WARNING
If the information in this manual is not
followed exactly, a re or explosion may
result causing property damage, personal
injury or loss of life.
-
Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
-
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your
building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
• If you cannot reach your gas supplier,
call the re department.
-
Installation and service must be
performed by a qualied installer,
service agency or the gas supplier.
AVERTISSEMENT
Assurez-vous de bien suivre les instructions
données dans cette notice pour réduire au
minimum le risque d'incendie ou d'explosion
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
- Ne pas entreposer ni utiliser d'essence
ni d'autres vapeurs ou liquides inam-
mables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE
ODEUR DE GAZ:
• Ne pas tenter d'allumer d'appareils.
• Ne touchez à aucun interrupteur. Ne
pas vous servir des téléphones dans
le bâtiment où vous vous trouvez.
Appelez immédiatement votre
fournisseur de gaz depuis un voisin.
Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le
fournisseur de gaz, appelez le service
des incendies.
- L'installation et I'entretien doivent
être assuréx par un installateur ou un
service d'entretien qualié ou par le
fournisseur de gaz.
USER'S INFORMATION MANUAL
CAST IRON GAS-FIRED
HOT WATER AND STEAM BOILERS
2
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels.
Basic Operation and Maintenance
DANGER
There are no user serviceable parts on this boiler. Attempts to service this boiler by someone other than a
qualied gas service technician could void the warranty, cause property damage, personal injury or loss of
life.
CAUTION
Should overheating occur or the gas supply fail to shut o, do not turn o or disconnect the electrical
supply to the pump. Instead, shut o the gas supply at a location external to the appliance.
En cas de surchaue ou si I'admission de gaz ne peut étre coupée, ne pas couper ni débrancher
l'alimentation électrique de la pompe. Fermer plutôt le robinet d'admission de gaz à l'extérieur de I'appareil.
Do not use this boiler if any part has been under water. Immediately call a qualied service technician to
inspect the boiler and to replace any part of the control system and any gas control which has been under
water.
WARNING
Like all central heating appliances, this boiler is equipped with safety devices, which could cause it to
shutdown, requiring service to restore normal operation. Where such a shutdown could result in damage
from low temperatures (such as frozen pipes), do not leave the heating system unattended during cold
weather unless alarms or other safeguards are in place to prevent damage.
DANGER
Indicates an imminently hazardous situation
which, if not avoided, will result in death, serious
injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation
which, if not avoided, could result in death,
serious injury or substantial property damage.
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, may result in moderate or
minor injury or property damage.
NOTICE
Indicates special instructions on installation,
operation, or maintenance which are important
but not related to personal injury hazards.
3
DANGER
THERE ARE NO USER SERVICEABLE PARTS ON THIS BOILER. ATTEMPTS TO
SERVICE THIS BOILER BY SOMEONE OTHER THAN A QUALIFIED GAS SERVICE
TECHNICIAN COULD VOID THE WARRANTY, CAUSE PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
• Do not use this boiler if any part has been under water. Immediately call a qualied service
technician to inspect the boiler and to replace any part of the control system and any gas
control which has been under water.
• Should overheating occur or the gas supply fail to shut o, do not turn o or disconnect the
electrical supply to the pump. Instead shut o the gas supply at a location external to the
appliance/En cas de surchaue ou si l’admission de gaz ne peut étre coupée, ne pas couper ni
débrancher l’alimentation électrique de la pompe. Fermer plutot le robinet d’admission de gaz
à l’extérieur de l’appareil.
This boiler may have parts containing refractory ceramic bers (RCF). See the safety
information on page 8 if this boiler must be serviced or repaired.
1) Thismanualcoversthepropercareanduseofyournewcastiron,gas-redhotwaterorsteamboiler.
2) Instructionstosafelylightandshutdownthisboilerareshownonpages6&7,aswellasonalabelaxed
to the boiler.
3) Allboilersareequippedwithaamerolloutswitch(Figure1).Thisswitchwillshuttheburnersdownin
theeventthatamesexittheburnercompartmentthroughthefrontopening.Iftheboilerfailstore,calla
qualiedheatingserviceagencytodiagnoseandcorrecttheproblem.
4) Allboilersareequippedwithablockedventshut-oswitch(Figure2).Thisswitchwillshuttheboilerdown
intheeventthatthereisanexcessiveblockageintheventsystem.Thisswitchhasaresetbutton,whichmust
be pressed before the boiler can be restarted.
Figure2:BlockedVentSwitchFigure1:FlameRolloutSwitch
4
WARNING
• In the event that the ame rollout switch opens, the cause of the ame rollout must be diagnosed
and corrected by a qualied gas service technician before the boiler is restarted.
• A “tripped” rollout switch must be replaced by an identical switch having the same
temperature setting.
WARNING
A shutdown of the burners due to the blocked vent switch is an indication that there is a problem with the
vent system, such as a blockage. The blocked vent switch should only be reset after a qualied gas service
technician has diagnosed and corrected the venting problem that caused the blocked vent switch to open.
Maintenance
1) Safereliableoperationofthisboilerdependsuponproperperiodicmaintenance.
2) The following should be done on a continuous basis:
• Keeptheareaaroundtheboilerfreeofobjects,whichareammableorwhichcouldobstructtheowof
air into and around the boiler.
Do not store or use sources of hydrocarbons such as bleaches, fabric softeners, paints, cleaners,
refrigerants,andcatboxesneartheboiler.Tracesofthesechemicalscanbedrawnintotheboiler,
causing severe corrosion damage to the boiler and/or objectionable odors.
• Donotexposetheboilertolargeamountsofdustsuchasthatgeneratedbydrywallconstructionor
woodworking.
