Allen-Bradley MicroLogix 1200 Installation Instructions Manual

Taper
Installation Instructions Manual
Publication 1762-IN016B-EN-P - December 2005
Installation Instructions
MicroLogix 1200 Analog Output Module
Catalog Number 1762-OF4
Inside...
For See Page
Important User Information 2
Before Installation 3
Prevent Electrostatic Discharge 3
Remove Power 4
Hazardous Location Considerations 4
Environnements dangereux 5
About the Analog Output Module 6
Install the Analog Output Module 7
Mount the Module on a DIN Rail 7
Mount the Module on a Panel 8
Wire the Analog Output Module 9
Ground the Module 10
System Assembly 12
I/O Memory Mapping 13
Input Data File 13
Output Data File 14
Configuration Data File 14
Specifications 17
Additional Resources 19
2 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls publication
SGI-1.1 available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature describes some important differences between solid state
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of
the product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
SHOCK HAZARD
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people
that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people
that surfaces may be dangerous temperatures.
MicroLogix 1200 Analog Output Module 3
Publication 1762-IN016B-EN-P - December 2005
Before Installation
1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding
Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Prevent Electrostatic Discharge
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
ATTENTION
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow these
guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
4 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Remove Power
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
ATTENTION
Remove power before removing or installing this module. When
you remove or install a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
sending an erroneous signal to your system’s field devices,
causing unintended machine motion,
causing an explosion in a hazardous environment, or
causing permanent damage to the module’s circuitry.
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
page 7. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
All wiring must comply with N.E.C. article 501-4(b).
MicroLogix 1200 Analog Output Module 5
Publication 1762-IN016B-EN-P - December 2005
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
WARNING
DANGER D’EXPLOSION
La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1,
Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est coupée.
Ne pas connecter ou déconnecter des composants sans s'être
assuré que l'alimentation est coupée.
Ce produit doit être installé dans une armoire.
Pour les applications de Classe I, Division 2, le connecteur de
bus doit être correctement installé et son couvercle
enclenché.
Pour les applications de Classe 1, Division 2, tous les modules
doivent être installés en contact direct les uns avec les autres,
comme indiqué page 7. Si on utilise le montage sur rail DIN,
une butée doit être placée à l'avant de l'automate et après la
dernière unité d'E/S 1762.
6 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
About the Analog Output Module
Figure 1 Product Description
Item Description Item Description
1a upper panel mounting tab 5 bus connector cover
1b lower panel mounting tab 6 flat ribbon cable with bus connector
(female)
2 power diagnostic LED 7 terminal block
3 module door with terminal identification
label
8 DIN rail latch
4 bus connector
with male pins
9 pull loop
1a
1b
5
2
3
9
4
6
7
1a
1b
2
6
8
MicroLogix 1200 Analog Output Module 7
Publication 1762-IN016B-EN-P - December 2005
Install the Analog Output Module
Maintain spacing from enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown:
Figure 2 Module Spacing
Mount the Module on a DIN Rail
The module can be mounted using the following DIN rails: 35 x 7.5 mm
(1.38 x 0.30 in.) (EN 50 022 - 35 x 7.5)
or 35 x 15 mm (1.38 x 0.60 in.) (EN 50 022 - 35 x 15).
ATTENTION
Do not remove protective debris strip until after the module and
all other equipment near the module is mounted and wiring is
complete. Once wiring is complete and the module is free of
debris, carefully remove protective debris strip. Failure to remove
strip before operating can cause overheating.
TIP 1762 expansion I/O is only mounted horizontally.
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all
debris (for example, metal chips and wire strands) is kept from
falling into the module. Debris that falls into the module could
cause damage when power is applied to the module.
Side
Side
Top
Bottom
MicroLogix
1200
1762 I/O
1762 I/O
1762 I/O
8 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN
rail mounting area of the module against the DIN rail. The latch will momentarily
open and lock into place.
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35)
for environments with vibration or shock concerns.
