Astria Fireplaces Scorpio Instruction Sheet

Catégorie
Cheminées
Taper
Instruction Sheet

Ce manuel convient également à

GAS CONVERSION KIT FOR FIREPLACES WITH ELECTRONIC IGNITION
NATURAL GAS TO PROPANE GAS (ECOFLOW VALVE)
[FOR USE IN FIREPLACE MODELS LISTED IN TABLE 1 ON PAGE 2]
KIT COMPONENTS
Main Burner Orifice, Low-Rate Orifice, LP Regulator, Conversion
Sticker and Conversion Sticker Form (to be filled out and affixed by
installer)
REQUIRED TOOLS AND SUPPLIES
Safety Gloves, Adjustable Wrench, Channel Locks, Flat Blade
Screwdriver, 4mm Allen Wrench (for some pilot assemblies - see
Figure 5), 5/16” Nutdriver, Pipe Wrench, Pipe Joint Compound
or Teflon Tape
TURN OFF THE GAS SUPPLY TO THE APPLIANCE. DISCONNECT
ELECTRICAL POWER SUPPLY.
READ ALL THE STEPS BEFORE STARTING THE CONVERSION. IN-
STALLER NOTICE: THESE INSTRUCTIONS MUST BE LEFT WITH THE
APPLIANCE.
When installing gas components use pipe joint compound or
Teflon tape on all pipe fittings before installing (Do not use pipe
joint compounds on flare fittings).
NOTE: THE FIREPLACE MUST BE OFF AND COLD BEFORE PERFORM-
ING THE GAS CONVERSION.
ALL WARNINGS, PRECAUTIONS AND INSTRUCTIONS IN THE INSTAL-
LATION AND OPERATION MANUAL PROVIDED WITH THE APPLIANCE
APPLY TO THESE INSTRUCTIONS.
GENERAL INFORMATION
Gas conversion kits are available to adapt the fireplace from the
use of one type of gas to the use of another. These kits contain all
the necessary components needed to complete the task including
labeling that must be affixed to ensure safe operation.
WARNING
This conversion kit shall be installed by a qualified
service agency in accordance with the manufac-
turer's instructions and all applicable codes and
requirements of the authority having jurisdiction. If
the information in these instructions is not followed
exactly, a fire, explosion or production of carbon
monoxide may result causing property damage,
personal injury or loss of life. The qualified service
agency performing this installation is responsible
for the proper installation of this kit and assumes
responsibility for this conversion. The installation
is not proper and complete until the operation of the
converted appliance is checked as specified in the
manufacturers instructions supplied with the kit.
IMPORTANT LE CANADA SEULEMENT
La conversion devra être effectuée conformément aux
recommandations des autorités provinciales ayant
juridiction et conformément aux exigences du code
d'installation CAN/CSA B149.1.
IMPORTANT CANADA
The conversion shall be carried out in accordance with
the requirements of the provincial authorities having
jurisdiction and in accordance with the requirements
of the CAN/CSA B149.1 Installation code.
AVERTISSEMENT
Cet équipement de conversion sera installé par
une agence qualifiée de service conformément aux
instructions du fabricant et toutes exigences et codes
applicables de l'autorisés avoir la juridiction. Si
l'information dans cette instruction n'est pas suivie
exactement, un feu, explosion ou production de
protoxyde de carbone peut résulter le dommages
causer de propriété, perte ou blessure personnelle de
vie. L'agence qualifiée de service est esponsable de
l'installation propre de cet équipment. L'installation
n'est pas propre et compléte jusqu'à l'opération de
l'appareil converti est chéque suivant les critères
établis dans les instructions de propriétaire provi-
sionnées avec l'équipement.
ECOFLOW GAS CONVERSION KITS
P/N 900835-00
Rev. A, 09/2017
HEARTH PRODUCTS
KITS AND ACCESSORIES
IHP.us.com
900835-00A 1
IHP.us.com 900835-00A
2
Gas Conversion Kits, Natural Gas (NG) to Propane Gas (LP)
Cat. No. Model Ecoflow Electronic Model Fireplaces
F2624 GCK-SKT5757NP DRT3033, Gemini33
F2621 GCK-SKT5555NP DRT3040, DRC3040, DRT3535, DRC3535,
Gemini40, Gemini40CD, Scorpio35, Scorpio35CD
F2492 GCK-SKT5655NP DRT3035, DRC3035, Gemini35, GeminiCD35
F2705 GCK-SKT5450NP DRT3540, DRC3540, Scorpio40, Scorpio40CD
F2706 GCK-SKT5350NP DRT3545, DRC3545, Scorpio45, Scorpio45CD
F2491 GCK-SKT5455NP DRT3045, Gemini45
Table 1
INSTALLING GAS CONVERSION KITS
CAUTION
The gas supply shall be shut OFF prior to discon-
necting the electrical power, before proceeding with
the conversion.
ATTENTION
Avant d’effecteur la conversion, coupez d’abord
l’alimentation en gaz, ensuite, coupez l’alimentation
electrique.
1. Disconnect power supply at the circuit breaker. Ensure fire-
place is cold.
2. TURN OFF THE GAS SUPPLY TO THE FIREPLACE AND DIS-
CONNECT THE FLEX LINE AT THE ELBOW FITTING ON THE
REGULATOR INLET (SEE FIGURE 3).
3. Remove the barrier, facade, and glass door per instruction in the
Installation and Operation Manual.
4. Open the lower control compartment door.
5. (Traditional Models) Remove the logs per instruction in the
Installation and Operation Manual. If necessary, remove the log
grate. Exercise care so as not to break the logs.
6. (Contemporary Models) Remove the glass media from firebox.
7. Perform the following conversion instructions:
Figure 1
Figure 2
Step 2. Remove the low-rate orifice from the valve and replace with the
orifice supplied in kit. See Figure 2.
IMPORTANT
The burner orifice provided in this kit are only for use
at elevations of 0 to 2,000 feet (610 M) in the USA
and 0 to 4,500 feet (0-1372 M) in Canada. At higher
elevations the BTU input must be de-rated by 4% for
every 1,000 feet (305 M) to maintain the proper ratio
of gas to air. If the installer must convert the unit to
adjust for varying altitudes, a deration information
sticker must be filled out by the installer and adhered
to the appliance at the time of the conversion. Contact
your local gas supplier for deration requirements for
your area.
GAS CONVERSION INSTRUCTIONS
IMPORTANT NOTE: When installing gas components use pipe joint com-
pound or Teflon tape on all pipe fittings before installing (ensure pro-
pane resistant compounds are used, do not use pipe joint compounds
on flare fittings).
Step 1. Remove Burner assembly and replace the main burner orifice sup-
plied in this kit. Refer to Table 5 on Page 5 for verification of proper main
burner orifice size supplied in kit.
Figure 3A
Step 3. Install the new LP regulator per instructions A through F.
A. Remove the screw shown below per instruction in Figure 3A.
Remove Phillips Screw
Remove this screw (located in the lower control compartment).
900835-00A 3
IHP.us.com
B. Pull entire valve, regulator and mounting bracket out of the firebox per
instruction in Figure 3B.
C. Remove the gas inlet line (that includes the pressure tap) per instruc-
tions in Figure 3C.
Figure 3B Pull entire valve, regulator and mounting
bracket out of firebox as shown here
Figure 3C
USING 2 WRENCHES, remove the gas inlet line
(that includes the pressure tap) as shown here.
Gas Inlet Line
D. Remove the 4 screws that attach the valve mounting bracket per instruc-
tions in Figure 3D.
Figure 3D
Remove the 4 screws (indicated by arrows) that attach the
valve mounting bracket as shown here.
IHP.us.com 900835-00A
4
Step 6. Reinstall pilot hood. See Figure 4.
Step 7. Retrieve the burner and hold the venturi tube above the orifice.
Place the shutter adjusting rod in the slot of the shutter arm (Figure 6). Set
the burner assembly into its position and secure the trapezoidal plate with
the two screws previously removed.
Step 8. Reinstall the baffle with the two baffle securing screws.
Figure 4 - Pilot Hood
Step 4. Pull the pilot hood straight up to remove and expose the pilot
orifice.
Step 5. For propane - Turn pilot orifice clockwise until it stops (do not
tighten). See Figure 5.
Pilot Hood
Figure 3F
Elbow Fitting
Elbow Fitting
Flex Line
Regulator
Regulator
Pipe Nipple
Pipe Nipple
E. Place pipe wrench on pipe nipple and remove regulator per instructions
in Figure 3E.
F. Install new LP regulator by reversing steps A through E.
Figure 3E Place pipe wrench on pipe nipple and
remove regulator as shown here.
Figure 5 - Turn Pilot Orifice
Pilot Assemblies may vary. Type ‘A’ pilot will require a flat standard
screwdriver and Type ‘B’ pilot will require a 4mm allen wrench.
A
B
900835-00A 5
IHP.us.com
WARNING
Never use an open flame to check for leaks.
Step 9. Reinstall the log set (Traditional Models) or glass media (Contem-
porary Models). See log set installation or glass media installation and
door Assembly installation in the installation and operation manual.
Step 10. Reinstall the glass door.
Step 11. Turn on gas supply and test for gas leaks, using a gas leak test
solution—also known as bubble leak solution.
NOTE: Using a soapy water solution is an effective leak test solution but
it is not recommended, because the soap residue that is left on the pipes/
fittings can result in corrosion over time.
A. Light the fireplace (refer to the lighting instructions label in the control
compartment).
B. Brush all joints and connections with the gas leak test solution to
check for leaks. If bubbles are formed, or gas odor is detected, turn
off the appliance. Either tighten or refasten the leaking connection, and
then retest as described above.
C. When the gas lines are tested and leak free, rinse off the leak testing
solution.
Figure 7 - Burner Flame Appearance
Figure 6 - Burner Air Shutter Adjustment
No Blue Flame
Center
Soot at
Flame Tip
Dark Orange
Flame
IMPROPERLY
BURNING FLAME
Soot above
Flame Tip No Soot at
Flame Tip
PROPERLY
BURNING FLAME
Semi-Transparent
Yellow Flame
Blue Flame
Center
Burner Air Shutter Gap
Models Propane Gas
All Models 1/8”
(3.2 mm)
Table 2
Air Shutter
Adjustment
Rod Down
(Fully-Open
Position)
Burner
Tube
Adjustment
Rod Up
(Fully-Closed
Position)
Adjustment
Set-Screw
Step 12. Adjust the burner air shutter per instructions in the Installation
and Operation manuals and Table 2 and Figures 6 and 7.
CAUTION: The air shutter should never be set so as to make the tips of
the flames sooty or create sooting on the viewing glass, logs, or media.
If soot begins to form after burning, the air shutter should be opened
gradually until the sooting condition stops. Gas quality and gas pres-
sure may vary, which can affect the burning characteristics of the ap-
pliance.
Figure 8 - Pilot Flame Appearance
Step 13. Relight the main burner. The lighting instructions can be found on
the lighting label in the control compartment. Verify proper burner ignition
and operation (Figure 7).
Inspect the pilot system for proper flame. The pilot flame should engulf the
flame sensor (Figure 8).
Using a manometer, test the inlet and manifold gas pressures (Tables 3–4,
Page 6). The inlet pressure is tested at elbow fitting removable plug and
the outlet pressure is tested at gas valve outlet test port (see Figures 12
and 13 on Page 7).
Always test pressures with the valve regulator control at the highest
setting.
Figure 9 - Ensure Proper Alignment Between Pilot And Burner
Pilot
Hood
Sensor
Ignitor
Igniter
Pilot Hood
Thermocouple
Pilot Hood
Thermocouple
Igniter
Step 14. Ensure the proper relationship of the pilot to the main burner as
shown in Figure 9.
Burner
Pilot Hood
Igniter
Flame
Sensor
Burner Ports
3/4” ± 1/16”
IHP.us.com 900835-00A
6
THIS APPLIANCE HAS BEEN CONVERTED TO:
INPUT BTU / HR - ##, ###
MANIFOLD PRESSURE - 10”
ORIFICE SIZE: ## (#.##”)
PROPANE GAS
Figure 10 - Affix Gas Conversion Sticker
Figure 11 - Fill Out and Affix Gas Conversion Form Sticker
Step 15. Affix the supplied gas conversion sticker next to the rating plate
label stating this unit has been converted to propane gas. See Figure 10.
Step 16. Fill out, then affix the supplied gas conversion form sticker next
to the rating plate. See Figure 11.
Inlet Gas Supply Pressure
Fuel # Minimum Maximum
Propane 11.0” WC (2.74 kPa) 13.0” WC (3.23 kPa)
Table 3
Manifold Gas Supply Pressure
Fuel # Pressure
Propane 10.0” WC / (2.49 kPa)
Table 4
Main Burner Orifice Sizes
Fireplace Model Drill Size
Propane
DRT3033, Gemini33 #57
DRT3035, DRC3035, Gemini35, Gemini35CD, Aries40, Aries40CD,
Aries40CB #56
DRT3040, DRC3040, DRT3535, DRC3535, Gemini40, Gemini40CD,
Scorpio35, Scorpio35CD, Aries45, Aries45CD #55
DRT3045, Gemini45 #54
DRT3540, DRC3540, Scorpio40, Scorpio40CD #54
DRT3545, DRC3545, Scorpio45, Scorpio45CD #53
Table 5
BTU Input
Models
Propane Gas
High
Rate
Low-
rate
DRT3033, Gemini33 13,000 9,500
DRT3035, DRC3035, Gemini35, Gemini35CD 15,000 11,000
DRT3040, DRC3040, Gemini40, Gemini40CD 19,000 14,000
DRT3045, Gemini45 21,500 13,500
DRT3535, DRC3535, Scorpio35, Scorpio35CD 19,000 13,000
DRT3540, DRC3540, Scorpio40, Scorpio40CD 22,000 17,000
DRT3545, DRC3545, Scorpio45, Scorpio45CD 26,000 20,000
Table 6
REFERENCE INFORMATION
Step 17. Reinstall the facade, and barrier.
NOTE: A BARRIER DESIGNED TO REDUCE THE RISK OF BURNS
FROM HOT VIEWING GLASS SHALL BE USED DURING OPERA-
TION OF THIS FIREPLACE FOR THE PROTECTION OF CHILDREN
AND OTHER AT-RISK INDIVIDUALS.
THIS APPLIANCE HAS BEEN CONVERTED ON (MM/DD/YY)
________________ TO _____________ GAS WITH KIT NO.
_______________ BY (NAME AND ADDRESS OF ____________
_______________________________________ ORIGANIZATION
MAKING THIS CONVERSION), WHICH ACCEPTS THE
RESPONSIBILITY THAT THIS CONVERSION HAS BEEN
PROPERLY MADE.”
“CET APPAREIL ELAIT CONVERT SUR LE (MM/DD/YY)
________________ A _______________ GAZ AVEC
L’EQUIPEMENT NO. ____________________ PAR (NOM ET
ADRESSE_____________________________________________
D’ORGANISATION FAISANT CETTE CONVERSION), QUI ACCEPTE
LA RESPONSABILITE QUE CETTE CONVERSION A ETE FAITE
CORRECTEMENT”. LB-104682A
900835-00A 7
IHP.us.com
Gas Pressure Test Points
The outlet manifold test gauge connection is provided on the valve stem (see
Figure 12). The inlet line gas pressure test point is shown in Figure 13. The
control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the
valve.
Figure 12 - Ecoflow Electronic Valve
Outlet Pressure
Test Point
Some parts have been removed for clarity
1/8” Inlet gas pressure ‘test point’ plug (in control compartment)
Testing Inlet Gas Pressure (Qualified Technicians Only):
1. Turn off gas shutoff valve and electrical.
2. Remove 1/8” plug (shown in diagram below).
3. Install an 1/8” nipple in place of plug.
4. Connect manometer to nipple, using an 1/8” NPT air hose nipple/
fitting.
5. Turn on shutoff valve and check for proper inlet gas pressure.
6. Reverse steps 1-5.
Figure 13 - Ecoflow Inlet Gas Pressure Test Point
REFERENCE INFORMATION (continued)
Printed in U.S.A. © 2017 Innovative Hearth Products
P/N 900835-00 Rev. A 09/2017
IHP reserves the right to make changes at any time, without notice, in design, materials, specifica-
tions, prices and also to discontinue colors, styles and products. Consult your local distributor
for fireplace code information.
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
8
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Astria Fireplaces Scorpio Instruction Sheet

Catégorie
Cheminées
Taper
Instruction Sheet
Ce manuel convient également à

dans d''autres langues