3) Aqualiedgasservicetechnicianshouldperformthemaintenanceprocedureshownintheinstallation
manual on an annual basis.
4) The owner should visually inspect the venting system on a monthly basis. If any of the following conditions
are found, theboilershouldbeshutdownandaqualiedgasservicetechniciancalledtocorrecttheproblem
before the boiler is placed back in service:
Loose joints, corrosion or other deterioration
Condensate leakage
• Sagsinhorizontalrunsofventpipe
5) The owner should also perform a monthly visual inspection of the boiler and the surrounding system piping.
Todothis,removetheboilerjacketdoor.Ifanyofthefollowingarefound,aqualiedgasservicetechnician
shouldbeconsultedimmediately:
Deterioration of the visible controls, wiring, and sheet metal components
Heating system water Leaks
• Carbon(“soot”)inorneartheburnercompartmentarea
5
WARNING
Carbon (“soot”) in or near the burner compartment area is an indication of a potential carbon monoxide
hazard. If carbon is found, the boiler should be shut down immediately and inspected by a qualied gas
service technician. The cause of the sooting should be found and corrected before the boiler is restarted.
CAUTION
• Failure to regularly blow down the oat type low water cut-o can result in severe damage to boiler.
• If it is necessary to either manually or automatically add water to the boiler more than once a
month, a qualied gas service technician should inspect the system for leaks or defective vents.
Frequent additions of fresh water could result in severe damage to boiler.
Figure3:FloatTypeLowWaterCut-o
7) AuxilaryControls – Many boilers are installed with equipment not supplied with the boiler, but which is
criticalforsafe,reliableoperationoftheboiler.Someexamplesofthistypeofequipmentinclude:
Zone Controls
• BoilerFeedPumps
• DraftInducersandPowerVenters
Motorized Combustion Air Louvers
Make sure that this equipment is maintained in accordance with its manufacturers instructions.
6) SteamBoilersOnly–Steamboilersrequirethefollowingmaintenance:
• Somesteamboilersareequippedwithaoattypelowwatercut-o(Figure3).Thiscontrolmustbe
“blowndown”onaweekly basis, or more often if needed. To do this, follow the instructions on the label
adjacenttothelowwatercut-o.
It will occasionally be necessary to add water to the boiler. In most cases this will be true even if the boiler
isequippedwithanautomaticwaterfeeder(mostautomaticwaterfeedersmaintainthewaterlevelatthe
minimumpointrequiredtoassureboileroperation).Onamonthly basis,turntheboileroandwaitat
least 10 minutes for any water in the system to return to the boiler. Add water to the boiler until the water
levelintheglassisapproximately6”(about3/4oftheway)fromthebottomoftheglass.
6
LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELL
VR8204 AND VR8304 SERIES GAS VALVES (INTERMITTENT PILOT)
A. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do try to light the pilot by hand.
B. BEFORE LIGHTING smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not
use any phone in your building.
Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
suppliers instructions.
not
If you cannot reach your gas supplier, call
the fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don’t try to repair it,
call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on
this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do try to light the pilot by hand.not
5. Remove front access panel.
6. Rotate the gas control knob clockwise to OFF.
7. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you then
smell gas, STOP! Follow “B” in the safety inform-
ation above on this label. If you don’t smell gas
go to the next step.
8. Rotate the gas control knob counter clockwise
to “ON”.
9. Replace front access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the
instructions “To Turn Off Gas To Appliance” and
call your service technician or gas supplier.
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if
service is to be performed.
3. Push in gas control knob slightly and turn
clockwise to “OFF”. Do not Force.
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
TO TURN OFF GAS TO APPLIANCE
FOR YOUR SAFETY READ BEFORE OPERATING
GAS OUTLET
GAS CONTROL KNOB
(SHOWN IN “ON” POSITION)
GAS INLET
GAS VALVE - TOP VIEW
7
LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH ROBERTSHAW
7000DERHC SERIES GAS VALVES (INTERMITTENT PILOT)
A. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do try to light the pilot by hand.
B. BEFORE LIGHTING smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not
use any phone in your building.
Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
suppliers instructions.
not
If you cannot reach your gas supplier, call
the fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don’t try to repair it,
call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on
this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do try to light the pilot by hand.not
5. Remove front access panel.
6. Rotate the gas control knob clockwise to OFF.
7. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you then
smell gas, STOP! Follow “B” in the safety inform-
ation above on this label. If you don’t smell gas
go to the next step.
8. Rotate the gas control knob counter clockwise
to “ON”.
9. Replace front access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the
instructions “To Turn Off Gas To Appliance” and
call your service technician or gas supplier.
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if
service is to be performed.
3. Push in gas control knob slightly and turn
clockwise to “OFF”. Do not Force.
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
TO TURN OFF GAS TO APPLIANCE
FOR YOUR SAFETY READ BEFORE LIGHTING
GAS
INLET
GAS CONTROL KNOB
SHOWN IN "OFF" POSITION
POSITION
INDICATOR
ON OFF
8
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
This boiler may include parts that contain refractory ceramic fibers (RCF).
RCF has been classified as a possible human carcinogen. When exposed to
temperatures about 1805°F, such as during direct flame contact, RCF changes
into crystalline silica, a known carcinogen. When disturbed as a result of
servicing or repair, these substances become airborne and, if inhaled, may be
hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures
:
Do not remove or replace RCF parts or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH)
approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF
and crystalline silica are not classified as hazardous wastes in the United
States and Canada.
First Aid Procedures
:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing
difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
980414 REV 0 - 11/17