Figure 3 DIN Rail Mount
Mount the Module on a Panel
Use the dimensional template to mount the module. The preferred mounting
method is to use two M4 or #8 panhead screws per module. M3.5 or #6 panhead
screws may also be used, but a washer may be needed to ensure a good ground
contact. Mounting screws are required on every module.
TIP
For environments with extreme vibration and shock concerns, use
the panel mounting method described below, instead of DIN rail
mounting.
End Anchor
End Anchor
MicroLogix 1200 Analog Output Module 9
Publication 1762-IN016B-EN-P - December 2005
Figure 4 Dimensional Template
Wire the Analog Output Module
The output type selection, current or voltage, is made by wiring to the appropriate
terminals, Iout or Vout, and by the type/range selection bits in the Configuration
Data File (see page 14).
Consider the following when wiring your system:
The analog common (COM) is not connected to earth ground inside the
module. All terminals are electrically isolated from the system.
Channels are not isolated from each other.
Use Belden 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire (shield) should be connected to the
metal mounting panel (earth ground). Keep shield connection to earth
ground as short as possible.
To ensure optimum accuracy for voltage type outputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the I/O
system as close to your voltage type sensors or actuators as possible.
ATTENTION
Analog outputs may fluctuate for less than a second when power
is applied or removed. This characteristic is common to most
analog outputs. While the majority of loads will not recognize this
short signal, it is recommended that preventive measures be taken
to ensure that connected equipment is not affected.
90
(3.54)
100
(3.94)
40.4
(1.59)
40.4
(1.59)
14.5
(0.57)
For more than 2 modules: (number of modules - 1) x 40.4 mm (1.59 in.)
NOTE:
Hole spacing tolerance:
±0.4 mm (0.016 in.).
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
10 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Figure 5 Terminal Block Layout
Figure 6 Differential Sensor Transmitter Types
A write-on label is provided with the module. Mark the identification of each
terminal with permanent ink, and slide the label back into the door.
Ground the Module
This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the module’s mounting
tabs or DIN rail (if used) are not required unless the mounting surface cannot be
TIP
Grounding the cable shield at the module end only usually
provides sufficient noise immunity. However, for best cable shield
performance, earth ground the shield at both ends, using a 0.01
µF capacitor at one end to block AC power ground currents, if
necessary.
V out 3
V out 2
V out 1
V out 0
I out 3
I out 2
I out 1
I out 0
COM
COM
Commons connected
internally.
I out 0
I out 1
V out 2
V out 3
V out 0
V out 1
COM
I out 3
I out 2
COM
Current Load
Voltage Load
MicroLogix 1200 Analog Output Module 11
Publication 1762-IN016B-EN-P - December 2005
grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.
Wire the Finger-safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
Figure 7 Finger-safe Terminal Block
To wire the terminal block:
1. Route the wire under the terminal pressure plate.
You can use the stripped end of the wire or a spade lug. The terminals will
accept a 6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.904 Nm
(8 in-lbs).
3. After wiring is complete, remove the debris shield.
TIP
If you need to remove the finger-safe cover, insert a screw driver
into one of the square wiring holes and gently pry the cover off.
If you wire the terminal block with the finger-safe cover removed,
you will not be able to put it back on the terminal block because
the wires will be in the way.
12 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
System Assembly
The expansion I/O module is attached to the controller or another I/O module by
means of a ribbon cable after mounting as shown below.
Figure 8 Ribbon Cable Connection
Wire Type Wire Size Terminal Screw Torque
Solid Cu-90 °C (194 °F) #14 to #22 AWG 0.904 Nm (8 in-lbs)
Stranded Cu-90 °C (194 °F) #16 to #22 AWG 0.904 Nm (8 in-lbs)
TIP
Use the pull loop on the connector to disconnect modules. Do
not pull on the ribbon cable.
ATTENTION
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
page 7. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
MicroLogix 1200 Analog Output Module 13
Publication 1762-IN016B-EN-P - December 2005
I/O Memory Mapping
The addressing scheme for 1762-OF4 is shown below.
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.
Input Data File
For each module, slot x, words 0 and 1 contain the analog output module status
data for use in the control program.
The bits are defined as follows:
SOx = General status bits for output channels 0 through 3. This bit is set
when an error (over- or under-range) exists for that channel, or there is a
general module hardware error.
OOx = Over-range flag bits for output channels 0 through 3. These bits
indicate an input signal above the user range and can be used in the control
program for error detection. The module continues to convert analog data to
the maximum full range value while this bit is set (1). The bit is reset (0)
when the error clears.
UOx = Under-range flag bits for output channels 0 through 3. These bits
indicate an input signal below the user range. They can be used in the
control program for error detection. The module continues to convert analog
data to the minimum full range value while this bit is set (1). The bit is reset
(0) when the error clears.
Word
Bit Position
1514131211109876543210
0 Reserved SO3 SO2 SO1 SO0
1 Reserved UO0 OO0 UO1 OO1 UO2 OO2 UO3 OO3
O0:x.0/0
Output (O) File
Output Data File (0)
Slot Number
(1)
Word
Bit
Bit Delimiter
Word Delimiter
Slot Delimiter
14 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Output Data File
For each module, slot x, words 0 through 3 contain the channel output data.
Words 0 through 3 contain the analog output data for channels 0 through 3,
respectively. The module ignores the “don’t care” bits (0 through 2), but checks the
sign bit (15). If bit 15 equals 1, the module sets the output value to 0V or 0 mA.
Words 0 through 3 contain the analog output data for channels 0 through 3,
respectively. The module ignores the “don’t care” bits (0 and 1), but checks the sign
bit (15), and bit 14. If bit 15 equals 1, the module sets the output value to 0V or
0 mA. If bit 15 equals zero and bit 14 equals 1, the module sets the output value to
10.5V dc or 21 mA.
Configuration Data File
The configuration of the format for analog outputs is made at going to run (GTR).
Changes made to the configuration file while in run mode have no effect on the
outputs.
The configuration table for analog outputs is shown in the Configuration Data FIle
table.
Raw/Proportional Format
Word
Bit Position
1514131211109876543210
0 0 Channel 0 Data 0 to 32,760 0 0 0
1 0 Channel 1 Data 0 to 32,760 0 0 0
2 0 Channel 2 Data 0 to 32,760 0 0 0
3 0 Channel 3 Data 0 to 32,760 0 0 0
Scaled-for-PID Format
Word
Bit Position
1514131211109876543210
0 0 0 Channel 0 Data 0 to 16,380 0 0
1 0 0 Channel 1 Data 0 to 16,380 0 0
2 0 0 Channel 2 Data 0 to 16,380 0 0
3 0 0 Channel 3 Data 0 to 16,380 0 0
MicroLogix 1200 Analog Output Module 15
Publication 1762-IN016B-EN-P - December 2005
Bit 15 and Bits 7 through 0 - Reserved
These bits are reserved and are not checked by the module.
Data Format (Bits 14 through 12)
These bits indicate the format of the data as shown in the following table. Other
combinations of these bits are not supported and result in an error.
Configuration Data File
Word
Bit Position
1514131211109876543210
0
reserved
Data Format
Output Channel 0
Type/Range Select
Output Channel 0
reserved
1 Data Format
Output Channel 1
Type/Range Select
Output Channel 1
reserved
2 Data Format
Output Channel 2
Type/Range Select
Output Channel 2
reserved
3 Data Format
Output Channel 3
Type/Range Select
Output Channel 3
reserved
4reserved
5reserved
6reserved
7reserved
Bit Settings Data Format
14 13 12
0 0 0 Raw/Proportional
0 1 0 Scaled for PID
other Not Supported
16 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Type/Range Select (Bits 11 through 8)
These bits indicate the type and range as in the following table. Other combinations
of these bits are not supported and result in an error.
Configuration via RSLogix 500
The module can be configured using RSLogix 500 programming software, as shown
below.
Bit Settings Data Format
11 10 9 8
0000Voltage Mode 0 to 10V dc
0011Current Mode 4 to 20 mA
other Not Supported
MicroLogix 1200 Analog Output Module 17
Publication 1762-IN016B-EN-P - December 2005
Specifications
Analog Input Module - 1762-OF4 General Specifications
Specification Value
Dimensions
(H x W x D), Approx.
90 mm (3.54 in) x 40 mm (1.58 in) x 87 mm (3.43 in)
height including mounting tabs is 110 mm (4.33 in)
Approx. Shipping Weight
(with carton)
235 g (0.517 lb)
Storage Temperature -40 … 85 °C (-40 … 185 °F)
Operating Temperature 0 … 55 °C (32 … 131 °F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 m (6561 ft)
Vibration Operating: 10 … 500 Hz, 5G, 0.030 in. max. peak-to-peak
Shock Operating: 30 g
Bus Current Draw (max.) 40 mA at 5V dc
165 mA at 24V dc
Analog Normal Operating Range Voltage: 0 … 10V dc
Current: 4 … 20 mA
Full Scale
(1)
Analog Ranges
(1) The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to
convert the analog output up to the maximum full scale range.
Voltage: 0 … 10.5V dc
Current: 0 … 21 mA
Resolution 12 bits (unipolar)
Repeatability
(2)
(2) Repeatability is the ability of the output module to reproduce output reading when the same controller value is applied to it
consecutively, under the same conditions and in the same direction.
±0.1%
Heat Dissipation 2.8 W
Output Group to System Isolation
30V ac/30V dc rated working voltage
(3)
(IEC Class 2 reinforced insulation)
type test: 500V ac or 707V dc for 1 minute
(3) Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth ground.
Recommended Cable Belden 8761 (shielded)
Vendor I.D. Code 1
Product Type Code 10
Product Code 66
18 MicroLogix 1200 Analog Output Module
Publication 1762-IN016B-EN-P - December 2005
Analog Output Module - 1762-OF4 Output Specifications
Specification Value
Number of Outputs 4 single-ended (bipolar)
D/A Converter Type R-2R Ladder Voltage Switching
Module Update Time 2.5 ms
Resistive Load on Current Output 0 … 500 (includes wire resistance)
Load Range on Voltage Output > 1K
Reactive Load, Current Output < 0.1 mH
Reactive Load, Voltage Output < 1 µF
Typical Overall Accuracy
(1)
±1% full scale at 0 … 55 °C (32 … 131 °F)
±0.5% full scale at 25 °C (77 °F)
Output Ripple
range 0 … 500 Hz
(referred to output range)
< ±0.1%
Non-linearity (in percent full scale) < ±0.5%
Open and Short-Circuit Protection Continuous
Output Protection ±32 mA
(1) Includes offset, gain, non-linearity and repeatability error terms.
MicroLogix 1200 Analog Output Module 19
Publication 1762-IN016B-EN-P - December 2005
Additional Resources
Certifications
Certification Value
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B,
C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Noise Immunity NEMA standard ICS 2-230
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following
levels:
ESD Immunity (EN61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (EN61000-4-3) 10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
Fast Transient Burst (EN61000-4-4) 2 kV, 5 kHz
Surge Immunity (EN61000-4-5) 1 kV galvanic gun
Conducted Immunity (EN61000-4-6)
10V, 0.15 to 80 MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
For Refer to this Publication
Information on installing, wiring, and operating a
MicroLogix 1200 Programmable Controller
MicroLogix 1200 Programmable Controllers User
Manual, 1762-UM001
Installation guide for the MicroLogix 1200
Programmable Controller.
MicroLogix 1200 Programmable Controllers
Installation Instructions, 1762-IN006
Installation guide for the MicroLogix 1200 Memory
Module and Real Time clock.
MicroLogix 1200 Memory Module and/or Real Time
Clock Installation Instructions, 1762-IN001
More information on proper wiring and grounding
techniques.
Industrial Automation Wiring and Grounding
Guidelines, 1770-4.1
Publication 1762-IN016B-EN-P - December 2005 PN 40072-120-01(2)
Supersedes Publication 1762-IN016A-EN-P - July 2003 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
´H'¶2-120-01(2)2¨
MicroLogix and RSLogix 500 are Trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respecive companies.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Allen-Bradley MicroLogix 1200 Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues