the finger-safe cover
removed, you will not be able to put it back on the terminal
block because the wires will be in the way.
AB Drives
10 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
A
ddressing
The addressing scheme for 1762-OX6I is shown below.
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.
Output Data File
Relay outputs are controlled using the bit positions in Word 0, as follows:
1 = relay energized (normally-open contact ON)
0 = relay not energized (normally-closed contact ON)
For each module, the output data file contains the controller-directed state of the
discrete output points. Bit positions 0 through 5 correspond to output points 0
through 5.
w = write only; 0 = always at 0 or OFF state
Wire Type Wire Size Terminal Screw Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.904 Nm (8 in-lbs)
Stranded Cu-90°C (194°F) #16 to #22 AWG 0.904 Nm (8 in-lbs)
Word
Bit Position
1514131211109876543210
00000000000wwwwww
O0:x.0/0
Output (O) File
Output Data File (0)
Slot Number
(1)
Word
Bit
Bit Delimiter
Word Delimiter
Slot Delimiter
MicroLogix™ 1200 Isolated Relay Output Module 11
Publication 1762-IN017B-EN-P - March 2004
Specifications
General Specifications
Specification Value
Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width)
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
220 g (0.485 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +55°C (-32°F to +131°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 0.030 in. max. peak-to-peak
DIN Rail Mounting: N.O. 2.5G, N.C. 2.5G
Panel Mounting: N.O. 2.5G, N.C. 0.5G
Shock Operating: 30G
Module Power LED On: indicates power is applied.
Vendor I.D. Code 1
Product Type Code 7
Product Code 124
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
(C-UL under CSA C22.2 No. 213)
Noise Immunity NEMA standard ICS 2-230
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (EN61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (EN61000-4-3) 10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
Fast Transient Burst (EN61000-4-4) 2 kV, 5 kHz
Surge Immunity (EN61000-4-5) 2 kV common mode, 1 kV differential mode
Conducted Immunity (EN61000-4-6)
10V, 0.15 to 80 MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
AB Drives
12 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
Output Specifications
Specification Value
Voltage Category AC/DC Type C relay
Operating Voltage Range 5 to 265V ac
5 to 125V dc
Number of Outputs 6
Bus Current Draw (max.) 110 mA at 5V dc
110 mA at 24V dc
Heat Dissipation 2.8 W
Signal Delay (max.) -Resistive Load
(1)
(1) Relay on-delay time does not include contact bounce time.
On Delay: 10 ms (max.), 6 ms (typical)
Off Delay: 20 ms (max.), 12 ms (typical)
Off-State Leakage Current 0 mA
On-State Current
100 mA at 5V dc
(2)
(2) This value is for reference only.
Continuous Current per Point 7A max. (See Relay Contact Ratings below.)
Continuous Current Per Module (max.) See Module Load Ratings on page 13.
Power Supply Distance Rating 6
Isolated Groups Outputs 0 to 5: Individually isolated
Output Group to Backplane Isolation Verified by one of the following dielectric tests:
1836V ac for 1 second or 2596V dc for 2 seconds.
265V ac working voltage (IEC Class 2 reinforced insulation)
Output Group to Output Group
Isolation
Verified by one of the following dielectric tests:
1836V ac for 1 second or 2596V dc for 2 seconds.
265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced insulation)
MicroLogix™ 1200 Isolated Relay Output Module 13
Publication 1762-IN017B-EN-P - March 2004
Relay Contact Ratings
Module Load Ratings
Volts (max.)
(ac:50/60 Hz)
Maximum
Amps per
Point
(Resistive)
(1)
(1) The continuous current per module must be limited so the module power does not exceed 1440VA.
Pilot Duty
(3)
(3) Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Voltamperes
Make Break Make Break
240V ac 5.0A 15A 1.5A
3600 VA 360 VA
120V ac
7.0A
(2)
(2) 6 A in ambient temperatures above 40°C.
30A 3.0A
125V dc 0.4A 0.4A
50 VA
(4)
(4) DC Make/Break Voltamperes must be limited to 50 VA for DC voltages between 28V dc and 125V dc. DC Make/Break
Voltamperes below 28V dc are limited by the 3 A Make/Break current limit.
24V dc
7.0A
(2)
3.0A
72 VA
(4)
IMPORTANT
Controller must be operated within Relay Contact Ratings (above)
and Module Load Ratings (page 13).
Volts (max.) Controlled Load (Current) per Module (max.)
240V ac
12A
(1)
120V ac
12A
(1)
(1) Current per relay limited to 6A at ambient temperatures above 40°C.
125V dc 2.4A
24V dc
30A
(2)
(2) 24A in ambient temperatures above 40°C. Limited by ambient temperature and the
number of relays controlling loads. See below.
IMPORTANT
Controller must be operated within Relay Contact Ratings
(page 13) and Module Load Ratings (above).
AB Drives
14 MicroLogix™ 1200 Isolated Relay Output Module
Publication 1762-IN017B-EN-P - March 2004
Relays Used vs. Maximum Current per Relay (24V dc)
123
3
4
5
6
7
8
456
Number of Relays Controlling Loads
Maximum Current per Relay (Amps)
Ambient Temperature
below 40°C
Ambient Temperature
above 40°C
MicroLogix™ 1200 Isolated Relay Output Module 15
Publication 1762-IN017B-EN-P - March 2004
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The module is rated Class I, Division 2 by C-UL only.
The following WARNING statement applies to use in hazardous locations.
!
WARNING
\
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page
5. If DIN rail mounting is used, an end stop must be installed
ahead of the controller and after the last 1762 I/O module.
All wiring must comply with N.E.C. article 501-4(b).
AB Drives
Publication 1762-IN017B-EN-P - March 2004 PN 40071-159-01(2)
Supersedes Publication 1762-IN017A-EN-P - January 2004 Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in Malaysia.
´H'+[!¶2:¨
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. The module is rated Class I,
Division 2 by C-UL only.
La mise en garde suivante s’applique à une utilisation dans des environnements
dangereux.
MicroLogix is a trademark of Rockwell Automation.
Belden is a trademark of Belden, Inc.
!
AVERTISSEMENT
DANGER D’EXPLOSION
La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1,
Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est
coupée.
Ne pas connecter ou connecter des composants sans s'être
assuré que l'alimentation est coupée.
Ce produit doit être installé dans une armoire.
Pour les applications de Classe I, Division 2, le connecteur
de bus doit être correctement installé et son couvercle
enclenché.
Pour les applications de Classe 1, Division 2, tous les
modules doivent être installés en contact direct les uns avec
les autres, comme indiqué page 5. Si on utilise le montage
sur rail DIN, une butée doit être placée à l'avant de
l'automate et après la dernière unité d'E/S 1762.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Allen-Bradley MicroLogix 1200 Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues